Download as pdf or txt
Download as pdf or txt
You are on page 1of 160

Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no : 0405-21-00 / 001 Date: 6/21/2021

Page 1 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no : 0405-21-00 / 001 Date: 6/21/2021

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-GF-1
Number off 1 AHU configuration Inline
Energy efficiency class C AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 1463.53
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.131 Max. external leakage rate % 0.131
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 47.9
SFPint W/m³/s 202.54
5823
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 55 49 46 47 49 37 19 53
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 050 Air volume m³/hr 13847
External static Pa 498 Unit velocity m/s 1.89
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 84 77 75 70 67 58 54 76
Outlet dB 93 89 86 83 80 75 68 88

Page 2 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no : 0405-21-00 / 001 Date: 6/21/2021

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 1900 1245 1785 Channel (150) 541.44
2 1900 1245 2180 Channel (150) 434.91
3 1900 1245 1530 Channel (150) 467.89

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 465mm Pressure drop: 37Pa


Recirc opening
Recirc opening
Standard mm 1790 x 447 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 1790 x 447 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 263Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 61
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 94
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 97
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 168
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W xH mm 1 x 490 x 490
Filter size: Qty x W xH mm 2 x 592 x 490
Filter size: Qty x W xH mm 1 x 490 x 592
Filter size: Qty x W xH mm 2 x 592 x 592

Page 3 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no : 0405-21-00 / 001 Date: 6/21/2021

COLD WATER COIL Length: 525mm Pressure drop: 157Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 32T 8R Fin material Epoxy-coated aluminium
1575A 3.2P 32NC
Hygienic coil Yes
Duty (calculated) kW 80.93 Coil length mm 1575
Duty (expected) kW 80.96 Coil height mm 1016
Sensible Duty / SHR kW / % 64.74 / 80.0 Coil depth mm 320
Internal volume (per coil) litres 58.56
Inlet connection size 66.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 3.85 Fluid flow rate l/s 3.472
Inlet air DB temperature °C 26.00 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 18.00 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 46.07 Fluid velocity m/s 0.9
Outlet air DB temperature °C 12.05 Fluid pressure drop kPa 22.14
Outlet air WB temperature °C 11.40 Fluid type 100% Water
Outlet air relative humidity % 92.85
Face velocity m/s 2.40
Air pressure drop coil Pa 122 Air pressure drop coil (Dry) Pa 110
(Wet)
Extras
Air pressure drop elim Pa 36
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 45-50

ELECTRIC HEATER Length: 590mm Pressure drop: 1Pa


Supplier UKS 40-50 Coil code E 40-50
Air volume (per coil) m³/hr 13847 Duty kW 2.00
Air on db °C 15.6 Number of steps 2
Air off db °C 16.0 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 1575
Coil height (per coil) mm 1016
Face velocity m/s 2.40
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 840mm Pressure drop: 22Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 90 / ELMC 40

Page 4 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no : 0405-21-00 / 001 Date: 6/21/2021

FAN SECTION Length: 1420mm Pressure drop: 0Pa


Fan type TLZ 500 Fan arrangement Single
Air volume m³/hr 13847 Motor x 1 Run
Fan outlet velocity m/s 9.45 Installed motor power kW 11.00
Required fan speed RPM 1033 Motor type IE2 One Speed
Max speed RPM 1300 Motor speed RPM 1465
External static pressure Pa 498 Voltage V 400
Extra static pressure Pa 0 Current A 21.3
System effect Pa 11 Motor efficiency % 90
Total static pressure Pa 989 Motor shaft power kW 6.94
Dynamic pressure Pa 54 Motor absorbed power kW 7.71
Total pressure Pa 1043 Total absorbed power kW 7.95
Fan absorbed power kW 6.24 Fan pulley SPZ DYNAM 118
Efficiency % 64 Motor pulley SPZ DYNAM 85
Fan bush -
Motor bush -
Belt length mm 1750
Number of belts 3
Flexible connection mm 638 x 638 x 100
Frequency inverter Standard

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 90 89 86 84 83 81 77 73
Outlet dB 100 93 89 86 83 80 75 68

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 5 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 002

Page 6 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 002

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-GF-2
Number off 1 AHU configuration Inline
Energy efficiency class D AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 1646.91
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.100 Max. external leakage rate % 0.100
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 49.2
SFPint W/m³/s 206.61
6409
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 56 50 47 48 50 38 20 54
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 055 Air volume m³/hr 18434
External static Pa 498 Unit velocity m/s 2.05
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 85 78 76 71 68 59 55 77
Outlet dB 92 87 88 85 83 80 75 90

Page 7 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 002

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 2170 1320 1785 Channel (150) 618.80
2 2170 1320 2180 Channel (150) 490.26
3 2170 1320 1530 Channel (150) 515.14

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 465mm Pressure drop: 48Pa


Recirc opening
Recirc opening
Standard mm 2060 x 447 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 2060 x 447 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 267Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 64
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 96
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 102
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 171
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W x H mm 8 x 490 x 592

Page 8 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 002

COLD WATER COIL Length: 525mm Pressure drop: 195Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 34T 6R Fin material Epoxy-coated aluminium
1850A 2.1P 34NC
Hygienic coil Yes
Duty (calculated) kW 121.24 Coil length mm 1850
Duty (expected) kW 123.20 Coil height mm 1080
Sensible Duty / SHR kW / % 92.14 / 76.0 Coil depth mm 250
Internal volume (per coil) litres 55.21
Inlet connection size 66.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 5.12 Fluid flow rate l/s 5.203
Inlet air DB temperature °C 27.00 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 19.00 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 47.17 Fluid velocity m/s 1.3
Outlet air DB temperature °C 12.16 Fluid pressure drop kPa 38.23
Outlet air WB temperature °C 11.75 Fluid type 100% Water
Outlet air relative humidity % 95.45
Face velocity m/s 2.56
Air pressure drop coil Pa 155 Air pressure drop coil (Dry) Pa 137
(Wet)
Extras
Air pressure drop elim Pa 41
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 55-60-65

ELECTRIC HEATER Length: 590mm Pressure drop: 0Pa


Supplier UKS 55-80 Coil code E 55-80
Air volume (per coil) m³/hr 18434 Duty kW 2.00
Air on db °C 15.6 Number of steps 2
Air off db °C 15.9 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 1850
Coil height (per coil) mm 1079
Face velocity m/s 2.57
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 840mm Pressure drop: 26Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 90 / ELMC 90

Page 9 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 002

FAN SECTION Length: 1420mm Pressure drop: 0Pa


Fan type TLZ 500 Fan arrangement Single
Air volume m³/hr 18434 Motor x 1 Run
Fan outlet velocity m/s 12.58 Installed motor power kW 15.00
Required fan speed RPM 1054 Motor type IE2 One Speed
Max speed RPM 1300 Motor speed RPM 1465
External static pressure Pa 498 Voltage V 400
Extra static pressure Pa 0 Current A 29.4
System effect Pa 13 Motor efficiency % 91
Total static pressure Pa 1047 Motor shaft power kW 9.58
Dynamic pressure Pa 95 Motor absorbed power kW 10.57
Total pressure Pa 1142 Total absorbed power kW 10.90
Fan absorbed power kW 8.62 Fan pulley SPZ DYNAM 118
Efficiency % 68 Motor pulley SPZ DYNAM 85
Fan bush -
Motor bush -
Belt length mm 1750
Number of belts 4
Flexible connection mm 638 x 638 x 100
Frequency inverter Standard

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 91 90 87 85 84 82 78 74
Outlet dB 96 92 87 88 85 83 80 75

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 10 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 003

Page 11 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 003

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-GF-3
Number off 1 AHU configuration Inline
Energy efficiency class C AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 1036.47
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.105 Max. external leakage rate % 0.106
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 47.2
SFPint W/m³/s 245.02
4581
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 54 48 45 46 48 36 18 52
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 040 Air volume m³/hr 9090
External static Pa 498 Unit velocity m/s 1.94
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 83 76 74 69 66 57 53 75
Outlet dB 91 88 83 83 79 78 71 87

Page 12 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 003

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 1495 1050 1760 Channel (150) 401.07
2 1495 1050 2080 Channel (150) 326.02
3 1495 1050 1330 Channel (150) 292.78

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 440mm Pressure drop: 41Pa


Recirc opening
Recirc opening
Standard mm 1385 x 360 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 1385 x 360 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 279Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 74
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 101
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 116
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 178
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W x H mm 1 x 287 x 592
Filter size: Qty x W x H mm 2 x 490 x 592
Filter size: Qty x W x H mm 2 x 490 x 287

Page 13 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 003

COLD WATER COIL Length: 525mm Pressure drop: 218Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 26T 8R Fin material Epoxy-coated aluminium
1175A 2.5P 26NC
Hygienic coil Yes
Duty (calculated) kW 59.37 Coil length mm 1175
Duty (expected) kW 58.00 Coil height mm 826
Sensible Duty / SHR kW / % 45.71 / 77.0 Coil depth mm 285
Internal volume (per coil) litres 35.76
Inlet connection size 54.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 2.52 Fluid flow rate l/s 2.547
Inlet air DB temperature °C 26.70 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 18.70 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 46.85 Fluid velocity m/s 0.8
Outlet air DB temperature °C 11.76 Fluid pressure drop kPa 17.16
Outlet air WB temperature °C 11.43 Fluid type 100% Water
Outlet air relative humidity % 96.29
Face velocity m/s 2.60
Air pressure drop coil Pa 176 Air pressure drop coil (Dry) Pa 157
(Wet)
Extras
Air pressure drop elim Pa 42
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 35-40

ELECTRIC HEATER Length: 590mm Pressure drop: 1Pa


Supplier UKS 40-50 Coil code E 40-50
Air volume (per coil) m³/hr 9090 Duty kW 2.00
Air on db °C 15.6 Number of steps 2
Air off db °C 16.2 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 1175
Coil height (per coil) mm 826
Face velocity m/s 2.60
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 740mm Pressure drop: 23Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 90

Page 14 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 003

FAN SECTION Length: 1220mm Pressure drop: 0Pa


Fan type TLZ 400 Fan arrangement Single
Air volume m³/hr 9090 Motor x 1 Run
Fan outlet velocity m/s 9.82 Installed motor power kW 7.50
Required fan speed RPM 1330 Motor type IE2 One Speed
Max speed RPM 1700 Motor speed RPM 1465
External static pressure Pa 498 Voltage V 400
Extra static pressure Pa 0 Current A 15.4
System effect Pa 11 Motor efficiency % 89
Total static pressure Pa 1072 Motor shaft power kW 4.95
Dynamic pressure Pa 58 Motor absorbed power kW 5.56
Total pressure Pa 1129 Total absorbed power kW 5.73
Fan absorbed power kW 4.46 Fan pulley SPZ DYNAM 118
Efficiency % 64 Motor pulley SPZ DYNAM 106
Fan bush -
Motor bush -
Belt length mm 1512
Number of belts 2
Flexible connection mm 507 x 507 x 100
Frequency inverter Standard

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 89 88 85 83 82 80 76 72
Outlet dB 99 91 88 83 83 79 78 71

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 15 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 004

Page 16 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 004

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-1F-1
Number off 1 AHU configuration Inline
Energy efficiency class D AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 1840.10
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.091 Max. external leakage rate % 0.091
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 50.2
SFPint W/m³/s 241.73
6835
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 58 52 49 50 52 40 22 56
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 060 Air volume m³/hr 21297
External static Pa 498 Unit velocity m/s 2.17
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 87 80 78 73 70 61 57 79
Outlet dB 97 92 88 85 82 77 69 90

Page 17 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 004

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 2170 1435 1865 Channel (150) 687.72
2 2170 1435 2180 Channel (150) 526.40
3 2170 1435 1720 Channel (150) 602.76

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 545mm Pressure drop: 45Pa


Recirc opening
Recirc opening
Standard mm 2060 x 535 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 2060 x 535 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 284Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 79
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 103
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 121
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 181
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W x H mm 8 x 490 x 592

Page 18 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 004

COLD WATER COIL Length: 525mm Pressure drop: 223Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 38T 8R Fin material Epoxy-coated aluminium
1850A 2.5P 76NC
Hygienic coil Yes
Duty (calculated) kW 124.04 Coil length mm 1850
Duty (expected) kW 125.40 Coil height mm 1207
Sensible Duty / SHR kW / % 99.23 / 80.0 Coil depth mm 320
Internal volume (per coil) litres 79.94
Inlet connection size 66.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 5.92 Fluid flow rate l/s 5.322
Inlet air DB temperature °C 26.11 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 18.35 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 47.58 Fluid velocity m/s 0.6
Outlet air DB temperature °C 12.22 Fluid pressure drop kPa 15.91
Outlet air WB temperature °C 11.87 Fluid type 100% Water
Outlet air relative humidity % 96.18
Face velocity m/s 2.65
Air pressure drop coil Pa 180 Air pressure drop coil (Dry) Pa 162
(Wet)
Extras
Air pressure drop elim Pa 44
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 55-60-65

ELECTRIC HEATER Length: 590mm Pressure drop: 1Pa


Supplier UKS 55-80 Coil code E 55-80
Air volume (per coil) m³/hr 21297 Duty kW 3.00
Air on db °C 15.6 Number of steps 3
Air off db °C 16.0 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 1850
Coil height (per coil) mm 1207
Face velocity m/s 2.65
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 840mm Pressure drop: 29Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 90 / ELMC 90 /
ELMC 20

FAN SECTION Length: 1610mm Pressure drop: 0Pa

Page 19 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 004

Fan type TLZ 630 Fan arrangement Single


Air volume m³/hr 21297 Motor x 1 Run
Fan outlet velocity m/s 9.22 Installed motor power kW 15.00
Required fan speed RPM 852 Motor type IE2 One Speed
Max speed RPM 1000 Motor speed RPM 1465
External static pressure Pa 498 Voltage V 400
Extra static pressure Pa 0 Current A 29.4
System effect Pa 14 Motor efficiency % 91
Total static pressure Pa 1094 Motor shaft power kW 11.68
Dynamic pressure Pa 51 Motor absorbed power kW 12.89
Total pressure Pa 1145 Total absorbed power kW 12.89
Fan absorbed power kW 10.51 Fan pulley SPZ DYNAM 150
Efficiency % 64 Motor pulley SPZ DYNAM 85
Fan bush -
Motor bush -
Belt length mm 2060
Number of belts 4
Flexible connection mm 801 x 801 x 100

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 93 92 89 87 86 84 80 76
Outlet dB 102 97 92 88 85 82 77 69

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 20 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 005

Page 21 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 005

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-1F-2
Number off 1 AHU configuration Inline
Energy efficiency class B AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 1671.23
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.109 Max. external leakage rate % 0.109
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 52.4
SFPint W/m³/s 175.71
6409
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 55 49 46 47 49 37 19 53
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 055 Air volume m³/hr 16990
External static Pa 498 Unit velocity m/s 1.89
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 84 77 75 70 67 58 54 76
Outlet dB 93 87 89 86 83 79 75 91

Page 22 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 005

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 2170 1320 1785 Channel (150) 610.66
2 2170 1320 2180 Channel (150) 499.96
3 2170 1320 1630 Channel (150) 537.90

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 465mm Pressure drop: 42Pa


Recirc opening
Recirc opening
Standard mm 2060 x 447 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 2060 x 447 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 258Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 57
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 92
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 92
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 166
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W x H mm 8 x 490 x 592

Page 23 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 005

COLD WATER COIL Length: 525mm Pressure drop: 144Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 34T 6R Fin material Epoxy-coated aluminium
1850A 2.5P 34NC
Hygienic coil Yes
Duty (calculated) kW 92.71 Coil length mm 1850
Duty (expected) kW 92.93 Coil height mm 1080
Sensible Duty / SHR kW / % 74.17 / 80.0 Coil depth mm 250
Internal volume (per coil) litres 55.21
Inlet connection size 66.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 4.72 Fluid flow rate l/s 3.978
Inlet air DB temperature °C 25.54 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 17.96 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 48.01 Fluid velocity m/s 0.9
Outlet air DB temperature °C 12.48 Fluid pressure drop kPa 23.30
Outlet air WB temperature °C 11.85 Fluid type 100% Water
Outlet air relative humidity % 93.17
Face velocity m/s 2.36
Air pressure drop coil Pa 109 Air pressure drop coil (Dry) Pa 99
(Wet)
Extras
Air pressure drop elim Pa 35
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 55-60-65

ELECTRIC HEATER Length: 590mm Pressure drop: 0Pa


Supplier UKS 55-80 Coil code E 55-80
Air volume (per coil) m³/hr 16990 Duty kW 3.00
Air on db °C 15.6 Number of steps 3
Air off db °C 16.1 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 1850
Coil height (per coil) mm 1079
Face velocity m/s 2.36
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 840mm Pressure drop: 22Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 90 / ELMC 60 /
ELMC 15

FAN SECTION Length: 1520mm Pressure drop: 0Pa

Page 24 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 005

Fan type TLZ 560 Fan arrangement Single


Air volume m³/hr 16990 Motor x 1 Run
Fan outlet velocity m/s 9.23 Installed motor power kW 11.00
Required fan speed RPM 900 Motor type IE2 One Speed
Max speed RPM 1200 Motor speed RPM 1465
External static pressure Pa 498 Voltage V 400
Extra static pressure Pa 0 Current A 21.3
System effect Pa 11 Motor efficiency % 90
Total static pressure Pa 975 Motor shaft power kW 7.91
Dynamic pressure Pa 51 Motor absorbed power kW 8.78
Total pressure Pa 1026 Total absorbed power kW 8.78
Fan absorbed power kW 7.11 Fan pulley SPZ DYNAM 150
Efficiency % 68 Motor pulley SPZ DYNAM 90
Fan bush -
Motor bush -
Belt length mm 1950
Number of belts 3
Flexible connection mm 715 x 715 x 100

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 90 89 86 84 83 81 77 73
Outlet dB 96 93 87 89 86 83 79 75

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 25 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 006

Page 26 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 006

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-1F-3
Number off 1 AHU configuration Inline
Energy efficiency class C AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 1465.90
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.100 Max. external leakage rate % 0.100
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 49.8
SFPint W/m³/s 212.71
5823
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 56 50 47 48 50 38 20 54
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 050 Air volume m³/hr 14866
External static Pa 498 Unit velocity m/s 2.03
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 85 78 76 71 68 59 55 77
Outlet dB 94 90 87 84 81 76 69 89

Page 27 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 006

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 1900 1245 1785 Channel (150) 543.81
2 1900 1245 2180 Channel (150) 434.91
3 1900 1245 1530 Channel (150) 467.89

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 465mm Pressure drop: 42Pa


Recirc opening
Recirc opening
Standard mm 1790 x 447 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 1790 x 447 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 270Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 67
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 98
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 106
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 173
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W xH mm 1 x 490 x 490
Filter size: Qty x W xH mm 2 x 592 x 490
Filter size: Qty x W xH mm 1 x 490 x 592
Filter size: Qty x W xH mm 2 x 592 x 592

Page 28 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 006

COLD WATER COIL Length: 525mm Pressure drop: 190Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 32T 8R Fin material Epoxy-coated aluminium
1575A 3P 32NC
Hygienic coil Yes
Duty (calculated) kW 100.98 Coil length mm 1575
Duty (expected) kW 100.67 Coil height mm 1016
Sensible Duty / SHR kW / % 74.73 / 74.0 Coil depth mm 320
Internal volume (per coil) litres 58.56
Inlet connection size 66.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 4.13 Fluid flow rate l/s 4.333
Inlet air DB temperature °C 27.27 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 19.14 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 46.74 Fluid velocity m/s 1.1
Outlet air DB temperature °C 12.24 Fluid pressure drop kPa 33.27
Outlet air WB temperature °C 11.66 Fluid type 100% Water
Outlet air relative humidity % 93.58
Face velocity m/s 2.58
Air pressure drop coil Pa 149 Air pressure drop coil (Dry) Pa 132
(Wet)
Extras
Air pressure drop elim Pa 41
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 45-50

ELECTRIC HEATER Length: 590mm Pressure drop: 1Pa


Supplier UKS 40-50 Coil code E 40-50
Air volume (per coil) m³/hr 14866 Duty kW 2.00
Air on db °C 15.6 Number of steps 2
Air off db °C 16.0 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 1575
Coil height (per coil) mm 1016
Face velocity m/s 2.58
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 840mm Pressure drop: 26Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 90 / ELMC 50

Page 29 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 006

FAN SECTION Length: 1420mm Pressure drop: 0Pa


Fan type TLZ 500 Fan arrangement Single
Air volume m³/hr 14866 Motor x 1 Run
Fan outlet velocity m/s 10.15 Installed motor power kW 11.00
Required fan speed RPM 1058 Motor type IE2 One Speed
Max speed RPM 1300 Motor speed RPM 1465
External static pressure Pa 498 Voltage V 400
Extra static pressure Pa 0 Current A 21.3
System effect Pa 12 Motor efficiency % 90
Total static pressure Pa 1040 Motor shaft power kW 7.77
Dynamic pressure Pa 62 Motor absorbed power kW 8.63
Total pressure Pa 1102 Total absorbed power kW 8.63
Fan absorbed power kW 6.99 Fan pulley SPZ DYNAM 118
Efficiency % 65 Motor pulley SPZ DYNAM 85
Fan bush -
Motor bush -
Belt length mm 1750
Number of belts 3
Flexible connection mm 638 x 638 x 100

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 91 90 87 85 84 82 78 74
Outlet dB 101 94 90 87 84 81 76 69

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 30 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 007

Page 31 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 007

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-1F-4
Number off 1 AHU configuration Inline
Energy efficiency class C AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 1826.18
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.096 Max. external leakage rate % 0.096
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 50.0
SFPint W/m³/s 228.95
6835
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 57 51 48 49 51 39 21 55
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 060 Air volume m³/hr 20261
External static Pa 498 Unit velocity m/s 2.06
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 86 79 77 72 69 60 56 78
Outlet dB 96 91 87 84 81 76 68 89

Page 32 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 007

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 2170 1435 1865 Channel (150) 673.80
2 2170 1435 2180 Channel (150) 526.40
3 2170 1435 1720 Channel (150) 602.76

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 545mm Pressure drop: 41Pa


Recirc opening
Recirc opening
Standard mm 2060 x 535 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 2060 x 535 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 278Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 73
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 101
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 114
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 177
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W x H mm 8 x 490 x 592

Page 33 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 007

COLD WATER COIL Length: 525mm Pressure drop: 174Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 38T 8R Fin material Epoxy-coated aluminium
1850A 3.2P 38NC
Hygienic coil Yes
Duty (calculated) kW 122.21 Coil length mm 1850
Duty (expected) kW 116.16 Coil height mm 1207
Sensible Duty / SHR kW / % 94.10 / 77.0 Coil depth mm 320
Internal volume (per coil) litres 79.80
Inlet connection size 66.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 5.63 Fluid flow rate l/s 5.244
Inlet air DB temperature °C 25.91 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 18.21 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 47.71 Fluid velocity m/s 1.1
Outlet air DB temperature °C 12.10 Fluid pressure drop kPa 41.48
Outlet air WB temperature °C 11.44 Fluid type 100% Water
Outlet air relative humidity % 92.73
Face velocity m/s 2.52
Air pressure drop coil Pa 135 Air pressure drop coil (Dry) Pa 121
(Wet)
Extras
Air pressure drop elim Pa 39
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 55-60-65

ELECTRIC HEATER Length: 590mm Pressure drop: 1Pa


Supplier UKS 55-80 Coil code E 55-80
Air volume (per coil) m³/hr 20261 Duty kW 3.00
Air on db °C 15.6 Number of steps 3
Air off db °C 16.0 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 1850
Coil height (per coil) mm 1207
Face velocity m/s 2.52
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 840mm Pressure drop: 26Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 90 / ELMC 90 /
ELMC 15

FAN SECTION Length: 1610mm Pressure drop: 0Pa

Page 34 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 007

Fan type TLZ 630 Fan arrangement Single


Air volume m³/hr 20261 Motor x 1 Run
Fan outlet velocity m/s 8.77 Installed motor power kW 15.00
Required fan speed RPM 827 Motor type IE2 One Speed
Max speed RPM 1000 Motor speed RPM 1465
External static pressure Pa 498 Voltage V 400
Extra static pressure Pa 0 Current A 29.4
System effect Pa 13 Motor efficiency % 91
Total static pressure Pa 1031 Motor shaft power kW 10.52
Dynamic pressure Pa 46 Motor absorbed power kW 11.61
Total pressure Pa 1077 Total absorbed power kW 11.61
Fan absorbed power kW 9.47 Fan pulley SPZ DYNAM 150
Efficiency % 64 Motor pulley SPZ DYNAM 85
Fan bush -
Motor bush -
Belt length mm 2060
Number of belts 4
Flexible connection mm 801 x 801 x 100

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 92 91 88 86 85 83 79 75
Outlet dB 101 96 91 87 84 81 76 68

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 35 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 008

Page 36 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 008

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-SF-01
Number off 1 AHU configuration Inline
Energy efficiency class B AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 1206.54
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.119 Max. external leakage rate % 0.119
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 49.2
SFPint W/m³/s 179.25
5121
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 53 47 44 45 47 35 17 51
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 045 Air volume m³/hr 10194
External static Pa 498 Unit velocity m/s 1.74
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 82 75 73 68 65 56 52 74
Outlet dB 90 87 82 82 78 77 70 86

Page 37 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 008

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 1720 1120 1760 Channel (150) 463.34
2 1720 1120 2180 Channel (150) 388.17
3 1720 1120 1410 Channel (150) 337.11

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 440mm Pressure drop: 38Pa


Recirc opening
Recirc opening
Standard mm 1610 x 360 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 1610 x 360 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 255Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 54
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 91
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 88
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 164
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W x H mm 6 x 490 x 490

Page 38 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 008

COLD WATER COIL Length: 525mm Pressure drop: 150Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 28T 8R Fin material Epoxy-coated aluminium
1400A 3P 28NC
Hygienic coil Yes
Duty (calculated) kW 68.13 Coil length mm 1400
Duty (expected) kW 66.90 Coil height mm 889
Sensible Duty / SHR kW / % 51.10 / 75.0 Coil depth mm 285
Internal volume (per coil) litres 44.69
Inlet connection size 54.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 2.83 Fluid flow rate l/s 2.922
Inlet air DB temperature °C 26.90 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 18.91 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 47.12 Fluid velocity m/s 0.9
Outlet air DB temperature °C 11.98 Fluid pressure drop kPa 22.25
Outlet air WB temperature °C 11.50 Fluid type 100% Water
Outlet air relative humidity % 94.70
Face velocity m/s 2.28
Air pressure drop coil Pa 118 Air pressure drop coil (Dry) Pa 105
(Wet)
Extras
Air pressure drop elim Pa 32
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 45-50

ELECTRIC HEATER Length: 590mm Pressure drop: 1Pa


Supplier UKS 40-50 Coil code E 40-50
Air volume (per coil) m³/hr 10194 Duty kW 2.00
Air on db °C 15.6 Number of steps 2
Air off db °C 16.1 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 1400
Coil height (per coil) mm 889
Face velocity m/s 2.28
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 840mm Pressure drop: 19Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 50 / ELMC 50

Page 39 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 008

FAN SECTION Length: 1300mm Pressure drop: 0Pa


Fan type TLZ 450 Fan arrangement Single
Air volume m³/hr 10194 Motor x 1 Run
Fan outlet velocity m/s 8.75 Installed motor power kW 7.50
Required fan speed RPM 1113 Motor type IE2 One Speed
Max speed RPM 1500 Motor speed RPM 1465
External static pressure Pa 498 Voltage V 400
Extra static pressure Pa 0 Current A 15.4
System effect Pa 9 Motor efficiency % 89
Total static pressure Pa 970 Motor shaft power kW 4.97
Dynamic pressure Pa 46 Motor absorbed power kW 5.59
Total pressure Pa 1016 Total absorbed power kW 5.59
Fan absorbed power kW 4.47 Fan pulley SPZ DYNAM 132
Efficiency % 64 Motor pulley SPZ DYNAM 100
Fan bush -
Motor bush -
Belt length mm 1650
Number of belts 2
Flexible connection mm 569 x 569 x 100

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 88 87 84 82 81 79 75 71
Outlet dB 98 90 87 82 82 78 77 70

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 40 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 009

Page 41 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 009

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-SF-02
Number off 1 AHU configuration Inline
Energy efficiency class C AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 1036.47
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.107 Max. external leakage rate % 0.107
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 48.6
SFPint W/m³/s 234.23
4581
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 53 47 44 45 47 35 17 51
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 040 Air volume m³/hr 8971
External static Pa 498 Unit velocity m/s 1.91
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 82 75 73 68 65 56 52 74
Outlet dB 91 88 83 83 79 78 71 87

Page 42 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 009

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 1495 1050 1760 Channel (150) 401.07
2 1495 1050 2080 Channel (150) 326.02
3 1495 1050 1330 Channel (150) 292.78

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 440mm Pressure drop: 40Pa


Recirc opening
Recirc opening
Standard mm 1385 x 360 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 1385 x 360 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 277Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 73
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 101
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 114
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 177
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W x H mm 1 x 287 x 592
Filter size: Qty x W x H mm 2 x 490 x 592
Filter size: Qty x W x H mm 2 x 490 x 287

Page 43 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 009

COLD WATER COIL Length: 525mm Pressure drop: 214Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 26T 8R Fin material Epoxy-coated aluminium
1175A 2.5P 26NC
Hygienic coil Yes
Duty (calculated) kW 61.41 Coil length mm 1175
Duty (expected) kW 59.84 Coil height mm 826
Sensible Duty / SHR kW / % 46.06 / 75.0 Coil depth mm 285
Internal volume (per coil) litres 35.76
Inlet connection size 54.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 2.49 Fluid flow rate l/s 2.636
Inlet air DB temperature °C 27.10 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 19.04 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 46.94 Fluid velocity m/s 0.8
Outlet air DB temperature °C 11.78 Fluid pressure drop kPa 18.28
Outlet air WB temperature °C 11.46 Fluid type 100% Water
Outlet air relative humidity % 96.44
Face velocity m/s 2.57
Air pressure drop coil Pa 173 Air pressure drop coil (Dry) Pa 153
(Wet)
Extras
Air pressure drop elim Pa 41
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 35-40

ELECTRIC HEATER Length: 590mm Pressure drop: 1Pa


Supplier UKS 40-50 Coil code E 40-50
Air volume (per coil) m³/hr 8971 Duty kW 2.00
Air on db °C 15.6 Number of steps 2
Air off db °C 16.2 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 1175
Coil height (per coil) mm 826
Face velocity m/s 2.57
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 740mm Pressure drop: 23Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 90

Page 44 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 009

FAN SECTION Length: 1220mm Pressure drop: 0Pa


Fan type TLZ 400 Fan arrangement Single
Air volume m³/hr 8971 Motor x 1 Run
Fan outlet velocity m/s 9.69 Installed motor power kW 7.50
Required fan speed RPM 1326 Motor type IE2 One Speed
Max speed RPM 1700 Motor speed RPM 1465
External static pressure Pa 498 Voltage V 400
Extra static pressure Pa 0 Current A 15.4
System effect Pa 11 Motor efficiency % 89
Total static pressure Pa 1064 Motor shaft power kW 4.86
Dynamic pressure Pa 56 Motor absorbed power kW 5.46
Total pressure Pa 1121 Total absorbed power kW 5.46
Fan absorbed power kW 4.37 Fan pulley SPZ DYNAM 118
Efficiency % 64 Motor pulley SPZ DYNAM 106
Fan bush -
Motor bush -
Belt length mm 1512
Number of belts 2
Flexible connection mm 507 x 507 x 100

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 88 87 84 82 81 79 75 71
Outlet dB 99 91 88 83 83 79 78 71

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 45 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 010

Page 46 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 010

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-SF-03
Number off 1 AHU configuration Inline
Energy efficiency class C AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 1026.47
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.113 Max. external leakage rate % 0.113
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 47.6
SFPint W/m³/s 223.52
4581
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 53 47 44 45 47 35 17 51
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 040 Air volume m³/hr 8495
External static Pa 498 Unit velocity m/s 1.81
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 82 75 73 68 65 56 52 74
Outlet dB 91 88 83 83 79 78 71 87

Page 47 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 010

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 1495 1050 1760 Channel (150) 401.07
2 1495 1050 2080 Channel (150) 326.02
3 1495 1050 1330 Channel (150) 282.78

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 440mm Pressure drop: 36Pa


Recirc opening
Recirc opening
Standard mm 1385 x 360 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 1385 x 360 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 271Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 68
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 98
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 106
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 173
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W x H mm 1 x 287 x 592
Filter size: Qty x W x H mm 2 x 490 x 592
Filter size: Qty x W x H mm 2 x 490 x 287

Page 48 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 010

COLD WATER COIL Length: 525mm Pressure drop: 191Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 26T 8R Fin material Epoxy-coated aluminium
1175A 2.5P 26NC
Hygienic coil Yes
Duty (calculated) kW 52.11 Coil length mm 1175
Duty (expected) kW 48.22 Coil height mm 826
Sensible Duty / SHR kW / % 40.65 / 78.0 Coil depth mm 285
Internal volume (per coil) litres 35.76
Inlet connection size 54.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 2.36 Fluid flow rate l/s 2.236
Inlet air DB temperature °C 25.80 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 18.14 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 47.82 Fluid velocity m/s 0.7
Outlet air DB temperature °C 11.52 Fluid pressure drop kPa 13.46
Outlet air WB temperature °C 11.23 Fluid type 100% Water
Outlet air relative humidity % 96.70
Face velocity m/s 2.43
Air pressure drop coil Pa 155 Air pressure drop coil (Dry) Pa 138
(Wet)
Extras
Air pressure drop elim Pa 37
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 35-40

ELECTRIC HEATER Length: 590mm Pressure drop: 1Pa


Supplier UKS 40-50 Coil code E 40-50
Air volume (per coil) m³/hr 8495 Duty kW 2.00
Air on db °C 15.6 Number of steps 2
Air off db °C 16.3 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 1175
Coil height (per coil) mm 826
Face velocity m/s 2.43
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 740mm Pressure drop: 20Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 90

Page 49 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 010

FAN SECTION Length: 1220mm Pressure drop: 0Pa


Fan type TLZ 400 Fan arrangement Single
Air volume m³/hr 8495 Motor x 1 Run
Fan outlet velocity m/s 9.18 Installed motor power kW 5.50
Required fan speed RPM 1304 Motor type IE2 One Speed
Max speed RPM 1700 Motor speed RPM 1465
External static pressure Pa 498 Voltage V 400
Extra static pressure Pa 0 Current A 11.2
System effect Pa 10 Motor efficiency % 88
Total static pressure Pa 1028 Motor shaft power kW 4.48
Dynamic pressure Pa 51 Motor absorbed power kW 5.09
Total pressure Pa 1078 Total absorbed power kW 5.09
Fan absorbed power kW 4.03 Fan pulley SPZ DYNAM 118
Efficiency % 63 Motor pulley SPZ DYNAM 106
Fan bush -
Motor bush -
Belt length mm 1512
Number of belts 2
Flexible connection mm 507 x 507 x 100

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 88 87 84 82 81 79 75 71
Outlet dB 99 91 88 83 83 79 78 71

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 50 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 011

Page 51 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 011

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-SF-04
Number off 1 AHU configuration Inline
Energy efficiency class C AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 1463.53
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.105 Max. external leakage rate % 0.105
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 49.5
SFPint W/m³/s 200.25
5823
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 55 49 46 47 49 37 19 53
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 050 Air volume m³/hr 14085
External static Pa 498 Unit velocity m/s 1.93
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 84 77 75 70 67 58 54 76
Outlet dB 94 90 87 84 81 76 69 89

Page 52 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 011

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 1900 1245 1785 Channel (150) 541.44
2 1900 1245 2180 Channel (150) 434.91
3 1900 1245 1530 Channel (150) 467.89

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 465mm Pressure drop: 39Pa


Recirc opening
Recirc opening
Standard mm 1790 x 447 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 1790 x 447 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 265Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 62
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 95
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 99
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 170
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W xH mm 1 x 490 x 490
Filter size: Qty x W xH mm 2 x 592 x 490
Filter size: Qty x W xH mm 1 x 490 x 592
Filter size: Qty x W xH mm 2 x 592 x 592

Page 53 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 011

COLD WATER COIL Length: 525mm Pressure drop: 165Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 32T 8R Fin material Epoxy-coated aluminium
1575A 3.2P 32NC
Hygienic coil Yes
Duty (calculated) kW 92.84 Coil length mm 1575
Duty (expected) kW 92.92 Coil height mm 1016
Sensible Duty / SHR kW / % 69.63 / 75.0 Coil depth mm 320
Internal volume (per coil) litres 58.56
Inlet connection size 66.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 3.91 Fluid flow rate l/s 3.983
Inlet air DB temperature °C 27.05 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 18.99 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 46.89 Fluid velocity m/s 1.0
Outlet air DB temperature °C 12.36 Fluid pressure drop kPa 28.50
Outlet air WB temperature °C 11.72 Fluid type 100% Water
Outlet air relative humidity % 92.97
Face velocity m/s 2.44
Air pressure drop coil Pa 128 Air pressure drop coil (Dry) Pa 114
(Wet)
Extras
Air pressure drop elim Pa 37
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 45-50

ELECTRIC HEATER Length: 590mm Pressure drop: 1Pa


Supplier UKS 40-50 Coil code E 40-50
Air volume (per coil) m³/hr 14085 Duty kW 2.00
Air on db °C 15.6 Number of steps 2
Air off db °C 16.0 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 1575
Coil height (per coil) mm 1016
Face velocity m/s 2.44
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 840mm Pressure drop: 23Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 90 / ELMC 50

Page 54 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 011

FAN SECTION Length: 1420mm Pressure drop: 0Pa


Fan type TLZ 500 Fan arrangement Single
Air volume m³/hr 14085 Motor x 1 Run
Fan outlet velocity m/s 9.61 Installed motor power kW 11.00
Required fan speed RPM 1039 Motor type IE2 One Speed
Max speed RPM 1300 Motor speed RPM 1465
External static pressure Pa 498 Voltage V 400
Extra static pressure Pa 0 Current A 21.3
System effect Pa 11 Motor efficiency % 90
Total static pressure Pa 1001 Motor shaft power kW 7.13
Dynamic pressure Pa 55 Motor absorbed power kW 7.92
Total pressure Pa 1056 Total absorbed power kW 7.92
Fan absorbed power kW 6.41 Fan pulley SPZ DYNAM 118
Efficiency % 64 Motor pulley SPZ DYNAM 85
Fan bush -
Motor bush -
Belt length mm 1750
Number of belts 3
Flexible connection mm 638 x 638 x 100

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 90 89 86 84 83 81 77 73
Outlet dB 101 94 90 87 84 81 76 69

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 55 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 012

Page 56 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 012

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-SF-05
Number off 1 AHU configuration Inline
Energy efficiency class B AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 1247.76
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.116 Max. external leakage rate % 0.116
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 49.2
SFPint W/m³/s 184.10
5168
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 54 48 45 46 48 36 18 52
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 045 Air volume m³/hr 10415
External static Pa 498 Unit velocity m/s 1.78
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 83 76 74 69 66 57 53 75
Outlet dB 90 87 82 82 78 77 70 86

Page 57 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 012

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 1720 1120 1835 Channel (150) 497.56
2 1720 1120 2180 Channel (150) 395.17
3 1720 1120 1410 Channel (150) 337.11

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 440mm Pressure drop: 40Pa


Recirc opening
Recirc opening
Standard mm 1610 x 360 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 1610 x 360 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 257Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 56
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 92
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 91
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 165
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W x H mm 6 x 490 x 490

Page 58 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 012

COLD WATER COIL Length: 600mm Pressure drop: 192Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 28T 10R Fin material Epoxy-coated aluminium
1400A 3P 35NC
Hygienic coil Yes
Duty (calculated) kW 122.83 Coil length mm 1400
Duty (expected) kW 124.25 Coil height mm 889
Sensible Duty / SHR kW / % 77.38 / 63.0 Coil depth mm 375
Internal volume (per coil) litres 56.69
Inlet connection size 66.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 2.89 Fluid flow rate l/s 5.269
Inlet air DB temperature °C 33.33 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 23.30 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 43.24 Fluid velocity m/s 1.2
Outlet air DB temperature °C 11.31 Fluid pressure drop kPa 39.38
Outlet air WB temperature °C 11.07 Fluid type 100% Water
Outlet air relative humidity % 97.31
Face velocity m/s 2.32
Air pressure drop coil Pa 159 Air pressure drop coil (Dry) Pa 133
(Wet)
Extras
Air pressure drop elim Pa 33
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 45-50

ELECTRIC HEATER Length: 590mm Pressure drop: 1Pa


Supplier UKS 40-50 Coil code E 40-50
Air volume (per coil) m³/hr 10415 Duty kW 2.00
Air on db °C 15.6 Number of steps 2
Air off db °C 16.1 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 1400
Coil height (per coil) mm 889
Face velocity m/s 2.32
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 840mm Pressure drop: 20Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 90 / ELMC 15

Page 59 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 012

FAN SECTION Length: 1300mm Pressure drop: 0Pa


Fan type TLZ 450 Fan arrangement Single
Air volume m³/hr 10415 Motor x 1 Run
Fan outlet velocity m/s 8.94 Installed motor power kW 7.50
Required fan speed RPM 1139 Motor type IE2 One Speed
Max speed RPM 1500 Motor speed RPM 1465
External static pressure Pa 498 Voltage V 400
Extra static pressure Pa 0 Current A 15.4
System effect Pa 9 Motor efficiency % 89
Total static pressure Pa 1017 Motor shaft power kW 5.33
Dynamic pressure Pa 48 Motor absorbed power kW 5.98
Total pressure Pa 1065 Total absorbed power kW 5.98
Fan absorbed power kW 4.79 Fan pulley SPZ DYNAM 132
Efficiency % 64 Motor pulley SPZ DYNAM 100
Fan bush -
Motor bush -
Belt length mm 1650
Number of belts 2
Flexible connection mm 569 x 569 x 100

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 89 88 85 83 82 80 76 72
Outlet dB 98 90 87 82 82 78 77 70

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 60 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 013

Page 61 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 013

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-SF-06
Number off 1 AHU configuration Inline
Energy efficiency class C AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 1031.86
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.100 Max. external leakage rate % 0.101
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 49.0
SFPint W/m³/s 250.56
4581
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 54 48 45 46 48 36 18 52
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 040 Air volume m³/hr 9548
External static Pa 498 Unit velocity m/s 2.04
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 83 76 74 69 66 57 53 75
Outlet dB 88 86 83 84 79 78 73 87

Page 62 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 013

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 1495 1050 1760 Channel (150) 396.46
2 1495 1050 2080 Channel (150) 326.02
3 1495 1050 1330 Channel (150) 292.78

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 440mm Pressure drop: 44Pa


Recirc opening
Recirc opening
Standard mm 1385 x 360 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 1385 x 360 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 285Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 80
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 104
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 123
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 181
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W x H mm 1 x 287 x 592
Filter size: Qty x W x H mm 2 x 490 x 592
Filter size: Qty x W x H mm 2 x 490 x 287

Page 63 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 013

COLD WATER COIL Length: 525mm Pressure drop: 208Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 26T 8R Fin material Epoxy-coated aluminium
1175A 3P 26NC
Hygienic coil Yes
Duty (calculated) kW 51.75 Coil length mm 1175
Duty (expected) kW 51.75 Coil height mm 826
Sensible Duty / SHR kW / % 41.92 / 81.0 Coil depth mm 285
Internal volume (per coil) litres 35.76
Inlet connection size 54.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 2.65 Fluid flow rate l/s 2.219
Inlet air DB temperature °C 25.50 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 17.95 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 48.14 Fluid velocity m/s 0.7
Outlet air DB temperature °C 12.50 Fluid pressure drop kPa 13.28
Outlet air WB temperature °C 11.88 Fluid type 100% Water
Outlet air relative humidity % 93.25
Face velocity m/s 2.73
Air pressure drop coil Pa 162 Air pressure drop coil (Dry) Pa 148
(Wet)
Extras
Air pressure drop elim Pa 46
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 35-40

ELECTRIC HEATER Length: 590mm Pressure drop: 1Pa


Supplier UKS 40-50 Coil code E 40-50
Air volume (per coil) m³/hr 9548 Duty kW 2.00
Air on db °C 15.6 Number of steps 2
Air off db °C 16.2 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 1175
Coil height (per coil) mm 826
Face velocity m/s 2.73
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 740mm Pressure drop: 26Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 90

Page 64 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 013

FAN SECTION Length: 1220mm Pressure drop: 0Pa


Fan type TLZ 400 Fan arrangement Single
Air volume m³/hr 9548 Motor x 1 Run
Fan outlet velocity m/s 10.32 Installed motor power kW 7.50
Required fan speed RPM 1330 Motor type IE2 One Speed
Max speed RPM 1700 Motor speed RPM 1465
External static pressure Pa 498 Voltage V 400
Extra static pressure Pa 0 Current A 15.4
System effect Pa 12 Motor efficiency % 89
Total static pressure Pa 1075 Motor shaft power kW 5.18
Dynamic pressure Pa 64 Motor absorbed power kW 5.82
Total pressure Pa 1139 Total absorbed power kW 5.82
Fan absorbed power kW 4.66 Fan pulley SPZ DYNAM 118
Efficiency % 65 Motor pulley SPZ DYNAM 106
Fan bush -
Motor bush -
Belt length mm 1512
Number of belts 2
Flexible connection mm 507 x 507 x 100

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 89 88 85 83 82 80 76 72
Outlet dB 94 88 86 83 84 79 78 73

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 65 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 014

Page 66 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 014

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-3F-01
Number off 1 AHU configuration Inline
Energy efficiency class B AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 1699.52
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.107 Max. external leakage rate % 0.107
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 52.4
SFPint W/m³/s 178.03
6409
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 55 49 46 47 49 37 19 53
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 055 Air volume m³/hr 17194
External static Pa 498 Unit velocity m/s 1.92
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 84 77 75 70 67 58 54 76
Outlet dB 93 87 89 86 83 79 75 91

Page 67 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 014

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 2170 1320 1785 Channel (150) 630.95
2 2170 1320 2180 Channel (150) 507.96
3 2170 1320 1630 Channel (150) 537.90

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 465mm Pressure drop: 43Pa


Recirc opening
Recirc opening
Standard mm 2060 x 447 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 2060 x 447 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 260Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 58
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 93
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 93
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 167
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W x H mm 8 x 490 x 592

Page 68 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 014

COLD WATER COIL Length: 525mm Pressure drop: 158Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 34T 8R Fin material Epoxy-coated aluminium
1850A 3.2P 34NC
Hygienic coil Yes
Duty (calculated) kW 110.10 Coil length mm 1850
Duty (expected) kW 105.60 Coil height mm 1080
Sensible Duty / SHR kW / % 82.57 / 75.0 Coil depth mm 320
Internal volume (per coil) litres 71.40
Inlet connection size 66.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 4.78 Fluid flow rate l/s 4.725
Inlet air DB temperature °C 26.41 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 18.56 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 47.39 Fluid velocity m/s 1.1
Outlet air DB temperature °C 12.03 Fluid pressure drop kPa 39.69
Outlet air WB temperature °C 11.41 Fluid type 100% Water
Outlet air relative humidity % 93.17
Face velocity m/s 2.39
Air pressure drop coil Pa 123 Air pressure drop coil (Dry) Pa 109
(Wet)
Extras
Air pressure drop elim Pa 35
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 55-60-65

ELECTRIC HEATER Length: 590mm Pressure drop: 0Pa


Supplier UKS 55-80 Coil code E 55-80
Air volume (per coil) m³/hr 17194 Duty kW 3.00
Air on db °C 15.6 Number of steps 3
Air off db °C 16.1 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 1850
Coil height (per coil) mm 1079
Face velocity m/s 2.39
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 840mm Pressure drop: 23Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 90 / ELMC 40 /
ELMC 40

FAN SECTION Length: 1520mm Pressure drop: 0Pa

Page 69 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 014

Fan type TLZ 560 Fan arrangement Single


Air volume m³/hr 17194 Motor x 1 Run
Fan outlet velocity m/s 9.34 Installed motor power kW 11.00
Required fan speed RPM 908 Motor type IE2 One Speed
Max speed RPM 1200 Motor speed RPM 1465
External static pressure Pa 498 Voltage V 400
Extra static pressure Pa 0 Current A 21.3
System effect Pa 11 Motor efficiency % 90
Total static pressure Pa 993 Motor shaft power kW 8.14
Dynamic pressure Pa 52 Motor absorbed power kW 9.05
Total pressure Pa 1045 Total absorbed power kW 9.05
Fan absorbed power kW 7.33 Fan pulley SPZ DYNAM 150
Efficiency % 68 Motor pulley SPZ DYNAM 90
Fan bush -
Motor bush -
Belt length mm 1950
Number of belts 3
Flexible connection mm 715 x 715 x 100

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 90 89 86 84 83 81 77 73
Outlet dB 96 93 87 89 86 83 79 75

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 70 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 015

Page 71 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 015

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-3F-02
Number off 1 AHU configuration Inline
Energy efficiency class B AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 1173.71
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.120 Max. external leakage rate % 0.120
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 49.2
SFPint W/m³/s 177.47
5099
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 53 47 44 45 47 35 17 51
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 045 Air volume m³/hr 10109
External static Pa 498 Unit velocity m/s 1.73
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 82 75 73 68 65 56 52 74
Outlet dB 89 86 81 81 77 76 69 85

Page 72 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 015

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 1720 1120 1725 Channel (150) 430.51
2 1720 1120 2180 Channel (150) 388.17
3 1720 1120 1410 Channel (150) 337.11

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 440mm Pressure drop: 38Pa


Recirc opening
Recirc opening
Standard mm 1610 x 360 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 1610 x 360 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 254Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 54
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 91
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 87
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 164
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W x H mm 6 x 490 x 490

Page 73 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 015

COLD WATER COIL Length: 490mm Pressure drop: 129Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 28T 4R Fin material Epoxy-coated aluminium
1400A 1.8P 14NC
Hygienic coil Yes
Duty (calculated) kW 50.52 Coil length mm 1400
Duty (expected) kW 51.80 Coil height mm 889
Sensible Duty / SHR kW / % 42.44 / 84.0 Coil depth mm 180
Internal volume (per coil) litres 24.16
Inlet connection size 54.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 2.81 Fluid flow rate l/s 2.167
Inlet air DB temperature °C 25.11 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 17.66 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 48.30 Fluid velocity m/s 1.3
Outlet air DB temperature °C 12.66 Fluid pressure drop kPa 34.13
Outlet air WB temperature °C 12.06 Fluid type 100% Water
Outlet air relative humidity % 93.45
Face velocity m/s 2.26
Air pressure drop coil Pa 97 Air pressure drop coil (Dry) Pa 90
(Wet)
Extras
Air pressure drop elim Pa 32
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 45-50

ELECTRIC HEATER Length: 590mm Pressure drop: 1Pa


Supplier UKS 40-50 Coil code E 40-50
Air volume (per coil) m³/hr 10109 Duty kW 2.00
Air on db °C 15.6 Number of steps 2
Air off db °C 16.1 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 1400
Coil height (per coil) mm 889
Face velocity m/s 2.26
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 840mm Pressure drop: 18Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 50 / ELMC 50

Page 74 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 015

FAN SECTION Length: 1300mm Pressure drop: 0Pa


Fan type TLZ 450 Fan arrangement Single
Air volume m³/hr 10109 Motor x 1 Run
Fan outlet velocity m/s 8.67 Installed motor power kW 7.50
Required fan speed RPM 1099 Motor type IE2 One Speed
Max speed RPM 1500 Motor speed RPM 1465
External static pressure Pa 498 Voltage V 400
Extra static pressure Pa 0 Current A 15.4
System effect Pa 9 Motor efficiency % 89
Total static pressure Pa 947 Motor shaft power kW 4.81
Dynamic pressure Pa 45 Motor absorbed power kW 5.40
Total pressure Pa 992 Total absorbed power kW 5.40
Fan absorbed power kW 4.33 Fan pulley SPZ DYNAM 132
Efficiency % 64 Motor pulley SPZ DYNAM 100
Fan bush -
Motor bush -
Belt length mm 1650
Number of belts 2
Flexible connection mm 569 x 569 x 100

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 88 87 84 82 81 79 75 71
Outlet dB 97 89 86 81 81 77 76 69

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 75 of 75
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no : 0405-21-00 / 016 Date: 6/21/2021

Page 1 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no : 0405-21-00 / 016 Date: 6/21/2021

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-3F-03
Number off 1 AHU configuration Inline
Energy efficiency class B AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 1204.69
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.117 Max. external leakage rate % 0.117
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 49.3
SFPint W/m³/s 182.54
5121
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 53 47 44 45 47 35 17 51
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 045 Air volume m³/hr 10364
External static Pa 498 Unit velocity m/s 1.77
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 82 75 73 68 65 56 52 74
Outlet dB 90 87 82 82 78 77 70 86

Page 2 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no : 0405-21-00 / 016 Date: 6/21/2021

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 1720 1120 1760 Channel (150) 461.49
2 1720 1120 2180 Channel (150) 388.17
3 1720 1120 1410 Channel (150) 337.11

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 440mm Pressure drop: 40Pa


Recirc opening
Recirc opening
Standard mm 1610 x 360 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 1610 x 360 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 257Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 55
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 92
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 90
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 165
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W x H mm 6 x 490 x 490

Page 3 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no : 0405-21-00 / 016 Date: 6/21/2021

COLD WATER COIL Length: 525mm Pressure drop: 148Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 28T 8R Fin material Epoxy-coated aluminium
1400A 3.2P 28NC
Hygienic coil Yes
Duty (calculated) kW 61.75 Coil length mm 1400
Duty (expected) kW 59.90 Coil height mm 889
Sensible Duty / SHR kW / % 48.16 / 78.0 Coil depth mm 285
Internal volume (per coil) litres 44.69
Inlet connection size 54.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 2.88 Fluid flow rate l/s 2.650
Inlet air DB temperature °C 25.98 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 18.26 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 47.67 Fluid velocity m/s 0.8
Outlet air DB temperature °C 12.18 Fluid pressure drop kPa 18.53
Outlet air WB temperature °C 11.60 Fluid type 100% Water
Outlet air relative humidity % 93.57
Face velocity m/s 2.31
Air pressure drop coil Pa 115 Air pressure drop coil (Dry) Pa 103
(Wet)
Extras
Air pressure drop elim Pa 33
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 45-50

ELECTRIC HEATER Length: 590mm Pressure drop: 1Pa


Supplier UKS 40-50 Coil code E 40-50
Air volume (per coil) m³/hr 10364 Duty kW 2.00
Air on db °C 15.6 Number of steps 2
Air off db °C 16.1 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 1400
Coil height (per coil) mm 889
Face velocity m/s 2.31
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 840mm Pressure drop: 19Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 50 / ELMC 50

Page 4 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no : 0405-21-00 / 016 Date: 6/21/2021

FAN SECTION Length: 1300mm Pressure drop: 0Pa


Fan type TLZ 450 Fan arrangement Single
Air volume m³/hr 10364 Motor x 1 Run
Fan outlet velocity m/s 8.89 Installed motor power kW 7.50
Required fan speed RPM 1113 Motor type IE2 One Speed
Max speed RPM 1500 Motor speed RPM 1465
External static pressure Pa 498 Voltage V 400
Extra static pressure Pa 0 Current A 15.4
System effect Pa 9 Motor efficiency % 89
Total static pressure Pa 971 Motor shaft power kW 5.05
Dynamic pressure Pa 47 Motor absorbed power kW 5.67
Total pressure Pa 1019 Total absorbed power kW 5.67
Fan absorbed power kW 4.54 Fan pulley SPZ DYNAM 132
Efficiency % 65 Motor pulley SPZ DYNAM 100
Fan bush -
Motor bush -
Belt length mm 1650
Number of belts 2
Flexible connection mm 569 x 569 x 100

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 88 87 84 82 81 79 75 71
Outlet dB 98 90 87 82 82 78 77 70

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 5 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 017

Page 6 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 017

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-3F-04
Number off 1 AHU configuration Inline
Energy efficiency class C AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 1325.81
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.097 Max. external leakage rate % 0.098
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 50.5
SFPint W/m³/s 222.44
5168
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 55 49 46 47 49 37 19 53
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 045 Air volume m³/hr 12403
External static Pa 498 Unit velocity m/s 2.12
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 84 77 75 70 67 58 54 76
Outlet dB 89 87 84 85 80 79 74 88

Page 7 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 017

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 1720 1120 1835 Channel (150) 495.25
2 1720 1120 2180 Channel (150) 395.17
3 1720 1120 1460 Channel (150) 417.47

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 440mm Pressure drop: 54Pa


Recirc opening
Recirc opening
Standard mm 1610 x 360 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 1610 x 360 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 276Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 72
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 100
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 112
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 176
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W x H mm 6 x 490 x 490

Page 8 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 017

COLD WATER COIL Length: 600mm Pressure drop: 253Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 28T 10R Fin material Epoxy-coated aluminium
1400A 3.2P 35NC
Hygienic coil Yes
Duty (calculated) kW 101.34 Coil length mm 1400
Duty (expected) kW 101.00 Coil height mm 889
Sensible Duty / SHR kW / % 70.94 / 70.0 Coil depth mm 375
Internal volume (per coil) litres 56.69
Inlet connection size 66.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 3.45 Fluid flow rate l/s 4.347
Inlet air DB temperature °C 28.97 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 20.31 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 45.66 Fluid velocity m/s 1.0
Outlet air DB temperature °C 11.87 Fluid pressure drop kPa 27.56
Outlet air WB temperature °C 11.45 Fluid type 100% Water
Outlet air relative humidity % 95.32
Face velocity m/s 2.77
Air pressure drop coil Pa 205 Air pressure drop coil (Dry) Pa 177
(Wet)
Extras
Air pressure drop elim Pa 48
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 45-50

ELECTRIC HEATER Length: 590mm Pressure drop: 1Pa


Supplier UKS 40-50 Coil code E 40-50
Air volume (per coil) m³/hr 12403 Duty kW 2.00
Air on db °C 15.6 Number of steps 2
Air off db °C 16.0 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 1400
Coil height (per coil) mm 889
Face velocity m/s 2.77
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 840mm Pressure drop: 28Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 90 / ELMC 30

Page 9 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 017

FAN SECTION Length: 1350mm Pressure drop: 0Pa


Fan type TLZ 450 Fan arrangement Single
Air volume m³/hr 12403 Motor x 1 Run
Fan outlet velocity m/s 10.64 Installed motor power kW 11.00
Required fan speed RPM 1194 Motor type IE2 One Speed
Max speed RPM 1500 Motor speed RPM 1465
External static pressure Pa 498 Voltage V 400
Extra static pressure Pa 0 Current A 21.3
System effect Pa 13 Motor efficiency % 90
Total static pressure Pa 1122 Motor shaft power kW 6.90
Dynamic pressure Pa 68 Motor absorbed power kW 7.66
Total pressure Pa 1190 Total absorbed power kW 7.66
Fan absorbed power kW 6.21 Fan pulley SPZ DYNAM 118
Efficiency % 66 Motor pulley SPZ DYNAM 95
Fan bush -
Motor bush -
Belt length mm 1650
Number of belts 3
Flexible connection mm 569 x 569 x 100

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 90 89 86 84 83 81 77 73
Outlet dB 95 89 87 84 85 80 79 74

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 10 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 018

Page 11 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 018

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-3F-05
Number off 1 AHU configuration Inline
Energy efficiency class B AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 516.94
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.180 Max. external leakage rate % 0.181
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 38.9
SFPint W/m³/s 190.77
3032
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 49 43 40 41 43 31 13 47
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 010 Air volume m³/hr 1784
External static Pa 872 Unit velocity m/s 1.24
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 78 71 69 64 61 52 48 70
Outlet dB 100 90 87 84 83 79 75 91

Page 12 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 018

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 825 670 1760 Channel (150) 195.48
2 825 670 2080 Channel (150) 196.39
3 825 670 910 Channel (150) 113.76

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 440mm Pressure drop: 24Pa


Recirc opening
Recirc opening
Standard mm 715 x 185 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 715 x 185 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 243Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 44
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 86
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 74
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 157
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W x H mm 1 x 592 x 490

Page 13 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 018

COLD WATER COIL Length: 525mm Pressure drop: 116Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 14T 8R Fin material Epoxy-coated aluminium
550A 3.2P 7NC
Hygienic coil Yes
Duty (calculated) kW 11.74 Coil length mm 550
Duty (expected) kW 11.97 Coil height mm 445
Sensible Duty / SHR kW / % 8.92 / 76.0 Coil depth mm 285
Internal volume (per coil) litres 9.28
Inlet connection size 28.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 0.50 Fluid flow rate l/s 0.503
Inlet air DB temperature °C 27.14 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 19.06 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 46.88 Fluid velocity m/s 0.6
Outlet air DB temperature °C 12.31 Fluid pressure drop kPa 11.46
Outlet air WB temperature °C 11.82 Fluid type 100% Water
Outlet air relative humidity % 94.62
Face velocity m/s 2.03
Air pressure drop coil Pa 90 Air pressure drop coil (Dry) Pa 80
(Wet)
Extras
Air pressure drop elim Pa 26
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 10-15

ELECTRIC HEATER Length: 590mm Pressure drop: 2Pa


Supplier UKS 10-15 Coil code E 10-15
Air volume (per coil) m³/hr 1784 Duty kW 2.00
Air on db °C 15.6 Number of steps 2
Air off db °C 18.9 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 550
Coil height (per coil) mm 445
Face velocity m/s 2.03
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 740mm Pressure drop: 9Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 20

Page 14 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 018

FAN SECTION Length: 800mm Pressure drop: 0Pa


Fan type TLZ 180 Fan arrangement Single
Air volume m³/hr 1784 Motor x 1 Run
Fan outlet velocity m/s 9.45 Installed motor power kW 2.20
Required fan speed RPM 3415 Motor type IE2 One Speed
Max speed RPM 4000 Motor speed RPM 2870
External static pressure Pa 872 Voltage V 400
Extra static pressure Pa 0 Current A 4.5
System effect Pa 5 Motor efficiency % 85
Total static pressure Pa 1271 Motor shaft power kW 1.37
Dynamic pressure Pa 54 Motor absorbed power kW 1.62
Total pressure Pa 1325 Total absorbed power kW 1.62
Fan absorbed power kW 1.23 Fan pulley SPZ 71
Efficiency % 53 Motor pulley SPZ 85
Fan bush -
Motor bush -
Belt length mm 862
Number of belts 1
Flexible connection mm 229 x 229 x 100

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 84 83 80 78 77 75 71 67
Outlet dB 105 100 90 87 84 83 79 75

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 15 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 019

Page 16 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 019

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-3F-06
Number off 1 AHU configuration Inline
Energy efficiency class B AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 516.94
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.180 Max. external leakage rate % 0.181
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 38.9
SFPint W/m³/s 190.77
3032
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 49 43 40 41 43 31 13 47
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 010 Air volume m³/hr 1784
External static Pa 872 Unit velocity m/s 1.24
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 78 71 69 64 61 52 48 70
Outlet dB 100 90 87 84 83 79 75 91

Page 17 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 019

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 825 670 1760 Channel (150) 195.48
2 825 670 2080 Channel (150) 196.39
3 825 670 910 Channel (150) 113.76

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 440mm Pressure drop: 24Pa


Recirc opening
Recirc opening
Standard mm 715 x 185 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 715 x 185 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 243Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 44
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 86
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 74
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 157
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W x H mm 1 x 592 x 490

Page 18 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 019

COLD WATER COIL Length: 525mm Pressure drop: 116Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 14T 8R Fin material Epoxy-coated aluminium
550A 3.2P 7NC
Hygienic coil Yes
Duty (calculated) kW 11.74 Coil length mm 550
Duty (expected) kW 11.97 Coil height mm 445
Sensible Duty / SHR kW / % 8.92 / 76.0 Coil depth mm 285
Internal volume (per coil) litres 9.28
Inlet connection size 28.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 0.50 Fluid flow rate l/s 0.503
Inlet air DB temperature °C 27.14 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 19.06 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 46.88 Fluid velocity m/s 0.6
Outlet air DB temperature °C 12.31 Fluid pressure drop kPa 11.46
Outlet air WB temperature °C 11.82 Fluid type 100% Water
Outlet air relative humidity % 94.62
Face velocity m/s 2.03
Air pressure drop coil Pa 90 Air pressure drop coil (Dry) Pa 80
(Wet)
Extras
Air pressure drop elim Pa 26
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 10-15

ELECTRIC HEATER Length: 590mm Pressure drop: 2Pa


Supplier UKS 10-15 Coil code E 10-15
Air volume (per coil) m³/hr 1784 Duty kW 2.00
Air on db °C 15.6 Number of steps 2
Air off db °C 18.9 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 550
Coil height (per coil) mm 445
Face velocity m/s 2.03
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 740mm Pressure drop: 9Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 20

Page 19 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 019

FAN SECTION Length: 800mm Pressure drop: 0Pa


Fan type TLZ 180 Fan arrangement Single
Air volume m³/hr 1784 Motor x 1 Run
Fan outlet velocity m/s 9.45 Installed motor power kW 2.20
Required fan speed RPM 3415 Motor type IE2 One Speed
Max speed RPM 4000 Motor speed RPM 2870
External static pressure Pa 872 Voltage V 400
Extra static pressure Pa 0 Current A 4.5
System effect Pa 5 Motor efficiency % 85
Total static pressure Pa 1271 Motor shaft power kW 1.37
Dynamic pressure Pa 54 Motor absorbed power kW 1.62
Total pressure Pa 1325 Total absorbed power kW 1.62
Fan absorbed power kW 1.23 Fan pulley SPZ 71
Efficiency % 53 Motor pulley SPZ 85
Fan bush -
Motor bush -
Belt length mm 862
Number of belts 1
Flexible connection mm 229 x 229 x 100

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 84 83 80 78 77 75 71 67
Outlet dB 105 100 90 87 84 83 79 75

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 20 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 020

Page 21 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 020

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-4F-01
Number off 1 AHU configuration Inline
Energy efficiency class C AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 1430.68
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.110 Max. external leakage rate % 0.110
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 49.2
SFPint W/m³/s 190.37
5798
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 55 49 46 47 49 37 19 53
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 050 Air volume m³/hr 13456
External static Pa 498 Unit velocity m/s 1.84
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 84 77 75 70 67 58 54 76
Outlet dB 93 89 86 83 80 75 68 88

Page 22 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 020

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 1900 1245 1750 Channel (150) 508.40
2 1900 1245 2180 Channel (150) 434.91
3 1900 1245 1530 Channel (150) 468.09

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 465mm Pressure drop: 36Pa


Recirc opening
Recirc opening
Standard mm 1790 x 447 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 1790 x 447 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 260Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 58
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 93
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 94
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 167
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W xH mm 1 x 490 x 490
Filter size: Qty x W xH mm 2 x 592 x 490
Filter size: Qty x W xH mm 1 x 490 x 592
Filter size: Qty x W xH mm 2 x 592 x 592

Page 23 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 020

COLD WATER COIL Length: 490mm Pressure drop: 140Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 32T 5R Fin material Epoxy-coated aluminium
1575A 2.1P 20NC
Hygienic coil Yes
Duty (calculated) kW 72.94 Coil length mm 1575
Duty (expected) kW 70.50 Coil height mm 1016
Sensible Duty / SHR kW / % 59.08 / 81.0 Coil depth mm 215
Internal volume (per coil) litres 36.91
Inlet connection size 54.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 3.74 Fluid flow rate l/s 3.131
Inlet air DB temperature °C 25.39 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 17.85 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 48.08 Fluid velocity m/s 1.3
Outlet air DB temperature °C 12.35 Fluid pressure drop kPa 42.22
Outlet air WB temperature °C 11.76 Fluid type 100% Water
Outlet air relative humidity % 93.59
Face velocity m/s 2.34
Air pressure drop coil Pa 107 Air pressure drop coil (Dry) Pa 97
(Wet)
Extras
Air pressure drop elim Pa 34
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 45-50

ELECTRIC HEATER Length: 590mm Pressure drop: 1Pa


Supplier UKS 40-50 Coil code E 40-50
Air volume (per coil) m³/hr 13456 Duty kW 2.00
Air on db °C 15.6 Number of steps 2
Air off db °C 16.0 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 1575
Coil height (per coil) mm 1016
Face velocity m/s 2.34
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 840mm Pressure drop: 21Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 90 / ELMC 40

Page 24 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 020

FAN SECTION Length: 1420mm Pressure drop: 0Pa


Fan type TLZ 500 Fan arrangement Single
Air volume m³/hr 13456 Motor x 1 Run
Fan outlet velocity m/s 9.18 Installed motor power kW 11.00
Required fan speed RPM 1021 Motor type IE2 One Speed
Max speed RPM 1300 Motor speed RPM 1465
External static pressure Pa 498 Voltage V 400
Extra static pressure Pa 0 Current A 21.3
System effect Pa 10 Motor efficiency % 90
Total static pressure Pa 966 Motor shaft power kW 6.60
Dynamic pressure Pa 51 Motor absorbed power kW 7.34
Total pressure Pa 1016 Total absorbed power kW 7.34
Fan absorbed power kW 5.94 Fan pulley SPZ DYNAM 125
Efficiency % 64 Motor pulley SPZ DYNAM 85
Fan bush -
Motor bush -
Belt length mm 1750
Number of belts 3
Flexible connection mm 638 x 638 x 100

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 90 89 86 84 83 81 77 73
Outlet dB 100 93 89 86 83 80 75 68

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 25 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 021

Page 26 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 021

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-4F-02
Number off 1 AHU configuration Inline
Energy efficiency class C AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 1287.40
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.100 Max. external leakage rate % 0.100
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 50.4
SFPint W/m³/s 215.22
5121
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 54 48 45 46 48 36 18 52
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 045 Air volume m³/hr 12063
External static Pa 498 Unit velocity m/s 2.06
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 83 76 74 69 66 57 53 75
Outlet dB 88 86 83 84 79 78 73 87

Page 27 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 021

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 1720 1120 1760 Channel (150) 457.57
2 1720 1120 2180 Channel (150) 395.17
3 1720 1120 1460 Channel (150) 416.74

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 440mm Pressure drop: 51Pa


Recirc opening
Recirc opening
Standard mm 1610 x 360 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 1610 x 360 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 273Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 69
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 99
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 108
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 174
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W x H mm 6 x 490 x 490

Page 28 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 021

COLD WATER COIL Length: 525mm Pressure drop: 213Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 28T 6R Fin material Epoxy-coated aluminium
1400A 2.1P 21NC
Hygienic coil Yes
Duty (calculated) kW 76.69 Coil length mm 1400
Duty (expected) kW 77.44 Coil height mm 889
Sensible Duty / SHR kW / % 59.05 / 77.0 Coil depth mm 250
Internal volume (per coil) litres 36.16
Inlet connection size 66.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 3.35 Fluid flow rate l/s 3.292
Inlet air DB temperature °C 26.79 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 18.81 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 47.06 Fluid velocity m/s 1.3
Outlet air DB temperature °C 12.23 Fluid pressure drop kPa 34.90
Outlet air WB temperature °C 11.78 Fluid type 100% Water
Outlet air relative humidity % 95.03
Face velocity m/s 2.69
Air pressure drop coil Pa 168 Air pressure drop coil (Dry) Pa 150
(Wet)
Extras
Air pressure drop elim Pa 45
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 45-50

ELECTRIC HEATER Length: 590mm Pressure drop: 1Pa


Supplier UKS 40-50 Coil code E 40-50
Air volume (per coil) m³/hr 12063 Duty kW 2.00
Air on db °C 15.6 Number of steps 2
Air off db °C 16.1 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 1400
Coil height (per coil) mm 889
Face velocity m/s 2.69
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 840mm Pressure drop: 26Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 90 / ELMC 30

Page 29 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 021

FAN SECTION Length: 1350mm Pressure drop: 0Pa


Fan type TLZ 450 Fan arrangement Single
Air volume m³/hr 12063 Motor x 1 Run
Fan outlet velocity m/s 10.35 Installed motor power kW 11.00
Required fan speed RPM 1169 Motor type IE2 One Speed
Max speed RPM 1500 Motor speed RPM 1465
External static pressure Pa 498 Voltage V 400
Extra static pressure Pa 0 Current A 21.3
System effect Pa 13 Motor efficiency % 90
Total static pressure Pa 1075 Motor shaft power kW 6.43
Dynamic pressure Pa 64 Motor absorbed power kW 7.14
Total pressure Pa 1140 Total absorbed power kW 7.14
Fan absorbed power kW 5.79 Fan pulley SPZ DYNAM 118
Efficiency % 66 Motor pulley SPZ DYNAM 95
Fan bush -
Motor bush -
Belt length mm 1650
Number of belts 2
Flexible connection mm 569 x 569 x 100

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 89 88 85 83 82 80 76 72
Outlet dB 94 88 86 83 84 79 78 73

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 30 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 022

Page 31 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 022

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-4F-03
Number off 1 AHU configuration Inline
Energy efficiency class C AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 1702.97
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.108 Max. external leakage rate % 0.108
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 52.3
SFPint W/m³/s 177.74
6409
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 56 50 47 48 50 38 20 54
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 055 Air volume m³/hr 17143
External static Pa 498 Unit velocity m/s 1.91
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 85 78 76 71 68 59 55 77
Outlet dB 93 87 89 86 83 79 75 91

Page 32 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 022

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 2170 1320 1785 Channel (150) 643.40
2 2170 1320 2180 Channel (150) 499.96
3 2170 1320 1630 Channel (150) 536.90

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 465mm Pressure drop: 42Pa


Recirc opening
Recirc opening
Standard mm 2060 x 447 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 2060 x 447 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 259Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 58
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 93
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 93
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 166
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W x H mm 8 x 490 x 592

Page 33 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 022

COLD WATER COIL Length: 525mm Pressure drop: 188Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 34T 8R Fin material Epoxy-coated aluminium
1850A 2.5P 68NC
Hygienic coil Yes
Duty (calculated) kW 131.00 Coil length mm 1850
Duty (expected) kW 137.28 Coil height mm 1080
Sensible Duty / SHR kW / % 95.63 / 73.0 Coil depth mm 320
Internal volume (per coil) litres 71.52
Inlet connection size 66.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 4.76 Fluid flow rate l/s 5.619
Inlet air DB temperature °C 28.80 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 20.20 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 45.80 Fluid velocity m/s 0.7
Outlet air DB temperature °C 12.25 Fluid pressure drop kPa 18.62
Outlet air WB temperature °C 11.98 Fluid type 100% Water
Outlet air relative humidity % 97.00
Face velocity m/s 2.38
Air pressure drop coil Pa 152 Air pressure drop coil (Dry) Pa 133
(Wet)
Extras
Air pressure drop elim Pa 35
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 55-60-65

ELECTRIC HEATER Length: 590mm Pressure drop: 0Pa


Supplier UKS 55-80 Coil code E 55-80
Air volume (per coil) m³/hr 17143 Duty kW 3.00
Air on db °C 15.6 Number of steps 3
Air off db °C 16.1 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 1850
Coil height (per coil) mm 1079
Face velocity m/s 2.39
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 840mm Pressure drop: 23Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 90 / ELMC 60 /
ELMC 15

FAN SECTION Length: 1520mm Pressure drop: 0Pa

Page 34 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 022

Fan type TLZ 560 Fan arrangement Single


Air volume m³/hr 17143 Motor x 1 Run
Fan outlet velocity m/s 9.31 Installed motor power kW 11.00
Required fan speed RPM 922 Motor type IE2 One Speed
Max speed RPM 1200 Motor speed RPM 1465
External static pressure Pa 498 Voltage V 400
Extra static pressure Pa 0 Current A 21.3
System effect Pa 11 Motor efficiency % 90
Total static pressure Pa 1021 Motor shaft power kW 8.37
Dynamic pressure Pa 52 Motor absorbed power kW 9.30
Total pressure Pa 1073 Total absorbed power kW 9.30
Fan absorbed power kW 7.53 Fan pulley SPZ DYNAM 132
Efficiency % 68 Motor pulley SPZ DYNAM 85
Fan bush -
Motor bush -
Belt length mm 1900
Number of belts 3
Flexible connection mm 715 x 715 x 100

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 91 90 87 85 84 82 78 74
Outlet dB 96 93 87 89 86 83 79 75

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 35 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 023

Page 36 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 023

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-4F-04
Number off 1 AHU configuration Inline
Energy efficiency class C AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 1222.99
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.108 Max. external leakage rate % 0.108
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 49.6
SFPint W/m³/s 200.03
5121
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 54 48 45 46 48 36 18 52
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 045 Air volume m³/hr 11213
External static Pa 498 Unit velocity m/s 1.92
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 83 76 74 69 66 57 53 75
Outlet dB 91 88 83 83 79 78 71 87

Page 37 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 023

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 1720 1120 1760 Channel (150) 473.19
2 1720 1120 2180 Channel (150) 395.17
3 1720 1120 1410 Channel (150) 336.71

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 440mm Pressure drop: 45Pa


Recirc opening
Recirc opening
Standard mm 1610 x 360 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 1610 x 360 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 265Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 62
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 95
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 99
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 170
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W x H mm 6 x 490 x 490

Page 38 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 023

COLD WATER COIL Length: 525mm Pressure drop: 206Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 28T 8R Fin material Epoxy-coated aluminium
1400A 2.5P 28NC
Hygienic coil Yes
Duty (calculated) kW 85.80 Coil length mm 1400
Duty (expected) kW 82.40 Coil height mm 889
Sensible Duty / SHR kW / % 61.78 / 72.0 Coil depth mm 320
Internal volume (per coil) litres 46.43
Inlet connection size 66.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 3.11 Fluid flow rate l/s 3.681
Inlet air DB temperature °C 28.00 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 19.65 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 46.30 Fluid velocity m/s 1.1
Outlet air DB temperature °C 11.54 Fluid pressure drop kPa 27.66
Outlet air WB temperature °C 11.24 Fluid type 100% Water
Outlet air relative humidity % 96.60
Face velocity m/s 2.50
Air pressure drop coil Pa 167 Air pressure drop coil (Dry) Pa 145
(Wet)
Extras
Air pressure drop elim Pa 39
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 45-50

ELECTRIC HEATER Length: 590mm Pressure drop: 1Pa


Supplier UKS 40-50 Coil code E 40-50
Air volume (per coil) m³/hr 11213 Duty kW 2.00
Air on db °C 15.6 Number of steps 2
Air off db °C 16.1 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 1400
Coil height (per coil) mm 889
Face velocity m/s 2.50
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 840mm Pressure drop: 23Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 90 / ELMC 20

Page 39 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 023

FAN SECTION Length: 1300mm Pressure drop: 0Pa


Fan type TLZ 450 Fan arrangement Single
Air volume m³/hr 11213 Motor x 1 Run
Fan outlet velocity m/s 9.62 Installed motor power kW 7.50
Required fan speed RPM 1155 Motor type IE2 One Speed
Max speed RPM 1500 Motor speed RPM 1465
External static pressure Pa 498 Voltage V 400
Extra static pressure Pa 0 Current A 15.4
System effect Pa 11 Motor efficiency % 89
Total static pressure Pa 1048 Motor shaft power kW 5.86
Dynamic pressure Pa 56 Motor absorbed power kW 6.58
Total pressure Pa 1103 Total absorbed power kW 6.58
Fan absorbed power kW 5.27 Fan pulley SPZ DYNAM 112
Efficiency % 65 Motor pulley SPZ DYNAM 90
Fan bush -
Motor bush -
Belt length mm 1587
Number of belts 2
Flexible connection mm 569 x 569 x 100

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 89 88 85 83 82 80 76 72
Outlet dB 99 91 88 83 83 79 78 71

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 40 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 024

Page 41 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 024

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-4F-05
Number off 1 AHU configuration Inline
Energy efficiency class C AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 1001.65
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.114 Max. external leakage rate % 0.114
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 46.6
SFPint W/m³/s 215.05
4324
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 54 48 45 46 48 36 18 52
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 035 Air volume m³/hr 7221
External static Pa 498 Unit velocity m/s 1.81
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 83 76 74 69 66 57 53 75
Outlet dB 93 90 85 85 81 80 73 89

Page 42 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 024

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 1370 990 1880 Channel (150) 414.04
2 1370 990 2080 Channel (150) 316.61
3 1370 990 1260 Channel (150) 255.21

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 440mm Pressure drop: 32Pa


Recirc opening
Recirc opening
Standard mm 1260 x 360 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 1260 x 360 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 266Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 63
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 95
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 100
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 170
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W x H mm 2 x 592 x 287
Filter size: Qty x W x H mm 2 x 592 x 490

Page 43 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 024

COLD WATER COIL Length: 645mm Pressure drop: 354Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 24T 12R Fin material Epoxy-coated aluminium
1050A 2.1P 48NC
Hygienic coil Yes
Duty (calculated) kW 176.57 Coil length mm 1050
Duty (expected) kW 190.10 Coil height mm 762
Sensible Duty / SHR kW / % 86.52 / 49.0 Coil depth mm 450
Internal volume (per coil) litres 47.27
Inlet connection size 80.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 2.01 Fluid flow rate l/s 7.575
Inlet air DB temperature °C 46.00 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 32.00 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 38.29 Fluid velocity m/s 1.3
Outlet air DB temperature °C 9.86 Fluid pressure drop kPa 28.78
Outlet air WB temperature °C 9.86 Fluid type 100% Water
Outlet air relative humidity % 100.00
Face velocity m/s 2.51
Air pressure drop coil Pa 315 Air pressure drop coil (Dry) Pa 243
(Wet)
Extras
Air pressure drop elim Pa 39
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 35-40

ELECTRIC HEATER Length: 590mm Pressure drop: 2Pa


Supplier UKS 20-35 Coil code E 20-35
Air volume (per coil) m³/hr 7221 Duty kW 2.00
Air on db °C 15.6 Number of steps 2
Air off db °C 16.4 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 1050
Coil height (per coil) mm 762
Face velocity m/s 2.51
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 740mm Pressure drop: 20Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 40 / ELMC 30

Page 44 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 024

FAN SECTION Length: 1150mm Pressure drop: 0Pa


Fan type TLZ 355 Fan arrangement Single
Air volume m³/hr 7221 Motor x 1 Run
Fan outlet velocity m/s 9.77 Installed motor power kW 5.50
Required fan speed RPM 1594 Motor type IE2 One Speed
Max speed RPM 1900 Motor speed RPM 1465
External static pressure Pa 498 Voltage V 400
Extra static pressure Pa 0 Current A 11.2
System effect Pa 10 Motor efficiency % 88
Total static pressure Pa 1182 Motor shaft power kW 4.47
Dynamic pressure Pa 57 Motor absorbed power kW 5.09
Total pressure Pa 1239 Total absorbed power kW 5.09
Fan absorbed power kW 4.03 Fan pulley SPZ 80
Efficiency % 62 Motor pulley SPZ 85
Fan bush -
Motor bush -
Belt length mm 1320
Number of belts 3
Flexible connection mm 453 x 453 x 100

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 89 88 85 83 82 80 76 72
Outlet dB 101 93 90 85 85 81 80 73

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 45 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 025

Page 46 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 025

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-4F-OT-01
Number off 1 AHU configuration Inline
Energy efficiency class D AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 732.15
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.120 Max. external leakage rate % 0.120
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 43.2
SFPint W/m³/s 249.32
3525
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 54 48 45 46 48 36 18 52
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 020 Air volume m³/hr 4332
External static Pa 872 Unit velocity m/s 1.85
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 83 76 74 69 66 57 53 75
Outlet dB 98 93 86 86 83 81 76 91

Page 47 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 025

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 1110 760 1880 Channel (150) 294.22
2 1110 760 2080 Channel (150) 243.23
3 1110 760 1100 Channel (150) 181.10

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 440mm Pressure drop: 32Pa


Recirc opening
Recirc opening
Standard mm 1000 x 272 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 1000 x 272 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 272Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 69
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 98
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 108
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 174
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W x H mm 1 x 287 x 592
Filter size: Qty x W x H mm 1 x 592 x 592

Page 48 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 025

COLD WATER COIL Length: 645mm Pressure drop: 345Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 17T 12R Fin material Epoxy-coated aluminium
825A 2.5P 17NC
Hygienic coil Yes
Duty (calculated) kW 104.67 Coil length mm 825
Duty (expected) kW 0.00 Coil height mm 540
Sensible Duty / SHR kW / % 51.29 / 49.0 Coil depth mm 420
Internal volume (per coil) litres 26.23
Inlet connection size 66.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 1.20 Fluid flow rate l/s 4.492
Inlet air DB temperature °C 46.00 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 32.00 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 38.29 Fluid velocity m/s 2.2
Outlet air DB temperature °C 10.27 Fluid pressure drop kPa 89.69
Outlet air WB temperature °C 10.27 Fluid type 100% Water
Outlet air relative humidity % 100.00
Face velocity m/s 2.70
Air pressure drop coil Pa 300 Air pressure drop coil (Dry) Pa 234
(Wet)
Extras
Air pressure drop elim Pa 45
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 20-25-30

ELECTRIC HEATER Length: 590mm Pressure drop: 2Pa


Supplier UKS 20-35 Coil code E 20-35
Air volume (per coil) m³/hr 4332 Duty kW 2.00
Air on db °C 15.6 Number of steps 2
Air off db °C 16.9 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 825
Coil height (per coil) mm 508
Face velocity m/s 2.87
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 740mm Pressure drop: 21Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 50

Page 49 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 025

FAN SECTION Length: 990mm Pressure drop: 0Pa


Fan type TLZ 250 Fan arrangement Single
Air volume m³/hr 4332 Motor x 1 Run
Fan outlet velocity m/s 11.61 Installed motor power kW 5.50
Required fan speed RPM 2627 Motor type IE2 One Speed
Max speed RPM 3000 Motor speed RPM 2900
External static pressure Pa 872 Voltage V 400
Extra static pressure Pa 0 Current A 10.3
System effect Pa 10 Motor efficiency % 87
Total static pressure Pa 1555 Motor shaft power kW 3.78
Dynamic pressure Pa 81 Motor absorbed power kW 4.33
Total pressure Pa 1636 Total absorbed power kW 4.33
Fan absorbed power kW 3.40 Fan pulley SPZ 140
Efficiency % 58 Motor pulley SPZ 125
Fan bush -
Motor bush -
Belt length mm 1250
Number of belts 1
Flexible connection mm 322 x 322 x 100

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 89 88 85 83 82 80 76 72
Outlet dB 105 98 93 86 86 83 81 76

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 50 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 026

Page 51 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 026

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-4F-OT-02
Number off 1 AHU configuration Inline
Energy efficiency class D AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 732.15
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.120 Max. external leakage rate % 0.120
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 43.2
SFPint W/m³/s 249.32
3525
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 54 48 45 46 48 36 18 52
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 020 Air volume m³/hr 4332
External static Pa 872 Unit velocity m/s 1.85
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 83 76 74 69 66 57 53 75
Outlet dB 98 93 86 86 83 81 76 91

Page 52 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 026

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 1110 760 1880 Channel (150) 294.22
2 1110 760 2080 Channel (150) 243.23
3 1110 760 1100 Channel (150) 181.10

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 440mm Pressure drop: 32Pa


Recirc opening
Recirc opening
Standard mm 1000 x 272 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 1000 x 272 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 272Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 69
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 98
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 108
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 174
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W x H mm 1 x 287 x 592
Filter size: Qty x W x H mm 1 x 592 x 592

Page 53 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 026

COLD WATER COIL Length: 645mm Pressure drop: 345Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 17T 12R Fin material Epoxy-coated aluminium
825A 2.5P 17NC
Hygienic coil Yes
Duty (calculated) kW 104.67 Coil length mm 825
Duty (expected) kW 0.00 Coil height mm 540
Sensible Duty / SHR kW / % 51.29 / 49.0 Coil depth mm 420
Internal volume (per coil) litres 26.23
Inlet connection size 66.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 1.20 Fluid flow rate l/s 4.492
Inlet air DB temperature °C 46.00 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 32.00 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 38.29 Fluid velocity m/s 2.2
Outlet air DB temperature °C 10.27 Fluid pressure drop kPa 89.69
Outlet air WB temperature °C 10.27 Fluid type 100% Water
Outlet air relative humidity % 100.00
Face velocity m/s 2.70
Air pressure drop coil Pa 300 Air pressure drop coil (Dry) Pa 234
(Wet)
Extras
Air pressure drop elim Pa 45
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 20-25-30

ELECTRIC HEATER Length: 590mm Pressure drop: 2Pa


Supplier UKS 20-35 Coil code E 20-35
Air volume (per coil) m³/hr 4332 Duty kW 2.00
Air on db °C 15.6 Number of steps 2
Air off db °C 16.9 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 825
Coil height (per coil) mm 508
Face velocity m/s 2.87
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 740mm Pressure drop: 21Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 50

Page 54 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 026

FAN SECTION Length: 990mm Pressure drop: 0Pa


Fan type TLZ 250 Fan arrangement Single
Air volume m³/hr 4332 Motor x 1 Run
Fan outlet velocity m/s 11.61 Installed motor power kW 5.50
Required fan speed RPM 2627 Motor type IE2 One Speed
Max speed RPM 3000 Motor speed RPM 2900
External static pressure Pa 872 Voltage V 400
Extra static pressure Pa 0 Current A 10.3
System effect Pa 10 Motor efficiency % 87
Total static pressure Pa 1555 Motor shaft power kW 3.78
Dynamic pressure Pa 81 Motor absorbed power kW 4.33
Total pressure Pa 1636 Total absorbed power kW 4.33
Fan absorbed power kW 3.40 Fan pulley SPZ 140
Efficiency % 58 Motor pulley SPZ 125
Fan bush -
Motor bush -
Belt length mm 1250
Number of belts 1
Flexible connection mm 322 x 322 x 100

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 89 88 85 83 82 80 76 72
Outlet dB 105 98 93 86 86 83 81 76

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 55 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 027

Page 56 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 027

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-4F-OT-03
Number off 1 AHU configuration Inline
Energy efficiency class D AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 732.15
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.120 Max. external leakage rate % 0.120
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 43.2
SFPint W/m³/s 249.32
3525
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 54 48 45 46 48 36 18 52
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 020 Air volume m³/hr 4332
External static Pa 872 Unit velocity m/s 1.85
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 83 76 74 69 66 57 53 75
Outlet dB 98 93 86 86 83 81 76 91

Page 57 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 027

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 1110 760 1880 Channel (150) 294.22
2 1110 760 2080 Channel (150) 243.23
3 1110 760 1100 Channel (150) 181.10

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 440mm Pressure drop: 32Pa


Recirc opening
Recirc opening
Standard mm 1000 x 272 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 1000 x 272 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 272Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 69
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 98
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 108
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 174
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W x H mm 1 x 287 x 592
Filter size: Qty x W x H mm 1 x 592 x 592

Page 58 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 027

COLD WATER COIL Length: 645mm Pressure drop: 345Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 17T 12R Fin material Epoxy-coated aluminium
825A 2.5P 17NC
Hygienic coil Yes
Duty (calculated) kW 104.67 Coil length mm 825
Duty (expected) kW 0.00 Coil height mm 540
Sensible Duty / SHR kW / % 51.29 / 49.0 Coil depth mm 420
Internal volume (per coil) litres 26.23
Inlet connection size 66.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 1.20 Fluid flow rate l/s 4.492
Inlet air DB temperature °C 46.00 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 32.00 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 38.29 Fluid velocity m/s 2.2
Outlet air DB temperature °C 10.27 Fluid pressure drop kPa 89.69
Outlet air WB temperature °C 10.27 Fluid type 100% Water
Outlet air relative humidity % 100.00
Face velocity m/s 2.70
Air pressure drop coil Pa 300 Air pressure drop coil (Dry) Pa 234
(Wet)
Extras
Air pressure drop elim Pa 45
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 20-25-30

ELECTRIC HEATER Length: 590mm Pressure drop: 2Pa


Supplier UKS 20-35 Coil code E 20-35
Air volume (per coil) m³/hr 4332 Duty kW 2.00
Air on db °C 15.6 Number of steps 2
Air off db °C 16.9 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 825
Coil height (per coil) mm 508
Face velocity m/s 2.87
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 740mm Pressure drop: 21Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 50

Page 59 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 027

FAN SECTION Length: 990mm Pressure drop: 0Pa


Fan type TLZ 250 Fan arrangement Single
Air volume m³/hr 4332 Motor x 1 Run
Fan outlet velocity m/s 11.61 Installed motor power kW 5.50
Required fan speed RPM 2627 Motor type IE2 One Speed
Max speed RPM 3000 Motor speed RPM 2900
External static pressure Pa 872 Voltage V 400
Extra static pressure Pa 0 Current A 10.3
System effect Pa 10 Motor efficiency % 87
Total static pressure Pa 1555 Motor shaft power kW 3.78
Dynamic pressure Pa 81 Motor absorbed power kW 4.33
Total pressure Pa 1636 Total absorbed power kW 4.33
Fan absorbed power kW 3.40 Fan pulley SPZ 140
Efficiency % 58 Motor pulley SPZ 125
Fan bush -
Motor bush -
Belt length mm 1250
Number of belts 1
Flexible connection mm 322 x 322 x 100

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 89 88 85 83 82 80 76 72
Outlet dB 105 98 93 86 86 83 81 76

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 60 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 028

Page 61 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 028

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-4F-OT-04
Number off 1 AHU configuration Inline
Energy efficiency class D AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 732.15
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.120 Max. external leakage rate % 0.120
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 43.2
SFPint W/m³/s 249.32
3525
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 54 48 45 46 48 36 18 52
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 020 Air volume m³/hr 4332
External static Pa 872 Unit velocity m/s 1.85
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 83 76 74 69 66 57 53 75
Outlet dB 98 93 86 86 83 81 76 91

Page 62 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 028

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 1110 760 1880 Channel (150) 294.22
2 1110 760 2080 Channel (150) 243.23
3 1110 760 1100 Channel (150) 181.10

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 440mm Pressure drop: 32Pa


Recirc opening
Recirc opening
Standard mm 1000 x 272 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 1000 x 272 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 272Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 69
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 98
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 108
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 174
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W x H mm 1 x 287 x 592
Filter size: Qty x W x H mm 1 x 592 x 592

Page 63 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 028

COLD WATER COIL Length: 645mm Pressure drop: 345Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 17T 12R Fin material Epoxy-coated aluminium
825A 2.5P 17NC
Hygienic coil Yes
Duty (calculated) kW 104.67 Coil length mm 825
Duty (expected) kW 0.00 Coil height mm 540
Sensible Duty / SHR kW / % 51.29 / 49.0 Coil depth mm 420
Internal volume (per coil) litres 26.23
Inlet connection size 66.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 1.20 Fluid flow rate l/s 4.492
Inlet air DB temperature °C 46.00 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 32.00 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 38.29 Fluid velocity m/s 2.2
Outlet air DB temperature °C 10.27 Fluid pressure drop kPa 89.69
Outlet air WB temperature °C 10.27 Fluid type 100% Water
Outlet air relative humidity % 100.00
Face velocity m/s 2.70
Air pressure drop coil Pa 300 Air pressure drop coil (Dry) Pa 234
(Wet)
Extras
Air pressure drop elim Pa 45
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 20-25-30

ELECTRIC HEATER Length: 590mm Pressure drop: 2Pa


Supplier UKS 20-35 Coil code E 20-35
Air volume (per coil) m³/hr 4332 Duty kW 2.00
Air on db °C 15.6 Number of steps 2
Air off db °C 16.9 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 825
Coil height (per coil) mm 508
Face velocity m/s 2.87
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 740mm Pressure drop: 21Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 50

Page 64 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 028

FAN SECTION Length: 990mm Pressure drop: 0Pa


Fan type TLZ 250 Fan arrangement Single
Air volume m³/hr 4332 Motor x 1 Run
Fan outlet velocity m/s 11.61 Installed motor power kW 5.50
Required fan speed RPM 2627 Motor type IE2 One Speed
Max speed RPM 3000 Motor speed RPM 2900
External static pressure Pa 872 Voltage V 400
Extra static pressure Pa 0 Current A 10.3
System effect Pa 10 Motor efficiency % 87
Total static pressure Pa 1555 Motor shaft power kW 3.78
Dynamic pressure Pa 81 Motor absorbed power kW 4.33
Total pressure Pa 1636 Total absorbed power kW 4.33
Fan absorbed power kW 3.40 Fan pulley SPZ 140
Efficiency % 58 Motor pulley SPZ 125
Fan bush -
Motor bush -
Belt length mm 1250
Number of belts 1
Flexible connection mm 322 x 322 x 100

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 89 88 85 83 82 80 76 72
Outlet dB 105 98 93 86 86 83 81 76

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 65 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 029

Page 66 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 029

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-TF-01
Number off 1 AHU configuration Inline
Energy efficiency class D AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 1940.91
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.093 Max. external leakage rate % 0.093
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 51.3
SFPint W/m³/s 237.18
7176
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 58 52 49 50 52 40 22 56
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 065 Air volume m³/hr 23548
External static Pa 498 Unit velocity m/s 2.18
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 87 80 78 73 70 61 57 79
Outlet dB 97 92 88 85 82 77 69 90

Page 67 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 029

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 2370 1435 1865 Channel (150) 736.05
2 2370 1435 2180 Channel (150) 556.37
3 2370 1435 1720 Channel (150) 624.39

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 545mm Pressure drop: 46Pa


Recirc opening
Recirc opening
Standard mm 2260 x 535 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 2260 x 535 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 284Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 79
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 104
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 122
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 181
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W x H mm 4 x 490 x 592
Filter size: Qty x W x H mm 4 x 592 x 592

Page 68 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 029

COLD WATER COIL Length: 525mm Pressure drop: 228Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 38T 8R Fin material Epoxy-coated aluminium
2025A 2.5P 76NC
Hygienic coil Yes
Duty (calculated) kW 138.40 Coil length mm 2025
Duty (expected) kW 136.22 Coil height mm 1207
Sensible Duty / SHR kW / % 110.72 / 80.0 Coil depth mm 320
Internal volume (per coil) litres 86.46
Inlet connection size 66.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 6.54 Fluid flow rate l/s 5.939
Inlet air DB temperature °C 25.98 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 18.26 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 47.67 Fluid velocity m/s 0.6
Outlet air DB temperature °C 12.05 Fluid pressure drop kPa 20.07
Outlet air WB temperature °C 11.70 Fluid type 100% Water
Outlet air relative humidity % 96.13
Face velocity m/s 2.68
Air pressure drop coil Pa 184 Air pressure drop coil (Dry) Pa 165
(Wet)
Extras
Air pressure drop elim Pa 45
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 55-60-65

ELECTRIC HEATER Length: 590mm Pressure drop: 1Pa


Supplier UKS 55-80 Coil code E 55-80
Air volume (per coil) m³/hr 23548 Duty kW 3.00
Air on db °C 15.6 Number of steps 3
Air off db °C 15.9 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 2025
Coil height (per coil) mm 1207
Face velocity m/s 2.68
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 840mm Pressure drop: 30Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 90 / ELMC 90 /
ELMC 50

FAN SECTION Length: 1610mm Pressure drop: 0Pa

Page 69 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 029

Fan type TLZ 630 Fan arrangement Single


Air volume m³/hr 23548 Motor x 1 Run
Fan outlet velocity m/s 10.20 Installed motor power kW 15.00
Required fan speed RPM 852 Motor type IE2 One Speed
Max speed RPM 1000 Motor speed RPM 1465
External static pressure Pa 498 Voltage V 400
Extra static pressure Pa 0 Current A 29.4
System effect Pa 14 Motor efficiency % 91
Total static pressure Pa 1101 Motor shaft power kW 12.72
Dynamic pressure Pa 62 Motor absorbed power kW 14.04
Total pressure Pa 1163 Total absorbed power kW 14.04
Fan absorbed power kW 11.45 Fan pulley SPZ DYNAM 150
Efficiency % 66 Motor pulley SPZ DYNAM 90
Fan bush -
Motor bush -
Belt length mm 2060
Number of belts 4
Flexible connection mm 801 x 801 x 100

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 93 92 89 87 86 84 80 76
Outlet dB 102 97 92 88 85 82 77 69

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 70 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 030

Page 71 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 030

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-TF-02
Number off 1 AHU configuration Inline
Energy efficiency class C AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 2094.21
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.092 Max. external leakage rate % 0.092
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 52.3
SFPint W/m³/s 211.59
7706
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 58 52 49 50 52 40 22 56
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 070 Air volume m³/hr 25213
External static Pa 498 Unit velocity m/s 2.14
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 87 80 78 73 70 61 57 79
Outlet dB 93 90 89 85 82 79 74 90

Page 72 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 030

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 2370 1560 1965 Channel (150) 812.38
2 2370 1560 2180 Channel (150) 569.09
3 2370 1560 1760 Channel (150) 688.08

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 645mm Pressure drop: 40Pa


Recirc opening
Recirc opening
Standard mm 2260 x 622 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 2260 x 622 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 275Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 71
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 99
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 111
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 175
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W xH mm 2 x 490 x 490
Filter size: Qty x W xH mm 2 x 592 x 287
Filter size: Qty x W xH mm 2 x 592 x 490
Filter size: Qty x W xH mm 2 x 490 x 592
Filter size: Qty x W xH mm 2 x 592 x 592
Filter size: Qty x W xH mm 2 x 490 x 287

Page 73 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 030

COLD WATER COIL Length: 525mm Pressure drop: 215Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 42T 8R Fin material Epoxy-coated aluminium
2025A 2.5P 84NC
Hygienic coil Yes
Duty (calculated) kW 150.57 Coil length mm 2025
Duty (expected) kW 147.84 Coil height mm 1334
Sensible Duty / SHR kW / % 118.95 / 79.0 Coil depth mm 320
Internal volume (per coil) litres 99.42
Inlet connection size 80.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 7.00 Fluid flow rate l/s 6.461
Inlet air DB temperature °C 26.08 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 18.32 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 47.55 Fluid velocity m/s 0.6
Outlet air DB temperature °C 11.98 Fluid pressure drop kPa 13.34
Outlet air WB temperature °C 11.65 Fluid type 100% Water
Outlet air relative humidity % 96.33
Face velocity m/s 2.59
Air pressure drop coil Pa 173 Air pressure drop coil (Dry) Pa 156
(Wet)
Extras
Air pressure drop elim Pa 42
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 70-75-80

ELECTRIC HEATER Length: 590mm Pressure drop: 1Pa


Supplier UKS 55-80 Coil code E 55-80
Air volume (per coil) m³/hr 25213 Duty kW 3.00
Air on db °C 15.6 Number of steps 3
Air off db °C 15.9 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 2025
Coil height (per coil) mm 1334
Face velocity m/s 2.59
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 840mm Pressure drop: 28Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 90 / ELMC 90 /
ELMC 60

FAN SECTION Length: 1650mm Pressure drop: 0Pa

Page 74 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 030

Fan type TLZ 630 Fan arrangement Single


Air volume m³/hr 25213 Motor x 1 Run
Fan outlet velocity m/s 10.92 Installed motor power kW 18.50
Required fan speed RPM 837 Motor type IE2 One Speed
Max speed RPM 1000 Motor speed RPM 1470
External static pressure Pa 498 Voltage V 400
Extra static pressure Pa 0 Current A 34.5
System effect Pa 14 Motor efficiency % 91
Total static pressure Pa 1070 Motor shaft power kW 13.08
Dynamic pressure Pa 71 Motor absorbed power kW 14.33
Total pressure Pa 1142 Total absorbed power kW 14.33
Fan absorbed power kW 11.77 Fan pulley SPA DYNAM 280
Efficiency % 68 Motor pulley SPA DYNAM 160
Fan bush -
Motor bush -
Belt length mm 2430
Number of belts 2
Flexible connection mm 801 x 801 x 100

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 93 92 89 87 86 84 80 76
Outlet dB 99 93 90 89 85 82 79 74

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 75 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 031

Page 76 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 031

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-TF-03
Number off 1 AHU configuration Inline
Energy efficiency class D AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 1839.75
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.095 Max. external leakage rate % 0.096
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 49.8
SFPint W/m³/s 231.08
6835
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 58 52 49 50 52 40 22 56
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 060 Air volume m³/hr 20388
External static Pa 498 Unit velocity m/s 2.07
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 87 80 78 73 70 61 57 79
Outlet dB 97 92 88 85 82 77 69 90

Page 77 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 031

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 2170 1435 1865 Channel (150) 687.72
2 2170 1435 2180 Channel (150) 526.40
3 2170 1435 1720 Channel (150) 602.41

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 545mm Pressure drop: 42Pa


Recirc opening
Recirc opening
Standard mm 2060 x 535 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 2060 x 535 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 279Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 74
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 101
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 115
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 178
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W x H mm 8 x 490 x 592

Page 78 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 031

COLD WATER COIL Length: 525mm Pressure drop: 208Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 38T 8R Fin material Epoxy-coated aluminium
1850A 2.5P 76NC
Hygienic coil Yes
Duty (calculated) kW 127.74 Coil length mm 1850
Duty (expected) kW 130.30 Coil height mm 1207
Sensible Duty / SHR kW / % 99.64 / 78.0 Coil depth mm 320
Internal volume (per coil) litres 79.94
Inlet connection size 66.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 5.66 Fluid flow rate l/s 5.481
Inlet air DB temperature °C 26.70 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 18.81 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 47.48 Fluid velocity m/s 0.6
Outlet air DB temperature °C 12.21 Fluid pressure drop kPa 16.83
Outlet air WB temperature °C 11.90 Fluid type 100% Water
Outlet air relative humidity % 96.56
Face velocity m/s 2.54
Air pressure drop coil Pa 168 Air pressure drop coil (Dry) Pa 150
(Wet)
Extras
Air pressure drop elim Pa 40
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 55-60-65

ELECTRIC HEATER Length: 590mm Pressure drop: 1Pa


Supplier UKS 55-80 Coil code E 55-80
Air volume (per coil) m³/hr 20388 Duty kW 3.00
Air on db °C 15.6 Number of steps 3
Air off db °C 16.0 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 1850
Coil height (per coil) mm 1207
Face velocity m/s 2.54
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 840mm Pressure drop: 27Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 90 / ELMC 90 /
ELMC 15

FAN SECTION Length: 1610mm Pressure drop: 0Pa

Page 79 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 031

Fan type TLZ 630 Fan arrangement Single


Air volume m³/hr 20388 Motor x 1 Run
Fan outlet velocity m/s 8.83 Installed motor power kW 15.00
Required fan speed RPM 842 Motor type IE2 One Speed
Max speed RPM 1000 Motor speed RPM 1465
External static pressure Pa 498 Voltage V 400
Extra static pressure Pa 0 Current A 29.4
System effect Pa 13 Motor efficiency % 91
Total static pressure Pa 1067 Motor shaft power kW 10.98
Dynamic pressure Pa 47 Motor absorbed power kW 12.12
Total pressure Pa 1113 Total absorbed power kW 12.12
Fan absorbed power kW 9.88 Fan pulley SPZ DYNAM 224
Efficiency % 64 Motor pulley SPZ DYNAM 125
Fan bush -
Motor bush -
Belt length mm 2240
Number of belts 2
Flexible connection mm 801 x 801 x 100

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 93 92 89 87 86 84 80 76
Outlet dB 102 97 92 88 85 82 77 69

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 80 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 032

Page 81 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 032

Untes is participating in the EUROVENT CERTIFICATION Program for Air Handling Units.
The range UKS PKC 60 Hij is certified under the number AHU-04-05-055 and presented on
www.eurovent-certification.com

CUSTOMER DETAILS
Customer Name Customer Number
Address
Town
Postcode
Country

GENERAL DATA
Product Air handling unit Customer reference AHU-TF-04
Number off 1 AHU configuration Inline
Energy efficiency class C AHU range UKS PKC 60 Hij
(2016)
Location Internal Total weight (each) kg 1733.93
Roof type None Atmospheric pressure kPa 101.33
Max. external leakage rate % 0.112 Max. external leakage rate % 0.112
@ -400 @ +400
Casing strength D1(M) Casing Air Leakage L1(M)
Filter Bypass Leakage F9(M) Thermal Transmittance T2(M)
Thermal Bridging Factor TB2(M)

Outdoor design °C 46.1


temperature
ErP identification code NRVU/UVU
nvu % 53.0
SFPint W/m³/s 207.71
6409
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Radiated casework SWL, 57 51 48 49 51 39 21 55
dB

PANEL DATA
Panel internal finish Standard Panel external finish Standard

CASING DATA
Base frame material Carbon steel Base frame height mm 150

SUPPLY DATA
Type UKS 055 Air volume m³/hr 19666
External static Pa 498 Unit velocity m/s 2.19
Internal skin material inn 0,8 mm stainless External skin material ext 1,0 mm Coated
Panel type 60mm Polyurethane

Operating sound power


level
Frequency 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz dB(A)
Inlet dB 86 79 77 72 69 60 56 78
Outlet dB 94 88 90 87 84 80 76 92

Page 82 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 032

In direction of airflow, the unit comprises:


DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 2170 1320 1785 Channel (150) 647.06
2 2170 1320 2180 Channel (150) 514.96
3 2170 1320 1630 Channel (150) 549.20

SUPPLY COMPONENTS

SINGLE MIXING SECTION Length: 465mm Pressure drop: 53Pa


Recirc opening
Recirc opening
Standard mm 2060 x 447 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Fresh air opening
Fresh air opening
Standard mm 2060 x 447 x 110 Damper torque Nm
Damper motor None Air damper External, Opposed blades
Recirculated Air % 0
ACCESS
Access type Hinged door no key Access side Right

COMBINED FILTER SECTION Length: 685mm Pressure drop: 274Pa


Pre-filter
Manufacturer Üntes Initial pressure drop Pa 70
Sub type Panel Final pressure drop Pa 128
Filter class G4 (>=Coarse 60%) Design pressure drop Pa 99
Filter energy class
Media length mm 50
Final filter
Manufacturer Üntes Initial pressure drop Pa 110
Sub type HAV, Self-Sealing Final pressure drop Pa 240
Filter class F8 (>=ePM1 70%) Design pressure drop Pa 175
Filter energy class D
Media length mm 535
Combined filter
Withdrawal method Front Filter size: Qty x W x H mm 8 x 490 x 592

Page 83 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 032

COLD WATER COIL Length: 525mm Pressure drop: 245Pa


Designed for wet
conditions
Coil code F 32x28-1/2 C S 34T 8R Fin material Epoxy-coated aluminium
1850A 2.5P 34NC
Hygienic coil Yes
Duty (calculated) kW 167.98 Coil length mm 1850
Duty (expected) kW 0.00 Coil height mm 1080
Sensible Duty / SHR kW / % 115.91 / 69.0 Coil depth mm 320
Internal volume (per coil) litres 74.52
Inlet connection size 80.0 mm

Air Side Features Fluid Side Features


Air flow rate m³/s 5.46 Fluid flow rate l/s 7.206
Inlet air DB temperature °C 29.21 Inlet fluid temperature °C 7.2
Inlet air WB temperature °C 20.47 Outlet fluid temperature °C 12.8
Inlet air relative humidity % 45.49 Fluid velocity m/s 1.7
Outlet air DB temperature °C 11.57 Fluid pressure drop kPa 75.05
Outlet air WB temperature °C 11.20 Fluid type 100% Water
Outlet air relative humidity % 95.85
Face velocity m/s 2.74
Air pressure drop coil Pa 198 Air pressure drop coil (Dry) Pa 171
(Wet)
Extras
Air pressure drop elim Pa 47
Drain pan type Sloping
Drain plug and air vent Included

ACCESS SECTION Length: 440mm Pressure drop: 0Pa

Access type Hinged door no key Access side Right

EXTRAS
1 x UV LAMP FOR HEATEXCHANGER UKS 55-60-65

ELECTRIC HEATER Length: 590mm Pressure drop: 1Pa


Supplier UKS 55-80 Coil code E 55-80
Air volume (per coil) m³/hr 19666 Duty kW 3.00
Air on db °C 15.6 Number of steps 3
Air off db °C 16.0 Duty per step kW 1.25
Voltage 380 V
Number of coils 1
Coil width (per coil) mm 1850
Coil height (per coil) mm 1079
Face velocity m/s 2.74
Section length mm 590
EXTRAS
1 x MAINTENANCE SWITCH 0-4,0 kW

PLENUM SECTION Length: 200mm Pressure drop: 0Pa

INDIRECT STEAM HUMIDIFIER Length: 840mm Pressure drop: 30Pa


Model Type Proportional On/Off Mounting External / Right
Model Selected ELMC 90 / ELMC 90 /
ELMC 15

FAN SECTION Length: 1520mm Pressure drop: 0Pa

Page 84 of 85
Technical Specification

Project name : Shifa International Hospital, Hygienic AHU' WinTADS Lite - 1.10.00122.0
Quotation no. : 0405-21-00 / 032

Fan type TLZ 560 Fan arrangement Single


Air volume m³/hr 19666 Motor x 1 Run
Fan outlet velocity m/s 10.69 Installed motor power kW 15.00
Required fan speed RPM 959 Motor type IE2 One Speed
Max speed RPM 1200 Motor speed RPM 1465
External static pressure Pa 498 Voltage V 400
Extra static pressure Pa 0 Current A 29.4
System effect Pa 14 Motor efficiency % 91
Total static pressure Pa 1115 Motor shaft power kW 10.41
Dynamic pressure Pa 69 Motor absorbed power kW 11.49
Total pressure Pa 1184 Total absorbed power kW 11.49
Fan absorbed power kW 9.37 Fan pulley SPZ DYNAM 150
Efficiency % 69 Motor pulley SPZ DYNAM 100
Fan bush -
Motor bush -
Belt length mm 1950
Number of belts 3
Flexible connection mm 715 x 715 x 100

Fan sound data SWL


Frequency 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Inlet dB 92 91 88 86 85 83 79 75
Outlet dB 97 94 88 90 87 84 80 76

ACCESS
Access type Hinged door no key Access side Right
EXTRAS
1 x DOOR SWITCH AND EMERGENCY STOP BUTTON 1 x VARIABLE PITCH PULLEY
1 x SIDE GLASS 1 x LIGHTING

Page 85 of 85

You might also like