Professional Documents
Culture Documents
Dear Si1
Dear Si1
Dear Si1
Dear Sir,
For the power distribution system, we will require the exact AC power that the electrolyser will
consume on the AC side. This data is necessary for optimizing the system on the medium voltage
(MV) side.
Based on our understanding, please find below the calculation using the data received from Avina:
6.13333
MW AC Power
3
Assumed the Power Factor:0.9(to be
0.9
confirmed by the client)
6.81481
MVA MVA Per Stack
5
13.6296
MVA Total MVA for two stacks
3