32 GENERAL NOTES 32

31 A. FOR DETAILS ABOUT FIRE PROTECTION PHILOSOPHY, REFER TO DOCUMENT 31


"FIREFIGHTING SYSTEM SPECIFICATION" CODED AS 079254-0000-JSD-1900-001.
30 B. ALL FIREFIGHTING EQUIPMENT SHALL BE IN COMPLIANCE WITH PROJECT DOC 30
FIREFIGHTING SYSTEM SPECIFICATION CODED AS 079254C-0000-JSD-1900-001.
29 10-1E10-U-000-17- C. VERTICAL TRAFFIC POST (BOLLARDS) SHALL BE INSTALLED TO PROTECT HYDRANTS 29
FWA-PTJ-00046-U AND MONITORS WHEN REQUIRED.
28 D. HYDRANT TO BE LOCATED NOT LESS THAN 1.5 m FROM THE CURB OF ROAD. 0 28

27 PLZ PLZ 27
001 002
26 FIRE WATER FIRE WATER 26
14"-FWA-62701301 -ADP0HU1-N 14"-FWA-10701301 -ADP0HU1 -N 14"-FWA-59705302 -ADP0HU1 -N
43649 1062-701-1 43453 1M59-705-1
25
FROM/TO RR&L 14" 14" FROM/TO RIP NOTES 25

1M59
1E10
1062

1E10
24 6"X4" 6"X4" 6"X4" 1. FIRE MONITORS TO BE LOCATED IN A PLATFORM AND AT 1m ELEVATION ABOVE TANK 24

6"
DIKE T.O.C, IN ORDER TO FACILITATE THE COOLING OF TANK WALL (10-TK-101/102)
WHEN REQUIRED.

MIN
23 23
2. VALVE SHALL BE ACCESSIBLE AND OPERABLE FROM GRADE.
22 UG ADP0HU1 UG ADP0HU1 UG ADP0HU1 UG ADP0HU1 22
3. FOAM-WATER MONITOR EQUIPPED WITH ONE AFFF FOAM CONCENTRATE BULK DRUM
AG ACS3A00 AG ACS3A00 AG ACS3A00 AG ACS3A00 (1m3 CAPACITY) AND SELF-EDUCTING NOZZLE CAPABLE TO DELIVER 120m3/h
21 21
WATER-FOAM SOLUTION.
4. BUTTERFLY VALVE UL/FM CERTIFIED AND WAFER TYPE TO BE PROVIDED BY MONITOR
The present document or drawing is property of TECHNIP ENERGIES ITALY S.p.A. and shall not, under any circumstances, be totally or partially, drectly or undirectly, transferred, reproduced, copied, disclosed or used, without its prior written consent,

20 20
4"-FWA-10701309 -ACS3A00-N 4"-FWA-10701310 -ACS3A00-N 4"-FWA-10701311 -ACS3A00-N MANUFACTURER.
0
19 2 6" 5. BATTERY LIMIT FLANGE 2"-150# RF, LOCATED IN THE VERTICAL PIPE AT 1800mm 19
ELEVATION FROM H.P.P AND WITH AN HORIZONTAL OFFSET CORRESPONDING TO
18 600mm RESPECT TO THE CENTER OF THE HOSE REEL. GASKETS AND BOLTS IN 18
BATTERY LIMIT FLANGE ARE OUTSIDE OF MANUFACTURER SCOPE OF WORK.
17
6 6. INLET FLANGE 4"-150# RF TO BE LOCATED AT 1100mm ELEVATION FROM H.P.P AND 17
7

6"-FWA-10701302 -ACS3A00-N
6
SUITABLE TO CONNECT THE BATTERY LIMIT BUTTERFLY VALVE WAFER TYPE INSIDE
16 0 4" MFR 0 4" MFR MANUFACTURER SCOPE. GASKETS AND BOLTS IN BATTERY LIMIT FLANGE ARE OUTSIDE 16
0 4" MFR
OF MANUFACTURER SCOPE OF WORK.
15 4 4 15
4 7. INLET FLANGE 4"-150# RF SUITABLE TO CONNECT THE BATTERY LIMIT BUTTERFLY
VALVE WAFER TYPE INSIDE MANUFACTURER SCOPE. GASKETS AND BOLTS IN BATTERY
14 LIMIT FLANGE ARE OUTSIDE OF MANUFACTURER SCOPE OF WORK. 14
10-MLZ-003 10-MLZ-004 3
13 1 13

12 12
10-MLZ-005
11 11
MFR
10 10
HR

09 10-RLZ-002 09

5
08 08

0
07 07

06 06

05 05

04 04

03 2" 03

02 02

3
01 01
10-MLZ-002 2" 10-MLZ-001
0
1
4
TO DELUGE VALVE

4
1E10-702-1

4" 0 2 6" 4" 0


MFR MFR
1E10-DV-9501
FIRE WATER

7 6

4"-FWA-10701304 -ACS3A00-N
43467

4"-FWA-10701307-ACS3A00-N
for any purpose and in any way other than that for which it is specifically furnished or outside the extent of the agreed upon right of use.

0
5
MFR
ACS3A00 10-RLZ-001 AG ACS3A00
AG AG ACS3A00
ADP0HU1 HR
UG ADP0HU1
UG ADP0HU1 UG

MIN
MIN

6"-FWA-10701303 -ADP0HU1-N
6"X4" 6"X4"

6"-FWA-10701308 -ADP0HU1 -N 6"-FWA-10701306-ADP0HU1 -N


6"-FWA-10701305 -ADP0HU1-N

PLZ
Sneider Tavera Corrado Pigna
003
Mauro De Leonibus Claudia Pascali
6" 18 May ISSUE FOR CONSTRUCTION R.LIPPI/ C.PASCALI/
1E10 1E10 0
2022 (IFC)
M.DE LEONIBUS S.TAVERA C.PIGNA
1E10 1E10
1062 1062 27 Aug ISSUE FOR DETAILED DESIGN C.PASCALI/
1062 1062 D M.DE LEONIBUS
R.LIPPI/
S.TAVERA
2021 (IDD1) C.PIGNA

29 Jan ISSUE FOR REVIEW R.LIPPI/ C.PASCALI/


6"-FWA-62701311 -ADP0HU1 -N

6"-FWA-62701311 -ADP0HU1-N
S.OLIVA
6"-FWA-62701311 -ADP0HU1 -N

6"-FWA-62701311 -ADP0HU1 -N

2021 GENERAL REVISION S.TAVERA C.PIGNA

09 Aug ISSUE FOR EARLY WORKS C.PASCALI/


B M.GALLO S.TAVERA
2019 GENERAL REVISION C.PIGNA

24 May C.PASCALI/
A ISSUE FOR REVIEW M.GALLO S.TAVERA
C.PIGNA
2019

REV. DATE DESCRIPTION PREPARED CHECKED APPROVED/


AUTHORIZED

ANOPC
ASSIUT NATIONAL OIL PROCESSING COMPANY
‫ﴍﻛـﺔ ٔﺳـ ﯿﻮط اﻟﻮﻃﻨﯿـﺔ ﻟﺘﺼـﻨﯿﻊ اﻟﺒـﱰول‬

079254C-1E10-PID-1931-701-1.pid
ASSIUT HYDROCRACKING COMPLEX - ANOPC
PIPING & INSTRUMENT DIAGRAM
Sour Water Stripper Unit (SWSU)
1062-701-1
1062-701-1

1062-701-1

1062-701-1
FROM/TO RR&L
FIRE WATER
FIRE WATER

FIRE WATER

FIRE WATER

FIREWATER DISTRIBUTION
FROM RR&L

FROM RR&L

FROM RR&L
45421

45422

45424

CAD Model:
45560

Scale Project Unit Disc. Type Disc Subj Ser. No Sheet Rev.
NONE 079254C 1E10 PID 19 31 701 1 1
of 0

TECHNIP ENERGIES ITALY S.p.A. - 00148 ROMA - Viale Castello della Magliana, 68
PIP ING SPEC. C. A. DES. P RESS. OP ER. PRESS. DES. TEM P . OPER. TEM P. TEST P RESS. FLUID P AINT NDT PED TEST IPS NP D INS. INS. THK TRACING TRACING
or reverse engineer the same, in any manner, without ANOPC prior written consent and/or Technip Energies Italy S.p.A. prior written consent, and shall not put in use the information for any purpose unrelated to that for which it has been transmitted to recipient. An y disclosure and use of the contents hereof shall be subject
P&ID
SP EC.
SP EC. M A T
RATING (mm) (Kg/cm2g) (Kg/cm2g) (°C) (°C) (Kg/cm2g) PHA SE NO.
P WHT
RT / M T CA T. TYPE E (inch) TYPE (mm) CODE SIZE BILL OF MATERIAL SKETCH LIST
N
agreements between ANOPC, Technip Energies Italy S.p.A. and the intended recipient. The copyright in this document and/or attachments is owned by ANOPC and Technip Energies Italy S.p.A.. while the underlying IP is owned by other Tecnology Providers and an y reproduction or adaptation thereof to any subsisting
1E10-PID-1931-701-1 ADP 0HU1 HDPE 150 lbs 0 12 7 50 37 L NO PA INT - - H 14 0 POS DESCRIPTION THK1 THK2 ASBL/ IDENT DIAMETER QTY
1E10-PID-1931-701-1 ADP 0HU1 HDPE 150 lbs 0 12 7 50 37 L NO PA INT - - H 6 0 NO DEST (PCS/MM)
This document and its attachments, if any, contains confidential and proprietary information belonging to ANOPC, and/or other third parties, including Technip Energies Italy S.p.A. The intended recipient of the information contained here in shall not divu lge the same to any third part or sell, trade, publish, reproduce

1E10-PID-1931-701-1 ADP 0HU1 HDPE 150 lbs 0 12 7 50 37 L NO PA INT - - H 4 0


ERECTION

1 Pipes (Length),ASTM D3035,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44JJJ6C 14 11185

Ends,-, C44JJJ6C, 7,

2 Pipes (Length),ASTM D3035,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44JJJWW 6 1310

Ends,-, C44JJJWW, 7,

3 Pipes (Length),ASTM D3035,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44JJJT3 4 238
F8/13 G10 B11 12 Ends,-, C44JJJT3, 7,
381 STEM UP 4 Red Te,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion Ends,Mnf SDR9 SDR9 7 C44S0L06 14X6 1
PLZ-002 1 Std, C44S0L06, 7,

5 90° Elb LR,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44K99EG 14 2
Class 150 FF Ends,Mnf Std, C44K99EG, 7,
G10 B11
280 CLASS: 6 Conc Reducer,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C4TBFGZX 6X4 1

Ends,Mnf Std, C4TBFGZX, 7,


CONT. ON ACS3A00
7 90° Elb LR,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44K9A50 6 1
BT1 CLASS:
1M59U02-FWA-1M59705302-0001
64 0 29 ADP0HU1 Ends,Mnf Std, C44K9A50, 7,
W 1830900 305 FW 10 BT2
148
8 Back Flg (SO Stub),Mnf Std,ASTM A536 Gr.60-40-18,FF,150 Lbs, 7 C451R3DY 14 1
N 238170 F9/14 C451R3DY, 7,
EL.111750 1 9 Back Flg (SO Stub),Mnf Std,ASTM A536 Gr.60-40-18,FF,150 Lbs, 7 C451R3E5 4 1

304 1 69 C451R3E5, 7,

238
FW FW 10 NM Flat Gk,ASME B16.21,FF as per ASME B16.5,IBC Type,150 Lbs, , 2 C3P9L482 14 2
2 14"NS 2,
FW 3
11 HHx MBlt 1 HHx N&2W,ASME B18.2.1/ASME B18.2.2,Full Length 2 C88ZGDD 1 24
4 4"NS
14X6"NS 6 70 Threaded, C88ZGDD, 2, - 170 mm Length

12 Gat Flg,AWWA C509/C515,ASTM A536 Gr.65-45-12,FF,150 Lbs, 7 C4KDM3L9 14 1


W 1841900 232
B.O.P. 665 3 68 C4KDM3L9, 7,
1 FW 67 13 Stub SP,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion Ends,Mnf SDR9 7 C44K9201 14 1
EL.111572 6 FW
Std,
6X4"NS FW

202
5 432

2
14 Stub SP,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion Ends,Mnf SDR9 7 C44K92KS 4 1

B.O.P. 4 2 66 Std,

EL.111572 5 FW 11 FW
FW 665 08
CONT. ON 230
1E10A02-FWA-1E10701310-0001
W 1841900
N 236400
486

EL.112800

7
1

65
6 FW B.O.P.
FW 230 EL.111666
14"NS
665

665
CONT. ON 5
FWA-1E10701301-0001 SHT 02 B.O.P.
W 1844205 EL.109756
N 238170
EL.109933
shall require ANOPC's and/or, when needed, Technip Energies Italy S.p.A.'s express written approval.

TOTAL NUMBER OF SPOOLS: 0


SUPPORT SYMBOLOGY
Y
COM STD or SPC support common SPC
to more than one line Special Piping Support
S-
e.g.: line support Refer to supp. dwgs collections 079254C-"UNIT"-DW-1360-00
PRF STD Z X
STD or SPC support welded to pipe at Standard Piping Support
workshop during pipe spools prefabrication Refer to supp. dwgs collection 079254C-0000-STC-1390-000 INPUT AND OUTPUT
DATA FOR PIPELINE
MRS EFFORT ANALYSIS
Itemized Piping Supports ARE BASED ON
SYSTEM OF
For Itemized Piping Supports refer to Material Requisition 079254C-0000-MR-1383-001 COORDINATES AS
IN THE DRAWING

ASSIUT HYDROCRACKING COMPLEX - ANOPC


1) ALL DIMENSIONS ARE IN MILLIMITERS
1) CONSTRUCTION LINE LIST: 079254C-'UNIT'-NM-1300-012 4) CONSTRUCTION SPECIFICATION FOR PIPING PREFABRICATION ERECTION AND N WELD
REFERENCE

SYMBOLOGY
2) DIMENSIONS AND LAYOUT OF SOCKET WELDED AND THREADED LINES ARE INDICATIVE ONLY AND SHALL BE CHECKED
AT JOB SITE BEFORE ERECTION
DOCUMENTS 2) PIPING MATERIAL CLASSES: 079254C-0000-JSD-1300-001 NON DESTRUCTIVE EXAMINATION: 079254C-0000-MS-1320-051 N FIELD WELD
NOTES - VALID ONLY FOR U/G PIPING SKETCHES -
3) TOTAL LENGTH OF U/G PIPING TO BE CONSIDERED INCLUSIVE OF EXPANSION JOINTS OR ANY EMBEDDED PIPE INTO PITS FOR DESIGN 3) TECHNICAL SPECIFICATION FOR PIPING PREFABRICATION 5) FOR STRESS ANALYSIS "FLEXIBILITY LEVELS" AND STRESS ANALYSIS TRACED LINE No. 14"-FWA-1E10701301-ADP0HU1-N ISOMETRIC ID. 1E10U01-FWA-1E10701301
4) ISOMETRIC SKETCHES PREVAIL ON 2D AREA DRAWINGS
5) FOR 45deg MITER BENDS, ONLY ONE CONSTRUCTION WELD SHALL BE CONSIDERED (REF. TO APPLICABLE STANDARD) CONDITION AND ERECTION: 079254C-0000-MS-1300-001 CALCULATIONS NUMBERS REFER TO DOC.: 079254C-'UNIT'-NM-1370-001 SUPPORT
6) THE INITIAL AND FINAL COORDINATES IN ELEVATION ARE SHOWN AT CENTER OF PIPELINE. WHILE AT EACH CHANGE IN PIPE ELEVATION (COMPONENTS)
IT IS SHOWN AS BOP (BOTTOM OF PIPE) POSITION
PROJ. AREA DOC. TYPE SERVICE UNIT SEQUENCE N. SUBLINE SHEET OF SHEETS REV
1 21/06/2022 ISSUED FOR CONSTRUCTION N.A. N.A. A.S./F.F 0 16/06/2022 ISSUED FOR CONSTRUCTION N.A. N.A. A.S./F.F
REV DATE DESCRIPTION STRESS INSTR APPR. REV DATE DESCRIPTION STRESS INSTR APPR. REV DATE DESCRIPTION STRESS INSTR APPR.
079254C 1E10U01 ISO FWA 1E10 701301 0001 01 06 1
EXTRACTION DATE: 21/06/2022 15:42 Technip Energies Italy S.p.A - 00148 ROMA - Viale Castello della Magliana, 68
PIP ING SPEC. C. A. DES. P RESS. OP ER. PRESS. DES. TEM P . OPER. TEM P. TEST P RESS. FLUID P AINT NDT PED TEST IPS NP D INS. INS. THK TRACING TRACING
or reverse engineer the same, in any manner, without ANOPC prior written consent and/or Technip Energies Italy S.p.A. prior written consent, and shall not put in use the information for any purpose unrelated to that for which it has been transmitted to recipient. An y disclosure and use of the contents hereof shall be subject
P&ID
SP EC.
SP EC. M A T
RATING (mm) (Kg/cm2g) (Kg/cm2g) (°C) (°C) (Kg/cm2g) PHA SE NO.
P WHT
RT / M T CA T. TYPE E (inch) TYPE (mm) CODE SIZE BILL OF MATERIAL SKETCH LIST
N
agreements between ANOPC, Technip Energies Italy S.p.A. and the intended recipient. The copyright in this document and/or attachments is owned by ANOPC and Technip Energies Italy S.p.A.. while the underlying IP is owned by other Tecnology Providers and an y reproduction or adaptation thereof to any subsisting
1E10-PID-1931-701-1 ADP 0HU1 HDPE 150 lbs 0 12 7 50 37 L NO PA INT - - H 14 0 POS DESCRIPTION THK1 THK2 ASBL/ IDENT DIAMETER QTY
1E10-PID-1931-701-1 ADP 0HU1 HDPE 150 lbs 0 12 7 50 37 L NO PA INT - - H 6 0 NO DEST (PCS/MM)
This document and its attachments, if any, contains confidential and proprietary information belonging to ANOPC, and/or other third parties, including Technip Energies Italy S.p.A. The intended recipient of the information contained here in shall not divu lge the same to any third part or sell, trade, publish, reproduce

ERECTION

1 Pipes (Length),ASTM D3035,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44JJJ6C 14 3348

Ends,-, C44JJJ6C, 7,

2 Pipes (Length),ASTM D3035,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44JJJWW 6 27039

Ends,-, C44JJJWW, 7,

3 Red Te,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion Ends,Mnf SDR9 SDR9 7 C44S0L06 14X6 1

Std, C44S0L06, 7,

CONT. ON 4 90° Elb LR,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44K9A50 6 3

FWA-1E10701301-0001 SHT 01 Ends,Mnf Std, C44K9A50, 7,

W 1844205 5 Back Flg (SO Stub),Mnf Std,ASTM A536 Gr.60-40-18,FF,150 Lbs, 7 C451R3E6 6 1

N 238170 C451R3E6, 7,

EL.109933 6 Stub SP,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion Ends,Mnf SDR9 7 C44K92PJ 6 1

Std,
3 4 CONT. ON
14X6"NS B.O.P. 1E10A02-FWA-1E10701302-0001 CLASS:
W 1846000 EL.111416 W 1846000 ACS3A00
B.O.P. N 211982
EL.109756 CLASS:
EL.112800 ADP0HU1
230
305
90 59
14 7 FW 203
FW
25 F5/6
1 14"NS 08
304 58
FW 63
8 FW

867
FW
2 2
58 231 11 6"NS
18 50
0 230

1106
9
FW 57
FW
432 55 2 2
1 11 60 230
FW 05 FW
14"NS 8
CONT. ON
FWA-1E10701301-0001 SHT 03 230
W 1848163 62
N 238170 56 61 FW
EL.109933 FW FW 4

230 4
B.O.P.
EL.109849
shall require ANOPC's and/or, when needed, Technip Energies Italy S.p.A.'s express written approval.

TOTAL NUMBER OF SPOOLS: 0


SUPPORT SYMBOLOGY
Y
COM STD or SPC support common SPC
to more than one line Special Piping Support
S-
e.g.: line support Refer to supp. dwgs collections 079254C-"UNIT"-DW-1360-00
PRF STD Z X
STD or SPC support welded to pipe at Standard Piping Support
workshop during pipe spools prefabrication Refer to supp. dwgs collection 079254C-0000-STC-1390-000 INPUT AND OUTPUT
DATA FOR PIPELINE
MRS EFFORT ANALYSIS
Itemized Piping Supports ARE BASED ON
SYSTEM OF
For Itemized Piping Supports refer to Material Requisition 079254C-0000-MR-1383-001 COORDINATES AS
IN THE DRAWING

ASSIUT HYDROCRACKING COMPLEX - ANOPC


1) ALL DIMENSIONS ARE IN MILLIMITERS
1) CONSTRUCTION LINE LIST: 079254C-'UNIT'-NM-1300-012 4) CONSTRUCTION SPECIFICATION FOR PIPING PREFABRICATION ERECTION AND N WELD
REFERENCE

SYMBOLOGY
2) DIMENSIONS AND LAYOUT OF SOCKET WELDED AND THREADED LINES ARE INDICATIVE ONLY AND SHALL BE CHECKED
AT JOB SITE BEFORE ERECTION
DOCUMENTS 2) PIPING MATERIAL CLASSES: 079254C-0000-JSD-1300-001 NON DESTRUCTIVE EXAMINATION: 079254C-0000-MS-1320-051 N FIELD WELD
NOTES - VALID ONLY FOR U/G PIPING SKETCHES -
3) TOTAL LENGTH OF U/G PIPING TO BE CONSIDERED INCLUSIVE OF EXPANSION JOINTS OR ANY EMBEDDED PIPE INTO PITS FOR DESIGN 3) TECHNICAL SPECIFICATION FOR PIPING PREFABRICATION 5) FOR STRESS ANALYSIS "FLEXIBILITY LEVELS" AND STRESS ANALYSIS TRACED LINE No. 14"-FWA-1E10701301-ADP0HU1-N ISOMETRIC ID. 1E10U01-FWA-1E10701301
4) ISOMETRIC SKETCHES PREVAIL ON 2D AREA DRAWINGS
5) FOR 45deg MITER BENDS, ONLY ONE CONSTRUCTION WELD SHALL BE CONSIDERED (REF. TO APPLICABLE STANDARD) CONDITION AND ERECTION: 079254C-0000-MS-1300-001 CALCULATIONS NUMBERS REFER TO DOC.: 079254C-'UNIT'-NM-1370-001 SUPPORT
6) THE INITIAL AND FINAL COORDINATES IN ELEVATION ARE SHOWN AT CENTER OF PIPELINE. WHILE AT EACH CHANGE IN PIPE ELEVATION (COMPONENTS)
IT IS SHOWN AS BOP (BOTTOM OF PIPE) POSITION
PROJ. AREA DOC. TYPE SERVICE UNIT SEQUENCE N. SUBLINE SHEET OF SHEETS REV
1 21/06/2022 ISSUED FOR CONSTRUCTION N.A. N.A. A.S./F.F 0 16/06/2022 ISSUED FOR CONSTRUCTION N.A. N.A. A.S./F.F
REV DATE DESCRIPTION STRESS INSTR APPR. REV DATE DESCRIPTION STRESS INSTR APPR. REV DATE DESCRIPTION STRESS INSTR APPR.
079254C 1E10U01 ISO FWA 1E10 701301 0001 02 06 1
EXTRACTION DATE: 21/06/2022 15:42 Technip Energies Italy S.p.A - 00148 ROMA - Viale Castello della Magliana, 68
PIP ING SPEC. C. A. DES. P RESS. OP ER. PRESS. DES. TEM P . OPER. TEM P. TEST P RESS. FLUID P AINT NDT PED TEST IPS NP D INS. INS. THK TRACING TRACING
or reverse engineer the same, in any manner, without ANOPC prior written consent and/or Technip Energies Italy S.p.A. prior written consent, and shall not put in use the information for any purpose unrelated to that for which it has been transmitted to recipient. An y disclosure and use of the contents hereof shall be subject
P&ID
SP EC.
SP EC. M A T
RATING (mm) (Kg/cm2g) (Kg/cm2g) (°C) (°C) (Kg/cm2g) PHA SE NO.
P WHT
RT / M T CA T. TYPE E (inch) TYPE (mm) CODE SIZE BILL OF MATERIAL SKETCH LIST
N
agreements between ANOPC, Technip Energies Italy S.p.A. and the intended recipient. The copyright in this document and/or attachments is owned by ANOPC and Technip Energies Italy S.p.A.. while the underlying IP is owned by other Tecnology Providers and an y reproduction or adaptation thereof to any subsisting
1E10-PID-1931-701-1 ADP 0HU1 HDPE 150 lbs 0 12 7 50 37 L NO PA INT - - H 14 0 POS DESCRIPTION THK1 THK2 ASBL/ IDENT DIAMETER QTY
1E10-PID-1931-701-1 ADP 0HU1 HDPE 150 lbs 0 12 7 50 37 L NO PA INT - - H 6 0 NO DEST (PCS/MM)
This document and its attachments, if any, contains confidential and proprietary information belonging to ANOPC, and/or other third parties, including Technip Energies Italy S.p.A. The intended recipient of the information contained here in shall not divu lge the same to any third part or sell, trade, publish, reproduce

1E10-PID-1931-701-1 ADP 0HU1 HDPE 150 lbs 0 12 7 50 37 L NO PA INT - - H 4 0


ERECTION

1 Pipes (Length),ASTM D3035,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44JJJ6C 14 20978

Ends,-, C44JJJ6C, 7,

2 Pipes (Length),ASTM D3035,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44JJJWW 6 1310

Ends,-, C44JJJWW, 7,

3 Pipes (Length),ASTM D3035,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44JJJT3 4 238
5
Ends,-, C44JJJT3, 7,
665 B.O.P.
4 Red Te,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion Ends,Mnf SDR9 SDR9 7 C44S0L06 14X6 1
EL.111572
Std, C44S0L06, 7,

5 90° Elb LR,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44K99EG 14 2

Ends,Mnf Std, C44K99EG, 7,

665 6 Conc Reducer,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C4TBFGZX 6X4 1

Ends,Mnf Std, C4TBFGZX, 7,

2 7 90° Elb LR,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44K9A50 6 1
5 12
54 FW Ends,Mnf Std, C44K9A50, 7,

8 Back Flg (SO Stub),Mnf Std,ASTM A536 Gr.60-40-18,FF,150 Lbs, 7 C451R3E5 4 1

1
C451R3E5, 7,
1

486
9 Stub SP,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion Ends,Mnf SDR9 7 C44K92KS 4 1
13
Std,
FW
14 11
CONT. ON FW
1E10A02-FWA-1E10701311-0001 FW
CLASS:
W 1866750 00 ACS3A00 665
N 236400 1 15 CLASS:
EL.112800 Class 150 FF
ADP0HU1
305 1 148 10
15 14"NS
FW FW
F8/9

238
54 6
305 49 FW 6X4"NS
FW 665
0 3 232
3 54 4"NS
53
FW 52
16 432 FW

202
2
FW 51
2 FW
CONT. ON
1 4 FWA-1E10701301-0001 SHT 02
14"NS 14X6"NS 11
08 230 W 1848163
CONT. ON N 238170
FWA-1E10701301-0001 SHT 04 EL.109933
W 1870595
N 238170 50
EL.111750 FW

7 5
B.O.P. B.O.P.
EL.111666 EL.109756
230
shall require ANOPC's and/or, when needed, Technip Energies Italy S.p.A.'s express written approval.

TOTAL NUMBER OF SPOOLS: 0


SUPPORT SYMBOLOGY
Y
COM STD or SPC support common SPC
to more than one line Special Piping Support
S-
e.g.: line support Refer to supp. dwgs collections 079254C-"UNIT"-DW-1360-00
PRF STD Z X
STD or SPC support welded to pipe at Standard Piping Support
workshop during pipe spools prefabrication Refer to supp. dwgs collection 079254C-0000-STC-1390-000 INPUT AND OUTPUT
DATA FOR PIPELINE
MRS EFFORT ANALYSIS
Itemized Piping Supports ARE BASED ON
SYSTEM OF
For Itemized Piping Supports refer to Material Requisition 079254C-0000-MR-1383-001 COORDINATES AS
IN THE DRAWING

ASSIUT HYDROCRACKING COMPLEX - ANOPC


1) ALL DIMENSIONS ARE IN MILLIMITERS
1) CONSTRUCTION LINE LIST: 079254C-'UNIT'-NM-1300-012 4) CONSTRUCTION SPECIFICATION FOR PIPING PREFABRICATION ERECTION AND N WELD
REFERENCE

SYMBOLOGY
2) DIMENSIONS AND LAYOUT OF SOCKET WELDED AND THREADED LINES ARE INDICATIVE ONLY AND SHALL BE CHECKED
AT JOB SITE BEFORE ERECTION
DOCUMENTS 2) PIPING MATERIAL CLASSES: 079254C-0000-JSD-1300-001 NON DESTRUCTIVE EXAMINATION: 079254C-0000-MS-1320-051 N FIELD WELD
NOTES - VALID ONLY FOR U/G PIPING SKETCHES -
3) TOTAL LENGTH OF U/G PIPING TO BE CONSIDERED INCLUSIVE OF EXPANSION JOINTS OR ANY EMBEDDED PIPE INTO PITS FOR DESIGN 3) TECHNICAL SPECIFICATION FOR PIPING PREFABRICATION 5) FOR STRESS ANALYSIS "FLEXIBILITY LEVELS" AND STRESS ANALYSIS TRACED LINE No. 14"-FWA-1E10701301-ADP0HU1-N ISOMETRIC ID. 1E10U01-FWA-1E10701301
4) ISOMETRIC SKETCHES PREVAIL ON 2D AREA DRAWINGS
5) FOR 45deg MITER BENDS, ONLY ONE CONSTRUCTION WELD SHALL BE CONSIDERED (REF. TO APPLICABLE STANDARD) CONDITION AND ERECTION: 079254C-0000-MS-1300-001 CALCULATIONS NUMBERS REFER TO DOC.: 079254C-'UNIT'-NM-1370-001 SUPPORT
6) THE INITIAL AND FINAL COORDINATES IN ELEVATION ARE SHOWN AT CENTER OF PIPELINE. WHILE AT EACH CHANGE IN PIPE ELEVATION (COMPONENTS)
IT IS SHOWN AS BOP (BOTTOM OF PIPE) POSITION
PROJ. AREA DOC. TYPE SERVICE UNIT SEQUENCE N. SUBLINE SHEET OF SHEETS REV
1 21/06/2022 ISSUED FOR CONSTRUCTION N.A. N.A. A.S./F.F 0 16/06/2022 ISSUED FOR CONSTRUCTION N.A. N.A. A.S./F.F
REV DATE DESCRIPTION STRESS INSTR APPR. REV DATE DESCRIPTION STRESS INSTR APPR. REV DATE DESCRIPTION STRESS INSTR APPR.
079254C 1E10U01 ISO FWA 1E10 701301 0001 03 06 1
EXTRACTION DATE: 21/06/2022 15:42 Technip Energies Italy S.p.A - 00148 ROMA - Viale Castello della Magliana, 68
PIP ING SPEC. C. A. DES. P RESS. OP ER. PRESS. DES. TEM P . OPER. TEM P. TEST P RESS. FLUID P AINT NDT PED TEST IPS NP D INS. INS. THK TRACING TRACING
or reverse engineer the same, in any manner, without ANOPC prior written consent and/or Technip Energies Italy S.p.A. prior written consent, and shall not put in use the information for any purpose unrelated to that for which it has been transmitted to recipient. An y disclosure and use of the contents hereof shall be subject
P&ID
SP EC.
SP EC. M A T
RATING (mm) (Kg/cm2g) (Kg/cm2g) (°C) (°C) (Kg/cm2g) PHA SE NO.
P WHT
RT / M T CA T. TYPE E (inch) TYPE (mm) CODE SIZE BILL OF MATERIAL SKETCH LIST
N
agreements between ANOPC, Technip Energies Italy S.p.A. and the intended recipient. The copyright in this document and/or attachments is owned by ANOPC and Technip Energies Italy S.p.A.. while the underlying IP is owned by other Tecnology Providers and an y reproduction or adaptation thereof to any subsisting
1E10-PID-1931-701-1 ADP 0HU1 HDPE 150 lbs 0 12 7 50 37 L NO PA INT - - H 14 0 POS DESCRIPTION THK1 THK2 ASBL/ IDENT DIAMETER QTY
1E10-PID-1931-701-1 ADP 0HU1 HDPE 150 lbs 0 12 7 50 37 L NO PA INT - - H 6 0 NO DEST (PCS/MM)
This document and its attachments, if any, contains confidential and proprietary information belonging to ANOPC, and/or other third parties, including Technip Energies Italy S.p.A. The intended recipient of the information contained here in shall not divu lge the same to any third part or sell, trade, publish, reproduce

1E10-PID-1931-701-1 ADP 0HU1 HDPE 150 lbs 0 12 7 50 37 L NO PA INT - - H 4 0


ERECTION

1 Pipes (Length),ASTM D3035,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44JJJ6C 14 29677

Ends,-, C44JJJ6C, 7,

2 Pipes (Length),ASTM D3035,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44JJJWW 6 1284

Ends,-, C44JJJWW, 7,
CONT. ON 3 Pipes (Length),ASTM D3035,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44JJJT3 4 265
FWA-1E10701301-0001 SHT 03 Ends,-, C44JJJT3, 7,

W 1870595 4 Red Te,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion Ends,Mnf SDR9 SDR9 7 C44S0L06 14X6 1

N 238170 Std, C44S0L06, 7,

EL.111750 5 45° Elb LR,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44K9APP 14 2

Ends,Mnf Std, C44K9APP, 7,

6 Conc Reducer,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C4TBFGZX 6X4 1

Ends,Mnf Std, C4TBFGZX, 7,

CONT. ON 0 7 90° Elb LR,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44K9A50 6 1
0
1E10A01-FWA-1E10701309-0001 1 15 Class 150 FF Ends,Mnf Std, C44K9A50, 7,

8 Back Flg (SO Stub),Mnf Std,ASTM A536 Gr.60-40-18,FF,150 Lbs, 7 C451R3E5 4 1


W 1893900 17
N 236400 FW CLASS: C451R3E5, 7,
1 ACS3A00 9 Stub SP,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion Ends,Mnf SDR9 7 C44K92KS 4 1
EL.112800
CLASS: Std,
305 14"NS
19 5 00 ADP0HU1
FW 11 147
1 4 18 F8/9
305 14X6"NS FW

265
W 1893900 48
B.O.P. FW
336 EL.111572
70 3
53 4"NS 232
5 47
45° 1 432 6 FW 46
B.O.P. 337 6X4"NS FW

176
43

2
EL.111572 20 FW
FW 2 45
22
FW 11 FW
21 08
FW 230
07

1400

5
13

45°
23 B.O.P. 7
336 FW EL.110172 B.O.P.
EL.111666
1

44
337 FW
00 230
14

14"NS CONT. ON
FWA-1E10701301-0001 SHT 05
W 1901648
N 238170
EL.110350
shall require ANOPC's and/or, when needed, Technip Energies Italy S.p.A.'s express written approval.

TOTAL NUMBER OF SPOOLS: 0


SUPPORT SYMBOLOGY
Y
COM STD or SPC support common SPC
to more than one line Special Piping Support
S-
e.g.: line support Refer to supp. dwgs collections 079254C-"UNIT"-DW-1360-00
PRF STD Z X
STD or SPC support welded to pipe at Standard Piping Support
workshop during pipe spools prefabrication Refer to supp. dwgs collection 079254C-0000-STC-1390-000 INPUT AND OUTPUT
DATA FOR PIPELINE
MRS EFFORT ANALYSIS
Itemized Piping Supports ARE BASED ON
SYSTEM OF
For Itemized Piping Supports refer to Material Requisition 079254C-0000-MR-1383-001 COORDINATES AS
IN THE DRAWING

ASSIUT HYDROCRACKING COMPLEX - ANOPC


1) ALL DIMENSIONS ARE IN MILLIMITERS
1) CONSTRUCTION LINE LIST: 079254C-'UNIT'-NM-1300-012 4) CONSTRUCTION SPECIFICATION FOR PIPING PREFABRICATION ERECTION AND N WELD
REFERENCE

SYMBOLOGY
2) DIMENSIONS AND LAYOUT OF SOCKET WELDED AND THREADED LINES ARE INDICATIVE ONLY AND SHALL BE CHECKED
AT JOB SITE BEFORE ERECTION
DOCUMENTS 2) PIPING MATERIAL CLASSES: 079254C-0000-JSD-1300-001 NON DESTRUCTIVE EXAMINATION: 079254C-0000-MS-1320-051 N FIELD WELD
NOTES - VALID ONLY FOR U/G PIPING SKETCHES -
3) TOTAL LENGTH OF U/G PIPING TO BE CONSIDERED INCLUSIVE OF EXPANSION JOINTS OR ANY EMBEDDED PIPE INTO PITS FOR DESIGN 3) TECHNICAL SPECIFICATION FOR PIPING PREFABRICATION 5) FOR STRESS ANALYSIS "FLEXIBILITY LEVELS" AND STRESS ANALYSIS TRACED LINE No. 14"-FWA-1E10701301-ADP0HU1-N ISOMETRIC ID. 1E10U01-FWA-1E10701301
4) ISOMETRIC SKETCHES PREVAIL ON 2D AREA DRAWINGS
5) FOR 45deg MITER BENDS, ONLY ONE CONSTRUCTION WELD SHALL BE CONSIDERED (REF. TO APPLICABLE STANDARD) CONDITION AND ERECTION: 079254C-0000-MS-1300-001 CALCULATIONS NUMBERS REFER TO DOC.: 079254C-'UNIT'-NM-1370-001 SUPPORT
6) THE INITIAL AND FINAL COORDINATES IN ELEVATION ARE SHOWN AT CENTER OF PIPELINE. WHILE AT EACH CHANGE IN PIPE ELEVATION (COMPONENTS)
IT IS SHOWN AS BOP (BOTTOM OF PIPE) POSITION
PROJ. AREA DOC. TYPE SERVICE UNIT SEQUENCE N. SUBLINE SHEET OF SHEETS REV
1 21/06/2022 ISSUED FOR CONSTRUCTION N.A. N.A. A.S./F.F 0 16/06/2022 ISSUED FOR CONSTRUCTION N.A. N.A. A.S./F.F
REV DATE DESCRIPTION STRESS INSTR APPR. REV DATE DESCRIPTION STRESS INSTR APPR. REV DATE DESCRIPTION STRESS INSTR APPR.
079254C 1E10U01 ISO FWA 1E10 701301 0001 04 06 1
EXTRACTION DATE: 21/06/2022 15:42 Technip Energies Italy S.p.A - 00148 ROMA - Viale Castello della Magliana, 68
P IP ING SP EC. C. A . DES. P RESS. OP ER. P RESS. DES. TEM P . OP ER. TEM P . TEST P RESS. FLUID P A INT NDT P ED TEST IP S NP D INS. INS. THK TRA CING TRA CING
or reverse engineer the same, in any manner, without ANOPC prior written consent and/or Technip Energies Italy S.p.A. prior written consent, and shall not put in use the information for any purpose unrelated to that for which it has been transmitted to recipient. An y disclosure and use of the contents hereof shall be subject
P &ID
SP EC.
SP EC. M A T
RA TING (mm) (Kg/cm2g) (Kg/cm2g) (°C) (°C) (Kg/cm2g) P HA SE NO.
P WHT
RT / M T CA T. TYP E E (inch) TYP E (mm) CODE SIZE BILL OF MATERIAL SKETCH LIST
N
agreements between ANOPC, Technip Energies Italy S.p.A. and the intended recipient. The copyright in this document and/or attachments is owned by ANOPC and Technip Energies Italy S.p.A.. while the underlying IP is owned by other Tecnology Providers and an y reproduction or adaptation thereof to any subsisting
1E10-PID-1931-701-1 A DP 0HU1 HDP E 150 lbs 0 12 7 50 37 L " per
NOme
P AilINT
grado di maturità
- di questo
- setting è tale
H che po ssa essere
14 passato in pro duzio
0 ne" (A FIO 12-A P R-2016) POS DESCRIPTION THK1 THK2 ASBL/ IDENT DIAMETER QTY
NO DEST (PCS/MM)
This document and its attachments, if any, contains confidential and proprietary information belonging to ANOPC, and/or other third parties, including Technip Energies Italy S.p.A. The intended recipient of the information contained here in shall not divu lge the same to any third part or sell, trade, publish, reproduce

ERECTION

1 Pipes (Length),ASTM D3035,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44JJJ6C 14 18272

Ends,-, C44JJJ6C, 7,

2 45° Elb LR,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44K9APP 14 4

Ends,Mnf Std, C44K9APP, 7,

337 336 3 Back Flg (SO Stub),Mnf Std,ASTM A536 Gr.60-40-18,FF,150 Lbs, 7 C451R3DY 14 1

C451R3DY, 7,

4 NM Flat Gk,ASME B16.21,FF as per ASME B16.5,IBC Type,150 Lbs, , 2 C3P9L482 14 1


28 2,
FW 2 5 HHx MBlt 1 HHx N&2W,ASME B18.2.1/ASME B18.2.2,Full Length 2 C88ZGDD 1 12
45° Threaded, C88ZGDD, 2, - 170 mm Length
0
337 40 1 B.O.P. 6 Gat Flg,AWWA C509/C515,ASTM A536 Gr.65-45-12,FF,150 Lbs, 7 C4KDM3L9 14 1
11 13 EL.111572 24
07 86 C4KDM3L9, 7,

337 27 FW 7 Stub SP,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion Ends,Mnf SDR9 7 C44K9201 14 1

14"NS Std,

29 1 27 337 1
FW FW
2
45° 337
26

1400
FW 25
20 FW
12 2
30 45°
FW B.O.P.
1052 EL.110172
0 0
14
CONT. ON
FWA-1E10701301-0001 SHT 04
31 W 1901648
1

FW N 238170
12 EL.110350
20 337

2
F3/7 G4 B5 33 45°
FW
BT3
27 32
6 17 FW 337
STEM UP
PLZ-001
1
1 280 14"NS
381 CONT. ON
FWA-1E10701301-0001 SHT 06
W 1922191
N 236950
EL.111750
shall require ANOPC's and/or, when needed, Technip Energies Italy S.p.A.'s express written approval.

TOTAL NUMBER OF SPOOLS: 0


SUPPORT SYMBOLOGY
Y
COM STD or SPC support common SPC
to more than one line Special Piping Support
S-
e.g.: line support Refer to supp. dwgs collections 079254C-"UNIT"-DW-1360-00
PRF STD Z X
STD or SPC support welded to pipe at Standard Piping Support
workshop during pipe spools prefabrication Refer to supp. dwgs collection 079254C-0000-STC-1390-000 INPUT AND OUTPUT
DATA FOR PIPELINE
MRS EFFORT ANALYSIS
Itemized Piping Supports ARE BASED ON
SYSTEM OF
For Itemized Piping Supports refer to Material Requisition 079254C-0000-MR-1383-001 COORDINATES AS
IN THE DRAWING

ASSIUT HYDROCRACKING COMPLEX - ANOPC


1) ALL DIMENSIONS ARE IN MILLIMITERS
1) CONSTRUCTION LINE LIST: 079254C-'UNIT'-NM-1300-012 4) CONSTRUCTION SPECIFICATION FOR PIPING PREFABRICATION ERECTION AND N WELD
REFERENCE

SYMBOLOGY
2) DIMENSIONS AND LAYOUT OF SOCKET WELDED AND THREADED LINES ARE INDICATIVE ONLY AND SHALL BE CHECKED
AT JOB SITE BEFORE ERECTION
DOCUMENTS 2) PIPING MATERIAL CLASSES: 079254C-0000-JSD-1300-001 NON DESTRUCTIVE EXAMINATION: 079254C-0000-MS-1320-051 N FIELD WELD
NOTES - VALID ONLY FOR U/G PIPING SKETCHES -
3) TOTAL LENGTH OF U/G PIPING TO BE CONSIDERED INCLUSIVE OF EXPANSION JOINTS OR ANY EMBEDDED PIPE INTO PITS FOR DESIGN 3) TECHNICAL SPECIFICATION FOR PIPING PREFABRICATION 5) FOR STRESS ANALYSIS "FLEXIBILITY LEVELS" AND STRESS ANALYSIS TRACED LINE No. 14"-FWA-1E10701301-ADP0HU1-N ISOMETRIC ID. 1E10U01-FWA-1E10701301
4) ISOMETRIC SKETCHES PREVAIL ON 2D AREA DRAWINGS
5) FOR 45deg MITER BENDS, ONLY ONE CONSTRUCTION WELD SHALL BE CONSIDERED (REF. TO APPLICABLE STANDARD) CONDITION AND ERECTION: 079254C-0000-MS-1300-001 CALCULATIONS NUMBERS REFER TO DOC.: 079254C-'UNIT'-NM-1370-001 SUPPORT
6) THE INITIAL AND FINAL COORDINATES IN ELEVATION ARE SHOWN AT CENTER OF PIPELINE. WHILE AT EACH CHANGE IN PIPE ELEVATION (COMPONENTS)
IT IS SHOWN AS BOP (BOTTOM OF PIPE) POSITION
PROJ. AREA DOC. TYPE SERVICE UNIT SEQUENCE N. SUBLINE SHEET OF SHEETS REV
1 21/06/2022 ISSUED FOR CONSTRUCTION N.A. N.A. A.S./F.F 0 16/06/2022 ISSUED FOR CONSTRUCTION N.A. N.A. A.S./F.F
REV DATE DESCRIPTION STRESS INSTR APPR. REV DATE DESCRIPTION STRESS INSTR APPR. REV DATE DESCRIPTION STRESS INSTR APPR.
079254C 1E10U01 ISO FWA 1E10 701301 0001 05 06 1
EXTRACTION DATE: 21/06/2022 15:42 Technip Energies Italy S.p.A - 00148 ROMA - Viale Castello della Magliana, 68