31
FIRE WATER 31
1G00-701-1 43655
14"-FWA-62701306 -ADP0HU1 -N A. FOR DETAILS ABOUT FIRE PROTECTION PHILOSOPHY, REFER TO PROJECT DOCUMENT
30 MFR "FIREFIGHTING SYSTEM SPECIFICATION" CODED AS 079254C-0000JSD-1900-001.
FROM/TO UTILITY 30
62-MLZ-003 B. ALL FIREFIGHTING EQUIPMENT SHALL BE IN COMPLIANCE WITH PROJECT DOC
AG UG FIREFIGHTING SYSTEM SPECIFICATION CODED AS 079254C-0000-JSD-1900-001.
29 6" C. VERTICAL TRAFFIC POST (BOLLARDS) SHALL BE INSTALLED TO PROTECT HYDRANTS 29
ADP0HU1
ACS3A00
28 D. ALL HYDRANTS SHALL BE WET BARREL TYPE AND PROVIDED WITH A GATE VALVE 28
6"-FWA-62701307 -ACS3A00-N TO BE INSTALLED ABOVEGROUND AND BELOW THE HYDRANT.
27 F. HYDRANT TO BE LOCATED NOT LESS THAN 1.5 M FROM THE CURB OF ROAD. 27
26 26
1P70 - N0B 1W00 - UTILITY 1G00 - UTILITY 62-MLZ-002 MFR
25 AG UG
6"
PLZ NOTES 25
037
6" 1. DELETED.
ADP0HU1
ACS3A00
24 24
2. DELETED.
23
6"-FWA-62701308 -ACS3A00-N
23
14"
22 22
MFR 24"X14"
62-HLZ-026
21 21
AG UG
6"
The present document or drawing is property of TECHNIP ENERGIES ITALY S.p.A. and shall not, under any circumstances, be totally or partially, drectly or undirectly, transferred, reproduced, copied, disclosed or used, without its prior written consent,
20 20
6"
ADP0HU1
ACS3A00
19 6"-FWA-62701309 -ACS3A00 -N 19
18 18
17 17
16 16
43684
FROM/TO RIU
FIRE WATER
15 15
1M58-703-1
14 14
13 1M58 - RIU 13
12 12
1M58-703-1
11 11
FROM/TO RIU
FIRE WATER
10 10
09 09
43679
08 08
14"-FWA-58703301 -ADP0HU1-N
07 07
1M58
06 1062 06
14" 1M59 - RIP
05 05
PLZ
04 015 04
03 FIRE WATER 03
6" 43648 1E09-701-1
1M59-705-1
02
FROM/TO ARU 1E09 - ARU 02
FROM/TO RIP
FIRE WATER
01 01
14"-FWA-62701301 -ADP0HU1 -N
FIRE WATER
6" 43693 1E09-701-1
43716
TO ARU
14"-FWA-59705310 -ADP0HU1 -N
for any purpose and in any way other than that for which it is specifically furnished or outside the extent of the agreed upon right of use.
FIRE WATER
14" 43649 1E10-701-1 FIRE WATER
FROM/TO SWSU 1E10 - SWSU 1M59-705-1 45438 PLZ
1E10-701-1
FROM/TO SWSU
013
1E10-701-1
1E10-701-1
1E10-701-1
TO RIP
6"-FWA-62701305-ACS3A00-N
FIRE WATER
6"-FWA-62701313 -ADP0HU1-N
FIRE WATER
FIRE WATER
FIRE WATER
14" 1M59
45424
45422
45421
6"-FWA-62701303 -ACS3A00-N
6"-FWA-62701304 -ACS3A00-N
019
012
ANOPC
ASSIUT NATIONAL OIL PROCESSING COMPANY
FIRE WATER 1L54-001-1
45194
079254C-1062-PID-1931-701-1.pid
ASSIUT HYDROCRACKING COMPLEX - ANOPC
FROM/TO SSU
14"-FWA-54001303-ADP0HU1-N
1L54 - SSU
CAD Model:
Scale Project Unit Disc. Type Disc Subj Ser. No Sheet Rev.
NONE 079254C 1062 PID 19 31 701 1 1 of 1
TECHNIP ENERGIES ITALY S.p.A. - 00148 ROMA - Viale Castello della Magliana, 68
32 59-MLZ-007 59-MLZ-001 GENERAL NOTES 32
31 31
A. FOR DETAILS ABOUT FIRE PROTECTION PHILOSOPHY, REFER TO DOCUMENT "FIREFIGHTING
MFR MFR SYSTEM SPECIFICATION" CODED AS 079254C-0000-JSD-1900-001.
30 B. ALL FIREFIGHTING EQUIPMENT SHALL BE IN COMPLIANCE WITH PROJECT DOC FIREFIGHTING 30
6" 6"
SYSTEM SPECIFICATION CODED AS 079254C-0000-JSD-1900-001.
29 6"-FWA-59705307 -ACS3A00 -N 6"-FWA-59705306 -ACS3A00-N C. VERTICAL TRAFFIC POST (BOLLARDS) SHALL BE INSTALLED TO PROTECT HYDRANTS AND 29
MONITORS WHEN REQUIRED.
PLZ AG ACS3A00 AG ACS3A00 PLZ
28 D. ALL HYDRANTS SHALL BE WET BARREL TYPE AND PROVIDED WITH A GATE VALVE TO BE 28
014 UG ADP0HU1 UG ADP0HU1 015 INSTALLED ABOVE GROUND AND BELOW THE HYDRANT.
FIRE WATER 14" E. HYDRANT TO BE LOCATED NOT LESS THAN 1.5 M FROM THE CURB OF ROAD.
6"
6"
27 14"-FWA-58703301 -ADP0HU1 -N 14"-FWA-59705301 -ADP0HU1 -N 14"-FWA-59705310 -ADP0HU1 -N 27
1M58-703-1 43683
14"
1M59
1M58
26 FROM/TO RIU 26
6"
6"
6"
6"
6"
14"
25 PLZ NOTES 25
032
24 1. FIRE EQUIPMENT TO BE PROVIDED WITH AN ADEQUATE UNIT ACCESS, IN ORDER TO 24
UG ADP0HU1 UG ADP0HU1 UG ADP0HU1 FACILITATE INGRESS/EXIT OPERATIONS BY FIRE BRIGADIERS.
23 AG ACS3A00 AG ACS3A00 AG ACS3A00 23
6"-FWA-59705309-ACS3A00-N
6"-FWA-59705308-ACS3A00-N
6"-FWA-59705303-ACS3A00-N
22 22
1M58
21
RIU
21
The present document or drawing is property of TECHNIP ENERGIES ITALY S.p.A. and shall not, under any circumstances, be totally or partially, drectly or undirectly, transferred, reproduced, copied, disclosed or used, without its prior written consent,
20 20
19 19
18 18
17 17
43716
FROM/TO RR&L
FIRE WATER
16 16
14"-FWA-59705302 -ADP0HU1 -N
6" 6" 6"
1062-701-1
15 15
MFR MFR MFR
14 14
13 13
1 1
59-HLZ-001
12 59-HLZ-018 59-HLZ-019 12
11 11
10 10
TO ARU
FIRE WATER
1E09-701-1 43694
FROM/TO ARU
43451
FIRE WATER
09 09
08 08
1E09-701-1
07 07
06 06
1E09-ARU
05 05
04 04
03 03
1062-RR&L
02 02
01 01
for any purpose and in any way other than that for which it is specifically furnished or outside the extent of the agreed upon right of use.
FIRE WATER
1E10-701-1 43453
1M59-706-1
1M59-706-1
FIRE WATER
FIRE WATER
TO DELUGE
TO DELUGE
STATION #1
STATION #1
10-1E10-U-000-17-
FWA-PTJ-00058-U
45435
45436
Alice Baldini
Alice Baldini (May 24, 2023 14:57 GMT+2)
Salvatore Oliva Sneider Tavera Corrado Pigna
Salvatore Oliva (May 24, 2023 14:54 GMT+2) Sneider Tavera (May 24, 2023 10:37 CDT) Corrado Pigna (May 24, 2023 15:46 GMT+2)
079254C-1M59-PID-1931-705-1.pid
1062-RR&L
ASSIUT HYDROCRACKING COMPLEX - ANOPC
PIPING & INSTRUMENT DIAGRAM
Refinery Interconnecting Process Unit (RIU)
FIRE WATER DISTRIBUTION
CAD Model:
Scale Project Unit Disc. Type Disc Subj Ser. No Sheet Rev.
NONE 079254C 1M59 PID 19 31 705 1 1 of 1
TECHNIP ENERGIES ITALY S.p.A. - 00148 ROMA - Viale Castello della Magliana, 68
32 GENERAL NOTES 32
31 31
A. FOR DETAILS ABOUT FIRE PROTECTION PHILOSOPHY, REFER TO DOCUMENT "FIREFIGHTING
30
SYSTEM SPECIFICATION" CODED AS 079254C-0000-JSD-1900-001.
30
B. ALL FIREFIGHTING EQUIPMENT SHALL BE IN COMPLIANCE WITH PROJECT DOC FIREFIGHTING
SYSTEM SPECIFICATION CODED AS 079254C-0000-JSD-1900-001.
29 29
28 28
27 27
26 26
25 25
24 24
23 23
22
NOTES 22
21 21
1. DELETED.
The present document or drawing is property of TECHNIP ENERGIES ITALY S.p.A. and shall not, under any circumstances, be totally or partially, drectly or undirectly, transferred, reproduced, copied, disclosed or used, without its prior written consent,
ADP0HU1
ACS3A00
6" FROM RIP INTERCONNECTED WITH FIRE AND GAS SYSTEM (FGS). UPON ACTIVATION OF DIGITAL
HAND SWITCHES BY OPERATOR AT DCS OPERATOR WORKSTATION, THE FGS
17 17
TRANSMITS INTERFACE SIGNALS TO FIRE ALARM CONTROL PANEL PEB-1E-FACP-001
REQUESTING FACP TO TRIGGER THE ASSOCIATED TRANSFORMERS DELUGE VALVES:
16 - 1E71-DHSH-9521A (INTERFACE SIGNAL 1E71-XS-0301S) REQUESTS FACP TO OPEN THE 16
PLZ DELUGE VALVE OF TRANSFORMER 1E-TR-23-01A;
15 005 - 1E71-DHSH-9522A (INTERFACE SIGNAL 1E71-XS-0302S) REQUESTS FACP TO OPEN THE 15
AG UG FIRE WATER DELUGE VALVE OF TRANSFORMER 1E-TR-23-01B;
6" 6"-FWA-59705305-ADP0HU1 -N -1E71-DHSH-9523A (INTERFACE SIGNAL 1E71-XS-0303S) REQUESTS FACP TO OPEN THE
14 1M59-705-1 45436 14
DELUGE VALVE OF TRANSFORMER 1E-TR-24-01A;
ADP0HU1
ACS3A00
2 6" FROM RIP
8
13 - 1E71-DHSH-9524A (INTERFACE SIGNAL 1E71-XS-0304S) REQUESTS FACP TO OPEN THE 13
3" DELUGE VALVE OF TRANSFORMER 1E-TR-24-01B;
- 1E71-DHSH-9525A (INTERFACE SIGNAL 1E71-XS-0305S) REQUESTS FACP TO OPEN THE
12 12
IP-PI
DELUGE VALVE OF TRANSFORMER 1E-TR-24-02A;
1M59-1E71-001 -1E71-DHSH-9526A (INTERFACE SIGNAL 1E71-XS-0306S) REQUESTS FACP TO OPEN THE
11 DELUGE VALVE OF TRANSFORMER 1E-TR-24-02B. 11
10-1E10-U-000-17-
FWA-PTJ-00058-U 6. AT THE CONFIRMATION OF DELUGE VALVE OPENING (IN OWNER/BOP CONTRACTOR
10 10
SCOPE), THE FACP TRANSMITS THE INTERFACE SIGNAL 1E71-XA-0307R, CUMULATIVE
FOR ALL THE TRANSFORMERS DELUGE VALVES, TO FGS ALERTING OPERATOR VIA
09 1E71-UA-0307R. 09
7. IN THIS P&ID ARE INDICATED ONLY THE SIGNALS RELATED TO FIRE WATER SYSTEM.
08 FOR SIGNALS RELATED TO F&G REFER TO "FIRE & GAS CAUSE AND EFFECT DIAGRAM 08
RIP-1M59 (BLOCK E)" (DOC. 076254C-1M59-NM-1950-001).
07 07
2 8. PIPE BRANCH TO INTERCONNECT DELUGE VALVE FOR TRASFORMER PROTECTION. THE
8
3" BRANCH SHALL BE LOCETED IN HORIZONTAL POSITION AND THE DISTANCE BETWEEN
06 TWO BRANCHES SHALL BE ENOUGH TO ALLOW ACCESS TO DELUGE VALVES AS WELL 06
AS THEIR MANUAL OPERATION.
IP-PI
05 1M59-1E71-002 05
04 04
03 03
02 02
01
DHSH DHSH DHSH 01
9521A 9522A 9523A
2
8
DHSH DHSH DHSH 3"
9524A 9525A 9526A
IP-PI
1M59-1E71-003
5 1E71-XS-0305S
5
5
HOLDS
1E71-XS-0304S
BY T.EN 5 7 1E71 1. DELUGE VALVE SIZING FOR TRASFORMER PROTECTION (BOP CONTRACTOR
for any purpose and in any way other than that for which it is specifically furnished or outside the extent of the agreed upon right of use.
1E71-XS-0303S
SCOPE OF WORK).
BY OWNER/
(*) 4 2. DELETED. 1
BOP CONTRACTOR IP 5 1E71-XS-0302S IS UA
FGS 0307R
BY OWNER/ PEB-1E-FACP-001 7 6
BOP CONTRACTOR 5
1E71-XS-0301S
BY T.EN
2
8
5 1E71-XS-0306S
3"
6 1E71-XA-0307R IP-PI
1M59-1E71-004
8
2
4"
Alice Baldini
IP-PI
Alice Baldini (May 24, 2023 14:57 GMT+2)
2
4" REV. DATE DESCRIPTION PREPARED CHECKED APPROVED/
AUTHORIZED
IP-PI
1M59-1E71-006
ANOPC
6"-FWA-59706301-ACS3A00-N
079254C-1M59-PID-1931-706-1.pid
ASSIUT HYDROCRACKING COMPLEX - ANOPC
PIPING & INSTRUMENT DIAGRAM
Refinery Interconnecting Process Unit (RIU)
DELUGE STATION # 1
PEB-1E / LCB-1E
6"
CAD Model:
DELUGE STATION # 1 Scale Project Unit Disc. Type Disc Subj Ser. No Sheet Rev.
NONE 079254C 1M59 PID 19 31 706 1 1 of 1
TECHNIP ENERGIES ITALY S.p.A. - 00148 ROMA - Viale Castello della Magliana, 68
PIP ING SPEC. C. A. DES. P RESS. OP ER. PRESS. DES. TEM P . OPER. TEM P. TEST P RESS. FLUID P AINT NDT PED TEST IPS NP D INS. INS. THK TRACING TRACING
or reverse engineer the same, in any manner, without ANOPC prior written consent and/or Technip Energies Italy S.p.A. prior written consent, and shall not put in use the information for any purpose unrelated to that for which it has been transmitted to recipient. An y disclosure and use of the contents hereof shall be subject
P&ID
SP EC.
SP EC. M A T
RATING (mm) (Kg/cm2g) (Kg/cm2g) (°C) (°C) (Kg/cm2g) PHA SE NO.
P WHT
RT / M T CA T. TYPE E (inch) TYPE (mm) CODE SIZE BILL OF MATERIAL SKETCH LIST
N
agreements between ANOPC, Technip Energies Italy S.p.A. and the intended recipient. The copyright in this document and/or attachments is owned by ANOPC and Technip Energies Italy S.p.A.. while the underlying IP is owned by other Tecnology Providers and an y reproduction or adaptation thereof to any subsisting
1062-PID-1931-701-1 ADP 0HU1 HDPE 150 lbs 0 12 7 50 37 L NO PA INT - - H 14 N 0 POS DESCRIPTION THK1 THK2 ASBL/ IDENT DIAMETER QTY
1062-PID-1931-701-1 ADP 0HU1 HDPE 150 lbs 0 12 7 50 37 L NO PA INT - - H 6 N 0 NO DEST (PCS/MM)
This document and its attachments, if any, contains confidential and proprietary information belonging to ANOPC, and/or other third parties, including Technip Energies Italy S.p.A. The intended recipient of the information contained here in shall not divu lge the same to any third part or sell, trade, publish, reproduce
ERECTION
1 Pipes (Length),ASTM D3035,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44JJJ6C 14 30641
Ends,-, C44JJJ6C, 7,
2 Pipes (Length),ASTM D3035,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44JJJWW 6 2455
Ends,-, C44JJJWW, 7,
3 Red Te,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion Ends,Mnf SDR9 SDR9 7 C44S0L06 14X6 1
CONT. ON
TB1
F6/13 G8 B10 1062U03-FWA-1M59705310-0001 Std, C44S0L06, 7,
4 45° Elb LR,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44K9APP 14 1
BT2 W 1764900 Ends,Mnf Std, C44K9APP, 7,
N 281494 5 90° Elb LR,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44K9A50 6 1
381 EL.111750
G8 B10 Ends,Mnf Std, C44K9A50, 7,
280 6 Back Flg (SO Stub),Mnf Std,ASTM A536 Gr.60-40-18,FF,150 Lbs, 7 C451R3DY 14 1
C451R3DY, 7,
BT1 7 Back Flg (SO Stub),Mnf Std,ASTM A536 Gr.60-40-18,FF,150 Lbs, 7 C451R3E6 6 1
14
12 "N C451R3E6, 7,
S
STEM UP 77 CONT. ON 8 NM Flat Gk,ASME B16.21,FF as per ASME B16.5,IBC Type,150 Lbs, , 2 C3P9L482 14 2
PLZ-012 1 72 1062U03-FWA-1062701305-0001 2,
FW W 1767400 9 NM Flat Gk,ASME B16.21,FF as per ASME B16.5,IBC Type,150 Lbs, , 2 C3P9K0WS 6 1
N 261250 2,
TB2 2 11 1
36
6"NS 9 416
4
2 FW
230 1 417 1
38 30 432
32 18 FW
FW 5 14"NS 4
5 FW 45°
B.O.P. 295 B.O.P.
1 EL.111572
EL.111666 31
FW 295
230 1
CONT. ON
FWA-1062701314-0001 SHT 02
W 1764900
N 248865
EL.111455
1
shall require ANOPC's and/or, when needed, Technip Energies Italy S.p.A.'s express written approval.
SYMBOLOGY
2) DIMENSIONS AND LAYOUT OF SOCKET WELDED AND THREADED LINES ARE INDICATIVE ONLY AND SHALL BE CHECKED
AT JOB SITE BEFORE ERECTION
DOCUMENTS 2) PIPING MATERIAL CLASSES: 079254C-0000-JSD-1300-001 NON DESTRUCTIVE EXAMINATION: 079254C-0000-MS-1320-051 N FIELD WELD
NOTES - VALID ONLY FOR U/G PIPING SKETCHES -
3) TOTAL LENGTH OF U/G PIPING TO BE CONSIDERED INCLUSIVE OF EXPANSION JOINTS OR ANY EMBEDDED PIPE INTO PITS FOR DESIGN 3) TECHNICAL SPECIFICATION FOR PIPING PREFABRICATION 5) FOR STRESS ANALYSIS "FLEXIBILITY LEVELS" AND STRESS ANALYSIS TRACED LINE No. 14"-FWA-1062701314-ADP0HU1-N ISOMETRIC ID. 1062U03-FWA-1062701314
4) ISOMETRIC SKETCHES PREVAIL ON 2D AREA DRAWINGS
5) FOR 45deg MITER BENDS, ONLY ONE CONSTRUCTION WELD SHALL BE CONSIDERED (REF. TO APPLICABLE STANDARD) CONDITION AND ERECTION: 079254C-0000-MS-1300-001 CALCULATIONS NUMBERS REFER TO DOC.: 079254C-'UNIT'-NM-1370-001 SUPPORT
6) THE INITIAL AND FINAL COORDINATES IN ELEVATION ARE SHOWN AT CENTER OF PIPELINE. WHILE AT EACH CHANGE IN PIPE ELEVATION (COMPONENTS)
IT IS SHOWN AS BOP (BOTTOM OF PIPE) POSITION
PROJ. AREA DOC. TYPE SERVICE UNIT SEQUENCE N. SUBLINE SHEET OF SHEETS REV
1 25/11/2022 REVISED AS SHOWN N.A. N.A. A.S./L.B 0 16/06/2022 ISSUED FOR CONSTRUCTION N.A. N.A. A.S./L.B
REV DATE DESCRIPTION STRESS INSTR APPR. REV DATE DESCRIPTION STRESS INSTR APPR. REV DATE DESCRIPTION STRESS INSTR APPR.
079254C 1062U03 ISO FWA 1062 701314 0001 01 04 1
EXTRACTION DATE: 25/11/2022 14:47 Technip Energies Italy S.p.A - 00148 ROMA - Viale Castello della Magliana, 68
P IP ING SP EC. C. A . DES. P RESS. OP ER. P RESS. DES. TEM P . OP ER. TEM P . TEST P RESS. FLUID P A INT NDT P ED TEST IP S NP D INS. INS. THK TRA CING TRA CING
or reverse engineer the same, in any manner, without ANOPC prior written consent and/or Technip Energies Italy S.p.A. prior written consent, and shall not put in use the information for any purpose unrelated to that for which it has been transmitted to recipient. An y disclosure and use of the contents hereof shall be subject
P &ID
SP EC.
SP EC. M A T
RA TING (mm) (Kg/cm2g) (Kg/cm2g) (°C) (°C) (Kg/cm2g) P HA SE NO.
P WHT
RT / M T CA T. TYP E E (inch) TYP E (mm) CODE SIZE BILL OF MATERIAL SKETCH LIST
N
agreements between ANOPC, Technip Energies Italy S.p.A. and the intended recipient. The copyright in this document and/or attachments is owned by ANOPC and Technip Energies Italy S.p.A.. while the underlying IP is owned by other Tecnology Providers and an y reproduction or adaptation thereof to any subsisting
1062-PID-1931-701-1 A DP 0HU1 HDPE 150 lbs 0 12 7 50 37 L " per
NOme
P AilINT
grado di maturità
- di questo
- setting è tale
H che po ssa essere
14 passato
N in pro duzio
0 ne" (A FIO 12-A P R-2016) POS DESCRIPTION THK1 THK2 ASBL/ IDENT DIAMETER QTY
NO DEST (PCS/MM)
This document and its attachments, if any, contains confidential and proprietary information belonging to ANOPC, and/or other third parties, including Technip Energies Italy S.p.A. The intended recipient of the information contained here in shall not divu lge the same to any third part or sell, trade, publish, reproduce
ERECTION
1 Pipes (Length),ASTM D3035,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44JJJ6C 14 15302
Ends,-, C44JJJ6C, 7,
2 45° Elb LR,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44K9APP 14 3
CONT. ON
FWA-1062701314-0001 SHT 01
W 1764900
N 248865
EL.111455
1
6
FW
14
"N
S
44
605
1
0
1 2
7 417
FW 45°
416 B.O.P. 1
1
EL.111572
1
11 12
60 1 FW FW
1 5 8
2 FW 417 9 1 11
45° 1
FW 55
B.O.P. 0
EL.110672 44
1
1 17 1
67 11
417 1 50
416 0
10
1
900
FW
1
13
416 1 FW
1
2 90 14"NS
45° 0
CONT. ON
FWA-1062701314-0001 SHT 03
W 1764900
N 231689
EL.111750
shall require ANOPC's and/or, when needed, Technip Energies Italy S.p.A.'s express written approval.
SYMBOLOGY
2) DIMENSIONS AND LAYOUT OF SOCKET WELDED AND THREADED LINES ARE INDICATIVE ONLY AND SHALL BE CHECKED
AT JOB SITE BEFORE ERECTION
DOCUMENTS 2) PIPING MATERIAL CLASSES: 079254C-0000-JSD-1300-001 NON DESTRUCTIVE EXAMINATION: 079254C-0000-MS-1320-051 N FIELD WELD
NOTES - VALID ONLY FOR U/G PIPING SKETCHES -
3) TOTAL LENGTH OF U/G PIPING TO BE CONSIDERED INCLUSIVE OF EXPANSION JOINTS OR ANY EMBEDDED PIPE INTO PITS FOR DESIGN 3) TECHNICAL SPECIFICATION FOR PIPING PREFABRICATION 5) FOR STRESS ANALYSIS "FLEXIBILITY LEVELS" AND STRESS ANALYSIS TRACED LINE No. 14"-FWA-1062701314-ADP0HU1-N ISOMETRIC ID. 1062U03-FWA-1062701314
4) ISOMETRIC SKETCHES PREVAIL ON 2D AREA DRAWINGS
5) FOR 45deg MITER BENDS, ONLY ONE CONSTRUCTION WELD SHALL BE CONSIDERED (REF. TO APPLICABLE STANDARD) CONDITION AND ERECTION: 079254C-0000-MS-1300-001 CALCULATIONS NUMBERS REFER TO DOC.: 079254C-'UNIT'-NM-1370-001 SUPPORT
6) THE INITIAL AND FINAL COORDINATES IN ELEVATION ARE SHOWN AT CENTER OF PIPELINE. WHILE AT EACH CHANGE IN PIPE ELEVATION (COMPONENTS)
IT IS SHOWN AS BOP (BOTTOM OF PIPE) POSITION
PROJ. AREA DOC. TYPE SERVICE UNIT SEQUENCE N. SUBLINE SHEET OF SHEETS REV
1 25/11/2022 REVISED AS SHOWN N.A. N.A. A.S./L.B 0 16/06/2022 ISSUED FOR CONSTRUCTION N.A. N.A. A.S./L.B
REV DATE DESCRIPTION STRESS INSTR APPR. REV DATE DESCRIPTION STRESS INSTR APPR. REV DATE DESCRIPTION STRESS INSTR APPR.
079254C 1062U03 ISO FWA 1062 701314 0001 02 04 1
EXTRACTION DATE: 25/11/2022 14:47 Technip Energies Italy S.p.A - 00148 ROMA - Viale Castello della Magliana, 68
P IP ING SP EC. C. A . DES. P RESS. OP ER. P RESS. DES. TEM P . OP ER. TEM P . TEST P RESS. FLUID P A INT NDT P ED TEST IP S NP D INS. INS. THK TRA CING TRA CING
or reverse engineer the same, in any manner, without ANOPC prior written consent and/or Technip Energies Italy S.p.A. prior written consent, and shall not put in use the information for any purpose unrelated to that for which it has been transmitted to recipient. An y disclosure and use of the contents hereof shall be subject
P &ID
SP EC.
SP EC. M A T
RA TING (mm) (Kg/cm2g) (Kg/cm2g) (°C) (°C) (Kg/cm2g) P HA SE NO.
P WHT
RT / M T CA T. TYP E E (inch) TYP E (mm) CODE SIZE BILL OF MATERIAL SKETCH LIST
N
agreements between ANOPC, Technip Energies Italy S.p.A. and the intended recipient. The copyright in this document and/or attachments is owned by ANOPC and Technip Energies Italy S.p.A.. while the underlying IP is owned by other Tecnology Providers and an y reproduction or adaptation thereof to any subsisting
1062-PID-1931-701-1 A DP 0HU1 HDPE 150 lbs 0 12 7 50 37 L " per
NOme
P AilINT
grado di maturità
- di questo
- setting è tale
H che po ssa essere
14 passato
N in pro duzio
0 ne" (A FIO 12-A P R-2016) POS DESCRIPTION THK1 THK2 ASBL/ IDENT DIAMETER QTY
NO DEST (PCS/MM)
This document and its attachments, if any, contains confidential and proprietary information belonging to ANOPC, and/or other third parties, including Technip Energies Italy S.p.A. The intended recipient of the information contained here in shall not divu lge the same to any third part or sell, trade, publish, reproduce
ERECTION
1 Pipes (Length),ASTM D3035,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44JJJ6C 14 12168
Ends,-, C44JJJ6C, 7,
2 22.5° Elb LR,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44K9BZX 14 3
CONT. ON
FWA-1062701314-0001 SHT 02
W 1764900
N 231689
EL.111750
11 239
50
0
2
14 22.5°
FW 1
239 B.O.P.
EL.111572
14"NS
16
15 FW
250
FW
17
6
17
FW 239
1
CONT. ON
2 FWA-1062701314-0001 SHT 04
60 W 1764900
22.5° 4 18
B.O.P. FW 20 N 218170
EL.111322 FW EL.111659
239
176
31 1
6
239
19
FW 1
238 14"NS
159
2
22.5°
38
3
shall require ANOPC's and/or, when needed, Technip Energies Italy S.p.A.'s express written approval.
SYMBOLOGY
2) DIMENSIONS AND LAYOUT OF SOCKET WELDED AND THREADED LINES ARE INDICATIVE ONLY AND SHALL BE CHECKED
AT JOB SITE BEFORE ERECTION
DOCUMENTS 2) PIPING MATERIAL CLASSES: 079254C-0000-JSD-1300-001 NON DESTRUCTIVE EXAMINATION: 079254C-0000-MS-1320-051 N FIELD WELD
NOTES - VALID ONLY FOR U/G PIPING SKETCHES -
3) TOTAL LENGTH OF U/G PIPING TO BE CONSIDERED INCLUSIVE OF EXPANSION JOINTS OR ANY EMBEDDED PIPE INTO PITS FOR DESIGN 3) TECHNICAL SPECIFICATION FOR PIPING PREFABRICATION 5) FOR STRESS ANALYSIS "FLEXIBILITY LEVELS" AND STRESS ANALYSIS TRACED LINE No. 14"-FWA-1062701314-ADP0HU1-N ISOMETRIC ID. 1062U03-FWA-1062701314
4) ISOMETRIC SKETCHES PREVAIL ON 2D AREA DRAWINGS
5) FOR 45deg MITER BENDS, ONLY ONE CONSTRUCTION WELD SHALL BE CONSIDERED (REF. TO APPLICABLE STANDARD) CONDITION AND ERECTION: 079254C-0000-MS-1300-001 CALCULATIONS NUMBERS REFER TO DOC.: 079254C-'UNIT'-NM-1370-001 SUPPORT
6) THE INITIAL AND FINAL COORDINATES IN ELEVATION ARE SHOWN AT CENTER OF PIPELINE. WHILE AT EACH CHANGE IN PIPE ELEVATION (COMPONENTS)
IT IS SHOWN AS BOP (BOTTOM OF PIPE) POSITION
PROJ. AREA DOC. TYPE SERVICE UNIT SEQUENCE N. SUBLINE SHEET OF SHEETS REV
1 25/11/2022 REVISED AS SHOWN N.A. N.A. A.S./L.B 0 16/06/2022 ISSUED FOR CONSTRUCTION N.A. N.A. A.S./L.B
REV DATE DESCRIPTION STRESS INSTR APPR. REV DATE DESCRIPTION STRESS INSTR APPR. REV DATE DESCRIPTION STRESS INSTR APPR.
079254C 1062U03 ISO FWA 1062 701314 0001 03 04 1
EXTRACTION DATE: 25/11/2022 14:47 Technip Energies Italy S.p.A - 00148 ROMA - Viale Castello della Magliana, 68
P IP ING SP EC. C. A . DES. P RESS. OP ER. P RESS. DES. TEM P . OP ER. TEM P . TEST P RESS. FLUID P A INT NDT P ED TEST IP S NP D INS. INS. THK TRA CING TRA CING
or reverse engineer the same, in any manner, without ANOPC prior written consent and/or Technip Energies Italy S.p.A. prior written consent, and shall not put in use the information for any purpose unrelated to that for which it has been transmitted to recipient. An y disclosure and use of the contents hereof shall be subject
P &ID
SP EC.
SP EC. M A T
RA TING (mm) (Kg/cm2g) (Kg/cm2g) (°C) (°C) (Kg/cm2g) P HA SE NO.
P WHT
RT / M T CA T. TYP E E (inch) TYP E (mm) CODE SIZE BILL OF MATERIAL SKETCH LIST
N
agreements between ANOPC, Technip Energies Italy S.p.A. and the intended recipient. The copyright in this document and/or attachments is owned by ANOPC and Technip Energies Italy S.p.A.. while the underlying IP is owned by other Tecnology Providers and an y reproduction or adaptation thereof to any subsisting
1062-PID-1931-701-1 A DP 0HU1 HDPE 150 lbs 0 12 7 50 37 L " per
NOme
P AilINT
grado di maturità
- di questo
- setting è tale
H che po ssa essere
14 passato
N in pro duzio
0 ne" (A FIO 12-A P R-2016) POS DESCRIPTION THK1 THK2 ASBL/ IDENT DIAMETER QTY
NO DEST (PCS/MM)
This document and its attachments, if any, contains confidential and proprietary information belonging to ANOPC, and/or other third parties, including Technip Energies Italy S.p.A. The intended recipient of the information contained here in shall not divu lge the same to any third part or sell, trade, publish, reproduce
ERECTION
1 Pipes (Length),ASTM D3035,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44JJJ6C 14 48429
Ends,-, C44JJJ6C, 7,
2 Red Te,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion Ends,Mnf SDR9 SDR9 7 C44S0L06 14X6 1
Std, C44S0L06, 7,
3 22.5° Elb LR,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44K9BZX 14 1
3
Ends,Mnf Std, C44K9BZX, 7,
22.5°
4 Back Flg (SO Stub),Mnf Std,ASTM A536 Gr.60-40-18,FF,150 Lbs, 7 C451R3DY 14 1
239 B.O.P.
C451R3DY, 7,
EL.111572
5 NM Flat Gk,ASME B16.21,FF as per ASME B16.5,IBC Type,150 Lbs, , 2 C3P9L482 14 2
14"NS 2,
21 Std,
FW
91 11
1 50
0
221
23
FW 11
50 CONT. ON
0
1062U03-FWA-1062701313-0001
W 1765332
1 N 170200
11
24 50 EL.111750
FW 0
1 25 305
FW 11
50
CONT. ON 1 0
FWA-1062701314-0001 SHT 03 27
W 1764900 1 FW 305
26
N 218170 FW
EL.111659 F4/8 G5 B6
2
14X6"NS 12 BT4
22 280
432 28
FW 381
FW 1 7
29 BT5 STEM UP
FW PLZ-009
CONT. ON
1062U03-FWA-1062701312-0001
W 1764900 G5 B6
N 168007
EL.111750
TB3
shall require ANOPC's and/or, when needed, Technip Energies Italy S.p.A.'s express written approval.
SYMBOLOGY
2) DIMENSIONS AND LAYOUT OF SOCKET WELDED AND THREADED LINES ARE INDICATIVE ONLY AND SHALL BE CHECKED
AT JOB SITE BEFORE ERECTION
DOCUMENTS 2) PIPING MATERIAL CLASSES: 079254C-0000-JSD-1300-001 NON DESTRUCTIVE EXAMINATION: 079254C-0000-MS-1320-051 N FIELD WELD
NOTES - VALID ONLY FOR U/G PIPING SKETCHES -
3) TOTAL LENGTH OF U/G PIPING TO BE CONSIDERED INCLUSIVE OF EXPANSION JOINTS OR ANY EMBEDDED PIPE INTO PITS FOR DESIGN 3) TECHNICAL SPECIFICATION FOR PIPING PREFABRICATION 5) FOR STRESS ANALYSIS "FLEXIBILITY LEVELS" AND STRESS ANALYSIS TRACED LINE No. 14"-FWA-1062701314-ADP0HU1-N ISOMETRIC ID. 1062U03-FWA-1062701314
4) ISOMETRIC SKETCHES PREVAIL ON 2D AREA DRAWINGS
5) FOR 45deg MITER BENDS, ONLY ONE CONSTRUCTION WELD SHALL BE CONSIDERED (REF. TO APPLICABLE STANDARD) CONDITION AND ERECTION: 079254C-0000-MS-1300-001 CALCULATIONS NUMBERS REFER TO DOC.: 079254C-'UNIT'-NM-1370-001 SUPPORT
6) THE INITIAL AND FINAL COORDINATES IN ELEVATION ARE SHOWN AT CENTER OF PIPELINE. WHILE AT EACH CHANGE IN PIPE ELEVATION (COMPONENTS)
IT IS SHOWN AS BOP (BOTTOM OF PIPE) POSITION
PROJ. AREA DOC. TYPE SERVICE UNIT SEQUENCE N. SUBLINE SHEET OF SHEETS REV
1 25/11/2022 REVISED AS SHOWN N.A. N.A. A.S./L.B 0 16/06/2022 ISSUED FOR CONSTRUCTION N.A. N.A. A.S./L.B
REV DATE DESCRIPTION STRESS INSTR APPR. REV DATE DESCRIPTION STRESS INSTR APPR. REV DATE DESCRIPTION STRESS INSTR APPR.
079254C 1062U03 ISO FWA 1062 701314 0001 04 04 1
EXTRACTION DATE: 25/11/2022 14:47 Technip Energies Italy S.p.A - 00148 ROMA - Viale Castello della Magliana, 68
P IP ING SP EC. C. A . DES. P RESS. OP ER. P RESS. DES. TEM P . OP ER. TEM P . TEST P RESS. FLUID P A INT NDT P ED TEST IP S NP D INS. INS. THK TRA CING TRA CING
or reverse engineer the same, in any manner, without ANOPC prior written consent and/or Technip Energies Italy S.p.A. prior written consent, and shall not put in use the information for any purpose unrelated to that for which it has been transmitted to recipient. An y disclosure and use of the contents hereof shall be subject
P &ID
SP EC.
SP EC. M A T
RA TING (mm) (Kg/cm2g) (Kg/cm2g) (°C) (°C) (Kg/cm2g) P HA SE NO.
P WHT
RT / M T CA T. TYP E E (inch) TYP E (mm) CODE SIZE BILL OF MATERIAL SKETCH LIST
N
agreements between ANOPC, Technip Energies Italy S.p.A. and the intended recipient. The copyright in this document and/or attachments is owned by ANOPC and Technip Energies Italy S.p.A.. while the underlying IP is owned by other Tecnology Providers and an y reproduction or adaptation thereof to any subsisting
1062-PID-1931-701-1 A DP 0HU1 HDP E 150 lbs 0 12 7 50 37 L " per
NOme
P AilINT
grado di maturità
- di questo
- setting è tale
H che po ssa essere
6 passato
N in pro duzio
0 ne" (A FIO 12-A P R-2016) POS DESCRIPTION THK1 THK2 ASBL/ IDENT DIAMETER QTY
NO DEST (PCS/MM)
This document and its attachments, if any, contains confidential and proprietary information belonging to ANOPC, and/or other third parties, including Technip Energies Italy S.p.A. The intended recipient of the information contained here in shall not divu lge the same to any third part or sell, trade, publish, reproduce
ERECTION
1 Pipes (Length),ASTM D3035,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44JJJWW 6 3668
Ends,-, C44JJJWW, 7,
14X6"NS
1
FW
14"NS
68
36
1
FW
CONT. ON
1062U03-FWA-1062701314-0001
W 1765332
N 170200
EL.111750
CONT. ON
1M59U02-FWA-1M59705305-0001
W 1769000
N 170200
EL.111750
shall require ANOPC's and/or, when needed, Technip Energies Italy S.p.A.'s express written approval.
SYMBOLOGY
2) DIMENSIONS AND LAYOUT OF SOCKET WELDED AND THREADED LINES ARE INDICATIVE ONLY AND SHALL BE CHECKED
AT JOB SITE BEFORE ERECTION
DOCUMENTS 2) PIPING MATERIAL CLASSES: 079254C-0000-JSD-1300-001 NON DESTRUCTIVE EXAMINATION: 079254C-0000-MS-1320-051 N FIELD WELD
NOTES - VALID ONLY FOR U/G PIPING SKETCHES -
3) TOTAL LENGTH OF U/G PIPING TO BE CONSIDERED INCLUSIVE OF EXPANSION JOINTS OR ANY EMBEDDED PIPE INTO PITS FOR DESIGN 3) TECHNICAL SPECIFICATION FOR PIPING PREFABRICATION 5) FOR STRESS ANALYSIS "FLEXIBILITY LEVELS" AND STRESS ANALYSIS TRACED LINE No. 6"-FWA-1062701313-ADP0HU1-N ISOMETRIC ID. 1062U03-FWA-1062701313
4) ISOMETRIC SKETCHES PREVAIL ON 2D AREA DRAWINGS
5) FOR 45deg MITER BENDS, ONLY ONE CONSTRUCTION WELD SHALL BE CONSIDERED (REF. TO APPLICABLE STANDARD) CONDITION AND ERECTION: 079254C-0000-MS-1300-001 CALCULATIONS NUMBERS REFER TO DOC.: 079254C-'UNIT'-NM-1370-001 SUPPORT
6) THE INITIAL AND FINAL COORDINATES IN ELEVATION ARE SHOWN AT CENTER OF PIPELINE. WHILE AT EACH CHANGE IN PIPE ELEVATION (COMPONENTS)
IT IS SHOWN AS BOP (BOTTOM OF PIPE) POSITION
PROJ. AREA DOC. TYPE SERVICE UNIT SEQUENCE N. SUBLINE SHEET OF SHEETS REV
0 16/06/2022 ISSUED FOR CONSTRUCTION N.A. N.A. A.S./L.B
REV DATE DESCRIPTION STRESS INSTR APPR. REV DATE DESCRIPTION STRESS INSTR APPR. REV DATE DESCRIPTION STRESS INSTR APPR.
079254C 1062U03 ISO FWA 1062 701313 0001 01 01 0
EXTRACTION DATE: 20/06/2022 20:47 Technip Energies Italy S.p.A - 00148 ROMA - Viale Castello della Magliana, 68
P IP ING SP EC. C. A . DES. P RESS. OP ER. P RESS. DES. TEM P . OP ER. TEM P . TEST P RESS. FLUID P A INT NDT P ED TEST IP S NP D INS. INS. THK TRA CING TRA CING
or reverse engineer the same, in any manner, without ANOPC prior written consent and/or Technip Energies Italy S.p.A. prior written consent, and shall not put in use the information for any purpose unrelated to that for which it has been transmitted to recipient. An y disclosure and use of the contents hereof shall be subject
P &ID
SP EC.
SP EC. M A T
RA TING (mm) (Kg/cm2g) (Kg/cm2g) (°C) (°C) (Kg/cm2g) P HA SE NO.
P WHT
RT / M T CA T. TYP E E (inch) TYP E (mm) CODE SIZE BILL OF MATERIAL SKETCH LIST
N
agreements between ANOPC, Technip Energies Italy S.p.A. and the intended recipient. The copyright in this document and/or attachments is owned by ANOPC and Technip Energies Italy S.p.A.. while the underlying IP is owned by other Tecnology Providers and an y reproduction or adaptation thereof to any subsisting
1M 59-PID-1931-705-1 A DP 0HU1 HDP E 150 lbs 0 12 7 50 37 L " per
NOme
P AilINT
grado di maturità
- di questo
- setting è tale
H che po ssa essere
6 passato
N in pro duzio
0 ne" (A FIO 12-A P R-2016) POS DESCRIPTION THK1 THK2 ASBL/ IDENT DIAMETER QTY
NO DEST (PCS/MM)
This document and its attachments, if any, contains confidential and proprietary information belonging to ANOPC, and/or other third parties, including Technip Energies Italy S.p.A. The intended recipient of the information contained here in shall not divu lge the same to any third part or sell, trade, publish, reproduce
ERECTION
1 Pipes (Length),ASTM D3035,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44JJJWW 6 3037
Ends,-, C44JJJWW, 7,
2 90° Elb LR,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion SDR9 SDR9 7 C44K9A50 6 1
C451R3E6, 7,
2,
NS C4KDM3LG, 7,
6" 7 Stub SP,ASTM D3261,ASTM D3350 Gr. PE 445574C,Butt Fusion Ends,Mnf SDR9 7 C44K92PJ 6 3
CONT. ON Std,
CONT. ON 1062U03-FWA-1062701313-0001
Class 150 FF 1M59A04-FWA-1M59706301-0001 W 1769000 1
W 1772330 N 170200 FW
CLASS: N 170200 EL.111750
ACS3A00 EL.112803
CLASS:
ADP0HU1
203 TB4
BT3
6 2 9 0
FW
F3/7 G4 B5
FW 1 14
F3/7 G4 B5
6
6"NS
STEM UP BT1
PLZ-005
1
617
3
FW 204
266
204
BT2
5 0
FW 1 93 F3/7 G4 B5
230
2
B.O.P.
EL.111666 4 230
FW
shall require ANOPC's and/or, when needed, Technip Energies Italy S.p.A.'s express written approval.
SYMBOLOGY
2) DIMENSIONS AND LAYOUT OF SOCKET WELDED AND THREADED LINES ARE INDICATIVE ONLY AND SHALL BE CHECKED
AT JOB SITE BEFORE ERECTION
DOCUMENTS 2) PIPING MATERIAL CLASSES: 079254C-0000-JSD-1300-001 NON DESTRUCTIVE EXAMINATION: 079254C-0000-MS-1320-051 N FIELD WELD
NOTES - VALID ONLY FOR U/G PIPING SKETCHES -
3) TOTAL LENGTH OF U/G PIPING TO BE CONSIDERED INCLUSIVE OF EXPANSION JOINTS OR ANY EMBEDDED PIPE INTO PITS FOR DESIGN 3) TECHNICAL SPECIFICATION FOR PIPING PREFABRICATION 5) FOR STRESS ANALYSIS "FLEXIBILITY LEVELS" AND STRESS ANALYSIS TRACED LINE No. 6"-FWA-1M59705305-ADP0HU1-N ISOMETRIC ID. 1M59U02-FWA-1M59705305
4) ISOMETRIC SKETCHES PREVAIL ON 2D AREA DRAWINGS
5) FOR 45deg MITER BENDS, ONLY ONE CONSTRUCTION WELD SHALL BE CONSIDERED (REF. TO APPLICABLE STANDARD) CONDITION AND ERECTION: 079254C-0000-MS-1300-001 CALCULATIONS NUMBERS REFER TO DOC.: 079254C-'UNIT'-NM-1370-001 SUPPORT
6) THE INITIAL AND FINAL COORDINATES IN ELEVATION ARE SHOWN AT CENTER OF PIPELINE. WHILE AT EACH CHANGE IN PIPE ELEVATION (COMPONENTS)
IT IS SHOWN AS BOP (BOTTOM OF PIPE) POSITION
PROJ. AREA DOC. TYPE SERVICE UNIT SEQUENCE N. SUBLINE SHEET OF SHEETS REV
0 16/06/2022 ISSUED FOR CONSTRUCTION N.A. N.A. A.S./L.B
REV DATE DESCRIPTION STRESS INSTR APPR. REV DATE DESCRIPTION STRESS INSTR APPR. REV DATE DESCRIPTION STRESS INSTR APPR.
079254C 1M59U02 ISO FWA 1M59 705305 0001 01 01 0
EXTRACTION DATE: 15/06/2022 17:50 Technip Energies Italy S.p.A - 00148 ROMA - Viale Castello della Magliana, 68