Professional Documents
Culture Documents
A_new_electronic_feedback_compensation_method_for_rate_integrating_gyroscopes
A_new_electronic_feedback_compensation_method_for_rate_integrating_gyroscopes
(b)
(b) (c)
Fig. 3: (a) Gyro output with 200 dps rate applied with rate
table. (b) Residual error before and after compensation. (c)
Fourier components of error before and after compensation.
The dominant error terms are 2θ and 4θ harmonics.
modes, and θ is the angle (sensor’s output). Equation (4) shows
Fig. 2: (a) Block diagram of the RIG controller. (b) Measured the modified matrix G in which δτ (anisodamping error) and θτ
controller performance. Energy is controlled at an amplitude (primary axis of damping) is used to calculate its value.
of 70 nm, and the Q/E ratio is 0.004. (c) Measured bandwidths
The anisodamping error can be characterized through
of the energy controller (140 Hz) and the quadrature several test presented in [2]. In this paper, we use a method by
controller (105 Hz). applying a rate to calculate the anisodamping value and primary
where, xc and x s are in-phase and quadrature portions of the X axis of damping. Due to existence of anisodamping, the angle
axis resonance mode signal after demodulation and yc and y s precession measured from gyroscope includes 2θ angle
dependent error. By subtracting a linear fit (Fig. 3 (a)) from the
are in-phase and quadrature portions of the Y axis. The rate output and performing Fourier analysis on the residual (Fig.
anisodamping error and its compensation will be discussed later 3 (b)), the nθ components of the residual can be calculated. Also
in the paper. frequency sweeps in both X and Y axis confirms a 13.3%
In addition to closed-loop controller used to null difference in quality factor and 12% different in gain of each
anisoelasticity, a closed-loop energy controller is needed to axis due to transducer electrode gap difference and amplifiers
control the oscillation amplitude [2,4]. The energy is calculated gains.
by: After implementation of compensation for anisodamping
E xc2 xs2 yc2 ys2 (2) and gain difference due to transducer electrode gap difference
and amplifiers gains, the RIG is tested under rate from a rate
The implementation of closed-loop controllers on quadrature table for three different conditions presented in Fig. 4. The figure
and energy, result in measured stabilized quadrature and energy shows the angle dependency of the residual error calculated
for all angles illustrated in Fig. 1 (b). The measured bandwidth using the method presented in Fig. 3, and the measurements are
of the controllers are illustrated in Fig. 1 (c) respectively compared with simulation models made using a modified
showing a BW of 140 Hz and 105 Hz.
B. Anisodamping compensation
To compensate for anisodamping error a modified angle
dependent controller from [4] is used. The modified equation is:
FEx cos
Ey
F [k p ( E0 E ) k I ( E0 E )dt ]G
sin
(3)
cos sin
G I (4)
sin cos
Authorized licensed use limited to: Johns Hopkins University. Downloaded on March 03,2023 at 18:00:23 UTC from IEEE Xplore. Restrictions apply.
version of original base-band model presented in [4], showing a (a) (b)
significant reduction in residual error.
C. Phase-Locked loop (PLL)
The reference signal for phase-locked loop (PLL) used in this
work unlike [2] is a combination of signals from axis X and axis
Y. The signals of the feedback loop to the PI controller of the
PLL are shown in equation (5) and (6), Ls being the quadrature
and Lc being in phase portions of L signal: (c)
Ls 2xc xs yc ys (5)
Authorized licensed use limited to: Johns Hopkins University. Downloaded on March 03,2023 at 18:00:23 UTC from IEEE Xplore. Restrictions apply.
(a) (a) (b)
(b) (c)
(c)
Authorized licensed use limited to: Johns Hopkins University. Downloaded on March 03,2023 at 18:00:23 UTC from IEEE Xplore. Restrictions apply.