Professional Documents
Culture Documents
Automatic Fire Sprinkler System Installation T & C & O & M 06-08-21 -
Automatic Fire Sprinkler System Installation T & C & O & M 06-08-21 -
An Article Presentation by
Henry E. Suarez, pme/rmp
DISCLAIMER
This presentation material deals with some
subjects related to the installation, testing,
commissioning, operation and maintenance
of automatic fire protection. This, however,
does not attempt to cover the totality of the
subject matter.
2
COURSE OUTLINE
PART 1‐ INSTALLATION
20
PLANNING INSTALLER/ CONTRACTOR OWNER
DESIGN/
FCD
INSTALLATION Y
N
TESTING &
COMMISSIONING
N Y
Y OPERATION &
MAINTENANCE
N
20
PART 1‐ INSTALLATION
20
Components of an Automatic
Sprinkler System
20
COMPONENTS OF FIRE SPRINKLER
SYSTEM TERMINOLOGIES
89
COMPONENTS OF FIRE SPRINKLER
SYSTEM TERMINOLOGIES
Branch Lines. The pipes in which the sprinklers are placed, either directly or
through risers.
Cross Mains. The pipes supplying the branch lines, either directly or through
risers.
Feed Mains. The pipes supplying cross mains, either directly or through risers.
Flexible Listed Pipe Coupling. A listed coupling or fitting that allows axial
displacement, rotation, and at least 1 degree of angular movement of the pipe without
inducing harm on the pipe. For pipe diameters of 8 in. (203.2 mm) and larger, the angular
movement shall be permitted to be less than 1 degree but not less than 0.5 degree.
BRANCHLINE
SPRINKLER HEADS
CROSSMAIN
FEEDMAIN
16
90
Engine‐ Driven Vertical Turbine Pump
17
90
JOCKEY PUMP
18
90
Piping Installation Few Rules
1. Use flexible isolator or connector on both
suction and discharge pipes.
2. Suction pipe should provide a straight,
unrestricted run that is 5x to 10x the
diameter of that pipe, between the suction
reducer and the first obstruction in the line.
3. Install eccentric reducer with the straight
side on top at the pump suction.
Piping Installation Few Rules
4. The pipe diameter on both inlet and the outlet sides
of the pump should be at least one size larger than
the nozzle itself.
5. Eliminate elbows mounted, or close to, the inlet
nozzle of the pump.
6. Eliminate the potential for vortices or air
entrainment in the suction source.
7. Arrange the piping in such a way that there is no
strain imposed on the pump casing.
Figure A-2-9.6 Right and wrong pump suctions.
96
96
Figure A-3-3.1 Horizontal split-case fire pump installation with water supply under
a positive head.
96
Suction Pipe with Anti-Vortex Plate
96
Vertical- Turbine Pump with Strainer
96
Figure A-4-2.2.1 Vertical shaft turbine-type pump
installation in a well.
96
Figure A-4-2.2.2 Vertical shaft turbine-type pump
installation in a wet pit.
96
Figure A-4-3.1 Belowground discharge arrangement.
96
Submersible Fire Pump
96
Package-Type Fire/ Jockey Pump Assembly,
Skid- Mounted
96
Figure A-2-19.3 Jockey pump installation with fire pump.
96
Figure A-2-9.4 Schematic diagram of suggested arrangements for a fire pump
with a bypass, taking suction from public mains.
96
FIRE/JOCKEY PUMP CONTROLLER
96
Pressure Sensing Lines.
61
PIPE MATERIALS
61
PIPE FITTINGS
61
VALVES USED IN FIRE FIGHTING SYSTEM
Butterfly Valve
Resilient Seated Gate Valves
Strainer
Check Valve
Wall mounted
Flow Switch
Supervisory Switch
61
Alarm Check Valve
61
Figure A-5-13.22 One arrangement of flanged joint at sprinkler riser.
61
Figure A-5-14.1.1 Examples of acceptable valve arrangements.
61
Figure A-5-14.1.1.8 Pit for gate valve, check valve, and fire department connection.
61
Figure A-5-15.2(a) Fire department connection.
61
Figure A-5-15.2(b) Typical city water pit—valve arrangement.
61
Figure A-5-15.4.2(a) System test connection on wet pipe system.
61
Figure A-6-3.2(a) Thrust forces acting on a bend.
Figure A-6-3.2(b) Typical connection to a fire protection system riser.
Figure A-6-3.2(c) Bearing thrust block.
Figure A-6-3.2(d) Gravity thrust block.
HANGERS AND SUPPORTS
Table 6-2.2 Maximum Distance Between Hangers (ft-in.)
Nominal Pipe 3/
4 1 1 1 /4 1 1 /2 2 2 1 /2 3 3 1 /2
Size (in.)
Steel pipe except N/A 12‐0 12‐0 15‐0 15‐0 15‐0 15‐0 15‐0
threaded lightwall
Threaded lightwall steel N/A 12‐0 12‐0 12‐0 12‐0 12‐0 12‐0 N/A
pipe
Copper tube 8‐0 8‐0 10‐0 10‐0 12‐0 12‐0 12‐0 15‐0
Polybutylene (IPS) N/A 3‐9 4‐7 5‐0 5‐11 N/A N/A N/A
Polybutylene (CTS) 2‐11 3‐4 3‐11 4‐5 5‐5 N/A N/A N/A
Ductile Iron Pipe N/A N/A N/A N/A N/A N/A 15‐0 N/A
60
Frangible Glass Bulb Sprinkler
57 Orange
68 Red
79 Yellow
93 Green
141 Blue
182 Mauve
204 to 260 Black
68 to 74 Uncoloured
93 to 100 White
141 Blue
182 Yellow
227 Red
Water distribution pattern from typical upright and pendant spray sprinklers.
Water distribution pattern from a typical ‘conventional’ or ‘old style’ sprinkler.
Note that ‘conventional’ pattern sprinkler is able to be installed either upright or
pendant.
SPRINKLER HEADS
5 ft and greater 18
Figure 5-6.5.1.2(a) Positioning of sprinklers to avoid obstructions to
discharge (SSU/SSP).
61
Figure 5-6.5.2.2 Minimum distance from obstruction (SSU/SSP).
Figure 5-6.5.2.3 Suspended or floor-mounted obstructions (SSU/SSP).
Table 5-7.5.1.2 Positioning of Sprinklers to Avoid Obstructions
(Standard Sidewall Spray Sprinklers)
4 ft to less than 5 ft 1
8 ft 6 in. or greater 14
7 ft and greater 14
Figure 5-8.5.1.2(a) Position of sprinklers to avoid obstructions to discharge
(extended coverage upright and pendent spray sprinklers).
Figure 5-8.5.1.2(b) Obstructions against walls (extended coverage upright and
pendent spray sprinklers).
Figure 5-8.5.2.2 Minimum distance from obstruction (extended coverage
upright and pendent spray sprinklers).
Table 5-8.5.2.3 Suspended or Floor-Mounted Obstructions (Extended Coverage
Upright and Pendent Spray Sprinklers)
5-9.4.1.1
Sidewall sprinkler deflectors shall be located not more than 6 in. (152 mm) nor less
than 4 in. (102 mm) from ceilings.
Exception: Horizontal sidewall sprinklers are permitted to be located in a zone 6 in.
to 12 in. (152 mm to 305 mm) or 12 in. to 18 in. (305 mm to 457 mm) below
noncombustible or limited-combustible ceilings where listed for such use.
5-9.4.1.2
Sidewall sprinkler deflectors shall be located not more than 6 in. (229 mm) or less
than 4 in. (102 mm) from walls on which they are mounted.
Distance from Sidewall Maximum Allowable
Sprinkler to Side of Obstruction Distance of Deflector
(A) above Bottom of
Obstruction (in.) (B)
8 ft to less than 10 ft 1
10 ft to less than 11 ft 2
11 ft to less than 12 ft 3
12 ft to less than 13 ft 4
13 ft to less than 14 ft 6
14 ft to less than 15 ft 7
15 ft to less than 16 ft 9
16 ft to less than 17 ft 11
17 ft or greater 14
Figure 5-9.5.1.2 Positioning of sprinklers to avoid obstructions (extended
coverage sidewall sprinklers).
Figure 5-9.5.2.2 Minimum distance from obstruction (extended coverage sidewall).
Table 5-9.5.2.3 Suspended or Floor-Mounted Obstructions (Extended
Coverage Sidewall Sprinklers)
(1) For systems having less than 300 sprinklers, not fewer
than six sprinklers
(2) For systems with 300 to 1000 sprinklers, not fewer than
12 sprinklers
(3) For systems with over 1000 sprinklers, not fewer than 24
sprinklers
PART 2‐ TESTING & COMMISSIONING
Sprinkler System
Acceptance Testing
To complete the installation of
a sprinkler system, the
installing contractor must
complete the acceptance steps
required in NFPA 13: These
final steps in the design and
installation of sprinkler systems
are to confirm that the basic
requirements of NFPA 13 are
satisfied, that the work was
completed in an acceptable
manner, and that the customer
is receiving a system that
performs as intended.
The contractor must notify the Authority Having Jurisdiction, who will
then decide if they wish to witness the testing or not. The contractor
then conducts the individual system acceptance and operational testing
described in NFPA 13. The specific item tested will vary depending on
what type of sprinkler system is installed, but may include all or some
of the following:
2. Hydrostatic test.
Backflow Testing
A backflow preventer, or a double check valve backflow prevention assembly in
this case, is a device that is connected between the water line leading to the
sprinkler system and the public water line coming from the street. A backflow
preventer device is installed to prevent the reverse flow of water, which could
contaminate the public water supply.
Documentation of Inspections
After all inspections were completed, technicians filled out the necessary
documentation showing that all required inspections had been
completed according to codes and regulations. These documents are the
client’s records in case a Fire Marshal or other public official wants to
check that all inspections are up to date.
Figure A-11-2.6.3(f) Pump acceptance test data. (Courtesy of Factory Mutual
Research Corp.)
96
PART 3‐ OPERATION & TESTING &
MAINTENANCE
Step 1: Testing the Control Valve
The first step when inspecting the sprinkler system is to test the butterfly control
valve. while exercising the valve (closing) in this scenario the control valve has a
tamper switch installed, the tamper will transmit a supervisory signal and or a
trouble condition to the fire alarm panel. This is to notify building occupants,
owners and fire department there is a control valve closed or partially open. In the
event of a fire, the water may not reach the hazard area due to the valve being
closed. Once the technician in the attic confirms with the technician at the fire
control panel, that the panel recognizes the valve is turned off, he opens the valve
back up. Once the valve is returned to its normal position a tamper seal is placed
on the valve to ensure it is in the correct position before leaving. The tie can easily
be broke in the event that the valve needs to be closed. The seal also serves as a
deterrent to keep people from tampering with the valve.
Step 2: Gauge Readings & Activating the Sprinkler System
The next step the technician in the attic takes is to capture a reading of the
gauge. The gauge ensures there is proper water pressure for the fire sprinkler
system to operate effectively. Once the reading is taken, the technician then
opens the main drain of the fire sprinkler system to determine that there is
sufficient water pressure supplying the fire sprinkler system and there are no
blockages that will hinder the system from performing in the event of a fire.
After performing the main drain, the technician will then locate what is called
the inspector’s test. The inspector’s test is typically located at the farthest point
of the sprinkler system. The inspector will then open the inspector’s test, the
inspector’s test simulates a sprinkler activating and shall send a signal to the fire
alarm panel within 90 seconds. These same steps are taken on every floor as the
technician makes his way to the basement. After inspecting the fire sprinkler
systems the technician will then verify signals were transmitted to the
monitoring company and place systems back in service. If additional devices
are being tested (backflows) we will keep the system on test due to closing
additional valves.
Wet Pipe Sprinkler Systems Inspection
Testing and Maintenance
• Water Flow Alarms
– Test vane type and pressure switch typewater flow devices semiannually
– Water motor gongs tested quarterly
• System Gauges
– Test for accuracy every 5 years (or replace)
• Control Valves
– Test tamper switches semi annually
– Operate and lubricate valve through full range of operation annually
112
• Sprinkler Heads
– Standard sprinklers to be tested at 50 years and every 10 years thereafter
– Quick response sprinklers tested aftertwenty years and at ten year intervals
thereafter or replaced
– Sprinkler manufactured prior to 1920 are to be replaced
• Obstruction Investigation
– Flushing and removal of end sprinkler froma branch line — 5 years
112
Dry Pipe Sprinkler System Inspection Testing and
Maintenance
• System Gauges
– Test for accuracy every 5 years (or replace)
112
Dry Pipe Sprinkler System Inspection Testing and
Maintenance
•
• Sprinkler Heads
– Dry sprinklers to be tested every ten years or replaced
– Sprinkler manufactured prior to 1920 are to be replaced
• Fire Pump
– Diesel pump driver— Weekly start and run test for thirty minutes
– Electric pump driver— Monthly start and run test for 10 minutes
– Annual full flow test
– Exercise circuit breaker and isolating switch monthly
– Service electric driver— grease and check connections annually
– Check pump bearings and pump shaft transmission for lubrication annually
– Check pump shaft for excess end play annually
112
Common Components To All System Inspection
Testing and Maintenance
• Backflow Preventer
– Test and maintain annually
– Flow test to meet sprinkler system demand
• Fire Hydrants
– Annual test and lubrication
– Flow test every five years
112
96
References
1. Uniform Mechanical Code
2. Philippine Society of Mechanical Engineers
3. National Fire Protection Association, NFPA No.
13, 20 and 25 Standards
18