Professional Documents
Culture Documents
ENGM041 Unit 1
ENGM041 Unit 1
Introduction
The purpose of this package is to explain the principles and aims of the design of
reinforced concrete structures and to give some background to the design of these
buildings. Although much of the theory used in RC design is fundamental, adhering to
the laws of mechanics, ultimately the design must conform to the requirements of a code
of practice. In this course it is to BS EN 1992-1-1 Eurocode 2: Design of Concrete
Structures published by the British Standards Institution, and which is henceforth
referred to as EC2, Eurocode 2 or simply the Code. Eurocode 2 is a Europe wide code
which enables designers across Europe to practice in any country which adopts the code.
There is however, one proviso, the design of buildings in a specific country requires the
National Annex for that country to be applied in the design. The National Annex for the
UK for example contains all the nationally determined parameters which refer
specifically to the UK due to our unique circumstances.
Cement
powder Cement
paste
Water Mortar
Sand Concrete
Gravel
Reinforcing
rods
Reinforced concrete
Links Reinforced
concrete beam
Longitudinal bars
Reinforcement cage
(Section)
Reinforcement cage.
Formwork
Concrete being
delivered by pump.
The philosophy behind design has altered since reinforced concrete was first used as a
structural material. Initially the design was for strength. Structures were made strong
enough to sustain the loads they were to be subject to. The effects of serviceability then
needed to be considered. For example, structures were designed to have limited
deflections so users felt comfortable when using them. Aspects such as fire loading or
the effect of blasts on reinforced concrete had an influence on strength requiring
designers to also consider these. At present designers are being asked to consider all
these aspects as well as to consider the whole life of the structure. In effect designers
need to design economically, ensure the users are happy when occupying the building,
ensure unforeseen circumstances are catered for and then to design for the disposal of the
building in an economic manner when its design life is over. Further, they are required to
design such that the embodied energy is minimised with respect to the whole life running
costs of the building.
Tension Tension
Compression
Tension
Compression Compression
Practical issue.
In reality a cage of reinforcement is provided along the entire length of the beam. Bars
are bigger in the tension zones to carry this load but needed elsewhere to enable links to
be fixed. Links resist shear (covered later) as well as holding the longitudinal
reinforcement in place. The diagram below demonstrates the reinforcement needed
Continuity reinforcement
Load
Support Support
Stage 1. Load is applied to the concrete and the beam deflects slightly. The concrete and
steel behave as one until a load is achieved when the concrete in tension at the bottom of
the beam cracks. If the beam were not reinforced it would fail at this stage. The
photograph below indicates the beam in this stage. Failure of the reinforced concrete
beam has not occurred but the width of the cracks are very important and must be
controlled in order to satisfy the serviceability (appearance) of the beam and to ensure the
reinforcement is protected. The figure below is an idealised description of this
behaviour. Load
Cracking load
Deflection
Stage 2. The load on the beam is increased steadily. The cracks along the lower soffit of
the beam lengthen upwards and increase in number. The tension effects of the concrete
are now negligible but concrete in the top part of the beam which is under compression
and the reinforcement which is in tension are behaving nearly elastically until the strains
(deformations) reach a critical value. The precise location of this critical value will be
difficult to fix as judgement will be needed to determine when linear behaviour ceases.
This stage of a beam‟s behaviour generally extends beyond the normal serviceability
conditions expected of a beam in use and the ultimate capacity is said to be achieved
when the „critical‟ strains are reached. The figure below illustrates this behaviour.
Cracking load
Deflection
Stage 3. Increasing the load further will cause the steel in the tension zone to yield and
become plastic at the position of maximum bending moment in the beam. Alternatively,
the concrete in the top of the beam may develop longitudinal cracks and crush or in some
instances a combination of both may occur. The photograph and figure below illustrate
this.
Cracking load
Deflection
Stage 4. When plastic failure has occurred, the beam will continue to deform with no
further load until it fails either by tensile failure of the reinforcement or through concrete
crushing. The photograph and figure below illustrate this behaviour.
Ultimate load
Plastic failure
Failure
Range of service loading
Load
Cracking load
Deflection
The above example helps one to understand the concept of over and under reinforced
beams. Under reinforced beams reach the limit of their service loading capability and fail
when the reinforcement yields. They have been designed so the concrete in compression
is stronger than the tensile strength of the steel at this load. Failure is not catastrophic as
once it is reached, the steel yields until it fails. This may occur over a considerable
period of time and in many instances when the yield point of the steel is reached, strain
hardening of the reinforcement occurs so there may be a temporary strengthening of the
beam.
With over reinforced beams failure occurs when the concrete in compression crushes.
The beam in this instance is designed so the reinforcement is stronger than the concrete.
Unfortunately concrete is a brittle material and failure is instantaneous so beams which
fail in this manner fail catastrophically and without warning.
A concrete element in tension cracks at right angles to the load. If an element is under
compression, cracks are parallel to the load. The Figure illustrates this.
Tension crack
Compression cracks
Web
shear Uniformly distributed load Compression cracks
cracks
Compressive stresses take the form of an arch while the tensile stresses are shaped as a
catenary. In accordance with the rule that tensile cracks occur at right angles to the
stresses and compressive cracks in a direction, parallel to stresses, tensile and
compressive cracks are shown on the figure in black.
At mid span in the bottom where the beam is in tension, the cracks are at right
angles to the span. These are termed flexural cracks.
Nearer the supports the cracks are inclined towards the centre of the span due to
the relationship between the principal stresses at this location . These cracks are
termed the flexural-shear cracks.
At the top of the beam, where the beam is in compression, cracks are parallel to
the top face of the beam and are compression cracks
Near the supports the tensile stresses, aided by the orthogonal compressive
stresses, produce diagonal cracks at right angles to the tensile stresses. These are
termed web shear cracks.
Web
Compression cracks
shear
cracks
Flexural cracks
Flexural
Principal tensile stresses
shear cracks
Principal compressive stresses
This close up shows the compression cracks at the top of the beam and flexural and
flexural-shear cracks.
Aims of Design.
1. with an appropriate degree of reliability, the structure will sustain all loads and
external influences likely to occur during construction, and subsequent
occupation. It should also have adequate durability to keep maintenance costs at a
minimum. (ultimate limit state and durability)
2. with acceptable probability, the structure will remain fit for the use for which it is
required – keeping in mind the intended life of the structure and its costs.
(serviceability limit state).
3. the structure will remain ft for the use for which it is required and will not be
damaged by events such as explosions, impact or accidents “to an extent
disproportionate to the original cause”. (robustness).
Limit states.
Definition. Limit states are defined as states beyond which the structure no longer
satisfies the performance requirements of the design and are classified as :-
These are associated with collapse or other forms of structural damage likely to
endanger life. They include:
o Excessive deformation
o Transformation of the structure or any part of it into a mechanism.
o Rupture
o Loss of stability of the structure or any part of it, including supports and
foundations.
o Fatigue or other time dependant effects.
The ultimate limit state should ensure structures are designed so that adequate means
exist to transmit the design ultimate dead, imposed and wind loads safely from the
highest support to the foundations. Robustness within a structure is required to prevent
disproportionate failure or collapse and as such may be considered an ultimate limit state.
Structures should include in the design a degree of robustness. For example, they should
not be unreasonably susceptible to the effects of accidents or explosions.
To be robust, the layout of the structure should be such that damage to small areas or
failure of a single element will not lead to progressive collapse. The concept is, however,
wider than this and design should ensure when local high loads are sustained by part of a
structure, the whole does not fail. For example in the Ronan Point building the floor
above should have sustained all existing loads above it without collapse. Ties would
have prevented the walls from being dislodged. The best way of designing for this is to
link the structure together with ties. In addition, when designing, the removal of certain
elements from the structure must not result in the overall collapse of the building or
significant parts of the building. The collapse at Ronan Point was a significant catalyst in
causing the Building Regulations to be altered.
Current requirements
The Building Regulations in England and Wales were revised in 2004 to make the
requirements to avoid disproportionate collapse apply to all buildings. They state: "The
building shall be constructed so that in the event of an accident the building will not
suffer collapse to an extent disproportionate to the cause". BS EN 1991-1-7-2006+A1-
2014 uses a risk-based approach (also followed in PD 6688-1-7-2009+A1 - 2014) to
classify buildings according to their height and use. The method allows the risks
associated with a building to be considered against the consequences of failure.
Classifying a building
In BS EN 1991-1-7-2006+A1-2014 there are four building Classes: 1, 2A, 2B and 3. The
building type and occupancies for each class are given in Table A.1 of BS EN 1991-1-7-
2006+A1-2014, together with a summary of the requirements.
At first sight the classification of the building into one of the building classes looks
simple; however, further inspection reveals some complications. For instance, buildings
with varying numbers of storeys, mixed-use buildings or buildings constructed with
basements. To help with this, useful and clear guidance has been published by NHBC5
with the support of the CLG; this is freely available on the website
www.planningportal.gov.uk.
Typically, for a building with varying storey heights, which falls into more than one
class, the most onerous class for robustness requirements should be adopted. However, if
the building is large in plan area and divided into separate structures to allow for
movement, then each structure may be classified separately. This may lead to a lower
classification for some of the structures that make up the complete building.
In a mixed-use building the more onerous class should generally be adopted. Where the
lower occupancy class is above a higher occupancy class then it may be possible to
classify the upper storeys in the lower class. For example two storeys of apartments over
one-storey retail premises exceeding 2000 m2 would require Class 2B for the retail floor,
but 2A for the apartments.
Basement storeys may be omitted from the total building storeys provided the basement
storeys meet Class 2B or above. There is no further guidance in BS EN 1991-1-7-
2006+A1-2014 and PD 6688-1-7-2009+A1 – 2014 on how to classify a basement but the
NHBC technical guidance notes recommend that a floor must be 1.2 m below external
ground level for at least 50% of the plan area of the building to qualify as a basement.
Class 1 buildings
Provided the building has been designed and constructed to the rules given in BS EN
1991-1-7-2006+A1-2014 and PD 6688-1-7-2009+A1 – 2014 and/or appropriate codes of
practice and in line with general good practice, no additional measures are necessary.
Class 2A buildings
Class 2A buildings require horizontal ties in the floor plates. If dedicated horizontal ties
are not provided then there must be „effective anchorage‟ of the suspended floors to the
walls. In terms of concrete elements, the use of the effective anchorage concept is used
when concrete floors are supported on masonry walls, by reference to BS 5628. Class 2A
buildings do not require vertical ties.
Class 2B buildings
There are effectively three approaches:
1 Compliance with tying rules
2 Showing that the removal of a wall or column will cause only limited damage
3 Showing that key elements are „non-removable‟.
The simplest approach is to provide horizontal and vertical ties, using tie forces derived
from the codes of practice. Alternatively, where ties are not provided, a check should be
carried out to show that, upon notional removal of each supporting column and wall, and
each beam supporting columns or walls (one at a time in each storey of the building) that
the building remains stable. Further, the area of floor at any storey at risk of collapse
should not exceed 15% of the floor area of that storey or 70 m2, whichever is the smaller.
The collapse should not extend further than the immediate adjacent storeys (see Figure
below).
Finally, where the removal of an element results in a collapse greater than permitted, then
it should be designed as a key element. Further details on the design of key elements is
given later in this guide.
this guidance gives the designer little assistance and no references are provided. CLG has
acknowledged that there is a paucity of information and is planning to publish more
guidance.
perform well in such situations because they have redundancy due to their continuity and
tying through the reinforcement.
Design responsibility
BS 8110 states: "The engineer responsible for the overall stability of the structure should
ensure the compatibility of the design and details of parts and components, even where
some or all of the design and details of those parts and components are not made by this
engineer". This is particularly important when it comes to the robustness of the
structural frame. The Eurocodes are not as specific with regards to a single engineer
taking responsibility, but nevertheless it is good practice. Therefore, it is the
responsibility of the designer, before incorporating any proprietary system as part of the
structure, to ensure that the assumptions made in the design and construction of such
systems are compatible with the design of the whole structure. This should include:
An adequate specification for that part.
Where a standard product designed and detailed by the manufacturer is included,
it is suitable for the particular structure.
The design and detailing of any such part is checked by the designer to ensure that
it satisfies the design intent and is compatible with the rest of the structure.
Measures are in place on site to ensure the structure is built as designed.
Eurocode 2
Eurocode 2, Part 1–1, Cl. 9.10 supplemented by the UK National Annex to EC2 gives
guidance on the design of ties. The tying requirements can be met by using reinforcement
provided for other purposes. The partial factors for accidental situations can be reduced to
γC = 1.2 for concrete and
γS = 1.0 for reinforcement and prestressing steel.
Key elements
Where a building has key elements, each element and its connections should be capable
of withstanding a design load of 34 kN/m2 at ultimate limit state. This should be applied
from any direction to the projected area of the member together with the reaction from
the attached components, which should also be assumed to be subject to a loading of 34
kN/m2. The load from the attached components may be reduced to the maximum reaction
that can be transmitted by the attached components and their connections. This advice is
given in BS 8110: Part 2, Cl. 2.6 and in PD 6687, Cl. 20.2 b) for use with Eurocode 2.
The previous Section outlines the requirements in the codes and standards to provide a
robust design. This Section outlines the typical details used for generic concrete element
and building types.
Post-tensioned concrete
Clause 4.1.6 of BS 8110 implicitly directs the designer to the requirements of Cl. 3.12.3.8
for tying arrangements appropriate for prestressed concrete, and these rules should also
be applied to posttensioned concrete. This includes the requirement to ensure that the
horizontal ties interact „directly and robustly‟ with the vertical structure. Similarly
Eurocode 2 does not differentiate between prestressed and reinforced concrete and the
same rules apply, including the requirement for two bottom bars to pass through the
column in flat slabs. If the tendons themselves are not passed between the column
longitudinal reinforcement, then sufficient tie bars should be provided at the bottom
of the slab and be anchored adequately to ensure that the tie forces are carried into
tendons which will act as the horizontal ties across the structure.
The opening up of adjacent cores at the end supports of hollowcore units should
be avoided.
The recommended maximum length of an open core in a hollowcore unit is 600
mm. Vertical ties for Class 2B buildings and above should be designed to resist
the accidental load combination, Ed
Detailing at a corner.
Continuous
vertical ties from
foundation to roof
External column
and wall ties
anchored or tied
horizontally into the
structure at each
floor and roof level.
These are concerned with the functioning of the structure under normal use, the
comfort of the people using the structure, the appearance of the structure and damage
to finishes or non structural members. They include :-
Serviceability limit states are just as important as ultimate limit states and are often the
controlling factor in design. For example it is deflection limits, not strength that control
how most slabs will span and indeed the span / depth ratio of many beams, governs the
design, not ULS.
The following effects can all influence how a structure performs often affecting the
serviceability. In most cases, however, appropriate design loads, well specified material
properties, slenderness limits and other simple rules allow for them.
Creep
Sway
Shrinkage
Settlement
Temperature
Cyclic loading.
Serviceability criteria govern the deflection and deformation of a structure and in this
respect, should not adversely affect its efficiency or appearance. Deflections should be
compatible with the movements acceptable by the component parts. eg. Finishes,
services, partitions, glazing and cladding.
For tall slender structures, the effect of lateral deflections should be considered.
However, the accelerations associated with the deflections may be more critical as these
are what the occupants will notice.
Cracking will always occur in reinforced concrete. Generally this is not a sign of failure
but the widths of these cracks must be limited, to ensure water and other deleterious
substances do not penetrate the concrete and cause corrosion of the reinforcement but
also as they must not be visible to the general public from say a meter or so away. Rules
exist in the codes which enable the widths of the cracks to be controlled through
including secondary reinforcement.
Durability of concrete.
Concrete durability is largely affected by how the structure performs under service loads.
Consider, for example, crack widths which are directly related to reinforcement
corrosion. The consequences of durability, though, can have repercussions on the
ultimate limit state if deterioration progresses significantly.
It is important to ensure all concrete elements are sufficiently durable. For a concrete
element to be durable it must be designed and constructed to protect the embedded
reinforcement from corrosion and generally to perform in a satisfactory manner in the
environment it is placed in and for the design life of the structure. Durability mainly
affects the reinforcement embedded within the concrete, but there are instances when the
concrete itself is affected and degrades. For example, certain types of ground sulphates
(or even pollutants with particular sulphates in them) can cause expansive reactions in
concrete significantly weakening it. Further, certain alkalis which are sometimes found
in the aggregate used to manufacture concrete have similar effects. Fortunately, both
these problems are rare in this region.
The environment in which concrete finds itself refers to any chemical or physical
reactions to which the structure as a whole, individual elements of the structure, or the
concrete itself is exposed and which may result in effects not included in the loading
conditions considered at the structural design stage. Inadequate attention to the durability
at the design and construction stages may subsequently lead to considerable expenditure
on inspection, maintenance and repair. Consequently, durability has gained in
importance in all codes over the years.
Corrosion of Reinforcement.
Carbonation ingress.
Acidic gases like carbon dioxide combine with water to form weak solutions of carbonic
acid which is washed over the surface of the concrete usually as a result of rain. This
acid reacts with parts of the concrete to de-passivate it and turn it acidic. Over time the
acidic front penetrates deeper into the concrete and if it reaches the reinforcement can
result in corrosion if moisture and oxygen are present. The penetration of the carbon
front has been observed to be proportional to (time)0.5. The Figure below indicates early
and later stages of carbonation.
Exposed surface Exposed surface
Carbonation
zone
Chlorides diffuse into the concrete from the surface, the concentration decreasing with
depth. When chlorides reach the steel surface in sufficient concentration, the passive
layer is broken down and the protective alkaline environment is degraded so corrosion
can occur if water and oxygen are present.
In the past calcium chloride was used as an accelerating admixture. It caused the
concrete to gain strength more rapidly so that high rise buildings could be built more
quickly as the supporting formwork could be removed quickly. One serious side ffect of
calcium chloride was that if included in sufficient quantities and if oxygen and water
were present, reinforcement corrosion commenced. It is now banned but many buildings
still exist with calcium chloride included.
Concrete
cover
Chloride
profile.
Chloride profile. Ingress
Chlorides included from the Chloride ingress into concrete
at mixing surface
The chart shown below attempts to relate the age for corrosion activity to start, concrete
cover and concrete grade to carbonation and chloride attack.
C40 C30
C45 C35
Carbonation
C25
Chlorides
10 20 30 40 50 60 70 80 90 100
C50
Age of corrosion activation (years)
C45 Increasing
concrete
C40 strength
C35
C30
C25
10 20 30 40 50 60 70 80 90 100
Minimum cover (mm)
This reaction is an expansive reaction that can cause cracking and disruption of the
concrete. AAR is a reaction within the concrete unlike most durability problems which
are associated with reinforcement deterioration.
For AAR to occur all three of the following conditions must be met.
Alkali aggregate reaction is relatively rare in the UK and where past experience with
particular cement / aggregate combinations indicates no tendency to the reaction,
precautions need not be taken. If, however, unfamiliar materials are being used, there
may be a risk and additional testing or access to the national database on aggregates
should be made.
Sulphate attack.
Normally concrete is only at risk from sulphates if it is buried as it is the sulphates
present in ground water which cause degradation to the concrete. So foundations and
retaining walls for example are at risk. In addition, in areas with high atmospheric
pollution airborne suphates can cause degradation to the concrete if they are washed over
the concrete by rain over a long period of time.
Sulphates are, however, present in most cements and in some aggregates and excessive
amounts of water-soluble sulphates from these sources can be deleterious to concrete.
Sulphate attack in concrete is expansive and again affects the concrete itself.
The water soluble sulphate content (SO3) of the concrete mix should not exceed 4% by
mass of the cement in the mix. The sulphate content is calculated as the total obtained
from the various constituents of the mix.
Sulphate attack can often be offset by using sulphate resisting cement. Even using this
cement which has the ingredients likely to react with sulphates removed from it, is not
100% reliable. In association with sulphate resisting cements, good compaction and
quality control is necessary. Binary cements – those which contain pfa or ggbs are more
sulphate resistant than conventional Portland cements.
Designing for strength is relatively straight forward but designers need to be aware of the
long term requirements of building and consider durability. To assess the degree of
durability required designers should consider at least the following :-
Intended use of the structure. Designers need to view a nuclear power station
differently from a garden path. Consider a situation where many “heavy metal
rock” fans are dancing on a balcony in a purpose built venue and a car parking
garage. Different needs exist in the different situations and design will be
influenced by these.
Required performance criteria. Using the nuclear power station and the garden
path example again. Clearly very high performance criteria are consistently
needed in the former as a failure will be catastrophic whilst in the garden path
failure will be unlikely to affect anyone‟s life.
Expected environmental conditions. Concrete protection will vary, depending on
the environment. A sea wall exposed to splash will need greater protection than
say the internal beam in a department store.
Composition, properties and performance of materials. Durability is affected by
the aggregate and cement type and in some instances by the water used in the
concrete. These factors need to be considered at the design stage.
Shape of members and structural detailing. Designers have the ability to
influence the architectural details to some extent. Good detailing is essential to
reduce maintenance costs.
Quality of workmanship and level of supervision. This is obvious but sometimes
difficult to implement. The construction phase is very pressured and quality
control is important. A well built structure will always be more durable than a
poorly built one.
Particular protective measures. Designers can reduce degradation of reinforced
concrete by including targeted protective measures. For example, waterproof
membranes can be included to prevent groundwater from saturating concrete.
Good detailing can prevent concrete from being periodically wetted.
Likely maintenance during the intended life. Clients will want the best of both
worlds. Low build and zero maintenance costs. There is always a cost
implication in the long term if construction costs are cut.
Cover to the reinforcement is generally regarded as the most important line of defence
against reinforcement corrosion and is defined as the distance between the outer surface
of the reinforcement and the nearest concrete surface. It is always the least distance.
Cover
Main reinforcing bars
Stirrup Cover
Concrete cover is required for three main reasons. Firstly to ensure the reinforcement is
not affected by deleterious materials from the environment. Second to ensure the encased
reinforcement is fully bonded, and thirdly to provide resistance to fire.
The required cover is determined using Table 4.1 (Exposure classes - durability) and
Table 4.2 (Bond requirements) of part 1 of the code. In addition, Tables A.5 and A.11
from BS 8500-1 : 2006 Section 4 covers the durability requirement and Tables 5.2 – 5.11
from part 2 of EC2 cover the requirements for fire. These tables are given in unit 3.
The following clauses from EC2 give some indication of the durability requirements. In
this area in particular, ensure the NA is also consulted. An amendment to the NA in
December 2009 changed the durability criteria.
Fire design.
The structural design for fire is covered in BS EN 1992 – 1 – 2 and its associated
National Annex. The behavior of the structure exposed to fire is assessed by either :
This course only covers the second point, not fire testing.
Building Regulation requirements regarding internal fire spread fall into three categories
:-
In England and Wales the Building regulations specify the period of fire resistance which
the structure and its elements must provide. This ranges from 30 – 240 minutes,
depending on the use of the structure, to allow occupants to evacuate the building and to
enable fire fighters to deal with the blaze in safety. Standard fire resistances are
expressed by their category identifiers and the number of minutes. For example, - R120,
EI60 (non-loadbearing), REI240, etc.
Concrete covers that satisfy bond and durability requirements may not give adequate
resistance to fire.
The fire resistance of columns and walls will be based on the estimated capacity of the
element when burning and the load it sustains in the fire. As a simplification and to avoid
an extra analysis, design actions for fire design may be related to the ULS values by a
reduction factor, ηfi, as follows
Ed,fi = ηfi Ed
Nd,fi = ηfi Nd
Gk fi Qk ,1
For example fi
G Gk Q ,1 Qk ,1
Further details on the terms used in the above equations are given in Unit 3.
Which material?
Frame cost should not dictate the choice of frame material. Rather it should be just one of
a number of issues that should be considered when making the choice. Only then can one
be confident that the best and optimum structural solution is achieved. The following
checklist should assist designers and cost consultants to achieve the best value solution.
Frame costs
The recent rises in reinforcement and steel prices have increased frame costs but the
difference between the costs of steel and concrete frames still remains insignificant.
The table below gives the comparative costs for the substructure and frame of the same
building constructed in four different ways. Steel appears to have some advantages but
concrete should not be dismissed outright.
Substructure £56 /m2 GIFA £60 /m2 GIFA £72 /m2 GIFA £67 /m2 GIFA
Total Building £1,613 /m2 GIFA £1,643 /m2 GIFA £1,716 /m2 GIFA £1,696 /m2 GIFA
Foundation costs.
Foundations typically represent approximately 3% of whole project initial cost. For the
heavier reinforced concrete solution, the foundations will be more expensive, but this still
only represents a small proportion of total cost and can be offset by using post-tensioned
slabs typically 15% lighter.
Cladding costs.
The thinner the overall structural and services zone, the less the cladding costs. Given
that cladding can represent up to 25% of the construction cost it is worth minimising the
cladding area. The minimum floor-to-floor height is almost always achieved with a
concrete flat slab and separate services zone.
PG Cert/PG Diploma/MSc in Civil, Bridge & Structural Engineering Page ENGM041.1.38
Civil Engineering, Faculty of Engineering & Physical Science, University of Surrey
Partitions
Sealing and fire stopping at partition heads is simplest with flat soffits. Significant
savings of up to 10% of the partitions package can be made compared to the equivalent
dry lining package abutting a profiled soffit with downstands. This can represent up to
4% of the frame cost.
Air tightness
Part L of the Building Regulations now require pre-completion pressure testing. Failing
these tests means a time consuming process of inspecting joints and interfaces and then
resealing them where necessary. Concrete edge details are simpler to seal and have less
risk of failure. Some contractors have switched to concrete frames on this criterion alone.
The soffit of a concrete flat slab provides a zone for services distribution free of any
downstand beams. This reduces coordination effort for the design team and therefore the
risk of errors. It permits flexibility in design and allows co-ordination effort to be focused
elsewhere. Services installation is simplest below a flat soffit. This permits maximum off
site fabrication of services, higher quality of work and quicker installation.
These advantages should be reflected in cost and value calculations. Indeed, M&E
contractors quote an additional cost of horizontal services distribution below a profiled
slab of up to 15%. Flat soffits also allow greater future adaptability. New layouts and
cellular arrangements plus different service requirements are straightforward.
Fire protection
For concrete structures fire protection is generally not needed as the material has inherent
fire resistance of up to 4 hours. This removes the time, cost and separate trade required
for fire protection.
Acoustics
To meet the more stringent Part E of the Building Regulations, additional finishings to
walls and floors are often required. The inherent mass of concrete means these additional
finishings are minimised or even eliminated.
Vibration
The inherent mass of concrete means that concrete floors generally meet vibration criteria
at no extra cost without any extra stiffening. For more stringent criteria, such as for
laboratories or hospital operating theatres, the additional cost to meet vibration criteria is
small compared to other structural materials.
Exposed soffit
A concrete structure has a high thermal mass. By exposing the soffits this can be utilised
through fabric energy storage (FES) to reduce initial plant costs and ongoing operational
costs. Furthermore, the cost of suspended ceilings can be reduced or eliminated.
Programme
Concrete frames have short lead-in times and with modern framework systems floor-to-
floor construction periods are reduced. Most CONSTRUCT members quote
500m2/week/crane on reasonably large and simple flat slab projects and more where
Hybrid Concrete Construction can be used.
For example, where precast columns are used in conjunction with post-tensioning, one-
week cycle times are possible. However, more important is whole project programme.
Concrete provides a safe working platform and semi-internal conditions so that services
installation and follow-on trades can commence early in the programme. And concrete
has the flexibility to accommodate design changes later in the process.
The difference in net lettable area provided by different solutions for a building can be of
significant value. Whilst concrete structures may have larger columns, finishing is not
necessarily required and typically columns below 0.25m2 are not deducted from net
lettable area. Reduction in column size can be achieved by the use of high strength
concrete.
Concrete structures have reduced floor-to-floor heights, hence fewer steps between floors
and less plan area. Alongside these, RC shear walls are narrower than braced steel
frames. Therefore, the stair/stability core area is minimised freeing up more net lettable
area.
Concrete's range of inherent benefits, fabric energy storage, fire resistance and sound
insulation means that concrete buildings tend to have lower operating costs and lower
maintenance requirements. This is an important consideration for owner-occupiers and
PFI consortia.
Hybrid construction
Hybrid concrete construction marries together the advantages of precast and insitu
concrete construction with significant benefits. For example, the adoption of a hybrid
concrete frame instead of a composite steel frame on a shell-and core office project in
central London resulted in construction savings of 29 percent and a 13 percent increase in
net lettable floor area.
The UK has been slow to realise the benefits of hybrid concrete construction (HCC),
despite the widely appreciated construction benefits. Until recently one barrier to its use
was the lack of guidance but this has now been addressed by The Concrete Centre's 'Best
Practice Guidance for Hybrid Concrete Construction'.
Further, reports such as „Accelerating Change‟ from the Strategic Forum for Construction
and „Rethinking Construction‟ by Egan, have focused attention on the need for the UK
construction industry to move on from its inherent conservatism, modernise and increase
efficiency.
In terms of costs, insitu reinforced concrete is commonly viewed as being the most
economic framing option while precast concrete promotes speed and factory quality.
Combining the two as a hybrid frame results in even greater construction speed, quality
and overall economy. Traditional formwork typically accounts for up to 40 percent of an
insitu frame costs. These costs can be significantly reduced by increasing the use of
precast concrete which has no on-site formwork requirement. This also reduces the
duration of operations critical to the overall construction programme. Precasting is not
constrained by site progress or conditions and can continue independently of on-site
operations. Some HCC techniques can remove the need for follow-on trades such as
ceilings and finishes further improving the programme. HCC also encourages speed of
construction by promoting increased buildability.
Concrete produces robust, and adaptable buildings that are inherently fire resistant,
vibration free and quiet. Exposure of the hybrid concrete frame can be used to exploit
concrete's inherent thermal properties to form naturally ventilated, low-energy buildings.
The finish and shape of the exposed units can also assist with even distribution of lighting
levels and the reduction of noise levels. Long spans can be easily achieved using large
units or by pre-stressing or post-tensioning.
Tunnel form construction is used in 40% of all residential construction in Belgium and
Holland. It has been used on the largest demonstration project for the Housing Forum,
the Millennium Plus development in Hackney, London and is currently being used for the
construction of a number of hotels and student residences throughout the UK.
Using concrete results in a robust construction, with excellent sound insulation and
reduced heating costs as major advantages.
Tunnel form is a fast-track method of construction that is well suited to repetitive cellular
projects such as hotels, apartment blocks and student accommodation.
With tunnel form, the structural engineer designs the one-way spanning slabs and wall.
The innovation is with the formwork system. As long as the architect has chosen or is
prepared to work within the constraints of regular wall alignments, tunnel form is an
excellent structural solution.
Learning outcomes.
At the end of this unit you should be conversant with :
The basic constituents of reinforced concrete.
The fundamental aims of design and how various participants react to these.
The behaviour of reinforced concrete beams from initial load to collapse.
The different behaviours of over and under reinforced beams.
Ultimate and Serviceability limit states.
Robustness requirements.
Preventing chloride and carbonation ingress from corroding reinforcement.
The damage sulphate attack can inflict on concrete and how to abrogate this.
Cover requirements for reinforcement in concrete with respect to environmental
factors, fire resistance, bonding reinforcement into concrete and other deviations.
The relative benefits of steel and reinforced concrete frames.
Hybrid and tunnel forms of construction.