CONTENT
DESCRIPTION PAG E S
2.0 STARTING UP 02
9.0 DRAWING 05
1.0 SPECIFICATION – AIR SHOWER TUNNEL SYSTEM
MODEL MASTB-18m
PRIMARY FILTER
MODEL: M-DP
MEDIA: NON-WOVEN SYNTHETIC FIBER WITH METAL WIRE MESH
EFFICIENCY: G4
SIZE: 490MM x 330MM x 22MM
QUANTITY: 36 UNITS
FILTER
ELEMENT
ULPA FILTER
MODEL: M-UII
MEDIA: ULTRAFINE FIBERGLASS
EFFICIENCY: U15, 99.9995% @ MPPS
SIZE: 595MM x 595MM x 70MM (THK)
QUANTITY: 36 UNITS
BRAND: ECOFIT
FAN MODEL: 2GF65 180X52
QUANTITY: 36 UNITS
PLC CONTROL
CONTROL • BRAND: OMRON
• MODEL: CP1E
MOTION SENSOR
SENSOR • BRAND: PIR Motion Sensor
MODEL: YCA 1006A
• BRAND: SKL
EMERGENCY PUSH BUTTON
• MODEL: ZBE-102
1
2.0 STARTING UP
1. Ensure that both doors are closed correctly before “ON” the power supply.
2. Ensure that power supply from the MAIN SWITCH BOARD TO AIR SHOWER is on.
6. The AIR SHOWER TUNNEL SYSTEM should function according to the OPERATING SEQUENCE
(refer to attached sheet).
7. If any problems, please refer to TROUBLE SHOOTING or contact the manufacturer for further
advise.
5. Blowers stop
2
START
*To trigger
MOTION SENSOR 2 TRIGGERED fan blowing
TIMER 1 RESTART Yes
BLOWER 1 to 6 “ON”
*To trigger
MOTION SENSOR 3 TRIGGERED fan blowing
TIMER 2 RESTART Yes
BLOWER 7 to 12 “ON”
*To trigger
MOTION SENSOR 4 TRIGGERED fan blowing
TIMER 3 RESTART Yes
BLOWER 13 to 18 “ON”
TIMER
0-60 sec
BLOWER “OFF”
END
MAINTENANCE SCHEDULE
Filters should be replaced according to the amount of usage of the Air Shower. Pre-filter should be checked on a
more frequent basis. It is recommended to replace every THREE months to ensure optimum air flow, it depends
on room condition. Proper maintenance of the pre-filter will extend the life of the ULPA filter.
To replace the ULPA filter locate at the filter plenum box inside the nozzle panel, remove the nuts holding the
ULPA filter onto the plenum box and the ULPA filter can be removed. Reverse the process when installing a new
ULPA filter.
WARNING: Switch power off at electrical service panel and lockout/tagout electrical panel prior to servicing or
working on unit.
Means of disconnection must be incorporated in the fixed wiring in accordance with the wiring rules.
3
4.0 AIR SHOWER TUNNEL SPARE PART LIST
No Item Description Quantity
"Brand: Ecofit 36
2 Blower Fan
Model: 2GF65 180X52R" (2 each modules)
"Manufacturer: MayAir
Model: M-UII
Efficiency: U15, 99.9995% 36
3 ULPA filter - M-UII
MPPS (2 each modules)
Size: 595mm x 595mm x
70mm "
"Manufacturer: MayAir
Model: M-DP
36
4 Disposable Primary Filter - M-DP Efficiency: G4
(2 each modules)
Size: 490mm x 330mm x
22mm "
"Material: SUS304 252
5 SUS Air jet nozzle
Model: AN-03" (14 each modules)
"Brand: LUMITEC 36 sets
6 LED lighting
Model: LMT-T5L06" (2 sets each modules)
"Brand: SKL
7 Emergency push button 3
Model: ZBE-102 "
"Brand: Salzer "3 (green indicator light)
8 Indicator Light
Model: PL 16-22D" 3 (red indicator light) "
"Brand: Rits-N
9 Hand sensor (Touchless) 1
Model: MG 100"
"Brand: Baros
10 Automatic Single door system 1
Model: AD-500"
"Brand: PIR Motion Sensor
11 Motion sensor 4
Model: YCA 1006A "
"Brand: Rits-N
12 Beam sensor for single sliding door 1
Model: SK-10DA"
4
Check Wiring
No Power Supply Wiring Disconnection
Check Main Supply
5
6.0 AIR SHOWER TUNNEL SYSTEM
MAINTENANCE CHECK LIST
a) Indicating Light
b) Switch
c) Timer
2. CLEANING REMARKS
a) Blower Compartment
c) Casing
- Check all the fan blower, indicator light & accessories are working properly
- Check all the wiring & connections to ensure they are secure & free of damage
- Check all the sequences of door interlocking system are working properly
- Use soft & dry clothes to regular clean air shower casing
DONT’S
- Do not place object which obstruct the auto sliding door from closing
6
8.0 WARRANTY OF
AIR SHOWER TUNNEL SYSTEM
1. Air Shower carries a warranty from 27/4/2024 for a period of 24 months or four thousand
three hundred and eighty (4380) normal operating hours whichever is earlier.
2. In order to validate this warranty, the user must maintain and service the equipment periodically.
5. Any claim during warranty period, parts will be supplied at ex-factory basis.
6. Any labour involved for replacement of parts as well as inspection and rectification of faults not
covered by warranty will be charged according to the degree of complexity and on time and material
basis.
a) Visit and attend to reported faults within 72 hours from the time of the reported fault.
b) Provide a written report to the customer of the faults and the actions to be
taken for rectification work
c) Use our best endevour to procure and replace all faulty parts as soon as possible.
d) Provide the customer with alternative equivalent parts if the faulty parts are no longer available or if
the same replacement parts will incur a long delivery lead time
In the event of breakdown, MayAir will endevour to provide substitute equipment to enable the factory to
function. This is provided always that the exact part is not available.
7
9.0 DRAWING
2000 2000
370
SAFETY MOTION SENSOR 1
SUS 304 JET AIR NOZZLE
530
EMERGENCY STOP
EMERGENCY STOP
INDICATOR LIGHT INDICATOR LIGHT
TOUCH SENSOR
2800
2800
SUS 304 JET AIR NOZZLE
2385
2400
SINGLE GLAZED
ULPA FILTER
SUS DOOR HANDLE
SLIDE OPEN
BLOWER FAN
PERFORATED COVER
C/W PRIMARY FILTER
30
ENTRANCE
EXIT
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
370
LED LIGHT
SWITCH PANEL
EMERGENCY BUTTON
2800
2400
PERFORATED COVER
C/W PRIMARY FILTER
30
18000
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
350
1300
EXIT
SLIDE OPEN
ENTRANCE
350
PLAN VIEW
REMARK : DIMENSION MAY VARIOUS DUE TO FINAL DESIGN AND SITE CONDITION
Appendix
1. Technical drawing
2. Single line diagram drawing
3. Spare part list
4. Catalogue MDP & MUII
8
GLOBAL CLEANTECH SOLUTIONS PROVIDER
www.mayairgroup.com l www.mayair.com.my