Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

SGPVV2001

Outdoor unit specifications


MODEL RXMQ4AAVEG RXMQ5AAVEG RXMQ6AAVEG
Power supply 1-phase, 220-240/220 V, 50/60 Hz
Number of connectable indoor units 6 8 9
Btu/h 38,200 47,800 54,600
Cooling capacity
kW 11.2 14.0 16.0
Power consumption (Outdoor unit)*1
Capacity control
Casing colour
Type
kW
%
2.69
23-100
3.44

Ivory white
Hermetically sealed scroll type
14-100
3.59

S SERIES
Compressor
Motor output × Number of units kW 2.0 × 1 3.0 × 1 3.3 × 1
Airflow rate m³/min 74 133
Dimensions (H × W × D) mm 990 × 940 × 320 1,345 × 900 × 320
Machine weight kg 71 80 102
Sound level dB(A) 52 53 55
Operation range °CDB -5 to 46
Type R-410A
Refrigerant
Charge kg 2.9 3.4 3.6
Piping Liquid mm φ9.5 (Flare)
connections Gas mm φ15.9 (Flare) φ19.1 (Flare)
Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27˚CDB, 19˚CWB, Outdoor temp.: 35˚CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode.
When there is concern for noise the surrounding area such as residences, we recommend investigating the installation locationand taking soundproofing measures.
• Refrigerant charge is required.
*1 : Connection condition of indoor units
RXMQ4AAVEG : FXAQ20ARVEG × 4 + FXAQ25ARVEG × 1, RXMQ5AAVEG : FXAQ20ARVEG × 4 + FXAQ25ARVEG × 2, RXMQ6AAVEG : FXAQ20ARVEG × 5 + FXAQ25ARVEG × 2

Option list
Type
NO. RXMQ4AAVEG RXMQ5AAVEG RXMQ6AAVEG
Item
1 Header pack BHF6RHP6Z, BHF6ARHP6Z, BHF8RHP6Z
KHRP26M22H, KHRP26M33H
2 REFNET header (Max. 4 branch), (Max. 8 branch)
3 REFNET joint KHRP26A22T
4 Central drain plug KKPJ5G280 KKPJ5F180
5 Fixture for preventing overturning KKTP5B112 KPT-60B160
6 Wire fixture for preventing overturning – K-KYZP15C

Type
NO. FXAQ20ARVEG FXAQ25ARVEG FXAQ32ARVEG FXAQ40ARVEG FXAQ50ARVEG FXAQ63ARVEG
Item
BRC4M150W16
1 Wireless remote controller
BRC7N618-6
2 Navigation remote controller (Wired remote controller) BRC1E63
3 Stylish remote controller BRC1H61W (White) / BRC1H61K (Black)
4 Simplified remote controller BRC2E61
5 Wiring adaptor for electrical appendices (1) + KRP2A61 (Note 4)
6 Wiring adaptor for electrical appendices (2) + KRP4AA52 (Note 4)
7 Remote sensor (for indoor temperature) BRCS01A-1
8 Installation box for adaptor printed circuit board , KRP4B93 (Note 2, 3)
9 External control adaptor for outdoor unit + DTA104A61
Notes:
1. Installation box , is necessary for each adaptor marked +.
2. Up to 2 adaptors can be fixed for each installation box.
3. Only one installation box can be installed for each indoor unit.
4. Either Wiring adaptor for electrical appendices (1) or Wiring adaptor for electrical appendices (2) cannot be connected with Wireless remotecontroller.

VRV is a trademark of Daikin Industries, Ltd.


VRV Air Conditioning System is the world’s first individual air conditioning system with variable refrigerant flow control and was commercialised by Daikin in 1982.
VRV is the trademark of Daikin Industries, Ltd., which is derived from the technology we call “variable refrigerant volume.”

Daikin Airconditioning (Singapore) Pte. Ltd.


10 Ang Mo Kio Industrial Park 2 Singapore 569501
Phone: +65 6583 8888
Email: sales@daikin.com.sg

Specifications, designs and other content appearing in this brochure are current as of June 2020 but subject to change without notice.
Cooling Only 50 Hz
S SERIES Makes the long piping design possible
Piping length restriction Actual piping length
Max. 120 m
RXMQ-AAVEG
Total piping length

Cooling Only Max. 300 m


4 HP – 6 HP
(11.2 kW) (16.0 kW)

3 ticks 4, 5 HP 6 HP New MELS3 ticks product lineup 4, 5, 6 HP

Higher energy efficiency


as compared to VRV IV S series, especially for 6 HP.
16%
4 HP 5 HP 6 HP

EER increases Max. allowable piping


Actual piping length (Equivalent) a+b+c+d+i 70 m (90m) 70 m (90m) 120 m (150m)

7%
Total piping length a+b+c+d+e+f+g+h+i 250 m 250 m 300 m
length
4.6
increases 14% 4.46
Between the first indoor branch and the farthest indoor unit b+c+d+i 40 m 40 m 40 m

increases Between the indoor units j 10 m 15 m 15 m


Max. allowable level
4.2 4.16 difference Between the outdoor units If the outdoor unit is above k 30 m 30 m 50 m
4.07 and the indoor units If the outdoor unit is below k 30 m 30 m 40 m
Cooling Operation EER

3.8 Indoor units lineup New lineup

20 25 32 40 50 63 80 100 125 140


Type Model Name Capacity Range 0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3.2 HP 4 HP 5 HP 6 HP
3.4 Capacity Index 20 25 31.25 40 50 62.5 80 100 125 140

Ceiling Mounted Cassette


FXFSQ-AVM
(Round Flow with Sensing)
3
Ceiling Mounted Cassette
(Round Flow) FXFQ-AVM

0 FXDQ-PDVE
4 HP 5 HP 6 HP (with drain pump)

S SERIES S SERIES Slim Ceiling Mounted Duct


FXDQ-PDVET
(without drain pump)
(700mm width type)

(Standard Series) FXDQ-NDVE

Connectable up to 9 indoor units (with drain pump)

FXDQ-NDVET
(without drain pump)
(900/1,100mm width type)

As many as 9 indoor units can be connected to a single outdoor unit, making the VRV S series Slim Ceiling Mounted Duct FXDQ-SPV1
a remarkably versatile system. (Compact Series)

Note: Total capacity index of connectable indoor units must be 50-130% of the capacity index of the outdoor unit. Middle Static Pressure
FXSQ-PAVE
Ceiling Mounted Duct

Ceiling Mounted Duct FXMQ-PAVE

Outdoor-Air Processing Unit FXMQ-MFV1


Max.
indoor
9 units
Wall Mounted FXAQ-ARVEG

Indoor unit specifications New

VRV indoor units MODEL FXAQ20ARVEG FXAQ25ARVEG FXAQ32ARVEG FXAQ40ARVEG FXAQ50ARVEG FXAQ63ARVEG
Conditions of VRV indoor unit maximum connection capacity Power supply 1-phase, 220-240/220 V, 50/60 Hz
Cooling Capacity kW 2.2 2.8 3.6 4.5 5.6 7.1
Power consumption kW 0.042 0.046 0.047 0.048 0.051 0.056
Applicable Including FXFSQ25AVM or
Airflow rate (H/L) m³/min 7.5/4.5 9/5 11/5.5 13/9 15/12 19/14
VRV indoor units FXFSQ40AVM at least one unit
FXF(S)Q, FXDQ, FXSQ, FXMQ, FXAQ models Sound level (H/L) dB(A) 35/31 36/31 38/31 39/34 42/37 47/41
Dimensions (H × W × D) mm 298 × 929 × 258
S SERIES 130% 100% Machine weight kg 13

You might also like