Target group:
This document contains information for assembly, commissioning and maintenance staff.
2
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Table of contents
3
TR-M30X – TR-M1000X
Table of contents TR-MR30X – TR-MR1000X
4
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Safety instructions
1. Safety instructions
1.1. Prerequisites for the safe handling of the product
Standards/directives The end user or the contractor must ensure that all legal requirements, directives,
guidelines, national regulations and recommendations with respect to assembly,
electrical connection, commissioning and operation are met at the place of installation.
Depending on the actuator version, this includes:
● Standards and directives such as IEC 60079 “Explosive atmospheres":
- Part 14: Electrical installations design, selection and erection.
- Part 17: Electrical installations inspection and maintenance.
● Configuration guidelines for the respective fieldbus or network applications.
Safety instructions/
All personnel working with this device must be familiar with the safety and warning
warnings
instructions in this manual and observe the instructions given. Safety instructions
and warning signs on the device must be observed to avoid personal injury or property
damage.
Qualification of staff Assembly, electrical connection, commissioning, operation, and maintenance must
be carried out by suitably qualified personnel authorised by the end user or contractor
of the plant only.
Prior to working on this product, the staff must have thoroughly read and understood
these instructions and, furthermore, know and observe officially recognised rules
regarding occupational health and safety.
Work performed in potentially explosive atmospheres is subject to special regulations
which have to be observed. The end user or contractor of the plant is responsible
for respect and control of these regulations, standards, and laws.
Electrostatic charging Highly efficient charge generating processes (processes more efficient than manual
friction) on the device surface must be excluded at any time, since they will lead to
propagating brush discharges and therefore to ignition of a potentially explosive
atmosphere.
This also applies to fireproof coatings or covers available as an option.
Ignition dangers Gearboxes were subjected to an ignition hazard assessment in compliance with the
currently applicable standard according to ISO 80079-36/ -37. Hot surfaces,
mechanically generated sparks as well as static electricity and stray electric currents
were identified and assessed as major potential ignition sources. Protective measures
to prevent the likelihood that ignition sources arise were applied to the gearboxes.
This includes in particular lubrication of the gearbox, the IP protection codes and the
warnings and notes contained in these operation instructions.
Commissioning Prior to commissioning, imperatively check that all settings meet the requirements
of the application. Incorrect settings might present a danger to the application, e.g.
cause damage to the valve or the installation. The manufacturer will not be held
liable for any consequential damage. Such risk lies entirely with the user.
5
TR-M30X – TR-M1000X
Safety instructions TR-MR30X – TR-MR1000X
Protective measures The end user or the contractor are responsible for implementing required protective
measures on site, such as enclosures, barriers, or personal protective equipment
for the staff.
Maintenance To ensure safe device operation, the maintenance instructions included in this manual
must be observed.
Any device modification requires prior written consent of the manufacturer.
1.2. Range of application
AUMA multi-turn actuators TR-M30X – TR-M1000X / TR-MR30X – TR-MR1000X
are designed for the operation of industrial valves, e.g. globe valves, gate valves,
butterfly valves, and ball valves.
The devices described below are approved for use in the potentially explosive
atmospheres of zones 1, 2, 21, and 22.
If temperatures >40 °C are to be expected at the valve flange or the valve stem (e.g.
due to hot media), please consult AUMA.
Other applications require explicit (written) confirmation by the manufacturer.
The particular conditions of use are listed on the certificates supplied. Among others,
this includes the following conditions:
● Refer to page 5, Electrostatic charging for further references to minimise the
risk of electrostatic charging within a potentially explosive atmosphere.
● For information regarding the dimensions of the flameproof joints, contact the
manufacturer.
● Special fasteners according to IEC 60079-0 to seal flameproof enclosures must
have the following strength classes:
- Minimum A*-70 for screws for fixing electrical connections
- Minimum A*-80 for all other screws
● For fixing the screws, please also refer to page 78, Tightening torques for
screws.
● After tripping of the thermal motor protection (TMS), an acknowledgement
(RESET) of the thermal fault is required.
6
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Safety instructions
Information The term Information preceding the text indicates important notes and information.
7
TR-M30X – TR-M1000X
Short description TR-MR30X – TR-MR1000X
2. Short description
Multi-turn actuator Definition according to EN ISO 22153/EN ISO 5210:
A multi-turn actuator is an actuator which transmits torque to a valve for at least one
full revolution.
AUMA multi-turn actuat- Figure 1: AUMA multi-turn actuator TR-M120X
or with Combi-Switch
Using the AUMA CDT software for Windows-based computers (notebooks or tablets)
and the AUMA Assistant App, actuator data can be uploaded and read, settings
can be modified and stored. The connection between computer and AUMA actuator
is established wireless via Bluetooth interface. With the AUMA Cloud, we provide
an interactive platform to collect and assess e.g. detailed device data of all actuators
within a plant.
Figure 2: Communication via Bluetooth
8
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Short description
AUMA CDT AUMA CDT is a user-friendly setting and operation program for AUMA actuators.
Connection between computer (notebook, tablet) and actuator is wireless via
Bluetooth interface.
AUMA CDT software can be downloaded free of charge from our website
www.auma.com.
The AUMA Cloud is the driving element of the digital AUMA world, acting as
interactive platform for efficient maintenance of AUMA actuators at moderate cost.
AUMA Cloud The AUMA Cloud collects all device data of all actuators within one site and provides
a clear overview at a glance. Detailed analysis provides valuable information on
potential maintenance requirements. Additional functions foster smooth asset
management.
The AUMA Assistant App enables remote setting and remote diagnostics of AUMA
AUMA Assistant App actuators via Bluetooth using either smartphone or tablet.
The AUMA Assistant App can be downloaded free of charge from the Play Store
(Android) or App Store (iOS).
Figure 3: Link to AUMA Assistant App
9
TR-M30X – TR-M1000X
Name plate TR-MR30X – TR-MR1000X
3. Name plate
Figure 4: Name plate (example)
10
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Name plate
Order number The product can be identified using this number and the technical data as well as
order-related data pertaining to the device can be requested.
Please always state this number for any product inquiries.
On the Internet at http://www.auma.com > Service & Support >myAUMA, we offer
a service allowing authorised users to download order-related documents such as
wiring diagrams and technical data (both in German and English), inspection certificate
and the operation instructions when entering the order number.
Table 3:
Description of serial number as from 2023 (example of 0000-00101-2023)
0000-00101 – 2023
0000-00101 Serial number of sales articles
11-digit, internal number for unambiguous product identification
2023 Year of manufacture = 2023
Control Table 4:
Control examples (indications on actuator controls name plate)
Input signal Description
24/48/60 V DC Control voltage 24/48/60 V DC for OPEN-CLOSE control via digital inputs
(OPEN, STOP, CLOSE)
100 – 125 V DC Control voltage 100 – 125 V DC for OPEN-CLOSE control via digital inputs
(OPEN, STOP, CLOSE)
100 – 120 V AC Control voltage 100 – 120 V AC for OPEN-CLOSE control via digital inputs
(OPEN, STOP, CLOSE)
0/4 – 20 mA Input current for setpoint control via analogue input
Data Matrix code When registered as authorised user, you may use our AUMA Assistant App to scan
the Data Matrix code and directly access the order-related product documents without
having to enter order number or serial number.
11
TR-M30X – TR-M1000X
Name plate TR-MR30X – TR-MR1000X
12
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Transport and storage
Suspended load!
Death or serious injury.
→ Do NOT stand below suspended load.
→ Attach ropes or hooks for the purpose of lifting by hoist only to housing and NOT
to handwheel.
→ Actuators mounted on valves: Attach ropes or hooks for the purpose of lifting
by hoist to valve and NOT to actuator.
→ Actuators mounted to gearboxes: Attach ropes or hooks for the purpose of lifting
by hoist only to the gearbox using eyebolts and NOT to the actuator.
→ Respect total weight of combination (actuator, gearbox, valve)
→ Secure load against falling down, sliding or tilting.
→ Perform lift trial at low height to eliminate any potential danger e.g. by tilting.
13
TR-M30X – TR-M1000X
Transport and storage TR-MR30X – TR-MR1000X
14
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Transport and storage
Weights
The actuator weight is indicated on the name plate. ➭ page 10, Name plate The
indicated weight includes the actuator weight including output drive type B1, without
handwheel. For other output drive types, consider additional weights.
Table 5:
Weights for output drive type
Type designation Flange size [kg]
A 07.2 F07 1.1
F10 1.3
A 10.2 F10 2.8
A 14.2 F14 6.8
A 16.2 F16 11.7
Table 6:
Weights for output drive type
Type designation Flange size [kg]
AF 07.2 F10 5.2
AF 07.6 F10 5.2
AF 10.2 F10 5.5
AF 14.2 F14 13.7
AF 16.2 F16 23
4.2. Storage
Long-term storage For long-term storage (more than 6 months), observe the following points:
1. Prior to storage:
Protect uncoated surfaces, in particular the output drive parts and mounting
surface, with long-term corrosion protection agent.
2. At an interval of approx. 6 months:
Check for corrosion. If first signs of corrosion show, apply new corrosion protec-
tion.
15
TR-M30X – TR-M1000X
Assembly TR-MR30X – TR-MR1000X
5. Assembly
The product described in this document can be operated without restriction in any
mounting position.
The indicator glass (display) of local controls should be protected against strong
blows or impacts.
5.2. Handwheel fitting
Figure 9: Handwheel
[1] Spacer
[2] Input shaft
[3] Handwheel
[4] Retaining ring
16
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Assembly
17
TR-M30X – TR-M1000X
Assembly TR-MR30X – TR-MR1000X
Information For an unbored or pilot bore stem nut, the stem nut must be finish machined prior
to mounting valve stem and prior to performing the following steps: ➭ page 20, Finish
machining of stem nut for output drive type A
2. Apply a small quantity of grease to the valve stem.
3. Place output drive type A [2] on valve stem and turn until it is [4] flush on the
valve flange.
4. Turn output drive type A [2] until alignment of the fixing holes.
5. Fasten screws [5] between valve and output drive type A [2] without completely
tightening them.
Figure 12:
18
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Assembly
6. Fit multi-turn actuator on the valve stem so that the stem nut dogs engage into
the output drive sleeve.
Figure 13:
10. Turn multi-turn actuator with handwheel in direction OPEN until valve flange
[4] and output drive type A [2] are firmly placed together.
Figure 14:
11. Tighten screws [5] between valve and output drive type A crosswise applying
a torque according to table.
19
TR-M30X – TR-M1000X
Assembly TR-MR30X – TR-MR1000X
This working step is only required if stem nut is supplied unbored or with pilot bore.
Information For exact product version, please refer to the order-related technical data sheet or
the AUMA Assistant App.
Figure 15: Output drive type A
20
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Assembly
21
TR-M30X – TR-M1000X
Assembly TR-MR30X – TR-MR1000X
22
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Assembly
How to proceed 1. Screw and tighten stem protection tube [2] on stem protection tube adapter [3]
Information: A sealing ring is not required. An O-ring is provided underneath
the stem protection tube adapter.
2. For stem protection tubes made of two or more segments:
2.1 Seal threads of segments with hemp, Teflon tape, sealing agent or thread
sealing material and fasten tightly.
2.2 Push segments down to the sleeve (connecting piece).
3. Check whether protective cap [1] for stem protection tube is available, in perfect
condition and tightly placed on or screwed to the tube.
Since the connection between stem protection tube and stem protection tube adapter
is not separately sealed, this assembly variant is NOT adapted for complete immersion
under water or other liquids.
23
TR-M30X – TR-M1000X
Electrical connection TR-MR30X – TR-MR1000X
6. Electrical connection
6.1. Basic information
Wiring diagram/terminal The pertaining wiring diagram/terminal plan (in German or English) is attached to
plan the device in a weather-proof bag, together with these operation instructions. It can
also be requested from AUMA (state order number, refer to name plate) or
downloaded directly from the Internet (http://www.auma.com).
Permissible networks The actuators are suitable for use in TN and TT networks with directly grounded star
(supply networks) point for nominal voltages up to maximum 690 V AC and 24 V DC. Use in IT network
is permissible for nominal voltages up to maximum 600 V AC and 24 V DC. For IT
networks, a suitable, approved insulation monitor measuring the pulse code is
required.
Current type, mains Type of current, mains voltage and mains frequency must match the data on the
voltage, mains fre- name plate.
quency Figure 19: Name plate example
The selector switch is not a mains switch. When positioned to OFF, actuator control
is prevented. The actuator power supply remains connected.
External supply of the For external electronics supply, the power supply of integral controls must have an
electronics enhanced isolation against mains voltage in compliance with IEC 61010-1 and the
output power be limited to 150 VA.
24
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Electrical connection
Protection and sizing on For short-circuit protection and for disconnecting the actuator from the mains, fuses
site and disconnect switches have to be provided by the customer.
It is imperative to adapt the switchgear sizing to the max. current (Imax) as well as
select and set the overcurrent protection device in compliance with the indications
in the electrical data sheet.
Table 10:
Maximum permissible protection
Switchgear Rated power max. protection
(switchgear with power class)1)
Reversing contactor A1 up to 1.5 kW 16 A (gL/gG)
Reversing contactor A2 up to 7.5 kW 32 A (gL/gG)
Thyristor B1 up to 1.5 kW 16 A (g/R) I²t<1 500A²s
Thyristor B2 up to 3 kW 32 A (g/R) I²t<1 500A²s
Thyristor B3 up to 5.5 kW 63 A (g/R) I²t<5 000A²s
1) The AUMA power class (A1, B1, ...) is indicated on the name plate.
Consider the motor starting current (IA) (refer to electrical data sheet) when selecting
the circuit breaker. We recommend tripping characteristics D or K for circuit breakers
in accordance with IEC 60947-2. For controls equipped with thyristors, we recommend
safety fuses instead of circuit breakers. However, the use of circuit breakers is
basically permitted.
Circuit breakers suitable for DC must be used for actuators with DC motor. For the
24 V DC version, we recommend circuit breakers with tripping characteristic C, with
a nominal current of 32 A (power class C32).
We recommend refraining from using residual current devices (RCD). However, if
an RCD is used within the mains, the residual current device must be of type B.
When equipped with a heating system and external electronics power supply, the
fuses for the heating system have to be provided by the customer (refer to wiring
diagram F4 ext.).
Table 11:
Fuse for heating system
Designation in wiring diagram = F4 ext.
External power supply 115 V AC 230 V AC
Fuse 2AT 1AT
25
TR-M30X – TR-M1000X
Electrical connection TR-MR30X – TR-MR1000X
Connecting cables, ● We recommend using connecting cables and connecting terminals according
cable glands, reducers, to rated current (IN) (refer to motor or electrical data sheet).
blanking plugs ● For device insulation, appropriate (voltage-proof) cables must be used. Specify
cables for the highest occurring rated voltage.
● Use connecting cables, cable glands, reducers, blanking plugs with a minimum
temperature range of +80 °C.
● To avoid contact corrosion, we recommend the use of sealing agents for cable
glands and blanking plugs made of metal.
● For connecting cables exposed to UV radiation (outdoor installation), use UV
resistant cables.
● For the connection of position transmitters, screened cables must be used.
● For connecting fieldbus cables or network cables, respect the cable recommend-
ations for the respective fieldbus connection or network connection. Further
information is provided in the short instructions for fieldbus connection or network
connection (as far as available).
Cable installation in ac- Signal and fieldbus cables are susceptible to interference. Motor cables are
cordance with EMC interference sources.
● Lay cables being susceptible to interference or sources of interference at the
highest possible distance from each other.
● The interference immunity of signal and fieldbus cables increases if the cables
are laid close to the earth potential.
● If possible, avoid laying long cables and make sure that they are installed in
areas being subject to low interference.
● Avoid parallel paths with little cable distance of cables being either susceptible
to interference or interference sources.
6.2. KT/KM electrical connection
26
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Electrical connection
Both versions (KT and KM) are available with terminal compartment in protection
type Ex e (increased safety) as well as in protection type Ex d (flameproof enclosure)
(refer to Ex marking on name plate).
Plug-in connection is made via the connection frame. For cable connection, simply
remove the cover. The connection frame with the cable entries remains within the
device. The flameproof interior of the connected devices remains sealed.
Technical data Table 12:
KT/KM/KL electrical connection
Power contacts Control contacts
No. of contacts max. 6 + PE conductors1) 50
Designations U1, V1, W1, U2, V2, W2, 1 to 36, 37 to 50
27
TR-M30X – TR-M1000X
Electrical connection TR-MR30X – TR-MR1000X
How to proceed
Electric shock due to presence of hazardous voltage!
Death or serious injury.
→ Disconnect device from the mains before opening.
1) For dismantling length, refer to manufacturer's specifications for wire end sleeve or ring lug
2) Flexible cables for screw-type terminal with wire end sleeves
3) For two wires per terminal, a twin wire end sleeve must be used
4) Flexible cables for spring clamp terminals permissible even without wire end sleeve. Dismantling: 10 mm
28
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Electrical connection
Information For service purposes, each spring clamp terminal is equipped with a test contact
located above the numbering.
Information For flexible cables: for screw-type terminals, use wire end sleeves according to DIN
46228. For spring clamp terminals, connection is possible without wire end sleeves.
29
TR-M30X – TR-M1000X
Electrical connection TR-MR30X – TR-MR1000X
30
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Electrical connection
How to proceed 1. Clean sealing faces of cover [1] and connection frame [6].
2. For design in flameproof enclosure (Ex d): Preserve joint surfaces with an acid-
free corrosion protection agent.
3. Check whether O-ring [3] is in good condition, replace if damaged.
4. Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
5. Fit cover [1] and fasten screws [2] evenly crosswise.
For design in flameproof enclosure (Ex d):
6. Fasten cable glands and blanking plugs applying the specified torque to ensure
the required enclosure protection.
31
TR-M30X – TR-M1000X
Electrical connection TR-MR30X – TR-MR1000X
Table 14:
Terminal cross sections and earth connection tightening torques
Conductor type Terminal cross sections Tightening torques
Solid wire and stranded 2.5 mm² to 6 mm² 3 – 4 Nm
Fine stranded 1.5 mm² to 4 mm² 3 – 4 Nm
For fine stranded (flexible) wires, connection is made via cable lugs/ring terminals. When connecting
two individual wires with a U-bracket, cross sections have to be identical.
32
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Electrical connection
33
TR-M30X – TR-M1000X
Electrical connection TR-MR30X – TR-MR1000X
Risk of explosion!
Risk of death or serious injury!
→ Prior to opening the device (removing the plug) ensure that the device is free
of gas and voltage!
→ Do NOT switch on voltage in potentially explosive atmospheres.
34
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Menu navigation
7. Menu navigation
This section describes the basic information with regard to menu and indication
operation via the display.
7.1. Combi-Switch operation elements
For this, turn selector switch until it latches in one of the positions (LOCAL, OFF or
REMOTE).
[1] Selector switch ESC (Escape) back/abort procedure or (Enter) confirm menu/value.
toggle function Figure 33:
For this, turn selector switch briefly to the left or right and release again. The selector
switch toggles back into its initial position.
The toggle function is available for all three selector switch positions (LOCAL, OFF,
REMOTE) provided the respective symbol ESC/ is displayed in the bottom row.
[2] Shuttle dial The shuttle dial function depends on the selector switch position.
Figure 34:
●
In selector switch position LOCAL: / Execute operation commands
OPEN/CLOSE.
● In selector switch position OFF/REMOTE: Scroll within the menu/between
the display values or change values, e.g. 1, 2, 3, ....
The display bottom line indicates the direction available for scrolling ( ).
35
TR-M30X – TR-M1000X
Menu navigation TR-MR30X – TR-MR1000X
All pages which are shown in the display are marked by an ID. The ID is displayed
in the top right corner of the display.
Figure 35: Marking of a page by an ID in the display
If the display indicates a status indication, i.e. the ID of the displayed page starts
with S..., you may change to the device menu.
Figure 36:
If the ID of the indicated page starts with M, PRM, ..., you have already entered the
device menu.
How to proceed 1.
Set selector switch in position OFF or REMOTE / .
Figure 37:
2. Turn selector switch briefly towards the right in direction of (Enter) and release
again.
Figure 38:
➥ You are in the device menu if the ID of the displayed page starts with M....
Information Settings and parameters up to user level (4) can only be read in selector switch po-
sition REMOTE and not be modified.
After 10 minutes without operating an operation element, the display returns to the
status indications.
7.2.2. Exit device menu / show status indications
You may exit the device menu from all menu levels.
36
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Menu navigation
How to proceed 1.
Set selector switch in position OFF or REMOTE / .
2. Toggle the selector switch several times to the left (ESC) until the display enters
a status indication.
Figure 39:
➥ You are in the status indication if the ID of the displayed page starts with S....
37
TR-M30X – TR-M1000X
Menu navigation TR-MR30X – TR-MR1000X
A specific password is assigned to each user level and allows different actions.
Table 15:
User levels and authorisations
Authorisation/password
User (user level)
Verify settings
Observer (1)
No password required
Change settings
Operator (2)
Factory password: 000000
Reserved for future use
Maintenance (3)
Change device configuration
Specialist (4)
e.g. type of seating, assignment of output contacts
Factory password: 000000
Service staff
Service (5)
Change configuration settings
AUMA administrator
AUMA (6)
How to proceed 1. If the “Change user level” request appears: Select user level with .
Information: The black triangle ▶ shows the saved value. A white triangle ▷
shows the selected value which has not yet been saved.
2. Confirm selected user level with (Enter).
➥ Display indicates: Password 0*****
3. Enter digits 0 through 9 with .
4. Confirm first position of password with (Enter).
5. Repeat steps 3 and 4 for all further digits.
➥ Having confirmed the last digit with (Enter), access to all parameters within
the selected user level is possible, provided the password entry is correct.
Alternative procedure The user levels can also be changed directly and without request via menu M0808:
Display M0009
Navigation M0807
Select level M0808
38
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Menu navigation
39
TR-M30X – TR-M1000X
Menu navigation TR-MR30X – TR-MR1000X
40
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Commissioning
8. Commissioning
To correctly commission the device, your require the necessary basic know-
ledge for menu operation. If you do not have basic knowledge, make sure you
familiarise yourself with the basics prior to commissioning.
41
TR-M30X – TR-M1000X
Commissioning TR-MR30X – TR-MR1000X
Information Use (Enter) to change from user levels 1–3 to a higher user level. For further
information, refer to: ➭ page 38, Change user level
Change settings 3. Select new value via . (At least user level 4 required.)
→ Limit = Limit seating
→ Torque = Torque seating
Information: The black triangle ▶ shows the saved value. A white triangle ▷
shows the selected value which has not yet been saved.
4. Save selected value with (Enter).
➥ The display shortly indicates Value saved!. The type of seating is set for the
end position.
5. Press ESC (Escape) to return for further parameter setting.
42
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Commissioning
Change settings 3. Enter the new value for the tripping torque in direction CLOSE or OPEN with
.
Information: The adjustable torque range is shown in round brackets.
4. Save new value via (Enter).
➥ The display shortly indicates Value saved!. The tripping torque for the operation
direction is set.
5. Press ESC (Escape) to return for further parameter setting.
Information If the set torque is reached prior to reaching the end position, a fault signal is issued:
Torque fault OPEN or Torque fault CLOSE
The fault can be eliminated by an operation command in the opposite direction (for
Torque fault OPEN: operation command in direction CLOSE; for Torque fault CLOSE:
operation command in direction OPEN) or via the selector switch in LOCAL with
ESC (Escape).
Further information to fault signals: ➭ page 64, Table 22
43
TR-M30X – TR-M1000X
Commissioning TR-MR30X – TR-MR1000X
Information If required, change user level. For performing settings, at least user level 4 is re-
quired. For further information, refer to: ➭ page 38, Change user level
44
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Commissioning
Approach end position 5. For large strokes, approach the valve end position in motor operation:
5.1 Set selector switch to LOCAL.
5.2 For operation in direction CLOSE: turn yellow shuttle dial in direction .
5.3 For operation in direction OPEN: turn yellow shuttle dial in direction .
Information: To avoid damage, abort operation in time prior to reaching
the end stop (turn shuttle dial to the opposite direction of operation).
5.4 Set selector switch to position OFF.
6. Engage manual drive and turn handwheel until the valve is closed.
→ When selecting limit seating, turn back the handwheel (by approx. ½ turn
prior to reaching the end position) to allow for potential overrun.
→ For end position CLOSED, continue with step 7 (set end position
CLOSED).
→ For end position OPEN, continue with step 10 (set end position OPEN).
Set end position 7. Use (Enter) to save the current valve position as new “end position CLOSED”.
CLOSED in the current ➥ The display indicates End pos. CLOSED set! and the right LED (standard ver-
position CMD0009
sion) is illuminated. Now, the end position CLOSED of the limit switching is set.
Figure 54:
8. If the setting must be corrected: Reset settings with (Enter). The LED goes
out again.
→ Approach “again” the end position (steps 5 + 6) and reset the end position
CLOSED.
9. If end position CLOSED has been correctly set: Exit the menu with ESC (Es-
cape).
→ Then, proceed with the setting of end position OPEN (step 2).
Set end position OPEN 10. Use (Enter) to save the current valve position as new “end position OPEN”.
in the current position ➥ The display indicates End pos. OPEN set! and left LED (standard version) is
CMD0010
illuminated. Now, the end position OPEN of the limit switching is set.
Figure 55:
11. If the setting must be corrected: Reset settings with (Enter). The LED goes
out again.
→ Approach “again” the end position (steps 5 + 6) and reset the end position
OPEN.
12. If end position OPEN has been correctly set: Exit the menu with ESC (Escape).
→ Then, proceed with the setting of end position CLOSED (step 2).
45
TR-M30X – TR-M1000X
Commissioning TR-MR30X – TR-MR1000X
End position setting via Information: To allow the setting of an end position via stroke, the other end
stroke position must be set via the position.
13. Calculate the setting value for stroke setting: For this, multiply the “value per
turn” by the stroke.
Table 16:
Actuator Value per turn
TR-M30X/TR-M60X 118.108
TR-M120X 120.461
TR-M250X/TR-M500X 120.041
TR-M1000X 120.461
For actuators equipped with battery, commissioning can also be made in battery
operation without any further power supply.
The following commissioning functions are available in battery operation:
1. Type of seating
➭ page 47, Setting the type of seating during battery operation
2. Torque switching
➭ page 47, Setting the torque switching in battery operation
3. Limit switching
➭ page 48, Setting the limit switching in battery operation
8.3.1. Activate battery operation
If no power supply is applied, the battery operation can be activated via the
Combi-Switch or via the handwheel. Battery operation cannot be activated if power
supply is applied.
1. Via the Combi-Switch:
Turn shuttle dial to the right in direction of .
2. Via the handwheel:
Engage manual drive and turn the handwheel until activation of the indication
on the display. Activation requires a rotation of the output drive by > 90°.
Battery operation is activated if the battery symbol is displayed in the status line:
46
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Commissioning
To the left of the battery symbol, a reverse counter indicates for how long the battery
operation will remain active. If no operation elements are operated, the battery
operation will remain active for maximum 60 seconds. With every operation, the
counter starts the count again at 60 seconds.
Figure 58: Battery operation active until counter = 0
Change settings 4. Select a new value using the shuttle dial: Val- Val+
→ Limit = limit seating
→ Torque = torque seating
Information: If you are currently in user level 1–3, you will be prompted to
enter a password for access to a higher user level. For further information, refer
to: ➭ page 38, Change user level
5. Change to the next or previous parameter using the selector switch:
Back Next The set value is automatically saved when operating the shuttle
dial.
8.3.3. Setting the torque switching in battery operation
If the set tripping torque is specified for the indicated operation direction, the actuator
switches off (overload protection of the valve).
Information The torque switches may also trip during manual operation.
47
TR-M30X – TR-M1000X
Commissioning TR-MR30X – TR-MR1000X
Change settings 4. Select a new value using the shuttle dial: Val- Val+
Information: If you are currently in user level 1–3, you will be prompted to
enter a password for access to a higher user level. For further information, refer
to: ➭ page 38, Change user level
5. Change to the next or previous parameter using the selector switch:
Back Next The set value is automatically saved when operating the shuttle
dial.
8.3.4. Setting the limit switching in battery operation
48
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Commissioning
Approach end position 3. Engage manual drive and turn handwheel until the valve is closed or open.
→ When selecting limit seating, turn back the handwheel (by approx. ½
turn prior to reaching the end position) to allow for potential overrun.
→ For end position CLOSED, continue with step 4 (set end position
CLOSED).
→ For end position OPEN, continue with step 6 (set end position OPEN).
Set end position 4. Turn shuttle dial to the right: Set-Close
CLOSED in current posi-
tion ➥ Set-Close is briefly displayed in white writing on a black background.
Figure 62: The end position CLOSED can be set
Information If you are currently in user level 1–3, you will be prompted to enter a password
for access to a higher user level. For further information, refer to: ➭ page 38, Change
user level
5. To set the current valve position as new “end position CLOSED”: Toggle selector
switch to the right (Enter): This is only possible while Set-Close is displayed
on a black background.
➥ OK is briefly indicated on the display.
➥ The symbol CLOSED (0.0 %) is displayed at the bottom right.
Figure 63: End position CLOSED is set
Set end position OPEN 6. Turn shuttle dial to the left: Set-Open
in current position
➥ Set-OPEN is briefly displayed in white writing on a black background.
Figure 64: The end position OPEN can be set
Information If you are currently in user level 1–3, you will be prompted to enter a password
for access to a higher user level. For further information, refer to: ➭ page 38, Change
user level
7. The set the current valve position as new “end position OPEN”: Toggle selector
switch to the right (Enter): This is only possible while Set-Open is displayed
on a black background.
➥ OK is briefly indicated on the display.
➥ The symbol OPEN (100.0 %) is displayed at the bottom right.
Figure 65: End position OPEN is set
49
TR-M30X – TR-M1000X
Commissioning TR-MR30X – TR-MR1000X
Check direction of rota- 1. Move actuator manually to intermediate position or to sufficient distance from
tion end position.
2. Depending on the version: Unscrew threaded plug [1] with seal [2], protective
cap [4] or stem protection tube [6].
3. Switch on actuator in direction CLOSE and observe direction of rotation at hollow
shaft [3] or stem [5]:
➥ The direction of rotation is correct if the actuator moves in direction CLOSE
and the hollow shaft in clockwise direction, or the stem moves downward.
4. Correctly fit/screw on threaded plug [1] with seal [2], protective cap [4] for stem
protection tube [6], fasten thread.
8.4.2. Check limit switching (Combi-Switch version)
50
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Commissioning
51
TR-M30X – TR-M1000X
Operation and control of actuator TR-MR30X – TR-MR1000X
➥ The valve closing and opening directions are marked on the handwheel.
Drive shaft (valve) turns clockwise in direction Drive shaft (valve) turns counterclockwisein
CLOSE. direction OPEN.
Overload protection for To protect the valve, an overload protection is available as option for manual
manual operation operation. If the torque applied at the handwheel exceeds a certain value (refer to
order-related technical data sheet), the shear pins will rupture and thus protect the
valve from damage. The handwheel can no longer transmit the torque (= handwheel
is spinning). Motor operation is still possible. In case of shear pin rupture due to
overload, imperatively replace the safety hub.
52
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Operation and control of actuator
53
TR-M30X – TR-M1000X
Operation and control of actuator TR-MR30X – TR-MR1000X
2. For operation command in direction OPEN: Turn shuttle dial [2] in direction .
3. For operation command in direction CLOSE: Turn shuttle dial [2] in direction
.
4. Stop actuator:
→ For push-to-run operation: Release shuttle dial [2].
→ For self-retaining: Briefly toggle shuttle dial [2] in direction of the current
operation direction.
Information The OPEN and CLOSE operation commands can be given either in push-to-run or
in self-retaining operation mode. In self-retaining mode, the actuator runs to the
defined end position following brief toggle of shuttle dial, unless another command
has been received beforehand. For further information, please refer to the Manual
(Operation and setting).
54
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Indications
10. Indications
10.1. Indications and symbols in the display
Status bar Figure 71: Information in the status bar (top)
LOCAL
OFF
Priority REMOTE
Interlock
Enable Local
Setpoint control
EMERGENCY
Failure behaviour
Service
[2] Status
Information (Warnings / Out of specification)
Fault / Failure
[3] User
User level 1 – 6
The functions of the operation elements for menu operation are shown in the bottom
line of the display in operation modes OFF and REMOTE / . If no operation
55
TR-M30X – TR-M1000X
Indications TR-MR30X – TR-MR1000X
element is operated during 3 seconds, the line disappears. The navigation support
is shown again once an operation element is operated.
10.1.1. Feedback signals from actuator and valve
After approx. 3 seconds without operating the selector switch or the shuttle dial,
the navigation line is masked at the bottom of the display.
The display S0001 shows the following information on the valve:
● The applied torque appears as bar chart (left). Standard unit = Nm, selection
available between ft-lb and % via menu Torque unit M0051.
● Valve position between 0 – 100 % of travel. As bar chart (right) and as number
in the middle below.
Running and position indication via symbol .
● Operation direction indication: The direction of the active or the last operation
command is indicated by an arrow next to the bar chart:
= Operation command OPEN; = Operation command CLOSE
● Pivot points (intermediate positions) by arrows to the right of the valve position
bar chart:
56
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Indications
● The type of seating at the bar chart (right), with the letters L (Limit) = limit
seating and T (Torque) = torque seating. At 0 % for end position CLOSED and
at 100 for end position OPEN.
After approx. 3 seconds without operating the selector switch or the shuttle dial,
the navigation line is masked at the bottom of the display.
The display S0003 shows the following information on operation commands:
● The applied torque M as bar chart (left) and as figure
Standard unit = Nm, selection available between ft-lb and % via menu Torque
unit M0051.
For setpoint control (if positioner is enabled and activated), the setpoint position
E1 is displayed, or-N/A-.
● Operation direction indication: The direction of the active or the last operation
command is indicated by an arrow next to the bar chart:
= Operation command OPEN; = Operation command CLOSE
● Pivot points (intermediate positions) by arrows to the right of the valve position
bar chart:
57
TR-M30X – TR-M1000X
Indications TR-MR30X – TR-MR1000X
● The type of seating at the bar chart (right), with the letters L (Limit) = limit
seating and T (Torque) = torque seating. At 0 % for end position CLOSED and
at 100 for end position OPEN.
After approx. 3 seconds without operating the selector switch or the shuttle dial,
the navigation line is masked at the bottom of the display.
For further information on status indications, refer to page 62, Fault indications and
warning indications.
10.1.3. Status indications according to NAMUR recommendation
After approx. 3 seconds without operating the selector switch or the shuttle dial,
the navigation line is masked at the bottom of the display.
For further information on status indications, refer to page 62, Fault indications and
warning indications.
58
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Indications
59
TR-M30X – TR-M1000X
Signals (output signals) TR-MR30X – TR-MR1000X
The output signals Coding DOUT 1 – Coding DOUT 12 can be set either to high
active or low active.
● High active = output contact closed = signal active
● Low active = output contact open = signal active
Signal active means that the conditions for the signal are fulfilled.
Required user level: Specialist (4) or higher.
Device menu: Device configuration M0053
I/O interface M0139
Digital outputs M0110
Coding DOUT 1 M0102
Default values:
Coding DOUT 1 = Low active
Coding DOUT 2–Coding DOUT 6 = High active
11.2. Status signals via output contacts (digital outputs) in battery operation
If equipped for battery operation, status signals can be sent as binary signals to the
DCS even in case of power failure (mains voltage and auxiliary voltage). The signals
are provided via the battery module by means of separate output contacts.
11.2.1. Configuration of outputs for battery operation
60
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Signals (output signals)
The output signals Coding DOUT 1 – Coding DOUT 6 can be set either to high active
or low active.
● High active = output contact closed = signal active
● Low active = output contact open = signal active
Signal active means that the conditions for the signal are fulfilled.
Required user level: Specialist (4) or higher.
Device menu: Device configuration M0053
Battery module M3670
DOUT Batt.module M3671
Default values:
Coding DOUT 1 = Low active
Coding DOUT 2 – Coding DOUT 6 = High active
11.3. Analogue signals (analogue outputs)
Valve position Signal: E2 = 0/4 – 20 mA (galvanically isolated)
Designation in the wiring diagram: AOUT1 (position)
Torque feedback signal Signal: E6 = 0/4 – 20 mA (galvanically isolated)
(option) Designation in the wiring diagram: AOUT2 (torque)
61
TR-M30X – TR-M1000X
Corrective action TR-MR30X – TR-MR1000X
Table 19:
Faults during operation/commissioning
Faults Description/cause Remedy
In spite of correct setting of mechan- The overrun was not considered when setting the ● Determine overrun: Overrun = travel covered
ical limit switching, actuator operates limit switching. from switching off until complete standstill.
into the valve or actuator end position. The overrun is generated by the inertia of both the ● Set limit switching again considering the over-
actuator and the valve and the delay time of the run. (Turn handwheel back by the amount of
electronics. the overrun)
Handwheel rotates on the shaft Actuator in version with overload protection for Dismount handwheel. Replace overload protection
without transmitting torque. manual operation: Shear pin rupture due to excess- and remount handwheel.
ive torque at handwheel.
Faults interrupt or prevent the electrical actuator operation. In the event of a fault,
the display backlight is red.
Warnings have no influence on the electrical actuator operation. They only serve
for information purposes. The display remains white.
Collective signals include further indications or faults. These can be displayed via
(Enter) Details. The display remains white.
Table 20:
Faults and warnings via status indications in the display
Indication on display Description/cause Remedy
S0001 Instead of the valve position, a status text is dis- For a description of the status texts, refer to Manual
played. (Operation and setting).
S0005 Collective signal 02: For indicated value > 0: Show collective signal us-
Warnings Indicates the number of active warnings. ing (Enter).
For details, refer to page 63, Table 21.
S0006 Collective signal 04: For indicated value > 0: Show collective signal us-
Not ready REMOTE Indicates the number of active signals. ing (Enter).
For details, refer to page 65, Table 23.
Fault Collective signal 03: For indicated value > 0: Show collective signal us-
Indicates the number of active faults. ing (Enter).
The actuator cannot be operated. For details, refer to page 64, Table 22.
Out of specification Collective signal 07: For indicated value > 0: Show collective signal us-
Signal according to NAMUR recommendation NE ing (Enter).
107: For details, refer to page 63, Table 21.
Actuator is operated outside the normal operation
conditions.
Function check Collective signal 08: For indicated value > 0: Show collective signal us-
Signal according to NAMUR recommendation NE ing (Enter).
107: For details, refer to page 65, Table 23.
The actuator is being worked on; output signals are
temporarily invalid.
Maintenance required Collective signal 09: For indicated value > 0: Show collective signal us-
Signal according to NAMUR recommendation NE ing (Enter).
107:
Recommendation to perform maintenance.
Failure Collective signal 10: For indicated value > 0: Show collective signal us-
Signal according to NAMUR recommendation NE ing (Enter).
107: For details, refer to page 64, Table 22.
Actuator function failure, output signals are invalid
62
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Corrective action
Table 21:
Warnings and Out of specification
Indication on display Description/cause Remedy
Config. warning Collective signal 06: Show individual signals using (Enter).
Possible cause:
Configuration setting is incorrect.
The device can still be operated with restrictions.
Internal warning Collective signal 15: Show individual signals using (Enter).
Device warnings
The device can still be operated with restrictions.
24 V DC external The external 24 V DC voltage supply of the internal Check 24 V DC voltage supply.
controls has exceeded the power supply limits.
Wrn op.mode run time Warning on time max. running time/h exceeded ● Check modulating behaviour of actuator.
● Check parameter Perm. run timeM0356, re-set
if required.
Wrn op.mode starts Warning on time max. number of motor starts ● Check modulating behaviour of actuator.
(starts) exceeded ● Check parameter Permissible startsM0357, re-
set if required.
Failure behav. active The failure behaviour is active since all required Check signals:
setpoints and actual values are incorrect. ● Setpoint E1
● Actual value E2
● Actual process value E4
● For Profibus DP, Profinet, Modbus or Ethernet:
Check connection to master.
● For Profibus DP or Profinet: Check (clear) status
of master.
Wrn setpoint position Warning: Loss of signal setpoint position Check setpoint signal.
Possible causes:
For an adjusted setpoint range of e.g. 4 – 20 mA,
the input signal is 0 (signal loss)
For a setpoint range of 0 – 20 mA , monitoring is
not possible.
Op. time warning The set time (parameter Perm.op. time, manu- The warning indications are automatically cleared
alM0570) has been exceeded. The preset operating once a new operation command is executed.
time is exceeded for a complete travel from end ● Check valve.
position OPEN to end position CLOSED. ● Check parameter Perm.op. time, manualM0570.
Wrn controls temp. Temperature within actuator controls housing too Measure/reduce ambient temperature.
high.
Time not set Real time clock has not yet been set. Set time.
RTC voltage Voltage of RTC button cell too low. Replace button cell.
PVST fault Partial Valve Stroke Test (PVST) could not be suc- Check actuator (PVST settings).
cessfully completed.
PVST abort Partial Valve Stroke Test (PVST) was aborted or Perform RESET or restart PVST.
could not be started.
Wrn no reaction No actuator reaction to operation commands within ● Check movement at actuator.
the set reaction time. ● Check parameter Reaction timeM0634.
Wrn FOC1) Optical receiving signal (channel 1) incorrect (no or Check/repair FO cables.
insufficient Rx receive level) or RS-485 format error.
Wrn FO cable budget1) Warning: FO cable system reserve reached (critical Check/repair FO cables.
or permissible Rx receive level)
Wrn FOC connection1) Warning FO cable connection is not available. Fit FO cable connection.
Torque wrn OPEN Limit value for torque warning in direction OPEN Check parameter Wrn torque OPENM0768, re-set
exceeded. if required.
63
TR-M30X – TR-M1000X
Corrective action TR-MR30X – TR-MR1000X
Table 22:
Faults and Failure
Indication on display Description/cause Remedy
Configuration error Collective signal 11: Show individual signals using (Enter).
Configuration error has occurred.
Config. error REMOTE Collective signal 22: Show individual signals using (Enter).
Konfigurationsfehler REMOTE vorhanden
Internal error Collective signal 14: AUMA service
Internal error has occurred. Show individual signals using (Enter).
Torque fault CLOSE Torque fault in direction CLOSE Perform one of the following measures:
● Issue operation command in direction OPEN.
● Position selector switch to LOCAL and reset
fault signal by toggling the selector switch in
direction ESC.
● For control via fieldbus: Execute reset command
via fieldbus.
Torque fault OPEN Torque fault in direction OPEN Perform one of the following measures:
● Issue operation command in direction CLOSE.
● Position selector switch to LOCAL and reset
fault signal by toggling the selector switch in
direction ESC (Escape).
● For control via fieldbus: Execute reset command
via fieldbus.
Phase fault ● When connecting to a 3-phase AC system and Test/connect phases.
with internal 24 V DC supply of the electronics:
Phase 2 is missing.
● When connecting to a 3-phase AC system and
external 24 V DC supply of the electronics: One
of the phases L1, L2 or L3 is missing.
Incorrect phase seq The phase conductors L1, L2 and L3 are connected Correct the sequence of the phase conductors L1,
in the wrong sequence. L2 and L3 by exchanging two phases.
Only applicable if connected to a 3-ph AC system.
Thermal fault ● Motor overheating: Motor protection (thermal ● When overheating or falling short of temperature
monitoring) has tripped limits: Cooling down
● Temperature limits have been exceeded or If the fault indication display persists after cool-
fallen short of: Temperature monitoring of elec- ing down:
tronics has tripped - Position selector switch to LOCAL and reset
● Exceeding or falling short of temperature limits: fault signal by toggling the selector switch
Voltage monitoring of electronics has tripped in direction ESC (Escape).
- For control via fieldbus: Execute reset
command via fieldbus.
● Check fuses.
● Contact AUMA service
Fault no reaction No actuator reaction to operation commands within Check movement at actuator.
the set reaction time.
Wrn input AIN 1 Loss of signal analogue input 1 Check wiring.
64
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Corrective action
Table 23:
Not ready REMOTE and Function check (collective signal 04)
Indication on display Description/cause Remedy
Wrong oper. cmd Collective signal 13: ● Check operation commands (reset/clear all op-
Possible causes: eration commands and send one operation
● several operation commands (e.g. OPEN and command only).
CLOSE simultaneously) ● Set parameter Positioner to Function active.
● A setpoint is present and the positioner is not ● Check setpoint.
active For indicated value > 0: Toggle selector switch in
direction to display the individual indications.
Sel. sw. not REMOTE Selector switch is not in position REMOTE. Set selector switch to REMOTE.
Disabled The actuator is in operation mode Disabled. Check setting and status of function <Enable local
controls>.
EMCY behav. active Operation mode EMERGENCY is active (EMER- ● Detect cause for EMERGENCY signal.
GENCY signal was sent). ● Verify failure source.
0 V are applied at the EMERGENCY input (only for ● Apply +24 V DC at EMERGENCY input.
low active).
I/O interface The actuator is controlled via the I/O interface (par- Check I/O interface.
allel).
Handwheel active Manual operation is activated. Start motor operation.
FailState fieldbus Fieldbus connection available, however no process Verify master configuration.
data transmission by the master.
Interlock OPEN + CLOSE An interlock is active. Check interlock signal.
Interlock bypass Bypass function is interlocked. Check states of main and bypass valve.
Check states and signals.
PVST active Partial Valve Stroke Test (PVST) is active. Wait until PVST function is complete.
12.3. Fuses
12.3.1. Fuses used
65
TR-M30X – TR-M1000X
Corrective action TR-MR30X – TR-MR1000X
F1 Table 25:
Secondary fuse F1
G fuse according to IEC 60127-2/III F1 AUMA art. no.
Size 5 x 20 mm
Voltage output power supply unit 24 V DC SAFETY 0.8 A T; 250 V K004.328
Power supply for MWG and TMS
F6 Table 27:
Secondary fuse F6
G fuse according to IEC 60127-2/III F6 AUMA art. no.
Size 10.4 x 16 mm
Voltage output power supply unit 24 V 0.75 A T; 60 V K005.430
Short-circuit resistance of customer voltage. Is also used
for AOUT.
Information For active operation commands, the command is directly executed following acknow-
ledgement.
Manual acknowledgement can be made according to the following options:
● By toggling the selector switch in direction ESC (Escape) when selector switch
is set to LOCAL .
●
Actuators with parallel interface: in selector switch position REMOTE /
via a digital input (I/O interface) with the RESET command if a digital input is
configured for the RESET signal.
● Actuators with fieldbus or communication interface: in selector switch po-
sition REMOTE / :
- With the RESET command via fieldbus provided the fieldbus is the active
command source.
- Or via a digital input (I/O interface) with RESET command if a digital input
is configured for RESET signal and the I/O interface is the active command
source.
66
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Corrective action
Test correct function of the motor protection as described hereafter. Perform the
functional test at the latest within the framework of maintenance (refer to chapter
<Servicing and maintenance>).
The test is performed by simulating the motor protection signal via the menu:
Required user level: Specialist (4) or higher.
Diagnostics M0022
TMS proof test M1950
Test procedure: 1. Set selector switch to position OFF.
2. Return to the device menu and select the simulation value in parameter TMS
proof test M1950: Select Thermal test.
3. Activate motor protection simulation: Toggle selector switch in direction
(Enter).
The safety function is correct if no fault signal is displayed.
4. Reset simulation: Toggle selector switch in direction (Enter) (exit the simulation
menu) and turn the selector switch to the initial position.
67
TR-M30X – TR-M1000X
Servicing and maintenance TR-MR30X – TR-MR1000X
AUMA
AUMA offers extensive service such as servicing and maintenance as well as
Service & Support customer product training. For the contact addresses, refer to our website
(www.auma.com).
68
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Servicing and maintenance
13.2. Maintenance
Maintenance intervals In compliance with EN 60079-17, Ex certified products either require repeated testing
at an interval of 3 years or continuous monitoring by trained personnel.
Manual operation During maintenance, the mechanical parts of the handwheel activation, in particular
motor coupling and retaining spring, must be checked. Replace the parts in case of
visible wear.
Notes relating to main- ● Perform visual inspection of actuator and mounted accessories. Ensure that
tenance no outside damage, changes or leakage of grease and oil are visible.
● Check actuator for unusual running or grinding noise or vibration which might
be an indication of bearing or gear damage.
● Electrical connection cables must be placed properly and in perfect condition.
● Thoroughly touch up any possible damage to painting to prevent corrosion.
Original paint in small quantities can be supplied by AUMA.
● Cables and wire entries, blanking plug, cable glands, plugs etc. have to be
checked for correct tightness and sealing. Consider torques according to man-
ufacturer's details. If required, replace the components. Only use components
with appropriate Ex approval.
● Check whether Ex connections are fastened correctly.
● Take care of possible discolouration of the terminals and wires. This would in-
dicate an increased temperature.
● For Ex housings, pay special attention to a possible collection of water. This
may originate from “breathing” due to severe temperature variations (e. g.
change of night and day), from damaged seals etc. Remove any water immedi-
ately.
● The process temperature range must be within the range of the specified ambi-
ent temperature.
● Check the flame path gaps of flameproof enclosures for dirt and corrosion.
● Since the dimensions of all flameproof joints are strictly defined and inspected,
no mechanical work (such as grinding) shall be performed on them. The joint
surfaces have to be cleaned chemically (e. g. with Esso-Varsol).
● Consult manufacturer for indications regarding flameproof joints.
● Repair interventions on flameproof joints is not permitted.
● Prior to fitting, preserve joint surfaces with an acid-free corrosion protection
agent (e. g. Esso Rust-BAN 397).
● Ensure that all housing covers are handled carefully and that the seals are
checked.
● All cable and motor protection components have to be checked.
● If defects impairing the safety are detected during maintenance, repair measures
have to be initiated without delay.
● Any kind of surface coating for the joint surfaces is not permitted.
● When replacing parts, sealing elements, etc. only original spare parts shall be
used.
13.3. Replace batteries
69
TR-M30X – TR-M1000X
Servicing and maintenance TR-MR30X – TR-MR1000X
Table 29:
Variant Block battery1) Battery pack1)
Voltage 9V 9 V (3 x 3 V)
Type Ultralife U9VL-J-P AUMA art.-No.: Z139.857
identification battery type (refer to TPCxxxx4xxxxxxxxx TPCxxxx5xxxxxxxxx
name plate TPC ...) TPCxxxx6xxxxxxxxx TPCxxxx8xxxxxxxxx
1) The block battery may only be replaced by a block battery and the battery pack may only be replaced
by a battery pack. The battery type may only be exchanged after consultation with AUMA Riester
GmbH & Co. KG.
The basic procedure for replacing the battery and the battery pack is the same. For
this reason, the illustrations only show the block battery variant for battery
replacement. A thermoswitch is connected to the block battery, but not to the battery
pack.
1. ⇨ page 70, Remove local controls
2. ⇨ page 71, Replace battery for battery operation
3. ⇨ page 73, Mount local controls
13.3.1. Remove local controls
70
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Servicing and maintenance
How to proceed 1. Disconnect the connectors from all cables leading out of the retaining frame.
Figure 80: Disconnect connectors
2. Remove retaining frame: To do this, press in the retaining lugs (two lugs on the
right and one each on the top left and bottom left).
Information: When removing the retaining frame, make sure that the printed
boards do not slip out.
Figure 81: Remove retaining frame
3. Remove old battery: To do this, press down the retaining lug on the battery
holder and pull out the battery. Then pull off the battery clip.
Figure 82: Remove old battery
71
TR-M30X – TR-M1000X
Servicing and maintenance TR-MR30X – TR-MR1000X
4. Insert new battery: Connect battery clip and insert new battery into battery
holder. For correct positioning, make sure that the retaining lug engages.
Figure 83: Insert new battery
72
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Servicing and maintenance
73
TR-M30X – TR-M1000X
Technical data TR-MR30X – TR-MR1000X
3-phase AC
Voltages/frequencies
Volt 380 380 400 400 415 440 440 460 480 500
Hz 50 60 50 60 50 50 60 60 60 50
Special voltages:
3-phase AC
Voltages/frequencies
Volt 220 220 230 525 575 600 660
Hz 50 60 50 50 60 60 50
74
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Technical data
75
TR-M30X – TR-M1000X
Technical data TR-MR30X – TR-MR1000X
76
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Technical data
Service conditions
Use Indoor and outdoor use permissible
Mounting position Any position
Installation altitude ≤ 2,000 m above sea level
> 2 000 m above sea level on request
Ambient temperature Refer to name plate
Humidity Up to 100 % relative humidity across the entire permissible temperature range
Enclosure protection in accordance IP68 with AUMA 3-phase AC motor
with IEC 60529 Terminal compartment additionally sealed against interior of actuator (double sealed)
According to AUMA definition, enclosure protection IP68 meets the following requirements:
● Depth of water: maximum 8 m head of water
● Continuous immersion in water: maximal 96 hours
● Up to 10 operations during immersion
● Modulating duty is not possible during immersion.
Pollution degree according to Pollution degree 4 (when closed), pollution degree 2 (internal)
IEC 60664-1
Vibration resistance according to 2 g, 5 to 200 Hz
IEC 60068-2-6 Resistant up to maximum 2g to vibration during start-up or for failures of the plant. Resistance against
frequent or continuously occurring vibration cannot be derived from this. Not valid in combination with
gearboxes. Detailed information on request.
Corrosion protection Standard: KS: Suitable for use in areas with high salinity, almost permanent condensation, and high
pollution.
Options: KX: Suitable for use in areas with extremely high salinity, permanent condensation, and
high pollution.
Coating Double layer powder coating
Colour Standard: AUMA silver-grey (similar to RAL 7037)
Options: Available colours on request
Lifetime AUMA multi-turn actuators meet or exceed the lifetime requirements of EN ISO 22153. Detailed inform-
ation can be provided on request.
Sound pressure level < 72 dB (A)
77
TR-M30X – TR-M1000X
Technical data TR-MR30X – TR-MR1000X
Accessories
Wall mount controls Wall mount controls including local controls separately mounted from actuator, connecting cables on
(wall mounted version) request.
Recommended when difficult to access or heavy operational vibration occurring on site.
Cable length between actuator and separately mounted local controls amounts to max. 100 m.
Software tool AUMA CDT (Commissioning and Diagnostic Tool for Windows-based PC/notebook)
(via Bluetooth connection) AUMA Assistant App (Commissioning and Diagnostic Tool for Android and iOS devices)
Further information
EU Directives ATEX Directive 2014/34/EU
Machinery Directive 2006/42/EC
Low Voltage Directive 2014/35/EU
EMC Directive 2014/30/EU
RoHS Directive 2011/65/EU
Reference documents Dimensions Multi-turn actuators TR-M30X – TR-M1000X/TR-MR30X – TR-MR1000X
Electrical data Multi-turn actuators TR-M30X – TR-M1000X/TR-MR30X – TR-MR1000X
Table 30:
Tightening torques for screws
Threads Tightening torque [Nm]
Strength class
A2-70/A4-70 A2-80/A4-80
M6 7.4 10
M8 18 24
M10 36 48
M12 61 82
M16 150 200
M20 294 392
M30 1,015 1,057
M36 1,769 2,121
78
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Spare parts
79
TR-M30X – TR-M1000X
Spare parts TR-MR30X – TR-MR1000X
Please state device type and our order number (see name plate) when ordering spare parts. Only original AUMA spare parts should be used.
Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Representation of spare parts may slightly vary
from actual delivery.
80
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X Index
G
Index GSD file 61
A H
Accessories (electrical con- 33 Handwheel 16
nection) Heating system 25
Accessories for assembly 23 Hollow shaft 50
Actual value 57
Actuator operation from Local 53 I
Actuator operation from Re- 54 Indication lights 59
mote Indications 55, 55
Ambient temperature 10 Input current 11
Analogue signals 61 Input signal 11
Applications 6 Input signals Potential 25
Assembly 16 Inspection certificate 11
Assistant App 11 Insulation class 10
AUMA Assistant App 9, 11 Intermediate position indica- 59
AUMA Cloud 9 tion via LEDs
B L
Battery mode 60 LEDs (indication lights) 59
Blanking plug 26 Limit switching 50
Bluetooth 9 Local controls 53
Local setting 35
C Lubrication 69
Cable glands 26
Cables 26 M
Cable set 33 Mains connection 24
CDT 9 Mains frequency 10, 10, 24
Change passwords 39 Mains voltage 10, 24
Commissioning 5 Maintenance 6, 68, 69
Connecting cable 33 Manual operation 52
Connecting cables 26 Menu navigation 35
Control 11, 52 Motor operation 53
Control inputs Potential 25 Motor protection 10
Control voltage 11 Motor type 10
Corrective action 62
N
Corrosion protection 15
Name plate 10, 24
Current consumption 25
Current type 24 O
Operation 5, 52
D
Operation commands 57
Data Matrix code 11
Order number 10, 11
Digital outputs 60
Out of specification - indica- 58
Direct display via ID 37
tion on display
Direction of rotation 50
Output contact 60
Directives 5
Output contacts 60
Display 55
Output drive type A 17
E Output drive types 17
Earth connection 32 Output drive types B 21
Electrical connection 24 Output signals 60
EMC 26 Output signals Potential 25
Enclosure protection 10, 10 Overload protection 52
F
Fault 62
Flange size 11
Fuses 65
81
TR-M30X – TR-M1000X
Index TR-MR30X – TR-MR1000X
P T
Parking frame 34 Technical data 74
Password 37 Temperature protection 10
Password entry 38 Terminal plan 24
Positioner 57 Test run 50
Power factor 10 Torque - indication on display 56
Power failure 60 Torque range 10
Power supply of electronics 24 Torque switching 43, 47
Production, year 11 Transport 13
Protection on site 25 Type 11
Protective measures 6 Type designation 10
Push-to-run operation 54 Type of current 10
Type of duty 10, 74
Q Type of lubricant 10
Qualification of staff 5 Type of networks 24
R U
Range of application 6 User 37
Rated current 10 User level 37
Rated power 10
reductions 26 V
Remote actuator operation 54 Valve attachment 17
Residual current device 25 Valve position - indication on 56
(RCD) display
Valve stem 23
S
Safety instructions 5 W
Safety instructions/warnings 5 Wall bracket 33
Safety measures 25 Warnings - indication on dis- 58
Safety standards 25 play
Screw plugs 26 Wiring diagram 11, 24
Self-retaining 54
Separately mounted controls 33 Y
Serial number 10, 11 Year of production 11
Service 68
Servicing 68
Setpoint 57
Short-circuit protection 25
Signals 60
Signals (analogue) 61
Size 11
Spare parts 79
Speed 10, 10
Standards 5
Status signals 60, 60
Status signals Potential 25
Stem 50
Stem nut 20
Stem protection tube 23
Storage 15
Supply networks 24
Support 68
Symbols 55
82