CCTV - CVHG780-700RT HFO R514 - Product Report
CCTV - CVHG780-700RT HFO R514 - Product Report
Unit Features
Refrigeration
Chiller Model Total Power Fullload Eff Refrigerant Line Volt Line Frequency
Capacity
CVHG 2462 kW 394.7 kW 0.1603 kW/kW R-514A 380 50. Hz
Unit Overview
Application type Standard cooling
Compressor 780
Motor 435
Impeller 292
Orifice 900
Selection Tolerances
AHRI NPLV.IP 0.4781 kW/ton
Selection Tolerance Standard air run and vibration
Rated NPLV.IP 0.1359 kW/kW
Shell Information
Evaporator Condenser Evaporator Condenser
Fluid Temperature Construction Features
Entering 12.00 C 32.00 C Shell Size 080S 080S
Leaving 7.00 C 37.00 C Bundle Size 880 710
Fluid Properties Tube Type IMCU TECU
Fluid Type water water Tube Thickness 0.025" 0.025"
Fluid Concentration 0.00 % 0.00 % Victaulic connection Victaulic connection
Connection Type
evap. cond.
0.017610 m2-deg 0.044025 m2-deg
Fouling Factor Water box type non-marine non-marine
C/kW C/kW
Flow Rate Water box pressure 150 psig 150 psig
In RH end - out RH In RH end - out RH
Design Flow 117.2 L/s 138.3 L/s Wbox Arrangement
end end
Min Flow 21.90 L/s 43.28 L/s
Two pass evap water Two pass cond water
Number of Passes
Max Flow 160.6 L/s 158.7 L/s box box
Fluid Pressure Drop
PD at Design Flow 68.0 kPa 102 kPa
PD at Min Flow 2.15 kPa 11.2 kPa
PD at Max Flow 128 kPa 132 kPa
Unit Electrical
Wye-delta starter type Unit Mounted WyeD Min Circuit Ampacity 868.00 A
Wye-delta starter conn type Terminal block connection Max Overcurrent Protection 1200.0 A
Wye-delta starter size (max RLA) 707 max RLA Nameplate RLA 685.80 A
Motor 435 Primary RLA 696.40 A
Total Power 394.7 kW Motor Locked Rotor Amps 4225.0 A
Un-Corrected Power Factor 0.91
Physical Information
Operating Weight 11745 kg Shipping Weight - No Refrigerant charge 362.87 kg
10357 kg
Charge
Cond Shell Standard condenser
Construction construction Chiller Heat Rejected
1.975 kW
to ambient