Contract No
Request Submission
Employer Reem Hills Sole-Proprietorship LLC 19-Jun-24
(Date & Time)
PMC Royal Development Company Inspection 20-Jun-24
PMC Royal Architect Project Management (Date & Time ) 04:00PM
Engineer AECOM Middle East LLC Rev No: 1
Main Contractor Trojan General Contracting LLC WIR Submitted By: M/s.TROJAN
MEP Contractor Royal Advance Electro Mechanical Works LLC WIR Submitted To: Consultant-AECOM
D - Rejected
CHECKLIST FOR THE INSTALLATION OF UNDERGROUND UPVC DUCT PIPE & ACCESSORIES
MS-Reference Number- RHP1P2-BW-TGC-ZZ-XX-MS-EL-00001
WIR NO.RHP1P2-BW-TGC-4TV-00-WI-EL-00001 Location: Villa-365, 4BR (Normal) Date:19-06-2024
Checked by Checked by
N/A
N/A
Yes
Yes
No
No
HSE Requirements
QA/QC Requirements
Check the site is well coordinated follow approved MEP
1 Yes
coordination Drawing.
Check the material used is as per specifications/approved material
2 Yes
submittal
5 Check the Duct pipes are supported and fixed properly Yes
6 Check all the damaged Duct pipes and sleeves are replaced Yes
Check Duct pipe ends are closed and all the pipes and sleeves are
8 Yes
properly protected to avoid damages and blockages.
1) Installation is carried out without Electrical drawing approval and material site
inspection approval.
2) uPVC duct pipes end cutting unequally and end caps are not provided.
3) uPVC and PVC conduits shall be installed following invert level and same level shall
be followed up to connection point.
4) Contractor shall verify the check list as per site installation status.
5) Incomplete work of conduits installation shall be completed.
6) Check list date shall be followed as per site work.
Irfan/A.Ayoubi
12-06-2024
13/06/2024
KEYPLAN:
1 2 3 N
WL12
WL12
WL12 WL12
WL12
J.B General Notes:
E 1. ALL DIMENSIONS ARE IN MILLIMETERS AND COORDINATES
ARE IN METERS UNLESS STATED OTHERWISE.
2. DO NOT SCALE FROM THE DRAWING.
FFL +0.15m
SSL +0.070m
WL12 Living +
Dining
REFERENCE DRAWINGS
00 REH-KEO-4TVM-00-DR-ARC-01003
00 REH-KEO-4TVM-ZZ-DR-STR-10001
00 REH-KEO-4TVM-00-DR-EPR-10100
D SSL +0.070 SSL +0.070
WL12 REVISIONS
12
DB-4TVM-01
REPRESENTATIVE
AECOM MIDDLE EAST LIMITED - ABU DHABI
Foyer WC
SMDB WC
ONU
Contractor :
468
600
J.B
WL12
TROJAN GENERAL CONTRACTING LLC
PO Box 111059, Abu Dhabi, UAE
T: +97125097300 | F: +97125097301
WL12
J.B J.B
WL12