2. Scope: Scope shall cover, but not limited to; design, manufacture, testing,
inspection before dispatch and supply of indoor type fully dry type epoxy cast
measuring , protection
3. and differential three core current transformer of ratio 1600/5/5/1 for use in 11
KV 3-phase 4 wire resistance earthed neutral system equipment.
4. Applicable Standards: The CTs shall comply with the latest versions of the
following standards:
IS: 2705 (1992), Part I, Part II, Part III Part IV
IS: 4201-1983.
IS/ICE: 60044-1 (2003)
IEC 61869-1, IEC 61869-2, IEC 61243-5, IEC 60068-2-11
5. Site conditions:
Ambient temperature Min / Max / Design Ref : 09 / 40 / 45 ºC
Altitude above MSL Less than 1000 m
Relative Humidity 100 %
Dusts- Urea, sand;
Atmospheric pollution
Vapour- Ammonia, Chloride in moisture
6. System Details:
Rated Voltage 11 KV +/- 10 %
Rated Frequency 50 Hz, +3%, -5%
No. of phases and wires 3-phase 4 wire
Highest system voltage 12.1 KV
Fault level 500 MVA
Earthing mode Resistance earthed
Short time current rating 26.3 KA for 3 sec
1/7
7. Type, rating and performance requirements: The 11 KV current transformers
shall be INDOOR type, EPOXY cast, suitable for 11 KV system and for use
under climate conditions as indicated above.
vi Accuracy Class 5P 1 PS
vii ALF 20 -- --
x Rct -- -- ≤ 8 Ohm
Rated Insulation
levels [Basic; 1 min As per Table 1A of IS:2705, Part-I
xi
power freq ; 1.2/50 [i.e. 12 / 28 rms / 75 peak KV]
µsec Impulse]
One minute power
freq dry withstand
xii 3 KV rms
test voltage on
secondary terminals
Maximum
xiii temperature rise 45 ºC
above ambient
2/7
The polarity of the C.T. shall be clearly marked.
Identification labels shall be put near both primary and secondary
terminals.
CT Name plate shall be pasted preferably on P2 side as marked on the
drawing. Labels and name plate shall be of non-conducting material
and self-adhesive type.
The ratios of the current transformers shall be as indicated prominently.
The C.T.s shall be capable of withstanding momentary open-circuit on
the secondary side without injurious effects.
8. Tests: All routine and acceptance tests in accordance with IS:2705 shall be
carried out at the manufacturer’s place. RCF reserves the right to witness
these tests. Seven days’ advance intimation shall be given. Type test
certificate shall be submitted from NABL accredited laboratory for acceptance
purpose. It shall not be older than Five years on the bid opening date.
Height of primary terminals from base 140 mm +35% for additional core
10. Inspection: All routine tests shall be carried out at manufacturer’s works in
presence of RCF’s representative. One week’s advance intimation shall be
given for inspection call after readiness of the material.
3/7
11. Guarantee: The supplied material shall be guaranteed for a period of 12
months from date of successful installation and commissioning or 18 months
from the date of supply and acceptance, whichever is earlier.
13. Makes acceptable: L & T / Siemens / Areva T&D / Epoxy House / ABB /
Automatic Electric / Kappa Electrical / Avcon/ Silkans / Pragati.
4/7
CURRENT TRANSFORMERS
Parameter Offered
Make
Maker’s Type
Ref. Standard(s)
Type of Primary Winding
Rated Voltage
Rated Frequency
No. of Cores
Primary current
Secondary current Core-1: ______, Core-2: ______ Core-3: ______
Rated Burden Core-1: ______, Core-2: ______ Core-3: ______
Accuracy Class Core-1: ______, Core-2: ______ Core-3: ______
ALF / ISF Core-1: ______, Core-2: ______ Core-3: ______
STC _________ for ___ sec.
Thermal Limit
Dynamic Limit
Insulation Class /
Material
Basic Insulation Level
1 min power freq dry
withstand test voltage
Maximum temperature
rise above ambient
Mounting details
Overall dimensions
5/7
Annexure-A1
Photo of existing CT
Note: Secondary circuit wiring of existing CTs are done with 4 sq mm stranded Cu wires with round
lugs. Hence Secondary terminals shall be suitable for theses connection.
6/7
Annexure-A2
Drawing of existing CT