Technical Bid

Sr. Material Qty. Unit


No.
1 CURRENT TRANSFORMER THREE CORE EPOXY CAST RESIN AS PER LATEST IS/IEC 15 NO
RATED VOLTAGE:11KV, 50HZ, SHORT TIME CURRENT:26.3KA FOR 3 SEC.
SUITABLE FOR AMMONIA INCOMER AS PER SPECS:662_CT_ OLD AMM SS 11KV
IC
Note:
1. Bidders shall give confirmation to specification with sign and stamp on each page.

Deviation If any (Mentioned anywhere else is not consider):

Company Seal, Sign and Stamped


SPECS:662_CT_ OLD AMM SS 11KV

TECHNICAL SPECIFICATION FOR 11KV CURRENT TRANSFORMER

1. Application: Current Transformers (CT) are required for replacement and


installation of new CTs or replacement of existing CTs due to change in rating
for infrastructure strengthening purpose. It will be mounted in existing 11KV
incomer panel. Hence no deviations in critical mounting dimensions shall be
acceptable.

2. Scope: Scope shall cover, but not limited to; design, manufacture, testing,
inspection before dispatch and supply of indoor type fully dry type epoxy cast
measuring , protection

3. and differential three core current transformer of ratio 1600/5/5/1 for use in 11
KV 3-phase 4 wire resistance earthed neutral system equipment.

4. Applicable Standards: The CTs shall comply with the latest versions of the
following standards:
 IS: 2705 (1992), Part I, Part II, Part III Part IV
 IS: 4201-1983.
 IS/ICE: 60044-1 (2003)
 IEC 61869-1, IEC 61869-2, IEC 61243-5, IEC 60068-2-11

5. Site conditions:
Ambient temperature Min / Max / Design Ref : 09 / 40 / 45 ºC
Altitude above MSL Less than 1000 m
Relative Humidity 100 %
Dusts- Urea, sand;
Atmospheric pollution
Vapour- Ammonia, Chloride in moisture

6. System Details:
Rated Voltage 11 KV +/- 10 %
Rated Frequency 50 Hz, +3%, -5%
No. of phases and wires 3-phase 4 wire
Highest system voltage 12.1 KV
Fault level 500 MVA
Earthing mode Resistance earthed
Short time current rating 26.3 KA for 3 sec

1/7
7. Type, rating and performance requirements: The 11 KV current transformers
shall be INDOOR type, EPOXY cast, suitable for 11 KV system and for use
under climate conditions as indicated above.

 Rating and electrical characteristics shall be as below:

Sr Parameter Core - 1 Core – 2 Core -3

i Purpose Protection Metering Differential

ii Primary current 1600 amps 1600 amps 1600 amps

iii Secondary current 5 amps 5 amps 1 amps


Rated Thermal
iv 120% In 120% In 120% In
Continues Current
v Rated burden 15 VA 15 VA 15 VA

vi Accuracy Class 5P 1 PS

vii ALF 20 -- --

viii ILF -- <5 --

ix Vk Knee vtg -- -- 300

x Rct -- -- ≤ 8 Ohm
Rated Insulation
levels [Basic; 1 min As per Table 1A of IS:2705, Part-I
xi
power freq ; 1.2/50 [i.e. 12 / 28 rms / 75 peak KV]
µsec Impulse]
One minute power
freq dry withstand
xii 3 KV rms
test voltage on
secondary terminals
Maximum
xiii temperature rise 45 ºC
above ambient

 C.T.s shall be class F insulated and vacuum impregnated or resin cast


type.
 The C.T.s shall be rigidly mounted and shall be easily accessible for
maintenance and testing.
 The C.T. cores for metering, protection and differential protection shall
be separate.
 Secondary terminals of the C.T.s shall be provided with overall
transparent protection cover. These terminals shall be provided as
marked on the attached drawing Annexure-A1 or on the P1 side.

2/7
 The polarity of the C.T. shall be clearly marked.
 Identification labels shall be put near both primary and secondary
terminals.
 CT Name plate shall be pasted preferably on P2 side as marked on the
drawing. Labels and name plate shall be of non-conducting material
and self-adhesive type.
 The ratios of the current transformers shall be as indicated prominently.
 The C.T.s shall be capable of withstanding momentary open-circuit on
the secondary side without injurious effects.

8. Tests: All routine and acceptance tests in accordance with IS:2705 shall be
carried out at the manufacturer’s place. RCF reserves the right to witness
these tests. Seven days’ advance intimation shall be given. Type test
certificate shall be submitted from NABL accredited laboratory for acceptance
purpose. It shall not be older than Five years on the bid opening date.

9. Drawings and documents: Bidder shall submit fully dimensioned drawing of


the offered CT with the offer. Any other drawing found necessary by the
bidder shall also be submitted with the offer.
 Critical dimensions as below shall be matching with the existing CTs:
Primary terminals (P1 and P2) Two studs of M16,
connection Spaced 40 mm,
Spacing between P1 and P2 170 mm

Height of primary terminals from base 140 mm +35% for additional core

Overall Width Of CT 175mm +/- 5%


Four holes of size 18 x 12 mm
slotted, at 140 x 140 mm spacing.
Bidder shall provide adapter plate to
Mounting plate holes
match existing mounting
arrangement if mounting is different
than as mentioned above

 For Detailed dimensions refer Annexure A2


 Party may visit site to prepare detailed requirement and drawings, if
required.
 Successful bidder shall submit copies of dimensional drawing and
other documents after receipt of purchase order/LOI for approval.
 THREE sets of drawings and documents like test reports, inspection
certificates etc. along with delivery of material. One set of all these
documents shall be submitted in electronic form.

10. Inspection: All routine tests shall be carried out at manufacturer’s works in
presence of RCF’s representative. One week’s advance intimation shall be
given for inspection call after readiness of the material.

3/7
11. Guarantee: The supplied material shall be guaranteed for a period of 12
months from date of successful installation and commissioning or 18 months
from the date of supply and acceptance, whichever is earlier.

12. Deviations: Deviations, if any, shall be furnished separately in detail.

13. Makes acceptable: L & T / Siemens / Areva T&D / Epoxy House / ABB /
Automatic Electric / Kappa Electrical / Avcon/ Silkans / Pragati.

14. Annexure-A1,A2 may be used as guidelines. Actual data to be verified by


bidder.
== ** == ** ==

4/7
CURRENT TRANSFORMERS

Guaranteed Technical Particulars

Party shall fill up and submit with the technical bid:

Parameter Offered
Make
Maker’s Type
Ref. Standard(s)
Type of Primary Winding
Rated Voltage
Rated Frequency
No. of Cores
Primary current
Secondary current Core-1: ______, Core-2: ______ Core-3: ______
Rated Burden Core-1: ______, Core-2: ______ Core-3: ______
Accuracy Class Core-1: ______, Core-2: ______ Core-3: ______
ALF / ISF Core-1: ______, Core-2: ______ Core-3: ______
STC _________ for ___ sec.
Thermal Limit
Dynamic Limit
Insulation Class /
Material
Basic Insulation Level
1 min power freq dry
withstand test voltage
Maximum temperature
rise above ambient
Mounting details
Overall dimensions

5/7
Annexure-A1

Photo of existing CT

Primary terminals P2 Terminal Location for secondary terminals

Note: Secondary circuit wiring of existing CTs are done with 4 sq mm stranded Cu wires with round
lugs. Hence Secondary terminals shall be suitable for theses connection.

Existing CT mounting arrangement

Primary terminals P2 Terminal

6/7
Annexure-A2

Drawing of existing CT

ALL DIMENSIONS ARE IN MM