Professional Documents
Culture Documents
Lecture 10_Rev 02_May 2019_Generator Prot
Lecture 10_Rev 02_May 2019_Generator Prot
EE 442
Prepared by
Dr. Khaled El Bahrawy
Lecture #10
Generator Protection
Contents
1 Generators in Power Plant
4
2 – Generating Unit SLD
5
3 – Typical protection functions of generators
1. Differential protection.
5. Voltage protection.
6. Frequency protection.
6
4 – Typical protection functions of generating unit
7
5 – a - Generator differential protection
To Gen.
GCB Step Up
Transf.
Differential Relay
8
5 – b - Unit overall differential protection
9
6 – Generator grounding protection
10
Why Generator grounding ?
1. Improved Safety.
11
Generator grounding and restricted earth fault protection
12
7 – Generator Restricted Earth Fault protection
R.E.F.
13
8 – Sizing calculations for Neutral Point Resistor
Earth Fault current is reduced with higher neutral resistance, hence, smaller portion
of winding should be protected by Restricted Earth Fault protection
Where :
Io = Relay setting.
V = Phase voltage.
14
Example 1
5MVA, 11kV generator is protected by Restricted Earth Fault protection relay with
25% out of balance setting. The percentage of protected winding against phase to
ground fault is 80%. Calculate the neutral point resistance.
Solution 1
% of unprotected winding = ( R x Io / V ) x 100
V = 11 x 1000 / √3 = 6340 V
Accordingly
Then,
R = 1.94 Ohm
15
Example 2
11kV, 3 phase alternator has full load rated current of 200A. Resistance of armature
winding is 15%. The differential protection system is set to operate on earth fault
currents of more than 200A. Find the neutral earthing resistance, which gives earth
fault protection to 90% of stator winding
Solution 2
Neglecting the impedance of alternator winding, then
V = 11 x 1000 / √3 = 6350 V
I = 200 A
Then, Io = I = 200 A
Accordingly
Then,
R = 3.18 Ohm 16
Example 3
Solution 3
V = 11 x 1000 / √3 = 6350 V
Accordingly
Then,
% of unprotected winding = 23.62
17
Solution 3 (Cont.)
When the protected portion = 90%, then the unprotected portion = 10%
V = 11 x 1000 / √3 = 6350 V
Accordingly
Then,
R = 2.12 Ohm
18
Example 4
A 5MVA, 6.6kV, star connected alternator has a synchronous reactance of 2 Ohm per
phase and 0.5 Ohm resistance. It is protected by a Mertz-Price balance current
system which operates when out of balance current exceeds 30% of load current.
Determine what portion of alternator winding is unprotected if the star point is
earthed through a resistance of 6.5 Ohms.
Solution 4
Neglecting the impedance of alternator winding, then
% of unprotected winding = ( R x Io / V ) x 100
Accordingly
Then,
% of unprotected winding = 22.4
19
Solution 4 (Cont.)
Alternative solution
Neglecting the reactance of alternator winding, then
The resistance affecting the earth fault = Neutral point resistance + the resistance
of unprotected winding portion
20
Example 5
A 6.6kV, 10MVA star connected alternator has a reactance of 2 Ohms per phase and
a negligible resistance. Mertz-price protection is used for winding protection. The
neutral grounding resistance is 5 Ohm. If only, 10% of the winding is to remain
unprotected, determine the setting of the relay
Solution 5
Io = Unknown
Accordingly
10 = ( 5 x Io / 3810.5 ) x 100
Io = 8.71%
21
Example 6
22
Solution 6
23
End of Lecture #10