Professional Documents
Culture Documents
Lecture 7_Rev 00_Jan 2018_Trafo REF
Lecture 7_Rev 00_Jan 2018_Trafo REF
EE 442
Prepared by
Dr. Khaled El Bahrawy
Lecture #7
Transformer Protection (Cont.)
Contents
1 Restricted Earth Fault Protection REF
2 – Transformer Restricted Earth Fault protection
- Differential protection can not protect complete transformer winding due to its
setting sensitivity.
- The only requirement is that the power transformer winding is connected to earth
in the star point (in case of star-connected windings) or via separate earthing
transformer (in case of delta-connected windings).
- The restricted earth fault function is used as a unit protection function. It protects
the power transformer winding against the faults involving earth.
- Restricted earth fault protection is the fastest and the most sensitive protection a
power transformer winding can have and will detect faults such as:
• earth faults in the transformer winding when the network is earthed through
an impedance
• earth faults in the transformer winding in solidly earthed network when the
point of the fault is close to the winding star point.
• Inter-turn faults
Contents
- When there is an earth fault outside the protective zone, say at F1, it causes the
currents I2 and I1 in CT secondaries as illustrated above. So, the resultant current
in the REF is negligible. Accordingly REF shall not trip the circuit breaker.
- When there is an earth fault inside the protective zone, say at F2, only current I2
shall exist and current I1 shall be negligible. Then the current I2 is only shall flow in
the REF which shall trip the circuit breaker.
Connection of Restricted Earth Fault protection`
- Setting of Restricted Earth Fault relay is made so that the REF is sensitive for
faults near the neutral point of transformer star connected winding (up to 15-20%
of the winding from neutral point).
Classification of Restricted Earth Fault Protection
- Non-linear resisters are connected in parallel with the relay circuit to limit the peak
voltage developed across the high impedance components during internal faults to a
safe level below the insulation level of the current transformers, relay and
interconnecting leads .
If a Metrosil is not used to protect the relay, the approximate voltage developed
by a current transformer under internal fault conditions may be given by Mathews’
formula
- Shunt resistor may be used in order to increase the relay operating current.
Example 1
Standard Metrosil (Metrosil constants are C = 450 and β = 0.25) shall be used with
the relay, the relay operating current including the Metrosil is given in the table below.
Calculate: