SOIL RESISTIVITY TESTING METHOD – THE WENNER 4 PROBE TEST

Soil Resistivity Testing Methods a popular post. Originally published in 2013 and now updated.

A Wenner probe test is a geotechnical investigation method used to determine the electrical resistivity of
the soil.

Soil resistivity testing can be carried out using different methods. The Wenner 4 Probe test is one of the
most common soil resistivity testing methods. Also, its one of the three most popular soil resistivity
methods employed, to perform a soil resistivity test. Therefore, this piece describes how to carry out the
Wenner 4 Probe Test Method

To complete a Wenner probe test, you will need the following equipment:

 Four electrodes (usually copper rods or pipes)


 A resistivity meter or multi-meter
 A hammer or other tool for driving the electrodes into the ground

Process for conducting a Wenner probe test:

 Determine the desired length of the probe. This will depend on the depth of soil you want to test
and the spacing between the electrodes.
 Set up the electrodes. The electrodes should be spaced a set distance apart, typically 20 cm, 50
cm, or 100 cm. The center two electrodes are the current electrodes, and the outer two
electrodes are the potential electrodes.
 Drive the electrodes into the ground, the electrodes should be driven to the desired depth.
 Connect the resistivity meter or multi-meter to the electrodes. The meter should be connected to
the current electrodes and the potential electrodes.
 Take a reading. The resistivity meter will measure the resistance between the current electrodes
and the potential electrodes.
 Repeat the process at multiple locations to get a representative sample of the soil.
 Calculate the average resistivity of the soil using the readings from each location.

Wenner 4 Probe Soil Resistivity Testing Method

Wenner array is probably the most labour-intensive of all the ways when performing the longer traverses.
Hence, this method can call on up to four people to accomplish the task in a sensible time frame.

On the other hand, it is the optimal Soil Resistivity Testing Method (to date) of choice for Earthing
Designs, due to its ratio of received voltage per unit of transmitted current.

Therefore, this means the Wenner Method is considered one of the more ‘reliable’ methods for testing
soils to deeper depths.
Soil Resistivity Testing Methods – The Wenner 4 Probe test.

In the Figure above, the illustration shows how the probe spacings relate to the apparent depth under
test, e.g. a 6m probe spacing. As a result, indicates the soil resistivity at a depth of ~6m.

So, do your soil testing using the Wenner 4-probe method specified in IEEE Standard 81 Part 1, BS EN
50522 or BS 7430.

So, for each measurement traverse. The pin spacings (between adjacent probes) need to begin at 6″ to
12”. And increase after that by a factor of approximately 1.5. Then, up to the maximum pin spacing
chosen for that traverse.

Therefore it is highly desirable to have 2 to 3 traverses centred at different locations. Likewise, whose
maximum probe spacing (between adjacent probes) reaches a distance that exceeds the maximum
extent of the substation. For example, its largest diagonal dimension (and any other facility associated
with the substation), preferably twice this diagonal dimension or more. While avoiding the influence of
buried metallic structures.

Hence, requiring a number of additional shorter traverses (0.15 up to 6m) to obtain data sufficiently
representing soil conditions at shallower depths throughout the site.

So, the Wenner 4 Probe Soil Resistivity Test method consists of four-electrode probes; two are for the
current injection. And two for potential measurement

Wenner 4 Probe Test Arrangement

Figure 1 (above) shows the Wenner 4 Probe Test Arrangement. Soil resistivity calculation
formula Equation 1: shows the soil resistivity formula associated with the Wenner 4 Probe test method.

Where R is the resistance measured by the machine


a is the spacing of the probe

So, an example of a probe to probe spacings for a Wenner 4 probe configuration is as follows:

When designing to IEC BS EN 50522, there are 14 predefined spacings PER traverse.

Probe Spacing
Table NC.2 – Recommended Wenner spacings in metres
1.0
2.0

3.0

4.5

6.0

9.0

13.5

18.0

27.0

36.0

54.0

81.0

100

The above are typical ‘minimum’ spacing-sets. So, the important thing to note, spacings are a ‘series‘ of
measurements taken along a single traverse. Thus, providing the appropriate level of granularity for data
analysis and inversion.

How Deep Does The Wenner 4 Probe Method Test

Readers often ask, “How deep does the Wenner 4 Probe method test?” The way the Wenner method
works is by emitting an electrical signal into the ground via the probes and measuring the returning
signal. The probes only penetrate the ground by a few inches, but the electrical signal itself can
penetrate many meters.

So, just to reiterate… the probes only physically penetrate a few inches. However, the volume of geology
under test is determined by the spacing between each test probe. So, in theory, the testable depth is
only limited by the instrument’s strength of the signal and the deployable distance between probes.

BS EN 50522 describes a typical set of probe distances that work on the most size of earth electrodes.

By the way, why not drop us a line or chat for more info on the peculiarities of BS EN50522 verses IEEE
Std 81.
Given the capital importance of the soil resistivity data for adequate Earthing, Grounding system design
calculations require a well-defined quality control program in the field to demonstrate that readings are
valid.

So, when capturing the data from a Wenner Soil Resistivity Test, this data then needs to be processed
further:

Soil Resistivity Testing Data Inversion

The measured soil resistivity data needs to be inverted to obtain equivalent multi-layer soils to before
using in the subsequent Earthing/Grounding Design.

So, this interpretation requires to account for electrode pin depth. Also, any irregular pin spacings (due to
obstacles in the field). And known buried metallic structures. That mildly to moderately distort the
measured values.

Therefore, chose one or more suitable soil models for the Earthing Study. From those obtained from all
measurement traverses. Also, explain these choices in the final report.

So, currently, the accepted practice for the Data analysis method is to use specialist software tools. Such
as CDEGS RESAP or XGS_SRA (From XGSLab) to deliver a 1-D (one dimensional) optimised model.
But note, 2-D pseudo sections are not readily usable for Earthing Design. However, the pseudo
segments are growing in popularity for geological exploration/investigations. Also, can provide useful
insights (3-D finite volume data) for Earthing System Design.

Therefore, it’s wise to have any approximations to the soil model justified for good measure. Account for
soil structure model variations due to local, and seasonal variations by developing soil model structure
limiting cases.

As a result, it can’t be understated. Just how important reliable, ACCURATE Soil Resistivity data is for
the subsequent Earthing Design. Also, it is the absolute foundational requirement that all following
safety calculations for touch and step voltages are derived.

Alternative Soil Resistivity Testing Methods:

o Schlumberger method

o Driven Rod

You might also like