10196-1-VCM-E00Z-00006
10196-1-VCM-E00Z-00006
10196-1-VCM-E00Z-00006
SUBMITTAL TYPE
Transformer Kiosk
DESCRIPTION OF
SPECIFICATION & SLD (Transformer Kiosk)
SUBMITTAL
SUPPLIER El sewedy For Engineering Inustring (Zaki El Sewedy Group)
VALID CERTIFICATE √
ATTACHMENTS NO. 1
ITEM
Transformer Kiosk
COMMENTS
Revision 01
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Fax:(+202)38164080
C Website: www.elsewedy.net C
F F
J J
Date Signature
[MEDIUM VOLTAGE]
K K
V.02
TECHNICAL OFFICE
Copyright 2019 SEI, All Rights Reserved-Do Not Copy Without Prior Permission.
L
FOR PRODUCTION L
CLIENT NAME :
CAIROMATIC ARGENZA.
ORDER NO. : SIZE
M
TITLE :
COVER SHEET 372_22 A4
M
Rev. Date Drawn Designed & Checked Approved ITEM NO. : ITEM QTY. CODE: SH. NO. :01
A 23/2/2023 Adel Ashour Eng.Ahmed Mounir Eng.Hossam Mohammed 01 (28) SCPS_12KV_AIR_31_T500KVA_OIL PAGES : 15
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A A
C C
Client
D Project D
Quotation Ref.
G G
Code SCPS_12KV_AIR_31_T500KVA_OIL
H KIOSK 500KVA (3+1) AIR 11/0.4 KV H
Panel Configuration
WITH OIL IMMERSED TRANSFORMER
I Item 1 I
QTY 28
J J
K
[MEDIUM VOLTAGE] K
TECHNICAL OFFICE
L L
CLIENT NAME :
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A A
SHEET INDEX.
No. DESIGNATION MODIFICATION
B B
1 COVER SHEET. 1 2 3 4 5 6
2 DOCUMENT INFO.
3 SHEET INDEX.
C C
4 GENERAL CHARACTERISTICS.
5 COMPONENT LIST.
6 COMPONENT LIST.
D D
7 COMPONENT LIST.
9 LV SIDE DESCRIPTION
E E
10 GENERAL DATA OF LBS
12 MV LAYOUT
F F
13 LV LAYOUT
17
18
H H
19
I I
J J
K K
L L
CLIENT NAME :
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A GENERAL CHARACTERISTICS A
MV LBS:
GENERAL DATA OF TRANSFORMER KIOSK Insulation AIR
B B
Type FN7-12D/630A
Standard IEC 62271-202 FN7-12R/12R/630A With HRCF 50A
Rated Voltage 12KV Busbar Rating(MV Side):
C 630A C
Service Voltage 10.5KV Rating
Power Frequency Withstand Voltage 28KV Main Busbar C.S.A 400mm2, Raychem Insulated
Frequency 50HZ Earthing Busbar C.S.A 125mm2 Bare
D D
Access Front Material Copper
Stand Free Busbar Rating(LV Side):
E Degree Of Protection MV Compartment Type IP54 Main Busbar C.S.A 600mm2, Heat Shrinkable Insulated E
TR Compartment Type IP23 Neutral Busbar C.S.A 400mm2, Heat Shrinkable Insulated
LV Compartment Type IP54 Earthing Busbar C.S.A 150mm2 Bare
F Cables Entry: F
Material Copper
Incoming Bottom
Heaters & Hygrostats:
Outgoing Bottom
G Every Heater is Completed With a Hygrostat G
Fire Fighting: Qty 1
L L
CLIENT NAME :
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A COMPONENT LIST A
C
3P- AIR Load Break Switch With Earthing Switch C
JGE
FN7-12D / 12KV / 630A/ 25KA .
E.S
D D
F F
Earth Fault Indicator With C.T
C.T E.F.I Trip Current:(25A +10%) EGETRONIC OR EQ.
G Reset Voltage: 220VAC G
ELECTROTECH
H1 Hygrostat
I I
J J
Anti-Condensation Heater 200WATT, 220VAC
H2 ELECTROTECH
K K
L L
CLIENT NAME :
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A COMPONENT LIST. A
C Digital Ammeter C
A
(0-1000)A - CL0.5 Frame:96*96 Cm.
D D
Digital Voltmeter
V
E (0-500)V - CL 0.5 Frame: 96*96 Cm. E
F F
Circuit Breaker
(With Thermal & Magnetic Protection). CHINT
G G
H H
MCB - 1P CHINT
I I
J J
L L
CLIENT NAME :
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
COMPONENT LIST. A
SV
220-230 VAC
H H
Fire Fighting System (Extinguisher CO2-10KG) Includes Sensitive Tube
FF
Passing Through the Protected Zones.
I I
K K
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
CU 3*(1*40*10)mm2
A A
Q1 Q2 Q3 Q4 TR.PROTECTION
MV COMPARTMENT INCOMING TIE IN TIE IN 3P Fused LBS
3P LBS 3P LBS 3P LBS AIR
AIR AIR AIR FN7-12R
B FN7-12D FN7-12D FN7-12D HRCF 12KV
B
12KV-630A
50A
12KV-630A 12KV-630A E4 12KV-630A WITH SHUNT TRIP
H1
COIL
C.T E.F.I 1 C.T E.F.I 2
C E.S E.S
H2
E.S
C
3*(1*70)mm2 (12/20)KV
CU (1*25*5)mm2
PE PE
CU XLPE
E1
TR. COMPARTMENT
PE
D TR 500 KVA
TH1 D
CU (1*25*5)mm2
V.F1 E2
FROM BUCHHOLZ RELAY 10.5/0.4 KV
FF1 FF2
OIL IMMERSED TH1
%IMPEDENCE:4 V.F1 E3
E CO2-10KG
Y 50HZ,DYN 11
E
PE
T1,T2,T3
(0-1000)A A (1000/5)A
F CL 0.5 CL 0.5
10VA
F
SPACE
MCB MCB MCB MCB MCB
DPM MCB MCB
1P 1P 1P 1P 1P 1P 1P
NB1-C 3 x 1P 2A NB1-C NB1-C NB1-C NB1-C NB1-C NB1-C
CU (1*60*10)mm2
SV
G In=10A
V
F1,F2,F3 In=16A In=10A In=10A In=16A In=16A In=10A G
Icu=6KA Icu=6KA Icu=6KA Icu=6KA Icu=6KA
Q15 Q16 Q17 Icu=6KA Q18 Icu=6KA
TRIP DIN (0-500)V
Q13 DIN Q14 DIN DIN DIN DIN DIN
CL 0.5 R S T
Q20 FLR2
H ACB H
LV COMPARTMENT
E3 E4
3P E1 E2
SO1 HEATER
NA1-2000XN H7 EFI FAN1 FAN2
1P+N
LED
In=1000A 16A
9 WATT
Icu=50KA Q5 CU (1*30*5)mm2
I FIXED MOUNTED PE PE
I
Q19 FLR1
MCB CU (1*40*10)mm2
N N
ALARM
1P CU 3*(1*60*10)mm2
NB1-C L L
CU (1*25*10)mm2
3*(1*20*5)mm2
In=10A
SWITCH FUSE
J Icu=6KA
DIN 3P
MCCB
3P J
CU
VERTICAL NM8-250S
In=100A
In=630A Icu=50KA
FUSES=400A FIXED MOUNTED
K Q12 K
Q6-Q11
P.F Capacitor Bank
Fixed Step.
25KVAR/400V
42.5KVAR/525V
L X6 L
CLIENT NAME :
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A LBS DATA A
STANDARD:
B B
Cable LBS IEC 62271-103
Fused LBS IEC 62271-105
Earthing Switch IEC 62271-102
C HRCF IEC 60282-1 C
Insulation AIR
FN7-12D/630A (Cable LBS)
D Code FN7-12R/630A (Fused LBS) D
Made JGE
Ur Rated Voltage 12KV
E E
28KV (Phase To Phase)
Ud Power Frequency Withstand 28KV (Phase To Earth)
32KV (Through Open Contacts)
F 75KV (Phase To Phase) F
Up Lightning Impulse Withstand Voltage 75KV (Phase To Earth)
85KV (Through Open Contacts)
G Fr Frequency 50HZ G
Ir Rated Current 630A
L L
CLIENT NAME :
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
B B
C C
D D
E E
F F
G G
H H
I I
J J
K K
Dimensions in mm
L L
CLIENT NAME :
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A MV LAYOUT A
NOTE:There is a Mechanical interlock in the Cell door to achieve that the door will be not open
B when the Earthing Switch is off. B
C C
D D
E E
F F
G G
H H
I I
RMU SARING-12KV
J IP protection degree J
41
Switchboard mounting Free Standing
Sheet Steel Thickness 2mm Rolled Cooled Steel
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A A
LV LAYOUT
B B
0:00 0:00 0:00 0:00
V A A A
S ET S ET S ET S ET
FLR1
SV FLR2
C C
D D
E E
F F
G G
H H
I I
J J
L L
Outgoing BOTTOM
Total dimensions (HxWxD) [cm] (190x180x50) [cm]
CLIENT NAME :
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A A
C C
D D
E E
F F
G G
H H
I I
J J
INCOMING CABLES
K K
- Contacts Close When E.F.I Current Reaches 25 +10% A.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A A
L N
B B
220V AC
C C
D D
E E
F F
G G
H1
H H
H2
I I
J J
K K
L L
CLIENT NAME :
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20