Download as pdf or txt
Download as pdf or txt
You are on page 1of 11

CONSULTANT CONTRACTOR OWNER

SUBMITTAL ID PROJECT ID PROJECT NAME DATE

IN/CMT /HK-10031-TRS-CP -2 10001-TF1 AL-Saf -HAYAH KARIMMA 23/10/2022

SUBMITTED TO PGESCO – AL-Saf

SUBMITTAL TYPE
Oil Transformers

DESCRIPTION OF
SPECIFICATION (Oil Transformers)
SUBMITTAL
EGYTRAFO For Industries (S.A.E)
SUPPLIER

VALID CERTIFICATE √

ATTACHMENTS NO. 1
P.M AHMED AWNY-MAHMOUD ZAKRIA

ITEM
Oil Transformers

COMMENTS

Revision 00
8 7 6 5 4 3 2 1

1135
F 665 F
9 8
7 No. Item

2 1 1/250 LV Bushing

2 10/250 HV Bushing
12 3 4
E 3 Normal Thermometer E

4 Normal Oil Indicator

1350
5 Tap Changer

6 Pressure Relief
14
7 Silica Gel (0.5 Kg)
D D
8 Oil Sleeve
10
9 Cover of Oil Sleeve
13
11 10 Valve (1 Inch)
602 602 11 100 mm Wheels
702 12 Lifting Lug
C C
5
6 13 Earthing Terminal
2
14 Name Plate

B 1 B
UNLESS OTHERWISE SPECIFIED: FINISH: DEBURR AND
DO NOT SCALE DRAWING REVISION
DIMENSIONS ARE IN MILLIMETERS BREAK SHARP
SURFACE FINISH: EDGES

T1 100 10 A1
TOLERANCES: Design Code:
LINEAR:
ANGULAR:

NAME SIGNATURE DATE TITLE:


DRAWN A.Hossam 3/18/2018
CHK'D

APPV'D
Ibrahim
Khalifa
100 KVA - 10.5/0.4 KV
A MFG A
Q.A DWG code.

MATERIAL:
A3
SCALE:1:20 T1 100 10 A1 01 SHEET 1 OF 1
WEIGHT:

8 7 6 5 4 3 2 1
Technical Offer
2021

Design Code 100 10.5-0.4LO2021

Technical Specifications:
No. Description Unit
1 Manufacturer EGYTRAFO
2 Standard on which performance data is based IEC60076
3 Type OIL IMMERSED
4 Method of cooling ONAN
5 Frequency HZ 50
6 Material of insulation
a-H.V winding VARNISH
b-L.V winding Paper
c-Major insulation OIL
Cold rolled grain oriented silicon
7 Material of core steel
8 Continuous maximum rating KVA 100
9 No-load voltage ratio KV 10.5 / 0.4
10 Vector connection group Dyn11
11 Rated Current at H.V Amp 5.4
12 Rated Current at L.V Amp 144.3
13 Iron losses at 50 Hz and at 100 % rated voltage Watt 272
14 Copper losses at full load, 95 ºC Watt 1505
15 Total Losses Watt 1777
16 Regulation at full load at 95 °C
a-Unity p.f % 1.5
b-0.8 p.f lagging % 3.57

18 Primary voltage at normal tapping kv 10.5


19 Secondary voltage at:
No load v 400
Full load at 1pf at 95°C v 394.4
Full load at 0.8pf at 95°C v 386
20 Maximum ambient temperature °C 45
21 Maximum top oil temperature rise °C 45
22 Maximum winding temperature rise °C 55
23 Impedance voltage at full load and at 95 °C % 4
24 Resistance of H.V winding per phase at 20 °C Ω 19.8
25 Resistance of L .V winding per phase at 20 °C Ω 0.0068
26 Efficiency
a-At 100% load, 1 p.f % 98.2
b-At 100% load, 0.8 p.f % 97.8

1
EGYTRAFO
Tel.: + 202 417 49 21-2 Fax: + 202 415 11 97
E-mail: technical@egytrafo.com
Website: www.egytrafo.com
Technical Offer
2021

Design Code 100 10.5-0.4LO2021

c-At 75% load, 1 p.f % 98.5


d-At 75% load, 0.8 p.f % 97.8
e-At 50% load, 1 p.f % 98.1
f-At 50% load, 0.8 p.f % 98.7
g-At 25% load, 1 p.f % 98.3
h-At 25% load, 0.8 p.f % 98.1
27 One minute H.V test KV 28/3
28 Induced voltage test KV 2U
29 Tap Changer
a-Type Off load
b-Step of one tap in percent of rated voltage 2.50%
c-No. of positions 7
30 Type of core
31 Thickness of transformer tank
a-Cover mm 5
b-Bottom mm 4
c-Corrugated radiators mm 1.2
32 Weights
a-Weight of core Kg 263
b-Weight of copper Kg 89
c-Weight of insulation oil Kg 260
d-Total weight of transformer Kg 850
33 Dimensions of transformer
a-Approximate overall length (A) mm 1135
b-Approximate overall width (B) mm 665
c-Approximate overall height (C) mm 1350
20 % overload for 1.5 hours
Standard fitting
Oil conservator with Oil indicator at L.T side .
Rating and diagram plate.
Off circuit tap changer.
pressure relief valve.
Four steel rollers.
Dial thermometer.
Earth terminal.
Filling valve.
Drain valve.
Lifting lugs.
silica gel

Prep by: Rev by:

eman gwad Ibrahim Farag


2
EGYTRAFO
Tel.: + 202 417 49 21-2 Fax: + 202 415 11 97 23\8\2021
E-mail: technical@egytrafo.com