Ecology Unit- Catalogue
Ecology Unit- Catalogue
and
ENVICLEANTM & ENVIWASHTM
ESP ELECTROSTATIC FILTERS
In today’s busy world, more people are going out to particulates and smoke efficiently and effectively to
eat. For restaurants this growing trend not only in- ASHRAE Standard 52.2 thereby eliminating fire and
creases traffic and revenue but also the kitchen haz- other hazards. EnviTec’s ESP’s can be installed in-
ards associated with this new volume. doors or on the rooftop.
As kitchen cooking production grows, restaurants will EnviTec’s ESP units can be supplied as stand alone
exhaust more smoke, grease, and odors into the air. systems or with UV and/or odor removal systems,
Local neighbors may raise concerns about air quality, including media or ozone, or as part of an ecology
and restaurants may put their roofs at risk with unit. The ESP units can be either self-cleaning or
grease pooling that attacks roof materials. manual cleaned type depending on the specific pro-
ject requirements and budget.
To help restaurants keep pace, EnviTec offers its EN-
VIPURETM Kitchen Exhaust Air Cleaning Systems. When part of an ecology unit the ESP can be supplied
These systems use proven static filtration and/or elec- along with a safety filter, final filter, UV and/or odor
tronic air cleaning techniques to remove smoke, dust, removal modules and fan section with a housed high
grease, mist, and other particulates from the air. temperature rated DWDI fan or external SWSI fan or
coupled to the ecology unit filter/odor removal sec-
Grilling, frying and charbroiling emissions can be- tion. These ESP Ecology units are factory fully as-
come a problem if these emissions are not properly sembled and shipped in sections for on-site joining.
controlled. Also, visible smoke and odor may alert
authorities to possible compliance problems, result- EnviTec is the only Ecology and ESP unit manufactur-
ing in potential fines. EnviTec’s Ecology Unit and er that fabricates ESP’s specifically for the harsh Mid-
Electrostatic Precipitator (ESP) filtration systems elim- dle East climate. We understand the Middle East’s
inate these problems. requirements based on hands-on experience with nu-
merous Ecology Unit and ESP installations in the re-
EnviTec’s ENVIPURETM APU, EAPU and ESPEU Series gion. EnviTec ENVIPURETM APU’s, EAPU,’s, ESPEU’s
ecology kitchen hood exhaust filtration systems effec- Ecology Units and ENVICLEANTM and ENVIWASHTM
tively remove up to 99%+ of all grease and smoke effi- ESP’s are engineering to withstand very high ambient
ciently and effectively to ASHRAE Standard 52-2-2017 temperatures and are simple to install and maintain.
thereby eliminating fire hazards and odors. EnviTec’s
Ecology units can be installed indoors or outdoors on
the rooftop. PRODUCT SERIES
The EnviTec ECOLOGY APU series utilizes a three
stage filtration system to eliminate grease and oil par- Ecology Units
ticles and smoke from the kitchen hood exhaust air
stream while the EAPU series utilizes a combination Air Purification Unit (APU)
of electrostatic filters and standard filters. Through
the use of a media or liquid odor removal system ob- ESP Air Purification Unit (EAPU)
jectionable odors from commercial kitchen cooking ESP Ecology Unit (ESPEU)
and frying are removed effectively. A fan module used
to exhaust the purified air completes the unit. The ES-
PEU series includes an ESP and an optional safety
ESP Units
filter, UV and/or media system and the fan module.
The units have been designed to operate with all dry, Manual Wash (EC)
wet and UV exhaust hoods in order to provide opti- Self-Cleaning (EWF and EWO)
mum filter life. All models can meet the requirements UV Module (UV)
of NFPA 96 if an optional dedicated fire suppression Safety Filter Module (SF)
system is installed on the units.
Final Filter Module (FF)
EnviTec’s ENVICLEANTM and ENVIWASHTM ESP filtra- Carbon Module (CM)
tion systems effectively remove up to 99%+ of all Ozone Generator (OZ)
1 2 3 4
The EnviTec ENVIPURETM EAPU Ecology unit is available in 4 basic configurations as follows:
1. Manual wash ESP (ENVICLEANTM) section 3. Self-cleaning ESP (ENVIWASHTM) section
with DWDI Fan in Sound Insulated Housing with DWDI Fan in Sound Insulated Housing
2. Manual wash ESP (ENVICLEANTM) section 4. Self-cleaning ESP (ENVICLEANTM) section
with External SWSI Fan with External SWSI Fan
EAPU with Manual Wash ESP SECTION and External UL762 Listed Fan
ESP
EnviTec’s electrostatic precipitators conform to
UL 867 and include two parts: the charging and
collecting sections.
9
EAPU ECOLOGY UNIT
PRINCIPLE OF OPERATION
Odor Neutralization Module
The exhaust air is then drawn from the filter section
through the Odor Reducing Section, which uses ei-
ther EnviTec’s odor neutralization solution or media.
Odor Neutralizer Solution
The atomized particle spray mist permeates the ex-
haust air, attacks and neutralizes airborne odor par-
ticulates and the bacteria that cause odors. The odor
neutralization solution effectively reduces unwanted
organic odors. The solution was exclusively devel-
oped for application to the kitchen exhaust air
stream, and is specifically formulated to break down
organic odors produced from commercial cooking.
10
EAPU ECOLOGY UNIT
PRINCIPLE OF OPERATION
Optional External Fan Section Fan
The exhaust air then travels through the Exhaust
Fan. The exhaust fan can be high temperature rated
or UL 762 listed single width, single inlet Class 1 or 2
type with backward inclined type blades. It features
non-overloading horsepower characteristics, smooth
airflow design and includes the following:
• Base frame mounted on spring isolators.
• TEFC High Efficiency (IE2) Motor, Class F insulation with
a service factor of 1.1.
• Optional combination motor starter and fused disconnect
switch can be supplied loose for on-site installation.
• Inlet cones are designed for smooth acceleration of air-
flow into the wheel with clearances designed to maintain
efficiency and reduce noise.
• Complete assembly is statically and dynamically bal-
anced on precision electronic balancing machines.
The Exhaust Fan Section must be located immediate-
ly following the Filter and Odor Neutralization Sec-
tions.
FEATURES
Construction
EnviTec manufactures EAPU ECOLOGY
units to the highest quality standards. Filter
section casing panels are solid double wall
construction with 1” (or 2” for large models)
fireproof polyisocyanurate foam insulation.
As such, these units offer a number of ad-
vantages for Middle East clients, including
the following:
• Extruded aluminum framework
• Double wall construction
• Temperature resistant panels
• Nylon reinforced FRP corner brackets,
handles and latches
• Solid GI base frame
• Special mating brackets make installation
easy and simple
11
EAPU ECOLOGY UNIT
FEATURES
Optional Control Panel
The EnviTec EAPU ECOLOGY unit Optional Control
Panel features a standard 120 or 220-volt control
system and is constructed of heavy gauge stainless
steel. The panel contains an HOA switch, and sys-
tem status display, alarm buzzer, silencing button,
control relays and a terminal strip for field wiring.
The control panel can be surface mounted or re-
cessed in the wall.
Safety
The EnviTec ECOLOGY EAPU unit includes
a number of standard and optional safety
features. Features include an optional fire
detector (stat) at the inlet set at 165oF
(74oC), standard fireproof polyisocyanurate
foam insulation and an optional curtain fire
damper at the outlet of the filter module ac-
tivated by a fusible link.
12
EAPU ECOLOGY UNIT
FEATURES
EAPU OPTIONS
• Double pass ESP section
• UV Section
• 1 Stage of Filtration
• 50-50 blend of activated carbon and potassium permanganate impregnated
activated alumina or 100% pure impregnated activated alumina media
• Fire Detector (Fire Stat) at Inlet
• Curtain Fire Damper
• DP Monitoring Cabinet Mounted on Unit
• DP Transmitter
• High temperature rated (400oC for 2 hours) DWDI fan
• High temperature rated (400oC for 2 hours) SWSI fan
• UL762 SWSI listed fan
• IE3 and/or Class H Motor
• Motor Starter or VFD in cabinet mounted on unit or supplied loose
• Fan trip status
• 3rd stage box filters
• Remote Control Panel
• Washable metallic filters
• Final HEPA (99.97% DOP efficiency) filters
• ANSUL Fire suppression system
• PLC or sequence wash control panel (Self-cleaning ESP section only)
• Detergent tank (Self-cleaning ESP section only)
• Detergent (self-cleaning ESP section only)
13
EAPU ECOLOGY UNIT MODEL NOMENCLATURE
Configuration EAPU(EC)-04-OT/OS-X-X Options
EAPU(EC)-Manual wash ESP UV: UV section
EAPU(EC/L)-Manual wash ESP supplied loose FS: Fire stat
EAPU(EC/DP)-Manual wash double pass ESP 1S: 1 stage of filtration (Pre-filter or Bag
EAPU(EC/DP/L)-Manual wash double pass ESP Filter
supplid loose 3S: 3 stages of filtration
EAPU(EC/H)-Manual wash ESP in panel housing FD: Fire damper
EAPU(EC/DP/H)-Manual wash double pass ESP in FSS: Fire suppression system
panel housing EF: External SWSI fan
EAPU(EWF or EWO)-Auto Wash ESP with Fixed (EWF) or EF(762): External UL 762 listed fan
Oscillating (EWO) wash manifold F: DWDI High Temperature Rated Fan
EAPU(EWF/L or EWO/L)-Auto Wash ESP supplid loose VFD: Mounted (M) or Supplied loose (L)
EAPU(EWF/DP or EWO/DP)-Auto Wash double pass ESP TB: Transition and base
EAPU(EWF/DP/L or EWO/DP/L)-Auto Wash double pass (EF and F fans only)
ESP supplied loose MS: Motor starter
RP Remote control panel
Unit Size (x 1000 CFM nominal capacity) DP: DP cabinet mounted on unit
WP: PLC or sequence controller wash
01, 02, 03, 04, 06, 08, 10, 12, 16, 18, 20, 24, 28, 32 or 36 panel (EW models only)
(EW is only available up to 24) DT: Detergent tank with venturi injector or
with pump (P) (EW models only)
Odor Removal System C: Custom option(s) not listed above
OT: Media Odor Removal with Carbon
OT(50/50): Media Odor Removal with a 50-50 Blend of
Carbon and Impregnated Alumina
OT(100): Media Odor Removal with Impregnated Alumina
14
ESP UNIT
PRINCIPLE OF OPERATION
EnviTec’s ENVICLEANTM and ENVIWASHTM
dual-stage electrostatic precipitators (ESP’s)
conform to UL 867 and include two parts: the
charging and the collecting sections. In the
charging section, the incoming smoke, dust,
grease, mist, and other particulates pass by
ionizer wires which impart a positive electri-
cal charge to these contaminants. The posi-
tively charged contaminants are then drawn
through the collection section which contains
a secondary electrical field with negatively
charged plates. Since opposite charges at-
tract, the positively charged contaminants
collect on the negatively charged aluminum
plates, removing them from the airstream.
18
ESP UNIT
PRINCIPLE OF OPERATION
ENVIWASHTM
The ENVIWASHTM ESP features a fixed wash system that sprays the collector cells from the top
with fixed spray nozzles (EWF Series) or a dynamic wash system that uses oscillating multi jet
wash manifolds in both the front and rear of the electronic collector cells to insure complete cov-
erage and maximum wash results (EWO Series). The wash sequence can be operated through
the BMS or through an optional PLC or sequence controller control panel, which is factory pro-
grammed to control wash and rinse cycles. Units are available in single pass and double pass
configurations and can be washed with hot water or with hot water and detergent, which is much
more effective in removing oil and grease. Complete packages for the EW electronic air cleaners
are available that include detergent tanks and detergent (the required hot water for washing and
rinsing must be 60oC to 70oC at a minimum pressure of 40 psig/276 kpa). The ENVIWASHTM Series
offers impressive restaurant kitchen exhaust performance with a comparably lower price than
self-cleaning electrostatic air cleaners offered by others.
FEATURES
• Self-wash system to eliminate ESP cell manual
cleaning.
• Fixed or oscillating wash manifolds.
• Single or double pass configurations.
• Superior quality and construction virtually elimi-
nates maintenance costs.
• Various sizes provide design and installation
flexibility for any size installation.
• Up to 99%+ efficiency to ensure clean air.
• Optional PLC wash control panel.
• Optional detergent tank/pump and detergent.
• Optional UV and odor removal modules to con-
trol odors.
ENVICLEANTM
The ENVICLEANTM ESP offers economical exhaust air treatment with the same high efficiency
performance as the ENVIWASHTM electrostatic cleaners, but without the self-wash feature. The
ENVICLEANTM Series is ideal for exhaust systems that are lighter duty in nature and don't require
frequent cleaning. The ENVICLEANTM Series is offered to meet any size or efficiency require-
ments. These units are available in single and double pass configurations and optiona with UV
and/or media modules or ozone generators for odor removal.
FEATURES
• Economical, manual cleaning requires no
plumbing connections.
• Single or double pass configurations.
• No need to stack units for larger flows.
• Easy to install.
• Side access door for easy maintenance.
• Various sizes provide design and installa-
tion flexibility for any size installation.
• Up to 99%+ efficiency to ensure clean air.
• Removable bottom tray.
• Optional UV and odor removal modules to
control odors.
19
ESP UNIT
FEATURES
UV Module
Ozone Generator
20
ESP UNIT PERFORMANCE DATA
ESP EFFICIENCY
Efficiency Ratings based on
ASHRAE Standard 52.2-2017,
Method of Testing General Venti-
lation Air Cleaning Devices for
Removal Efficiency by Particle
Size, 3rd party testing.
21
ESP MODELS
Model Nominal Nominal Weight ESP Dimensions (3), No. of
Capacity Capacity (3) , kg L x D x H, mm Electronic Cells
(1), CFM (1), l/s
MANUAL CLEANING ENVICLEANTM UNITS (EC SERIES)
EC 1500 1,550 732 63 678 x 560 x 842 1
EC 2000 2,070 977 73 846 x 560 x 842 1
EC 3000 3,100 1463 95 1188 x 560 x 842 2
EC 4000 4,100 1935 119 1524 x 560 x 842 2
EC 5000 5,000 2360 129 1628 x 560 x 842 2
EC 6000 6,200 2926 168 2202 x 560 x 842 3
EC 7000 7,500 3540 182 2358 x 560 x 842 3
EC 8000 8,300 3917 218 1524 x 560 x 1545 4
EC 10000 10,350 4885 236 1628 x 560 x 1545 4
EC 12000 12,430 5866 300 2202 x 560 x 1545 6
EC 14000 14,900 7032 350 2358 x 560 x 1545 6
EC 16000 16,000 7551 380 1628 x 560 x 2248 6
EC 18000 18,650 8802 490 2202 x 560 x 2248 9
EC 21000 22,500 10,619 518 2358 x 560 x 2248 9
TM
SELF-CLEANING ENVIWASH UNITS (EWO SERIES)
EW 1500 1,550 732 110 800 x 1000 x 1000 1
EW 2000 2,070 977 132 1000 x 1000 x 1000 1
EW 3000 3,100 1463 156 1260 x 1000 x 1000 2
EW 4000 4,100 1935 202 1600 x 1000 x 1000 2
EW 5000 5,000 2360 219 1700 x 1000 x 1000 2
EW 6000 6,200 2926 281 2280 x 1000 x 1000 3
EW 7000 7,500 3540 314 2425 x 1000 x 1000 3
EW 8000 8,300 3917 371 1600 x 1000 x 1700 4
EW 10000 10,350 4885 401 1700 x 1000 x 1700 4
EW 12000 12,430 5866 510 2280 x 1000 x 1700 6
EW 14000 14,900 7032 567 2425 x 1000 x 1700 6
EW 16000 16,000 7551 646 1700 x 1000 x 2410 6
EW 18000 18,650 8802 833 2280 x 1000 x 2410 9
EW 21000 22,500 10,619 911 2425 x 1000 x 2410 9
1. Nominal Capacity is based on 95% efficiency for single pass units and 99% efficiency for double pass units.
2. Weight does not include UV or odor removal modules. Weight is double for double pass units.
3. Dimensions do not include UV or odor removal modules. Depth is double for double pass units. EWF dimensions are the same as
EC Series.
UK
ENVITEC LTD.
3rd Floor, 120 Baker Street
Westminster, London
W1U 6TU, United Kingdom
Phone: +44 20 37450718 , Fax: +44 20 7183 3073
Main Office
46 Elmar Circle, Royersford, PA 19468 USA
Phone: 1-610-792-1275, Fax: 1-610-792-4824
Washable filters.
EXCELAIR METALLIC filters are high velocity washable type permanent air filters suitable for HVAC
and Grease filtration applications.The media used is pleated layers of 14 screen aluminium / SS mesh
arranged in multi layers and encased in an aluminium or galvanized steel frame. An additional expanded
metal grid on upstream and downstream sides provides media support and strength to the filter. These
filters offers very low resistance to the airflow. Complete stainless steel construction is also available as
an option.
Construction:
EXCELAIR Metallic filters are washable metal series filters made up of multi pleated metal layers of wires,
encased in metal frames. The metal media reinforce with rigid expanded mesh. The drain holes will help
the dust, oil/grease to remove from the filter automatically. The metal media are available in Aluminum,
Galvanized Iron & Stainless steel construction.
The rigid construction of metal series filters shall ensure the performance in Heavy duty applications too.
Support Grids are available at air entry side & air exit side, upon special request.
Applications:
Metallic filters are best for Heavy duty filtration purpose, Industrial machine chip removal applications
& Commercial applications. Due to high dust holding capacity, the filters are suitable for Oil / Kitchen
grease filter applications. The filters are suitable for high moisture conditions also.
The filters are easy to install & clean. The filter can be washed with detergent and water or can be
cleaned with compressed air.
50
40
Pressure Drop (Pascal)
30
20
10
0
0 500 1000 1500 2000 2500
SIZE SELECTION
isometric view
07
15 EXCELAIR LIVE | Technical Catalogue | Pre-Filters www.cmsglobal.com
EXCELAIR
ULTRA-PAC
FILTER
EXTENDED SURFACE POCKET FILTER
SUPER FINE & MEDIUM SYNTHETIC MEDIA
Computer Rooms Airports Optical & Electronic Facilities Laboratories Food processing
EUPF-24x24x36-(F7/F8/F9)-10 23.30 23.30 36 10 2000 2500 3000 0.41 0.52 0.63 0.35 0.43 0.52 0.27 0.34 0.41 10.85
EUPF-24x24x30-(F7/F8/F9)-10 23.30 23.30 30 10 2000 2400 2800 0.47 0.56 0.68 0.41 0.49 0.58 0.33 0.40 0.47 9.10
EUPF-24x24x30-(F7/F8/F9)-8 23.30 23.30 30 8 1800 2000 2200 0.46 0.51 0.57 0.39 0.44 0.49 0.28 0.36 0.48 7.21
EUPF-24x24x26-(F7/F8/F9)-10 23.30 23.30 26 10 1800 2000 2400 0.42 0.50 0.62 0.38 0.43 0.51 0.30 0.34 0.40 7.81
EUPF-24x24x24-(F7/F8/F9)-10 23.30 23.30 24 10 1750 2000 2400 0.43 0.53 0.65 0.40 0.46 0.55 0.31 0.36 0.43 7.20
EUPF-24x24x24-(F7/F8/F9)-8 23.30 23.30 24 8 1400 2000 2400 0.40 0.56 0.67 0.35 0.50 0.60 0.28 0.40 0.48 5.70
EUPF-24x24x24-(F7/F8/F9)-6 23.30 23.30 24 6 1400 1800 2000 0.43 0.56 0.63 0.38 0.50 0.55 0.31 0.41 0.46 4.30
EUPF-24x24x22-(F7/F8/F9)-10 23.30 23.30 22 10 1750 2000 2250 0.56 0.64 0.72 0.51 0.59 0.67 0.42 0.48 0.54 6.52
EUPF-24x24x22-(F7/F8/F9)-8 23.30 23.30 22 8 1500 1750 2000 0.48 0.57 0.66 0.44 0.52 0.60 0.35 0.40 0.49 5.20
EUPF-24x24x22-(F7/F8/F9)-6 23.30 23.30 22 6 1500 1750 2000 0.55 0.65 0.75 0.48 0.56 0.65 0.39 0.46 0.54 3.90
EUPF-12x24x22-(F7/F8/F9)-3 11.30 23.30 22 3 750 875 1000 0.55 0.65 0.75 0.48 0.56 0.65 0.39 0.46 0.54 2.00
EUPF-24x24x21-(F7/F8/F9)-8 23.30 23.30 21 8 1500 1750 2000 0.49 0.58 0.67 0.45 0.53 0.61 0.37 0.43 0.50 5.10
EUPF-24x24x21-(F7/F8/F9)-6 23.30 23.30 21 6 1500 1750 2000 0.56 0.66 0.76 0.50 0.59 0.68 0.44 0.52 0.60 3.80
EUPF-24x24x20-(F7/F8/F9)-10 23.30 23.30 20 10 1500 2000 2200 0.51 0.69 0.77 0.46 0.62 0.69 0.41 0.54 0.61 6.00
EUPF-24x24x20-(F7/F8/F9)-8 23.30 23.30 20 8 1500 1750 2000 0.52 0.61 0.70 0.47 0.55 0.63 0.36 0.48 0.55 4.80
EUPF-24x24x20-(F7/F8/F9)-6 23.30 23.30 20 6 1500 1750 2000 0.59 0.69 0.79 0.52 0.61 0.70 0.46 0.54 0.62 3.60
EUPF-12x24x20-(F7/F8/F9)-3 11.30 23.30 20 3 750 875 1000 0.59 0.69 0.79 0.52 0.61 0.70 0.46 0.54 0.62 1.90
EUPF-24x24x18-(F7/F8/F9)-8 23.30 23.30 18 8 1500 1750 2000 0.61 0.70 0.80 0.54 0.63 0.72 0.42 0.56 0.65 4.33
EUPF-24x24x18-(F7/F8/F9)-6 23.30 23.30 18 6 1500 1750 2000 0.68 0.77 0.88 0.59 0.69 0.79 0.53 0.62 0.71 3.25
EUPF-24x24x15-(F7/F8/F9)-10 23.30 23.30 15 10 1350 1500 2000 0.59 0.66 0.88 0.50 0.56 0.75 0.44 0.49 0.66 4.52
EUPF-24x24x15-(F7/F8/F9)-8 23.30 23.30 15 8 1250 1500 2000 0.57 0.69 0.92 0.48 0.58 0.78 0.43 0.52 0.70 3.60
EUPF-24x24x36-(M5/M6)-10 23.30 23.30 36 10 2000 2500 3000 0.25 0.31 0.38 * * * 10.85
EUPF-24x24x30-(M5/M6)-10 23.30 23.30 30 10 2000 2400 2800 0.29 0.34 0.40 * * * 9.10
EUPF-24x24x30-(M5/M6)-8 23.30 23.30 30 8 1800 2000 2200 0.28 0.32 0.35 * * * 7.21
EUPF-24x24x26-(M5/M6)-10 23.30 23.30 26 10 1800 2000 2400 0.27 0.30 0.36 0.17 0.19 0.22 7.81
EUPF-24x24x24-(M5/M6)-10 23.30 23.30 24 10 1750 2000 2400 0.28 0.32 0.38 0.20 0.22 0.26 7.20
EUPF-24x24x24-(M5/M6)-8 23.30 23.30 24 8 1400 2000 2400 0.24 0.35 0.42 0.17 0.24 0.28 5.70
EUPF-24x24x24-(M5/M6)-6 23.30 23.30 24 6 1400 1800 2000 0.28 0.37 0.42 0.14 0.20 0.26 4.30
EUPF-24x24x22-(M5/M6)-10 23.30 23.30 22 10 1750 2000 2250 0.35 0.40 0.46 0.20 0.23 0.26 6.52
EUPF-24x24x22-(M5/M6)-8 23.30 23.30 22 8 1500 1750 2000 0.29 0.34 0.40 0.17 0.21 0.25 5.20
EUPF-24x24x22-(M5/M6)-6 23.30 23.30 22 6 1500 1750 2000 0.36 0.42 0.48 0.23 0.27 0.31 3.90
EUPF-12x24x22-(M5/M6)-3 11.30 23.30 22 3 750 875 1000 0.36 0.42 0.48 0.23 0.27 0.31 2.00
EUPF-24x24x21-(M5/M6)-8 23.30 23.30 21 8 1500 1750 2000 0.35 0.41 0.47 0.18 0.21 0.25 5.10
EUPF-24x24x21-( M5/M6)-6 23.30 23.30 21 6 1500 1750 2000 0.39 0.46 0.53 0.20 0.24 0.29 3.80
EUPF-24x24x20-(M5/M6)-10 23.30 23.30 20 10 1500 2000 2200 0.36 0.47 0.52 0.18 0.24 0.27 6.00
EUPF-24x24x20-(M5/M6)-8 23.30 23.30 20 8 1500 1750 2000 0.36 0.43 0.50 0.19 0.22 0.26 4.80
EUPF-24x24x20-(M5/M6)-6 23.30 23.30 20 6 1500 1750 2000 0.40 0.47 0.54 0.22 0.26 0.30 3.60
EUPF-12x24x20-(M5/M6)-3 11.30 23.30 20 3 750 875 1000 0.40 0.47 0.54 0.22 0.26 0.30 1.90
EUPF-24x24x18-(M5/M6)-8 23.30 23.30 18 8 1500 1750 2000 0.40 0.47 0.54 0.28 0.33 0.38 4.33
EUPF-24x24x18-(M5/M6)-6 23.30 23.30 18 6 1500 1750 2000 0.43 0.51 0.59 0.30 0.35 0.41 3.25
EUPF-24x24x15-(M5/M6)-10 23.30 23.30 15 10 1350 1500 2000 0.37 0.42 0.56 0.26 0.29 0.39 4.52
EUPF-24x24x15-(M5/M6)-8 23.30 23.30 15 8 1250 1500 2000 0.36 0.44 0.59 0.25 0.30 0.41 3.60
E : Excelair
M5/M6/F7/F8/F9 : Grade
8 : Number of Pockets
Height
Height
Depth
Note: The photos shown are only for illustration purpose. The actual product may vary. Please contact the technical/sales department for more information. As a part of continuous
improvement, CMS reserve the right to make technical modifications without prior notice. All non-standard sizes are available upon request. Please contact factory for details.
Fig. 1
IVC Level
Position 315° 45° 135° 225°
Dynamic Pressure
Both dynamic pressure and outlet air velocity values shown on each graph are calculated base on the full discharge area, i.e.
ducted outlet condition.
With free outlet condition the velocity pressure is higher. To determine this new value multiply the velocity pressure of
the ducted outlet obtained from the fan curve by the following correction factor “K”.
K = 1.67
Fan performance calculated with this correction factor is not licensed by AMCA.
Performance
The performance data shown on each graph is derived from tests conducted in accordance to AMCA Standard 210 –
Fig 12 – installation type B (free inlet and ducted outlet condition).
Ratings refer to the standard air density with the total pressure as a function of the air volume, using logarithmic scale.
It is essential that the same installation type and test standards are used at all times when comparing fan performance.
Noise
The noise levels shown on each graph refer to the "A-weighted" sound power values and the data on the inlet side
has been measured in accordance with AMCA Standard 300 diag. 2 - configuration "B". The noise levels of fans are
determined as follow :
a) free field
Lp(A) = Lw(A) - (20log10d) -11
b) room conditions
Lp(A) = Lw(A) - (20log10d) -8
where d = distance from fan (m)
6
BDB Series
Performance
Ratings refer to standard air density with the total pressure as a function
of the air volume, using logarithmic scale.
It is essential that the same installation type and test standards are used
at all time when comparing fan performance.
According to AMCA 205, BDB series can be classify as FEG 85~90 based
on fan peak efficiency. The following is the explanation of FEG
classification:
Fan Efficiency Grades (FEG) for Fans without Drives (SI) – AMCA 205
7
BDB Series
Example of Selection
BDB 500
Op Limit Cl. I Cl. II Cl. III
FEG 85 Type S-C T X
M. kW 10 20 45
M. RPM 1900 2500 3200
γ
η
Dynamic Pressure Pd = 62 Pa
Absorbed Power W = 8 kW
Total Efficiency η = 78 %
- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects
of appurtenances (accessories). Power rating kW does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A)
sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.
8
BDB ‘C’
‘C’
BDB 315-400 ‘C’
B
L
G
M = E = M
R
=
C
D
Ød-g6
F
A
uxs
=
= F = J
P H K
d
Model A B C D E F G H J K L M P R uxs
CL CM
315 578 518 340 404 404 330 236 480 434 464 600 68 38 3 25 25 13x18
355 654 578 383 452 452 368 260 548 492 532 672 70 30 6 30 30 13x18
400 736 650 432 506 506 402 290 612 546 586 726 70 38 5 30 30 13x18
All Dimensions in mm.
B
L
G
M = E = M
R
=
C
F
D
Ød-g6
F1
A
uxs
F=
= F F1 F = J
P H K
d
Model A B C D E F F1 G H J K L M P R uxs
CL CM
450 827 726 486 568 568 200 111 322 681 608 648 814 83 45 5 35 35 13x18
500 918 800 538 638 638 245 120 352 750 678 718 924 103 50 5 35 35 13x18
560 1030 892 603 714 714 280 125 390 844 764 814 1000 93 48 7 40 40 13x18
630 1157 998 679 800 800 328 110 434 945 850 900 1092 96 53 6 40 45 13x18
710 1302 1120 765 898 898 360 150 484 1057 948 998 1234 118 63 7 50 50 17x22
All Dimensions in mm.
27
OVERALL DIMENSION – BDB “C” SERIES
C C2
C C1
H
W L L W L W W L
CCW 90° (Pos W) CCW 270° (Pos Z) CCW 360° (Pos W) CCW 360° (Pos Z)
C C1 C2
C
H
H
H
L W W L L W W L
38
Kruger Ventilation Industries Pte Ltd
A member of
No. 17 Tuas Avenue 10 Singapore 639141
Tel. +65 68611577 - Fax +65 68613577
Website: www.krugerfan.com
CNo. - CAT008.E3 November 2011