ENVIPURETM ECOLOGY UNITS

and
ENVICLEANTM & ENVIWASHTM
ESP ELECTROSTATIC FILTERS

Eliminate Grease, Dust, Smoke, Odor…. And Worries!


INTRODUCTION

In today’s busy world, more people are going out to particulates and smoke efficiently and effectively to
eat. For restaurants this growing trend not only in- ASHRAE Standard 52.2 thereby eliminating fire and
creases traffic and revenue but also the kitchen haz- other hazards. EnviTec’s ESP’s can be installed in-
ards associated with this new volume. doors or on the rooftop.

As kitchen cooking production grows, restaurants will EnviTec’s ESP units can be supplied as stand alone
exhaust more smoke, grease, and odors into the air. systems or with UV and/or odor removal systems,
Local neighbors may raise concerns about air quality, including media or ozone, or as part of an ecology
and restaurants may put their roofs at risk with unit. The ESP units can be either self-cleaning or
grease pooling that attacks roof materials. manual cleaned type depending on the specific pro-
ject requirements and budget.
To help restaurants keep pace, EnviTec offers its EN-
VIPURETM Kitchen Exhaust Air Cleaning Systems. When part of an ecology unit the ESP can be supplied
These systems use proven static filtration and/or elec- along with a safety filter, final filter, UV and/or odor
tronic air cleaning techniques to remove smoke, dust, removal modules and fan section with a housed high
grease, mist, and other particulates from the air. temperature rated DWDI fan or external SWSI fan or
coupled to the ecology unit filter/odor removal sec-
Grilling, frying and charbroiling emissions can be- tion. These ESP Ecology units are factory fully as-
come a problem if these emissions are not properly sembled and shipped in sections for on-site joining.
controlled. Also, visible smoke and odor may alert
authorities to possible compliance problems, result- EnviTec is the only Ecology and ESP unit manufactur-
ing in potential fines. EnviTec’s Ecology Unit and er that fabricates ESP’s specifically for the harsh Mid-
Electrostatic Precipitator (ESP) filtration systems elim- dle East climate. We understand the Middle East’s
inate these problems. requirements based on hands-on experience with nu-
merous Ecology Unit and ESP installations in the re-
EnviTec’s ENVIPURETM APU, EAPU and ESPEU Series gion. EnviTec ENVIPURETM APU’s, EAPU,’s, ESPEU’s
ecology kitchen hood exhaust filtration systems effec- Ecology Units and ENVICLEANTM and ENVIWASHTM
tively remove up to 99%+ of all grease and smoke effi- ESP’s are engineering to withstand very high ambient
ciently and effectively to ASHRAE Standard 52-2-2017 temperatures and are simple to install and maintain.
thereby eliminating fire hazards and odors. EnviTec’s
Ecology units can be installed indoors or outdoors on
the rooftop. PRODUCT SERIES
The EnviTec ECOLOGY APU series utilizes a three
stage filtration system to eliminate grease and oil par- Ecology Units
ticles and smoke from the kitchen hood exhaust air
stream while the EAPU series utilizes a combination  Air Purification Unit (APU)
of electrostatic filters and standard filters. Through
the use of a media or liquid odor removal system ob-  ESP Air Purification Unit (EAPU)
jectionable odors from commercial kitchen cooking  ESP Ecology Unit (ESPEU)
and frying are removed effectively. A fan module used
to exhaust the purified air completes the unit. The ES-
PEU series includes an ESP and an optional safety
ESP Units
filter, UV and/or media system and the fan module.
The units have been designed to operate with all dry,  Manual Wash (EC)
wet and UV exhaust hoods in order to provide opti-  Self-Cleaning (EWF and EWO)
mum filter life. All models can meet the requirements  UV Module (UV)
of NFPA 96 if an optional dedicated fire suppression  Safety Filter Module (SF)
system is installed on the units.
 Final Filter Module (FF)
EnviTec’s ENVICLEANTM and ENVIWASHTM ESP filtra-  Carbon Module (CM)
tion systems effectively remove up to 99%+ of all  Ozone Generator (OZ)

ELIMINATE OIL, GREASE, DUST, SMOKE, ODOR…. AND WORRIES!

LET US SHOW YOU HOW WE CAN MEET YOUR


ECOLOGY UNIT AND ESP TECHNOLOGY NEEDS!
2
EAPU ECOLOGY UNIT
PRINCIPLE OF OPERATION

1 2 3 4

1. Electrostatic Filter (ESP) Section


2. Filter Section
3. Odor Neutralization Section
5 4. Exhaust Fan Section
5. Optional Control Panel (Mounted in
Kitchen)

The EnviTec ENVIPURETM EAPU Ecology unit is available in 4 basic configurations as follows:
1. Manual wash ESP (ENVICLEANTM) section 3. Self-cleaning ESP (ENVIWASHTM) section
with DWDI Fan in Sound Insulated Housing with DWDI Fan in Sound Insulated Housing
2. Manual wash ESP (ENVICLEANTM) section 4. Self-cleaning ESP (ENVICLEANTM) section
with External SWSI Fan with External SWSI Fan

EAPU with Manual Wash ESP SECTION and External UL762 Listed Fan

ESP
EnviTec’s electrostatic precipitators conform to
UL 867 and include two parts: the charging and
collecting sections.

In the charging section, the incoming smoke,


grease, dust, mist, and other particulates pass by
tungsten ionizer wires which impart a positive
electrical charge to these contaminants. The pos-
itively charged contaminants are then drawn
through the collection section which contains a
secondary electrical field with negatively charged
aluminum plates. Since opposite charges attract,
the positively charged contaminants collect on
the negatively charged aluminum plates, remov-
ing them from the airstream.
8
EAPU ECOLOGY UNIT
PRINCIPLE OF OPERATION
ESP Section
The ESP section can be either manual wash
(ENVICLEANTM) or self-cleaning (ENVIWASHTM).

A washable metal mesh pre-filter is included to


remove large grease and oil particles before
the air enters the ESP.

The ENVICLEANTM ESP offers the same high


efficiency performance as the ENVIWASHTM
electrostatic cleaner but without the self-wash
feature.

The ENVIWASHTM ESP features either a fixed


wash system that sprays the collector cells
from the top with fixed spray nozzles (EWF Se-
ries) or a dynamic wash system that uses multi
jet wash manifolds in both the front and rear of
the electronic collector cells to insure complete
coverage and maximum wash results (EWO Se-
ries). The wash sequence can be operated
through the BMS or through an optional PLC or
sequence controller wash control panel. Units
are available in single pass and double pass
configurations and can be washed with hot wa-
ter or with hot water and detergent, which is
much more effective in removing oil and
Filter Section grease.

The exhaust air from the ESP section enters


the Filter section, which consists of either 1
or a series of 2 filters designed to achieve up
to 99% (ASHRAE) particulate free air for ex-
cellent grease and smoke control.

PRE-FILTER - The UL Class 1 disposable


pleated 4” deep Pre-Filter is a MERV 8 (G4)
filter - 30%-40% dust spot efficiency based on
3.0 to 10.0 μm particles when tested in ac-
cordance with ASHRAE 52.2-2017.

SAFETY FILTER - The UL Class 1 disposable


20/21” deep Bag Filter is a MERV 14 (F8) filter
- 90%-95% dust spot efficiency based on 3.0
to 10.0 μm particles when tested in accord-
ance with ASHRAE 52.2-2017.

An optional differential pressure switch cabi-


net is located on the access side of the Filter
Module to monitor clean/dirty filter status and
filter missing condition.

9
EAPU ECOLOGY UNIT
PRINCIPLE OF OPERATION
Odor Neutralization Module
The exhaust air is then drawn from the filter section
through the Odor Reducing Section, which uses ei-
ther EnviTec’s odor neutralization solution or media.
Odor Neutralizer Solution
The atomized particle spray mist permeates the ex-
haust air, attacks and neutralizes airborne odor par-
ticulates and the bacteria that cause odors. The odor
neutralization solution effectively reduces unwanted
organic odors. The solution was exclusively devel-
oped for application to the kitchen exhaust air
stream, and is specifically formulated to break down
organic odors produced from commercial cooking.

Odor spray can be activated on a continuous cycle


during operation or an intermittent time cycle to best
suit the cooking operation.
Media
Media trays arranged in a V-bank configuration are
used to absorb odor from the air stream. Media is
available as activated carbon, a 50-50 blend of acti-
vated carbon and potassium permanganate impreg-
nated activated alumina or pure impregnated activat-
ed alumina. Average pressure drop through the me-
dia is 1” (250) and does not change.

Exhaust Fan Section - Housed Fan


The exhaust air then travels through the Exhaust Fan
Section, which is double wall construction with
sound insulation. The exhaust fan is double width,
double inlet Class 1 or 2 type with backward inclined
type blades for the EAPU. It features non-overloading
horsepower characteristics, smooth airflow design,
optional high temperature rated design and includes
the following:
• Base frame mounted on spring isolators.
• TEFC High Efficiency (IE2) Motor, Class F insulation with
a service factor of 1.1.
• An optional combination motor starter and fused discon-
nect switch can be mounted on the access side of the
Fan Section and factory prewired to the motor.
• Inlet cones are designed for smooth acceleration of air-
flow into the wheel with clearances designed to maintain
efficiency and reduce noise.
• Complete assembly is statically and dynamically bal-
anced on precision electronic balancing machines.
The Exhaust Fan Section may be located immediately
following the Filter and Odor Neutralization Sections,

10
EAPU ECOLOGY UNIT
PRINCIPLE OF OPERATION
Optional External Fan Section Fan
The exhaust air then travels through the Exhaust
Fan. The exhaust fan can be high temperature rated
or UL 762 listed single width, single inlet Class 1 or 2
type with backward inclined type blades. It features
non-overloading horsepower characteristics, smooth
airflow design and includes the following:
• Base frame mounted on spring isolators.
• TEFC High Efficiency (IE2) Motor, Class F insulation with
a service factor of 1.1.
• Optional combination motor starter and fused disconnect
switch can be supplied loose for on-site installation.
• Inlet cones are designed for smooth acceleration of air-
flow into the wheel with clearances designed to maintain
efficiency and reduce noise.
• Complete assembly is statically and dynamically bal-
anced on precision electronic balancing machines.
The Exhaust Fan Section must be located immediate-
ly following the Filter and Odor Neutralization Sec-
tions.

FEATURES
Construction
EnviTec manufactures EAPU ECOLOGY
units to the highest quality standards. Filter
section casing panels are solid double wall
construction with 1” (or 2” for large models)
fireproof polyisocyanurate foam insulation.
As such, these units offer a number of ad-
vantages for Middle East clients, including
the following:
• Extruded aluminum framework
• Double wall construction
• Temperature resistant panels
• Nylon reinforced FRP corner brackets,
handles and latches
• Solid GI base frame
• Special mating brackets make installation
easy and simple

11
EAPU ECOLOGY UNIT
FEATURES
Optional Control Panel
The EnviTec EAPU ECOLOGY unit Optional Control
Panel features a standard 120 or 220-volt control
system and is constructed of heavy gauge stainless
steel. The panel contains an HOA switch, and sys-
tem status display, alarm buzzer, silencing button,
control relays and a terminal strip for field wiring.
The control panel can be surface mounted or re-
cessed in the wall.

If an odor removal spray system is included the


panel can is equipped with Low Odor Solution Indi-
cators consisting of: Low Odor Solution light, Low
Odor solution Buzzer and Silence Buzzer Push But-
ton. Also available are sets of dry contacts for send-
ing status signals to the building management sys-
tem (BMS).

The panel is normally located in the kitchen where


the EnviTec ECOLOGY unit can be turned on and
off depending on hood use requirements .

Safety
The EnviTec ECOLOGY EAPU unit includes
a number of standard and optional safety
features. Features include an optional fire
detector (stat) at the inlet set at 165oF
(74oC), standard fireproof polyisocyanurate
foam insulation and an optional curtain fire
damper at the outlet of the filter module ac-
tivated by a fusible link.

The control panel includes an interlock that


shuts the unit down in the event of a fire
condition and activates a fire alarm locally
and through the BMS.

An optional ANSUL self contained Fire


Suppression System can be installed on
the unit to meet the requirements of NFPA
96.

12
EAPU ECOLOGY UNIT
FEATURES
EAPU OPTIONS
• Double pass ESP section
• UV Section
• 1 Stage of Filtration
• 50-50 blend of activated carbon and potassium permanganate impregnated
activated alumina or 100% pure impregnated activated alumina media
• Fire Detector (Fire Stat) at Inlet
• Curtain Fire Damper
• DP Monitoring Cabinet Mounted on Unit
• DP Transmitter
• High temperature rated (400oC for 2 hours) DWDI fan
• High temperature rated (400oC for 2 hours) SWSI fan
• UL762 SWSI listed fan
• IE3 and/or Class H Motor
• Motor Starter or VFD in cabinet mounted on unit or supplied loose
• Fan trip status
• 3rd stage box filters
• Remote Control Panel
• Washable metallic filters
• Final HEPA (99.97% DOP efficiency) filters
• ANSUL Fire suppression system
• PLC or sequence wash control panel (Self-cleaning ESP section only)
• Detergent tank (Self-cleaning ESP section only)
• Detergent (self-cleaning ESP section only)

13
EAPU ECOLOGY UNIT MODEL NOMENCLATURE
Configuration EAPU(EC)-04-OT/OS-X-X Options
EAPU(EC)-Manual wash ESP UV: UV section
EAPU(EC/L)-Manual wash ESP supplied loose FS: Fire stat
EAPU(EC/DP)-Manual wash double pass ESP 1S: 1 stage of filtration (Pre-filter or Bag
EAPU(EC/DP/L)-Manual wash double pass ESP Filter
supplid loose 3S: 3 stages of filtration
EAPU(EC/H)-Manual wash ESP in panel housing FD: Fire damper
EAPU(EC/DP/H)-Manual wash double pass ESP in FSS: Fire suppression system
panel housing EF: External SWSI fan
EAPU(EWF or EWO)-Auto Wash ESP with Fixed (EWF) or EF(762): External UL 762 listed fan
Oscillating (EWO) wash manifold F: DWDI High Temperature Rated Fan
EAPU(EWF/L or EWO/L)-Auto Wash ESP supplid loose VFD: Mounted (M) or Supplied loose (L)
EAPU(EWF/DP or EWO/DP)-Auto Wash double pass ESP TB: Transition and base
EAPU(EWF/DP/L or EWO/DP/L)-Auto Wash double pass (EF and F fans only)
ESP supplied loose MS: Motor starter
RP Remote control panel
Unit Size (x 1000 CFM nominal capacity) DP: DP cabinet mounted on unit
WP: PLC or sequence controller wash
01, 02, 03, 04, 06, 08, 10, 12, 16, 18, 20, 24, 28, 32 or 36 panel (EW models only)
(EW is only available up to 24) DT: Detergent tank with venturi injector or
with pump (P) (EW models only)
Odor Removal System C: Custom option(s) not listed above
OT: Media Odor Removal with Carbon
OT(50/50): Media Odor Removal with a 50-50 Blend of
Carbon and Impregnated Alumina
OT(100): Media Odor Removal with Impregnated Alumina

EAPU ECOLOGY UNIT MODELS


Nominal Nominal No. of Unit Dimensions, Unit Weight, Fan
Model (1) Capacity Capacity ESP (2-5) kg Motor Size (7),
CFM l/s Cells L x W x H, mm Spray Media (6) kw
EAPU-01 1,000 472 1 4800 x 1450 x 1450 509 536 2.2
EAPU-02 2,000 944 1 4800 x 1450 x 1450 561 570 3.0
EAPU-03 3,000 1,416 2 4900 x 1450 x 1550 623 673 4.0
EAPU-04 4,000 1,888 2 4900 x 1450 x 1550 743 943 5.5
EAPU-06 6,000 2,832 3 4900 x 1450 x 1650 830 991 7.5
EAPU-08 8,000 3,776 4 4900 x 1500 x 1650 911 1234 11.0
EAPU-10 10,000 4,720 6 4900 x 1600 x 1650 1130 1455 15.0
EAPU-12 12,000 5,664 6 4900 x 2700 x 1800 1409 1870 15.0
EAPU-16 16,000 7,552 6 4900 x 2700 x 1800 1650 2250 22.0
EAPU-18 18,000 8,496 9 5050 x 2700 x 1800 1668 2423 22.0
EAPU-20 20,000 9,440 12 5200 x 3200 x 2400 1991 2795 30.0
EAPU-24 24,000 11,328 12 5200 x 3200 x 2400 2173 3182 30.0
EAPU-28 28,000 13,216 12 5200 x 3200 x 2400 2325 3491 30.0
EAPU-32 32,000 15,104 12 5200 x 3200 x 2400 2477 3859 37.0
EAPU-36 36,000 16,992 18 5200 x 4400 x 2400 2714 4195 37.0
TM
1. EAPU models with ENVIWASH sections are only available up to EAPU-24.
2. Dimensions are the based on ENVICLEANTM ESP sections. ENVIWASHTM ESP section adds 750 mm to the length.
3. Dimensions are based on media units with 2 stages of static filtration and external fan sections. Single stage (pre-filter only) is 600 mm
shorter, single stage (bag filter only) is 150 mm shorter. Spray unit length is 65 mm) shorter.
4. Three stages of static filtration add 600 mm to the length.
5. Fan mounted in housing adds 200 mm to the length. Additional width varies based on unit model.
6. Media weight is based on 50-50 blend.
7. Fan motor size is based on media units at an external static pressure of 2.5” WG. (625 pa).

14
ESP UNIT
PRINCIPLE OF OPERATION
EnviTec’s ENVICLEANTM and ENVIWASHTM
dual-stage electrostatic precipitators (ESP’s)
conform to UL 867 and include two parts: the
charging and the collecting sections. In the
charging section, the incoming smoke, dust,
grease, mist, and other particulates pass by
ionizer wires which impart a positive electri-
cal charge to these contaminants. The posi-
tively charged contaminants are then drawn
through the collection section which contains
a secondary electrical field with negatively
charged plates. Since opposite charges at-
tract, the positively charged contaminants
collect on the negatively charged aluminum
plates, removing them from the airstream.

Ionizing wires are made from tungsten. Tung-


sten has the lowest coefficient of thermal ex-
pansion of any pure metal. The low thermal
expansion, high melting point and tensile
strength of tungsten make it one the hardest
materials known. This results in extremely
strong ionizing wires, which are superior to
spike type electrodes. Spike type electrodes
only impart the electrical charge at the spike,
which results in incomplete ionization and
spike wear. Tungsten ionizing wires, on the
other hand, impart a uniform electrical charge
along the whole length of the wire and do not
wear.

A washable metal mesh pre-filter is used to


remove large particles. In manual wash
(ENVICLEANTM) ESP’s particles that fall from
the negatively charged collection plates fall
into a removable tray located at the bottom of
the ESP unit. In self-cleaning (ENVIWASHTM)
ESP’s a flanged drain connection is located at
the bottom rear of the unit.

18
ESP UNIT
PRINCIPLE OF OPERATION
ENVIWASHTM
The ENVIWASHTM ESP features a fixed wash system that sprays the collector cells from the top
with fixed spray nozzles (EWF Series) or a dynamic wash system that uses oscillating multi jet
wash manifolds in both the front and rear of the electronic collector cells to insure complete cov-
erage and maximum wash results (EWO Series). The wash sequence can be operated through
the BMS or through an optional PLC or sequence controller control panel, which is factory pro-
grammed to control wash and rinse cycles. Units are available in single pass and double pass
configurations and can be washed with hot water or with hot water and detergent, which is much
more effective in removing oil and grease. Complete packages for the EW electronic air cleaners
are available that include detergent tanks and detergent (the required hot water for washing and
rinsing must be 60oC to 70oC at a minimum pressure of 40 psig/276 kpa). The ENVIWASHTM Series
offers impressive restaurant kitchen exhaust performance with a comparably lower price than
self-cleaning electrostatic air cleaners offered by others.
FEATURES
• Self-wash system to eliminate ESP cell manual
cleaning.
• Fixed or oscillating wash manifolds.
• Single or double pass configurations.
• Superior quality and construction virtually elimi-
nates maintenance costs.
• Various sizes provide design and installation
flexibility for any size installation.
• Up to 99%+ efficiency to ensure clean air.
• Optional PLC wash control panel.
• Optional detergent tank/pump and detergent.
• Optional UV and odor removal modules to con-
trol odors.
ENVICLEANTM
The ENVICLEANTM ESP offers economical exhaust air treatment with the same high efficiency
performance as the ENVIWASHTM electrostatic cleaners, but without the self-wash feature. The
ENVICLEANTM Series is ideal for exhaust systems that are lighter duty in nature and don't require
frequent cleaning. The ENVICLEANTM Series is offered to meet any size or efficiency require-
ments. These units are available in single and double pass configurations and optiona with UV
and/or media modules or ozone generators for odor removal.

FEATURES
• Economical, manual cleaning requires no
plumbing connections.
• Single or double pass configurations.
• No need to stack units for larger flows.
• Easy to install.
• Side access door for easy maintenance.
• Various sizes provide design and installa-
tion flexibility for any size installation.
• Up to 99%+ efficiency to ensure clean air.
• Removable bottom tray.
• Optional UV and odor removal modules to
control odors.

19
ESP UNIT
FEATURES
UV Module

The EnviTec UV module produces ultraviolet


light with a wavelength of 254 and 187 nm.
The UV wavelength oxidizes the chemicals
and odors present in commercial cooking
hood exhaust into odorless inoffensive by-
products. The system includes U shaped UV
lamps perpendicular to the airflow.

Media Module (Odor Removal)

Activated carbon is used to absorb odor com-


pounds from the air stream. Also available is a 50-
50 blend of activated carbon and potassium per-
manganate impregnated alumina or 100% impreg-
nated alumina as absorption media alternatives.
Air flows through the media that is housed in re-
fillable trays arranged in a V-bank configuration.
A differential pressure gauge is included. The car-
bon to airflow ratio is 50 kg/1000 l/s.

Ozone Generator

The EV5 is the largest of EnviTec’s EV Series


of Ozone Genrators. It is capable of producing
up to ~5 grams/hour of ozone under normal
operating conditions. The EV5 relatively com-
pact size, high output, and self contained feed
gas supply make it an ideal choice for congest-
ed install sites. It is an effective and efficient
odor removal unit.

20
ESP UNIT PERFORMANCE DATA

ESP EFFICIENCY
Efficiency Ratings based on
ASHRAE Standard 52.2-2017,
Method of Testing General Venti-
lation Air Cleaning Devices for
Removal Efficiency by Particle
Size, 3rd party testing.

ESP PRESSURE DROP


Pressure drop values based on
clean condition 3rd party testing.

Dirty condition adds 12.5 pa to the


pressure drop per each pass.

ESP UNIT MODEL NOMENCLATURE


ESP Type EC(DP)2000-Z-X Unit Options

EC: Manual wash ESP OZ: Ozone generator supplied loose


EC(DP): Manual wash double pass WP: PLC wash panel -EW models
ESP DT: Detergent tank - EW models
EWF or EWO: Self-cleaning ESP C: Custom option(s) not listed above
EW(DP): Self-cleaning double pass
ESP Configuration Options

Unit Size UV: UV section


CM: 100% carbon
1500,2000, 3000, 4000, 5000, 6000, CM(50-50): 50-50 blend
7000, 8000, 10000, 12000, 14000, CM(100): 100% impregnated alumina
16000, 18000 or 21000

21
ESP MODELS
Model Nominal Nominal Weight ESP Dimensions (3), No. of
Capacity Capacity (3) , kg L x D x H, mm Electronic Cells
(1), CFM (1), l/s
MANUAL CLEANING ENVICLEANTM UNITS (EC SERIES)
EC 1500 1,550 732 63 678 x 560 x 842 1
EC 2000 2,070 977 73 846 x 560 x 842 1
EC 3000 3,100 1463 95 1188 x 560 x 842 2
EC 4000 4,100 1935 119 1524 x 560 x 842 2
EC 5000 5,000 2360 129 1628 x 560 x 842 2
EC 6000 6,200 2926 168 2202 x 560 x 842 3
EC 7000 7,500 3540 182 2358 x 560 x 842 3
EC 8000 8,300 3917 218 1524 x 560 x 1545 4
EC 10000 10,350 4885 236 1628 x 560 x 1545 4
EC 12000 12,430 5866 300 2202 x 560 x 1545 6
EC 14000 14,900 7032 350 2358 x 560 x 1545 6
EC 16000 16,000 7551 380 1628 x 560 x 2248 6
EC 18000 18,650 8802 490 2202 x 560 x 2248 9
EC 21000 22,500 10,619 518 2358 x 560 x 2248 9
TM
SELF-CLEANING ENVIWASH UNITS (EWO SERIES)
EW 1500 1,550 732 110 800 x 1000 x 1000 1
EW 2000 2,070 977 132 1000 x 1000 x 1000 1
EW 3000 3,100 1463 156 1260 x 1000 x 1000 2
EW 4000 4,100 1935 202 1600 x 1000 x 1000 2
EW 5000 5,000 2360 219 1700 x 1000 x 1000 2
EW 6000 6,200 2926 281 2280 x 1000 x 1000 3
EW 7000 7,500 3540 314 2425 x 1000 x 1000 3
EW 8000 8,300 3917 371 1600 x 1000 x 1700 4
EW 10000 10,350 4885 401 1700 x 1000 x 1700 4
EW 12000 12,430 5866 510 2280 x 1000 x 1700 6
EW 14000 14,900 7032 567 2425 x 1000 x 1700 6
EW 16000 16,000 7551 646 1700 x 1000 x 2410 6
EW 18000 18,650 8802 833 2280 x 1000 x 2410 9
EW 21000 22,500 10,619 911 2425 x 1000 x 2410 9
1. Nominal Capacity is based on 95% efficiency for single pass units and 99% efficiency for double pass units.
2. Weight does not include UV or odor removal modules. Weight is double for double pass units.
3. Dimensions do not include UV or odor removal modules. Depth is double for double pass units. EWF dimensions are the same as
EC Series.

The following specifications are applicable to all models


 UL 867: Units conform fully to UL 867  Ionizer: 0.25 mm tungsten
(Standard for Electrostatic Air Cleaners)  Pre Filters: 0.5” (13 mm) thick washable metal mesh
 Cabinet : 1.9 mm (14 Gauge) welded steel cabinet
 Pre and Post Filters: 1/2” (13 mm) or 2” (50 mm) thick
with a corrosion resistant powder coat finish
washable metal mesh (EW models)
 Power Supply ; 100% Solid state
 Control: Optional PLC wash control panel (EW models)
 Input: 220-230 VAC / 60-50 HZ / 1 phase
 Hot Water Requirement: Hot water must be available
 Output: Ionizer 13,500 VDC / Collector 6,500 VDC at a temperature of 140oF to 160oF (60oC to 71oC) at
 Ambient Temperature Rating : Air flow through cells: a pressure of 40 to 60 psig (276 to 414 kpag) (EW models)
5°C minimum, 65°C maximum
22
SUMMARY
TM
ENVITEC ENVIPURE ECOLOGY
AND
ENVICLEANTM & ENVIWASHTM ESP
UNITS
THE ONLY CHOICE FOR
KITCHEN HOOD EXHAUST TREATMENT
AND
DUST REMOVAL
 Complete product line of Ecology and ESP Units, including APU, EAPU,
ESPEU and EC & EW Series.
 ESP units with capacities up to over 21,000 CFM (12,360 l/s) without the need
to stack individual units.
 Extensive installation list in the Middle East region.
 99%+ of all dust, grease and smoke is efficiently and effectively removed to
ASHRAE Standard 52.2.
 Objectionable cooking odors are reduced to an effective and acceptable
level.
 Systems can be located in the ceiling space, on the roof, or in a designated
mechanical room.
 Each Section can be assembled and installed as one common unit or
individually installed in separate areas.
 Complete with BMS monitoring and control points.
 Numerous optional features.

Eliminate Grease, Dust, Smoke, Odor…. And Worries!


LET US SHOW YOU HOW WE CAN MEET YOUR
ECOLOGY UNIT AND ESP TECHNOLOGY NEEDS!
23
ENVI Technologies ME DMCC
17th Floor, Office 1708, Jumeirah Business Centre 5, Jumeirah Lake Towers
P.O. Box 5004016, , Dubai, UAE
Phone: +971 4 514 7473, Fax: +971 4 514 7455

ENVI TECH Air Equipment Manufacturing LLC


Warehouse 5C, DREC Warehouses, Jebel Ali Industrial Area 1
P.O. Box 5004016, , Dubai, UAE
Phone: +971 4 888 6667, Fax: +971 4 514 7455

UK
ENVITEC LTD.
3rd Floor, 120 Baker Street
Westminster, London
W1U 6TU, United Kingdom
Phone: +44 20 37450718 , Fax: +44 20 7183 3073

Main Office
46 Elmar Circle, Royersford, PA 19468 USA
Phone: 1-610-792-1275, Fax: 1-610-792-4824

© Copyright 2021 EnviTec Corporation


ECOLOGY/ESP-ME Rev. 8 May 2021
EXCELAIR METALLIC

฀฀ Metal series for Heavy duty & Coarse filter appli


cations.

฀฀ Suitable for HVAC systems & kitchen extract units.

฀฀ Washable filters.

฀฀ High dust holding capacity

฀฀ Easy to install & maintain

EXCELAIR METALLIC filters are high velocity washable type permanent air filters suitable for HVAC
and Grease filtration applications.The media used is pleated layers of 14 screen aluminium / SS mesh
arranged in multi layers and encased in an aluminium or galvanized steel frame. An additional expanded
metal grid on upstream and downstream sides provides media support and strength to the filter. These
filters offers very low resistance to the airflow. Complete stainless steel construction is also available as
an option.

Construction:
EXCELAIR Metallic filters are washable metal series filters made up of multi pleated metal layers of wires,
encased in metal frames. The metal media reinforce with rigid expanded mesh. The drain holes will help
the dust, oil/grease to remove from the filter automatically. The metal media are available in Aluminum,
Galvanized Iron & Stainless steel construction.
The rigid construction of metal series filters shall ensure the performance in Heavy duty applications too.
Support Grids are available at air entry side & air exit side, upon special request.

Applications:
Metallic filters are best for Heavy duty filtration purpose, Industrial machine chip removal applications
& Commercial applications. Due to high dust holding capacity, the filters are suitable for Oil / Kitchen
grease filter applications. The filters are suitable for high moisture conditions also.

The filters are easy to install & clean. The filter can be washed with detergent and water or can be
cleaned with compressed air.

www.cmsglobal.com EXCELAIR LIVE | Technical Catalogue | Pre-Filters 06


14
SELECTION CHART

Model Filter size Arrestance Resistance (In. WG)


Inches 350 fpm 500 fpm
CAST1 24 x 24 x 1 G2 0.04 0.07
CAST1 12 x 24 x 1 G2 0.04 0.07
CAST2 24 x 24 x 2 G2 0.05 0.10
CAST2 12 x 24 x 2 G2 0.05 0.10
CAST4 24 x 24 x 4 G2 0.09 0.18

CAST4 12 x 24 x 4 G2 0.9 0.18


Recommended final resistance 0.50” WG

Clean Air Resistance VS Velocity

50

40
Pressure Drop (Pascal)

30

20

10

0
0 500 1000 1500 2000 2500

Air velocity (fpm)

SIZE SELECTION

isometric view

07
15 EXCELAIR LIVE | Technical Catalogue | Pre-Filters www.cmsglobal.com
EXCELAIR
ULTRA-PAC
FILTER
EXTENDED SURFACE POCKET FILTER
SUPER FINE & MEDIUM SYNTHETIC MEDIA

Features & Benefits | ULTRA-PAC FILTER


● Excelair Ultra Pac Bag Filters uses high dense melt blown media ● Robust metal header frame ensures quick and easy mounting
with high dust holding capacity.
● Utilizes Tapered Bag Design for ensuring optimum performance
● High-Loft, Multi Layered Media is non – shedding, water
resistant and improves performance. ● Flawless Performance even during temporary overload options
ensuring high clean air quality
● Ultrasonically – welded pocket arrangement that guarantees
optimum media utilization and eliminates crowding or leakage. ● Available with Anti-Microbial

Specifications | ULTRA-PAC FILTER


Type Extended Surface Multi Pocket Bag Filter
Filter Grades (EN 779) M5,M6, F7, F8, F9
Filter Grades (As per ASHRAE 52.2) MERV 10, MERV 11, MERV 13, MERV 14, MERV 15
Filter Media Synthetic
Dimensions Filter Front Dimensions According to EN 15805
Frame GI / SS / Al / Polystyrene Plastic (20 / 25 MM Header Configurations Available)
Maximum Humidity 100%
Maximum Temperature 80 °C
Recommended Final Pressure Drop 1.00” WG
Maximum Pressure Drop 1.80” WG
Flammability UL 900 Classified
Mounting Options Front and Side Access Frames and Housings are Available

Applications | ULTRA-PAC FILTER

Hospital Pharmaceutical units Chemical Processing units Biomedical Museums

Computer Rooms Airports Optical & Electronic Facilities Laboratories Food processing

Excelair Airfilters | Fine Filters Technical Catalogue 02


Selection Chart | ULTRA-PAC FILTER

Initial Resistance to Airflow( Inches W.G)


Actual Dimensions Media
Airflow (CFM) 98%/F9/MERV15 95%/F8/MERV14 85%/F7/MERV13
(inches) No. of Area
Model Reference CP9 CP8 CP7
Pockets (Sq.m.)
Width Height Depth Low Medium High Low Medium High Low Medium High Low Medium High

EUPF-24x24x36-(F7/F8/F9)-10 23.30 23.30 36 10 2000 2500 3000 0.41 0.52 0.63 0.35 0.43 0.52 0.27 0.34 0.41 10.85

EUPF-24x24x30-(F7/F8/F9)-10 23.30 23.30 30 10 2000 2400 2800 0.47 0.56 0.68 0.41 0.49 0.58 0.33 0.40 0.47 9.10

EUPF-24x24x30-(F7/F8/F9)-8 23.30 23.30 30 8 1800 2000 2200 0.46 0.51 0.57 0.39 0.44 0.49 0.28 0.36 0.48 7.21

EUPF-24x24x26-(F7/F8/F9)-10 23.30 23.30 26 10 1800 2000 2400 0.42 0.50 0.62 0.38 0.43 0.51 0.30 0.34 0.40 7.81

EUPF-24x24x24-(F7/F8/F9)-10 23.30 23.30 24 10 1750 2000 2400 0.43 0.53 0.65 0.40 0.46 0.55 0.31 0.36 0.43 7.20

EUPF-24x24x24-(F7/F8/F9)-8 23.30 23.30 24 8 1400 2000 2400 0.40 0.56 0.67 0.35 0.50 0.60 0.28 0.40 0.48 5.70

EUPF-24x24x24-(F7/F8/F9)-6 23.30 23.30 24 6 1400 1800 2000 0.43 0.56 0.63 0.38 0.50 0.55 0.31 0.41 0.46 4.30

EUPF-24x24x22-(F7/F8/F9)-10 23.30 23.30 22 10 1750 2000 2250 0.56 0.64 0.72 0.51 0.59 0.67 0.42 0.48 0.54 6.52

EUPF-24x24x22-(F7/F8/F9)-8 23.30 23.30 22 8 1500 1750 2000 0.48 0.57 0.66 0.44 0.52 0.60 0.35 0.40 0.49 5.20

EUPF-24x24x22-(F7/F8/F9)-6 23.30 23.30 22 6 1500 1750 2000 0.55 0.65 0.75 0.48 0.56 0.65 0.39 0.46 0.54 3.90

EUPF-12x24x22-(F7/F8/F9)-3 11.30 23.30 22 3 750 875 1000 0.55 0.65 0.75 0.48 0.56 0.65 0.39 0.46 0.54 2.00

EUPF-24x24x21-(F7/F8/F9)-8 23.30 23.30 21 8 1500 1750 2000 0.49 0.58 0.67 0.45 0.53 0.61 0.37 0.43 0.50 5.10

EUPF-24x24x21-(F7/F8/F9)-6 23.30 23.30 21 6 1500 1750 2000 0.56 0.66 0.76 0.50 0.59 0.68 0.44 0.52 0.60 3.80

EUPF-24x24x20-(F7/F8/F9)-10 23.30 23.30 20 10 1500 2000 2200 0.51 0.69 0.77 0.46 0.62 0.69 0.41 0.54 0.61 6.00

EUPF-24x24x20-(F7/F8/F9)-8 23.30 23.30 20 8 1500 1750 2000 0.52 0.61 0.70 0.47 0.55 0.63 0.36 0.48 0.55 4.80

EUPF-24x24x20-(F7/F8/F9)-6 23.30 23.30 20 6 1500 1750 2000 0.59 0.69 0.79 0.52 0.61 0.70 0.46 0.54 0.62 3.60

EUPF-12x24x20-(F7/F8/F9)-3 11.30 23.30 20 3 750 875 1000 0.59 0.69 0.79 0.52 0.61 0.70 0.46 0.54 0.62 1.90

EUPF-24x24x18-(F7/F8/F9)-8 23.30 23.30 18 8 1500 1750 2000 0.61 0.70 0.80 0.54 0.63 0.72 0.42 0.56 0.65 4.33

EUPF-24x24x18-(F7/F8/F9)-6 23.30 23.30 18 6 1500 1750 2000 0.68 0.77 0.88 0.59 0.69 0.79 0.53 0.62 0.71 3.25

EUPF-24x24x15-(F7/F8/F9)-10 23.30 23.30 15 10 1350 1500 2000 0.59 0.66 0.88 0.50 0.56 0.75 0.44 0.49 0.66 4.52

EUPF-24x24x15-(F7/F8/F9)-8 23.30 23.30 15 8 1250 1500 2000 0.57 0.69 0.92 0.48 0.58 0.78 0.43 0.52 0.70 3.60

Initial Resistance to Airflow( Inches W.G)


Actual Dimensions Media
Airflow (CFM) 65%/M6/MERV11 50%/M5/MERV10
(inches) No. of Area
Model Reference CP6 CP5
Pockets (Sq.m.)
Width Height Depth Low Medium High Low Medium High Low Medium High

EUPF-24x24x36-(M5/M6)-10 23.30 23.30 36 10 2000 2500 3000 0.25 0.31 0.38 * * * 10.85

EUPF-24x24x30-(M5/M6)-10 23.30 23.30 30 10 2000 2400 2800 0.29 0.34 0.40 * * * 9.10

EUPF-24x24x30-(M5/M6)-8 23.30 23.30 30 8 1800 2000 2200 0.28 0.32 0.35 * * * 7.21

EUPF-24x24x26-(M5/M6)-10 23.30 23.30 26 10 1800 2000 2400 0.27 0.30 0.36 0.17 0.19 0.22 7.81

EUPF-24x24x24-(M5/M6)-10 23.30 23.30 24 10 1750 2000 2400 0.28 0.32 0.38 0.20 0.22 0.26 7.20

EUPF-24x24x24-(M5/M6)-8 23.30 23.30 24 8 1400 2000 2400 0.24 0.35 0.42 0.17 0.24 0.28 5.70

EUPF-24x24x24-(M5/M6)-6 23.30 23.30 24 6 1400 1800 2000 0.28 0.37 0.42 0.14 0.20 0.26 4.30

EUPF-24x24x22-(M5/M6)-10 23.30 23.30 22 10 1750 2000 2250 0.35 0.40 0.46 0.20 0.23 0.26 6.52

EUPF-24x24x22-(M5/M6)-8 23.30 23.30 22 8 1500 1750 2000 0.29 0.34 0.40 0.17 0.21 0.25 5.20

EUPF-24x24x22-(M5/M6)-6 23.30 23.30 22 6 1500 1750 2000 0.36 0.42 0.48 0.23 0.27 0.31 3.90

EUPF-12x24x22-(M5/M6)-3 11.30 23.30 22 3 750 875 1000 0.36 0.42 0.48 0.23 0.27 0.31 2.00

EUPF-24x24x21-(M5/M6)-8 23.30 23.30 21 8 1500 1750 2000 0.35 0.41 0.47 0.18 0.21 0.25 5.10

EUPF-24x24x21-( M5/M6)-6 23.30 23.30 21 6 1500 1750 2000 0.39 0.46 0.53 0.20 0.24 0.29 3.80

EUPF-24x24x20-(M5/M6)-10 23.30 23.30 20 10 1500 2000 2200 0.36 0.47 0.52 0.18 0.24 0.27 6.00

EUPF-24x24x20-(M5/M6)-8 23.30 23.30 20 8 1500 1750 2000 0.36 0.43 0.50 0.19 0.22 0.26 4.80

EUPF-24x24x20-(M5/M6)-6 23.30 23.30 20 6 1500 1750 2000 0.40 0.47 0.54 0.22 0.26 0.30 3.60

EUPF-12x24x20-(M5/M6)-3 11.30 23.30 20 3 750 875 1000 0.40 0.47 0.54 0.22 0.26 0.30 1.90

EUPF-24x24x18-(M5/M6)-8 23.30 23.30 18 8 1500 1750 2000 0.40 0.47 0.54 0.28 0.33 0.38 4.33

EUPF-24x24x18-(M5/M6)-6 23.30 23.30 18 6 1500 1750 2000 0.43 0.51 0.59 0.30 0.35 0.41 3.25

EUPF-24x24x15-(M5/M6)-10 23.30 23.30 15 10 1350 1500 2000 0.37 0.42 0.56 0.26 0.29 0.39 4.52

EUPF-24x24x15-(M5/M6)-8 23.30 23.30 15 8 1250 1500 2000 0.36 0.44 0.59 0.25 0.30 0.41 3.60

Excelair Airfilters | Fine Filters Technical Catalogue 03


Model Ref.Numbering Scheme | ULTRA-PAC FILTER
EUPF-24x24x21-(M5/M6/F7/F8/F9)-8

E : Excelair

UPF : ULTRA PAC FILTER

24x24x21 : Width x Height x Depth

M5/M6/F7/F8/F9 : Grade

8 : Number of Pockets

Size Selection | ULTRA-PAC FILTER

Height

Height

Depth

Width Width Depth

General Isometric view Front View Side View

Note: The photos shown are only for illustration purpose. The actual product may vary. Please contact the technical/sales department for more information. As a part of continuous
improvement, CMS reserve the right to make technical modifications without prior notice. All non-standard sizes are available upon request. Please contact factory for details.

Excelair Airfilters | Fine Filters Technical Catalogue 04


BDB Series
DOUBLE INLET CENTRIFUGAL FAN with Backward Wheels

Kruger Ventilation Industries certifies that the BDB


series shown herein is licensed to bear the AMCA
Seal. The ratings shown are based on tests and
procedures performed in accordance with AMCA
publication 211 and AMCA publication 311 and comply
with the requirements of the AMCA Certified Ratings
Program.
BDB Series

IVC orientation and accessories


The standard orientation and lever position for the IVC is indicated in
Fig.2. When ordering a complete fan with IVC and accessories, please
specify as follow:
Fan orientation e.g. CCW270
lever position e.g. Pos. 45o
Example : Fan Model – CCW270/P45

Fig. 1

Orientation 90 180 270 360


225° 315° 45° 135°

IVC Level
Position 315° 45° 135° 225°

Fig. 2 - IVC Orientation and Level Position

Dynamic Pressure
Both dynamic pressure and outlet air velocity values shown on each graph are calculated base on the full discharge area, i.e.
ducted outlet condition.
With free outlet condition the velocity pressure is higher. To determine this new value multiply the velocity pressure of
the ducted outlet obtained from the fan curve by the following correction factor “K”.

K = 1.67
Fan performance calculated with this correction factor is not licensed by AMCA.

Performance
The performance data shown on each graph is derived from tests conducted in accordance to AMCA Standard 210 –
Fig 12 – installation type B (free inlet and ducted outlet condition).
Ratings refer to the standard air density with the total pressure as a function of the air volume, using logarithmic scale.
It is essential that the same installation type and test standards are used at all times when comparing fan performance.

Noise
The noise levels shown on each graph refer to the "A-weighted" sound power values and the data on the inlet side
has been measured in accordance with AMCA Standard 300 diag. 2 - configuration "B". The noise levels of fans are
determined as follow :

Sound power level - ("A" scale): Lw (A) as catalogue


Octave band spectrum: Lw = Lw(A) + Lw rel. dB [refer to Kruger for more details]
Sound pressure level:

a) free field
Lp(A) = Lw(A) - (20log10d) -11

b) room conditions
Lp(A) = Lw(A) - (20log10d) -8
where d = distance from fan (m)

6
BDB Series

Performance

The performance data shown on each diagram is derived from tests


conducted in accordance to AMCA Standard 210- Fig 12- Installation type
B (free inlet and duct outlet condition).

Ratings refer to standard air density with the total pressure as a function
of the air volume, using logarithmic scale.
It is essential that the same installation type and test standards are used
at all time when comparing fan performance.

According to AMCA 205, BDB series can be classify as FEG 85~90 based
on fan peak efficiency. The following is the explanation of FEG
classification:

1. Fan size is the impeller diameter in mm.


2. The fan peak efficiency shall be calculated from the fan (total)
pressure.
3. If this method is used for a direct driven fan, the fan efficiency is the
impeller efficiency.
4. The FEG label for a given fan size is assigned when the fan peak
efficiency is equal to or lower than the efficiency at the grade upper
limit, and higher than the efficiency at the grade upper limit of the
next lower grade for the fan size.
5. For any fan sizes larger than 1016 mm, the values of the grade upper
limits are the same as for a size of 1016 mm.
6. No labels are considered for the fans with the fan peak total
efficiency below FEG 50.
7. The values of efficiencies are calculated for fan sizes in the preferred
R40 Series.
8. Not all available fan sizes are shown.

Fan Efficiency Grades (FEG) for Fans without Drives (SI) – AMCA 205

7
BDB Series

Example of Selection

BDB 500
Op Limit Cl. I Cl. II Cl. III
FEG 85 Type S-C T X
M. kW 10 20 45
M. RPM 1900 2500 3200
γ
η

Air Volume Q = 14760 m3/h

Outlet Velocity V = 10.07 m/s

Dynamic Pressure Pd = 62 Pa

Total Pressure Pt = 1515 Pa

Fan Speed N = 1900 rpm

Absorbed Power W = 8 kW

Total Efficiency η = 78 %

Sound Power Level Lw(A) = 90.3 dB(A)

- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not include the effects
of appurtenances (accessories). Power rating kW does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA standard 301. Values shown are for inlet Lwi(A)
sound power levels for installation type B - free inlet, ducted outlet. Ratings do not include the effect of duct end corrections.

8
BDB ‘C’
‘C’
BDB 315-400 ‘C’
B
L
G
M = E = M
R

=
C
D

Ød-g6

F
A

uxs

=
= F = J
P H K

d
Model A B C D E F G H J K L M P R uxs
CL CM

315 578 518 340 404 404 330 236 480 434 464 600 68 38 3 25 25 13x18

355 654 578 383 452 452 368 260 548 492 532 672 70 30 6 30 30 13x18

400 736 650 432 506 506 402 290 612 546 586 726 70 38 5 30 30 13x18
All Dimensions in mm.

BDB 450-710 ‘C’

B
L
G
M = E = M
R

=
C

F
D

Ød-g6
F1
A

uxs
F=

= F F1 F = J
P H K

d
Model A B C D E F F1 G H J K L M P R uxs
CL CM

450 827 726 486 568 568 200 111 322 681 608 648 814 83 45 5 35 35 13x18

500 918 800 538 638 638 245 120 352 750 678 718 924 103 50 5 35 35 13x18

560 1030 892 603 714 714 280 125 390 844 764 814 1000 93 48 7 40 40 13x18

630 1157 998 679 800 800 328 110 434 945 850 900 1092 96 53 6 40 45 13x18

710 1302 1120 765 898 898 360 150 484 1057 948 998 1234 118 63 7 50 50 17x22
All Dimensions in mm.

27
OVERALL DIMENSION – BDB “C” SERIES

CW 90° (Pos Z) CW 270° (Pos W) CW 360° (Pos W) CW 360° (Pos Z)

C C2
C C1

H
W L L W L W W L

CCW 90° (Pos W) CCW 270° (Pos Z) CCW 360° (Pos W) CCW 360° (Pos Z)

C C1 C2
C

H
H

H
L W W L L W W L

Motor 90°/ 270° 360°


Model Frame C C * Wt * Wt
Size L W H C1 C2 L W H
(90°) (270°) (kg) (kg)
315 71 460 500 780 630 618 33 534 433 880 630 558 34
80 488 524 820 630 618 33 561 459 920 630 558 34
90 515 547 860 630 618 34 587 484 960 630 558 34
100 542 571 900 630 618 34 614 509 1000 630 558 34
112 568 594 940 630 618 34 638 533 1040 630 558 35
132 625 645 1020 630 618 35 694 587 1120 630 558 35
355 71 496 547 840 702 694 48 593 479 960 702 618 49
80 523 570 880 702 694 48 601 485 980 702 618 49
90 549 592 920 702 694 48 626 509 1020 702 618 49
100 576 615 960 702 694 49 652 534 1060 702 618 49
112 620 654 1020 702 694 49 695 575 1120 702 618 49
132 676 704 1100 702 694 49 749 628 1200 702 618 50
400 71 561 621 920 756 776 53 651 527 1040 756 690 53
80 569 626 940 756 776 53 677 550 1080 756 690 53
90 595 647 980 756 776 53 702 573 1120 756 690 54
100 621 669 1020 756 776 53 727 597 1160 756 690 54
112 664 708 1080 756 776 53 750 619 1200 756 690 54
132 719 756 1160 756 776 54 823 689 1300 756 690 55
160 776 806 1250 756 776 54 888 752 1400 756 690 55
450 80 633 701 1020 844 867 70 733 593 1160 844 766 71
90 658 722 1060 844 867 71 757 615 1200 844 766 71
100 684 743 1100 844 867 71 791 647 1250 844 766 72
112 707 763 1140 844 867 71 824 678 1300 844 766 72
132 741 790 1200 844 867 71 846 699 1350 844 766 72
160 856 894 1350 844 867 72 909 759 1450 844 766 73
500 80 661 740 1080 954 968 95 779 629 1250 954 850 97
90 686 760 1120 954 968 96 812 659 1300 954 850 97
100 711 780 1160 954 968 96 845 691 1350 954 850 97
112 734 799 1200 954 968 96 877 720 1400 954 850 98
132 805 861 1300 954 968 97 899 740 1450 954 850 98
160 870 917 1400 954 968 98 961 799 1550 954 850 99
560 90 739 830 1200 1030 1080 126 884 714 1400 1030 942 127
100 773 858 1250 1030 1080 126 916 744 1450 1030 942 128
112 804 884 1300 1030 1080 127 947 773 1500 1030 942 128
132 875 945 1400 1030 1080 127 968 792 1550 1030 942 129
160 938 998 1500 1030 1080 128 1076 895 1700 1030 942 130
180 1012 1064 1600 1030 1080 129 1100 917 1750 1030 942 130
630 90 816 923 1300 1122 1207 158 998 811 1550 1122 1048 160
100 848 950 1350 1122 1207 159 1031 840 1600 1122 1048 161
112 879 975 1400 1122 1207 159 1061 868 1650 1122 1048 161
132 948 1034 1500 1122 1207 160 1082 886 1700 1122 1048 162
160 1010 1085 1600 1122 1207 161 1140 940 1800 1122 1048 162
180 1082 1149 1700 1122 1207 162 1211 1008 1900 1122 1048 163
710 90 907 1028 1450 1264 1382 229 1080 868 1700 1264 1200 232
100 941 1055 1500 1264 1382 230 1112 897 1750 1264 1200 233
112 972 1080 1550 1264 1382 230 1142 924 1800 1264 1200 233
132 993 1095 1600 1264 1382 231 1162 941 1850 1264 1200 234
160 1054 1144 1700 1264 1382 232 1220 994 1950 1264 1200 235
180 1126 1207 1800 1264 1382 233 1290 1061 2050 1264 1200 236
200 1199 1272 1900 1264 1382 235 1313 1082 2100 1264 1200 237
* The above weight does not include motor and drive unit as these will vary with supplier. All Dimensions in mm.

38
Kruger Ventilation Industries Pte Ltd
A member of
No. 17 Tuas Avenue 10 Singapore 639141
Tel. +65 68611577 - Fax +65 68613577
Website: www.krugerfan.com
CNo. - CAT008.E3 November 2011