Harmonics Estimator Report

Industrial Edition

Date: 7/4/2024 Page: 1

To: Sr. Jones Prepared by:


Gerente

Project: Eficiencia

Linear: 0 HP

Non-Linear: 100 HP
Common Service Transformer

Utility: CEMIG
Source Data I
Source Frequency (Hz) Rating (kVA) Impedance Z (%) Sec. Voltage (V) Isc (A)
Utility XFMR 60 50,000 8.00 13,800 26,148
Service XFMR 60 600 5.75 230 26,194
Source Data II
Source Rated Amps, rms (A) Amps Fundamental (A) Amps Harmonics (A) Total Amps (A)
Utility XFMR 2,092 3.8 0.1 3.9
Service XFMR 1,506 230.9 6.9 231.0
Harmonic Summary
Location Current TDD (%) Voltage THD (%) Isc/Load Transformer Load (%)
PCC2 3.0 0.4 113.4 15.5

IEEE-519 (2014) limits for specified system based on Isc/IL: PCC: Voltage THD: 8.0 %, Current TDD: 15.0 %

Project Compliance at PCC


IEEE-519 (2014): Yes
PCC Location: Common Service Transformer Secondary Side (PCC2)

The results of this estimation may not represent the actual installed system due to insufficient system data and / or limits of the estimating software.
Yaskawa America, Inc. assumes no responsibility for the accuracy of the supplied data or of this report.

Yaskawa Harmonics Estimator (Industrial Edition) Page 1 of 4


Total System Graphs at PCC
Chart(s)

The results of this estimation may not represent the actual installed system due to insufficient system data and / or limits of the estimating software.
Yaskawa America, Inc. assumes no responsibility for the accuracy of the supplied data or of this report.

Yaskawa Harmonics Estimator (Industrial Edition) Page 2 of 4


Load System: 001
System Data
System Identification:
Type: Matrix System
Total Motor Power: 100.0HP (4 x 25.0HP)
Motor Efficiency: 0.88
Model/Catalog #: CIMR-UU2A0068***

Source Data
Source Rated Amps, rms (A) Amps Fundamental (A) Amps Harmonics (A) Total Amps (A)
Utility XFMR 2,092 3.8 0.1 3.9
Service XFMR 1,506 230.9 6.9 231.0

Harmonic Summary (With all other systems removed)


Location Current TDD (%) Voltage THD (%)
Drive 3.0 0.4

The results of this estimation may not represent the actual installed system due to insufficient system data and / or limits of the estimating software.
Yaskawa America, Inc. assumes no responsibility for the accuracy of the supplied data or of this report.

Yaskawa Harmonics Estimator (Industrial Edition) Page 3 of 4


Chart(s)

The results of this estimation may not represent the actual installed system due to insufficient system data and / or limits of the estimating software.
Yaskawa America, Inc. assumes no responsibility for the accuracy of the supplied data or of this report.

Yaskawa Harmonics Estimator (Industrial Edition) Page 4 of 4