Project: Eficiencia
Linear: 0 HP
Non-Linear: 100 HP
Common Service Transformer
Utility: CEMIG
Source Data I
Source Frequency (Hz) Rating (kVA) Impedance Z (%) Sec. Voltage (V) Isc (A)
Utility XFMR 60 50,000 8.00 13,800 26,148
Service XFMR 60 600 5.75 230 26,194
Source Data II
Source Rated Amps, rms (A) Amps Fundamental (A) Amps Harmonics (A) Total Amps (A)
Utility XFMR 2,092 3.8 1.5 4.1
Service XFMR 1,506 230.9 87.2 246.8
Harmonic Summary
Location Current TDD (%) Voltage THD (%) Isc/Load Transformer Load (%)
PCC2 37.7 2.6 113.4 20.4
IEEE-519 (2014) limits for specified system based on Isc/IL: PCC: Voltage THD: 8.0 %, Current TDD: 15.0 %
The results of this estimation may not represent the actual installed system due to insufficient system data and / or limits of the estimating software.
Yaskawa America, Inc. assumes no responsibility for the accuracy of the supplied data or of this report.
The results of this estimation may not represent the actual installed system due to insufficient system data and / or limits of the estimating software.
Yaskawa America, Inc. assumes no responsibility for the accuracy of the supplied data or of this report.
Source Data
Source Rated Amps, rms (A) Amps Fundamental (A) Amps Harmonics (A) Total Amps (A)
Utility XFMR 2,092 3.8 1.5 4.1
Service XFMR 1,506 230.9 87.2 246.8
The results of this estimation may not represent the actual installed system due to insufficient system data and / or limits of the estimating software.
Yaskawa America, Inc. assumes no responsibility for the accuracy of the supplied data or of this report.
The results of this estimation may not represent the actual installed system due to insufficient system data and / or limits of the estimating software.
Yaskawa America, Inc. assumes no responsibility for the accuracy of the supplied data or of this report.