Professional Documents
Culture Documents
2130165_08
2130165_08
OBJECTIVES: To find the voltages at primary and secondary side of a single phase transformer.
THEORY:
The voltage transformation ratio of a single phase transformer is given by the ratio of
the voltage at the secondary side & voltage primary side.
MACHINE SPECIFICATION:
Transformer:1KVA, 1-Φ, 50Hz, 230 / 115 volts
EQUIPMENTS REQUIRED:
Sl. No. Name of the Apparatus Type Range Quantity
CIRCUIT DIAGRAM(offline):
CIRCUIT DIAGRAM(Online):
DESCRIPTION:
A transformer is a static device which transfers electrical energy from one circuit to another
through the process of electromagnetic induction at constant frequency. It is most commonly
used to increase (‘step up’) or decrease (‘step down’) voltage levels between circuits.
The working principle of a transformer is very simple. Mutual induction between two or
more windings (also known as coils) allows for electrical energy to be transferred between
circuits.
PROCEDURE(offline):
a. Connect the circuit as shown in the circuit diagram.
b. AC supply is given to primary side of Transformer (V1) via 1-phase variac at no load.
c. By varying primary voltage note down the readings of primary and secondary
voltages.
OBSERVATION TABLE
PRECAUTION:
a. All connections should be tight.
b. The meter should be of proper range.
c. Before connecting the meters in the circuit check their zero position.
d. AC supply should be provided to primary side.
CONCLUSION : The voltage transformation ratio of the single phase transformer is found
________ and it is of __________ type transformer.
DISCUSSION QUESTIONS:
OBJECTIVES: Measure the amount of current drawn and power consumed by a no load
transformer.
THEORY
As we know that when the transformer is at no load, the no load current or primary
current is very small, typically 3 to 5 percent of the rated current value. Thus, the copper loss
in the primary winding is negligible. In OC test, transformer is operated at rated voltage at
rated frequency so the maximum will be the flux in the core. The iron loss (hysteresis and
eddy current loss) of the transformer depends on the flux. As iron loss is a function of applied
voltage, the iron loss is maximum at rated voltage. Since the iron or core losses are at rated
voltage, the power input is drawn to supply the iron losses by the transformer under no load.
The no-load current is very small and because the copper loss in the primary is proportional
to the square of this current, it is negligible. There is no copper loss in the secondary because
there is no secondary current.
MACHINE SPECIFICATION:
Transformer:1kVA, 1-Φ, 50Hz, 230 / 115 volts
EQUIPMENTS REQUIRED:
CIRCUIT DIAGRAM(online):
PROCEDURE
OBSERVATION TABLE(Online):
CALCULATION:
Io = No load current.
V = rated applied voltage
W = wattmeter reading = power input to transformer at no load = core loss = V. Io.cosφ
watts.
DISCUSSION QUESTIONS: