Painel de Média Tensão


Tipo SIMOPRIME, até 17.5 kV, Isolado a Ar
Soluções em Média Tensão · Catalogo HA 26.11 · 2017

Answers for infrastructure and cities.


Technical Data
Ratings

Electrical data (maximum values) of SIMOPRIME


Ratings Rated values Ratings Rated values
(max.) (max.)

Switchgear up to 7.2 kV Switchgear 15kV


Rated voltage 7.2kV Rated voltage 15kV
Rated frequency 50/60Hz Rated frequency 50/60Hz
Rated short-duration power-frequency withstandvoltage 20 kV 1) Rated short-duration power-frequency withstandvoltage 35kV
Rated lightning impulse withstand voltage 60 kV Rated lightning impulse withstand voltage 95 kV
Rated short-time withstand current, 3 s 40 kA Rated short-time withstand current, 3 s 40 kA
Rated peak withstand current at 50/60 Hz 100/104 kA Rated peak withstand current at 50/60 Hz 100/104 kA
Rated short-circuit breaking current 40 kA Rated short-circuit breaking current 40 kA
Rated short-circuit making current at 50/60 Hz 100/104 kA Rated short-circuit making current at 50/60 Hz 100/104 kA
Rated normal current of busbar 3600A Rated normal current of busbar 3600A
Rated normal current of feeders Rated normal current of feeders
– with circuit-breaker 3600A – with circuit-breaker 3600A
– with vacuum contactor 400 A 2)

Switchgear 12kV Switchgear 17.5kV


Rated voltage 12kV Rated voltage 17.5kV
Rated frequency 50/60Hz Rated frequency 50/60Hz
Rated short-duration power-frequency withstandvoltage 28 kV 1) Rated short-duration power-frequency withstandvoltage 38kV
Rated lightning impulse withstand voltage 75 kV 3) Rated lightning impulse withstand voltage 95 kV
Rated short-time withstand current, 3 s 40 kA Rated short-time withstand current, 3 s 40 kA
Rated peak withstand current at 50/60 Hz 100/104 kA Rated peak withstand current at 50/60 Hz 100/104 kA
Rated short-circuit breaking current 40 kA Rated short-circuit breaking current 40 kA
Rated short-circuit making current at 50/60 Hz 100/104 kA Rated short-circuit making current at 50/60 Hz 100/104 kA
Rated normal current of busbar 3600A Rated normal current of busbar 3600A
Rated normal current of feeders Rated normal current of feeders
– with circuit-breaker 3600A – with circuit-breaker 3600A
– with vacuum contactor 400 A 2)

1) Option: Higher values


acc. to GOST standards
2) Depending on the rated current
of the HV HRC fuses installed
3) 60 kV for vacuum contactor

4 Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kV, Air-Insulated · Siemens HA 26.11 · 2014
Technical Data
Classification, dimensions, room planning

Classification of the SIMOPRIME switchgear according toIEC 62271-200


Internal arcclassification Construction and design
Classification IAC Partition class PM (metallic partition)
Accessibility Loss of service continuity category LSC2B (metal-clad)
– Front TypeA Compartment accessibility (standard)
– Rear TypeA – Busbar compartment Tool-based
– Lateral TypeA – Switching-device compartment Interlock-controlled
Testcurrent kA 25/31.5/40 – Low-voltage compartment Tool-based
Arc duration s 0.1/1.0 – Connection compartment
– Front connection Interlock-controlled and
tool-based
– Rear connection Tool-based

Dimensions Room planning (room height W2800mm)

Front connection

?10
0
HA26-2024d

HA26-2025a
eps

eps
B B

T
40 40
H
2
H1

1500
?100 Front ?100

1)
H
3

Single-row arrangement (plan view)


For dimensions B (width) and T (depth) refer to table on this page
1)Control aisle widths
w 31.5 kA and w 3150 A versions: W1500 mm
40 kA or 3600 A versions: W1700 mm
B T For panel replacement: W2000 mm

Dimensions
All paneltypes in mm Rear connection
Width B upto
HA26-2026a

Circuit-breakerpanel 31.5kA 40kA

?80
w 1250 A 600 800

0
eps

2500 A, 3150 A, 3600 A 800 800


Contactor panel 435 2)/600 435 2)
B B
Disconnecting panel
T

w 1250 A 600 800


2500 A, 3150 A, 3600 A 800 800
Bus sectionalizer/circuit-breaker
panel w 1250 A 600 800
2500 A, 3150 A, 3600 A 800 800 40 40
1500

Bus sectionalizer/bus riserpanel ?500 ?500


Front
1)

w 2500 A 600 800


3150 A, 3600 A 800 800
Meteringpanel 600 800
Single-row arrangement (plan view)
Height H1 With standard low-voltage For dimensions B (width) and T (depth) refer to table on this page
compartment and IAC 0.1 s 2253 2253
1)Control aisle widths
H2 With standard low-voltage
compartment and IAC 1.0 s 2425 2460 w 31.5 kA and w 3150 A versions: W1500 mm
40 kA or 3600 A versions: W1700 mm
H3 – 1780 1780 For panel replacement: W2000 mm
Depth T Standard 1860 1860

2) Can be ordered as of the year 2009

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kV, Air-Insulated · Siemens HA 26.11 · 2014 5
Product Range
Panels

Circuit-breaker panel Disconnecting panel Vacuum cantactor panel


HA26-2016a

and/or or and/or or and/or


eps

or

and/or or and/or or and/or

and/or or and/or or and/or

HA26-2019b
eps
or and/or or and/or

and/or and/or
HA26-2017a
eps

Components

Current transformer Vacuum contactor Vacuum circuit-breaker 1) The details refer to con-
with HV HRC fuses ventional single-core
sealing ends.

Voltage transformer Vacuum contactor Disconnector


without primary fuses with control transformer
and HV HRC fuses

Current transformer Make-proof HV HRCfuse


in run of busbar earthing switch

Voltage transformer Cable sealing ends 1)


with primary fuses max. 4 x 500 mm 2
per phase

Capacitive voltage Barconnection


detecting system
HA26-2020d
eps

6 Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kV, Air-Insulated · Siemens HA 26.11 · 2014
Product Range
Panels

Bus sectionalizer (mirror-image installation also possible) Metering panel

Circuit- Busriser
breaker panel
panel
HA26-2021
eps

or or

or

and/or

HA26-2022a
eps
Components

Current transformer Withdrawable Make-proof


voltage transformer earthing switch
with primary fuses

Voltage transformer Capacitive voltage Vacuum circuit-breaker


without primary fuses detecting system

Current transformer
in run of busbar
HA26-2023a
eps

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kV, Air-Insulated · Siemens HA 26.11 · 2014 7
Contents Application
Benefits, typical uses

Application Page Benefits (see also page 10 for details)


Benefits 2
• Saves lives
Typical uses 2and 3
• Peace of mind
Technical Data
• Increases productivity
Ratings 4
Classification, dimensions, • Saves money
room planning 5

Product Range
Panels 6and 7 The circuit-breaker switchgear type
SIMOPRIME is a factory-assembled,
Design
type-tested switchgear for indoor
Panel design 8 installation according to
Compartments, interlocks, IEC 62271-200 and VDE 0671-200.
operation 9 Loss of service continuity
Benefits and features 10 category: LSC 2B
Standards Partition class: PM
Standards, specifications, Internal arc
guidelines 11and 12 classification: IAC AFLR,
Isc w 40 kA,
Comments arc duration: 1 or 0.1 s
13

Supersedes: Catalog HA 26.11 · 2008

010c.eps
R-HA26-

SIMOPRIMEpanel
Maximum ratings 17.5 kV /40 kA /3600 A

Typical uses
The SIMOPRIME circuit-breaker switchgear can be used in transformer
and switching substations, e.g.:

Application: Power supply system ■ Chemical industry


■ Power supply companies ■ Petroleum industry
Application: Industry ■ Pipeline installations
■Power stations ■ Offshore installations
■Cement industry ■ Electrochemical plants
■Automobile industry ■ Petrochemical plants
■Iron and steel works ■ Shipbuilding industry
The products and systems described in this catalog
are manufactured and sold according to a certified ■Rolling mills ■ Diesel power plants
quality and environmental managementsystem
(acc. to ISO 9001 and ISO 14001). ■Mining industry ■ Emergency power supply
(DQS Certificate Reg. No. DQS 003473 QM UM).
The certificate is accepted in all IQNet countries.
■Textile, paper and food installations
industries ■ Lignite open-cast mines
■Traction power supplies
Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kV, Air-Insulated · Siemens HA 26.11 · 2014
2
Design
Panel design

Legend for panel design:


1 Door oflow-voltage Basic panel design (example)
compartment
2 Opening for locking or un- Circuit-breaker panel

HA26-2115

HA26-2116a
locking the low-voltage 12 kV, 1250 A, 40 kA
compartment door 1

eps

eps
3 Option: Capacitive voltage
detecting system forfeeder 2 E
and busbar 13
4 High-voltage door 3 B
5 Inspection window for 14
checking the switching- 4
device truck 15
5 22
6 Opening for locking or
unlocking the high-voltage 6 16
door
7 23
7 Opening for mechanical
chargingof circuit-breaker 8
A
closing spring
9 17
8 Openings for manual 24
operation (ON/OFF) ofthe 1O
18
circuit-breaker
C
9 Inspection window for
reading theindicators D
10 Door handle 11
11 Openings for switching- 12 19
device truckoperation
12 Opening forearthing-switch 2O
operation
13 Pressure reliefduct 21
14 Busbars
15 Bushings
16 Postinsulators
17 Block-type current
transformer
18 Option: Make-proofearthing
switch
19 Cable sealing ends
20 Option: Voltage transformer
21 Earthingbusbar
22 Low-voltage plug connector
23 Vacuuminterrupters
24 Switching-device truck

A Switching-device
compartment
B.Busbar compartment
C.Connection compartment D
Vacuum circuit-breaker truck E
Low-voltage compartment

8 Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kV, Air-Insulated · Siemens HA 26.11 · 2014
Design
Compartments, interlocks,operation

Switching-device Connection compartment Interlocks Low-voltage compartment


compartment • Pressure relief upwards • Interlocking conditions • For accommodation of all
• All switching operations with through rear pressure relief are satisfied according to protection, control, measur-
high-voltage door closed duct IEC 62271-200 / ing and metering equipment
• Suitable for connection of VDE 0671-200
• Pressure relief upwards • Partitioned safe-to-touch
– Single-core XLPE cables up to • Earthing switch can only be from the high-voltage part
• Panel powder-coated with
max. 6 x 500 mm 2 per phase operated with circuit-breaker
epoxyresin • Low-voltage compartment
– Three-core XLPE cables up to truck in testposition
• Shutter operating mecha- can be removed, bus wires
nisms separately for max. 3 x 300 mm 2 per panel • Circuit-breaker truck can only and control cables are
– Busbar compartment – Bars made of flat copper with be moved with circuit-breaker plugged in
– Connection compartment bushings in a floor cover or “OPEN” and earthing switch
fully-insulated bars including • Option: Partition between
• Metallic, earthed shutters “OPEN”
floor cover panels
and partitions ensure parti- • Mechanical coding on the
• Shutters to be opened sepa-
Low-voltage cables
tion class PM circuit-breaker truck prevents
rately to permit cable testing insertion of similar circuit- • Control cables of the panel
• High-voltage door pressure-
• Earthing busbar breaker trucks for lower rated are flexible and have metallic
resistant in the event of
normal currents into panels covers
internal arcs in the panel • Connection from front or rear
with higher rated normal cur- • Connection of switching-
• Metallic ducts on the side for • Option: Pressure-resistant rents device truck and panel wiring
laying control cables floor cover
• Interlocking of high-voltage to low-voltage compartment
• Interlocking between • Use of block-type current via 64-pole coded plug con-
door against circuit-breaker
high-voltage door and transformers truck nectors
circuit-breaker truck ensures
• Bolted rear covers of the • The high-voltage door can • Bus wires are pluggable from
interlock-based access
connection compartment only be opened when the panel topanel
• Option: Test sockets for provide tool-based access circuit-breaker truck is in test
capacitive voltage detecting for panels with connection position
system from rear
• Option: Electromagnetic
• Switching-device compart- • Interlocked high-voltage door interlocks
ment to accommodate com- and bolted partitions be-
ponents for implementing tween connection compart-
various panel versions with ment and switching-device
– Vacuum circuit-breaker with compartment provide inter-
or without voltage trans- lock-based and tool-based
formers on the truck access for panels with con-
– Disconnector truck nection from
Components atfront
the panel
– Vacuum-contactor truck connection (option)
– Metering truck
Busbar compartment • Coupling electrode for
• Pressure relief upwards capacitive voltage detecting
and through rearpressure system
relief duct • Voltage transformers
– Cast-resin insulated
• Option: Busbar transverse
– Max. 3 x 1-pole
partition between panels
– Fixed-mounted, without
• Busbars made of flatcopper, primary fuses
bolted from panel to panel • Make-proof earthing switches
– For rated normal currents – With manual operating
up to 3600A mechanism
– Option: Insulated busbars – In addition to standard inter-
• Bolted rear and topcovers locking of earthing switch/
provide tool-based access circuit-breaker truck,
optionally lockable or with
• Option: Coupling electrode
electromagnetic interlock
for capacitive voltage
detecting system • Surge arresters or limiters
– Surge arresters for protecting
• Options: Possibility of install-
the switchgear against exter-
ing the following compo-
nal overvoltages
nents
– Surge limiters for protecting
– Voltage transformers
consumers against switching
– Busbar earthing switch
overvoltages
– Current transformers in the
run of busbars

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kV, Air-Insulated · Siemens HA 26.11 · 2014 9
Design
Benefits andfeatures

Benefits Features

• Saveslives • All switching operations including emergency manual operations


with high-voltage door closed
• Interlocking between high-voltage door and switching devices
• Rack-in, rack-out operations of the circuit-breaker truck with high-voltage door closed
• Metallic, earthed shutters and partitions, partition class: PM (metallic partition)
• Internal arc tested design up to 40 kA, 1 s, according to IEC 62271-200, VDE 0671-200
• Use of vacuum circuit-breakers
• Peace of mind • Factory-assembled, type-tested switchgear according to IEC 62271-200
• Type testing of the circuit-breaker inside thepanel
• Use of standard, world-wide available components
• Use of maintenance-free vacuum circuit-breakers
• Quality management according to DIN EN ISO 9001
• Design based on global best practice sharing and experience
• More than 300,000 air-insulated switchgear panels from Siemens in operation world-wide
• Increases productivity • Use of metallic, earthed shutters and partitions between the compartments ensures highest loss of
service continuity of the switchgear (LSC2B according to IEC 62271-200) during maintenance
• Use of maintenance-free vacuum circuit-breakers
• Savesmoney • Use of maintenance-free vacuum circuit-breakers

10 Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kV, Air-Insulated · Siemens HA 26.11 · 2014
Standards
Standards, specifications, guidelines

Standards Overview of standards (October 2008)


The switchgear complies with IECstandard VDEstandard ENstandard
the relevant standards and
Switchgear SIMOPRIME IEC 62271-1 VDE0671-1 EN 62271-1
specifications applicable at
the time of typetests. IEC62271-200 VDE0671-200 EN62271-200
Devices Circuit-breaker IEC62271-100 VDE0671-100 EN62271-100
In accordance with the Vacuum contactor IEC60470 VDE0670-501 EN60470
harmonization agreement Disconnector and IEC62271-102 VDE0671-102 EN62271-102
reached by the EUcountries, earthing switch
their national specifications HV HRCfuses IEC60282 VDE0670-4 EN60282
conform to the IEC standard. Voltage detecting IEC 61243-5 VDE0682-415 EN 61243-5
systems
Degree of – IEC60529 VDE0470-1 EN60529
protection
Insulation – IEC60071 VDE0111 EN60071
Instrument Current transformer IEC 60044-1 VDE0414-1 EN 60044-1
transformers Voltage transformer IEC 60044-2 VDE0414-2 EN 60044-2
Installation – IEC 61936-1 VDE0101 –

Type ofservice location Table –Dielectric strength Dielectric strength


The switchgear can be used Rated voltage (rms value) kV 7.2 12 15 17.5 • The dielectric strength is veri-
for indoor installation in fied by testing the switchgear
accordance with IEC 61936 Rated short-duration power-frequency withstand voltage (rms value) with rated values of short-
(Power installations exceeding – Across isolating distances kV 23 32 39 45 duration power-frequency
1 kV AC) and VDE 0101 – Between phases and to earth kV 20 28 35 38 withstand voltage and light-
• Outside lockable electrical
ning impulse withstand volt-
Rated lightning impulse withstand voltage (peak value) age according to IEC 62271-1 /
service locations at places – Across isolating distances kV 70 85 105 110
which are not accessible to VDE 0671-1 (see table
– Between phases and to earth kV 60 75 95 95 “Dielectric strength”).
the public. Enclosures of
switchgear can only be • The rated values are referred
removed with tools. Altitude correction factorKa to sea level and to normal
• Inside lockable electrical For site altitudes Ka atmospheric conditions
above 1000 m, the 1.50 (1013 hPa, 20 °C, 11 g/m3
service locations. A lockable
HA40-2037a en

altitude correction A m= 1 humidity in accordance with


electrical service location is
Altitude correction factor

a place outdoors or indoors


factor Ka is recom- 1.40 IEC 60071 /VDE 0111).
mended, depend-
eps

that is reserved exclusively • The dielectric strength


ing on the actual
for housing electrical equip- site altitude above 1.30 decreases with increasing
ment and which is kept un- sealevel. altitude.
der lock and key. Access is 1.20
For site altitudes above
restricted to authorized per- 1000 m (above sea level)
sonnel and persons who the standards do not provide
have been properly instruc- 1.10 any guidelines for the insula-
ted in electrical engineering. tion rating. Instead, special
Untrained or unskilled per- 1.00 arrangements apply to these
1000 1500 2000 2500 3000 3500
sons may only enterunder 4000 altitudes.
the supervision of authorized Site altitude in m above sea level • Site altitude
personnel or properly in- – As the altitude increases, the
structed persons. dielectric strength in air de-
Rated short-dur. power-freq. withstand volt. tobe selected for site altitudes > 1000 m
WRated short-duration power-frequency withstand voltage up to w 1000 m · Ka creases due to the decreasing
air density. This reduction is
Rated lightning impulse withstand volt. to be selected for site altitudes > 1000 m permitted up to a sitealtitude
W Rated lightning impulse withstand voltage up to w 1000 m · Ka of 1000 m according to IEC
and VDE.
– For site altitudes above 1000
Example: Result:
m, a higher insulation level
1800 m site altitude above sea level According to the above
table, a switchgear fora
must be selected. It results
12 kV switchgear rated voltage
rated voltage of 17.5 kV from the multipli- cation of
75 kV rated lightning impulse withstand voltage
is to beselected. the ratedinsulation
Rated lightning impulse withstand level for 0 to 1000 m with the
voltage to be selected 75 kV · 1.10 = 82.5 kV altitude correction factor Ka.

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kV, Air-Insulated · Siemens HA 26.11 · 2014 11
Standards
Standards, specifications, guidelines

Terms Current-carrying capacity Protection against solid


“Make-proof earthing switches” • According to IEC 62271-1/ foreign bodies, electric shock
are earthing switches with VDE 0671-1and and ingress ofwater
short-circuit making capacity IEC 62271-200 / SIMOPRIME switchgear fulfills
according to VDE 0671-200 current- acc. to the standards
– IEC 62271-102and carrying capacities referto – IEC62271-200
– VDE 0671-102/ the following ambient air – IEC60529
EN 62271-102 temperatures: – VDE0470-1
– Maximumof – VDE0671-200
Internal arcclassification 24-hour mean + 35 °C
– Maximum + 40 °C the following degrees of pro-
• Protection of operating per- tection:
sonnel by means of tests for • The current-carrying capacity – Enclosure:
verifying the internal arc of the panels and busbars IP 4X, IP 5X (protection
classification depends on the ambient air against solid foreign bodies)
temperature outside the IP X1, IP X2 (protection
• Internal arcing tests must be
enclosure. against ingress ofwater)
performed in accordance with
IEC 62271-200/ • To attain the maximum rated – Compartments:
VDE 0671-200 normal currents, the panels IP 2X (protection against
are provided with natural or solid foreign bodies)
• The switchgear complies with
criteria 1 to 5 specified in the forced ventilation. Higher degree of protection for
mentioned standards for the Climate and environmental enclosure on request.
basic version up to 40 kA. influences
• Definitions of the criteria: The switchgear may be used,
– Criterion1 subject to possible additional
Correctly secured doors and measures, under the following
covers do not are
deformations open.Limited
accepted. environmental influences and
– Criterion2 climate classes:
No fragmentation of the Environmental influences
enclosure. Projection of small – Natural foreign materials
parts up to an individual mass – Chemically active pollutants
of 60 g are accepted. – Small animals
– Criterion3
Climate classes
Arcing does not cause holes
– 3K3
in the accessible sides up to
– 3K5
a height of 2 m.
– Criterion4 The climate classes are
Horizontal and vertical classified according to
indicators do no ignite due IEC60721-3-3.
to the effect of hot gases.
– Criterion5
The enclosure remains
connected to its earthing
point.

12 Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kV, Air-Insulated · Siemens HA 26.11 · 2014
Application
Typicaluses

R-HA25-326
Application
Industry
eps
R-HA25-308
eps

R-HA26-012.tif

Application
Public power
R-HA25-327

supply system
eps

SIMOPRIMEswitchgear

Application
Industry

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kV, Air-Insulated · Siemens HA 26.11 · 2014 3
Published by and copyright © 2014:
Siemens AG
Wittelsbacherplatz 2
80333 Munich, Germany

Siemens AG
Infrastructure & Cities Sector
Low and Medium Voltage Division
Medium Voltage
Postfach 3240
91050 Erlangen, Germany
www.siemens.com/medium-voltage-switchgear

All rights reserved.


If not stated otherwise on the individual pages of this
catalog, we reserve the right to include modifications,
especially regarding the stated values,
dimensions and weights.

Drawings are not binding.


All product designations used are trademarks or product
names of Siemens AG or other suppliers.
If not stated otherwise, all dimensions in this
catalog are given in mm.

Subject to change without prior notice.


The information in this document contains general
descriptions of the technical options available, which
may not apply in all cases. The required technical
options should therefore be specified in the contract.

For more information, please contact our Sales


www.incoteq.com.br
Department

Phone: +55 11 3466 56 55


Mobile: +55 11 9 8578 08 71
(Charges depending on provider) E-mail:
eduardo.penteado@incoteq.com.br