Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

GOST

Devices
on V a C
at

nfigur

om ter
pu
Co
AC441 1
AC441 are 48 x 48 mm They are to
measure the temperature, pressure, speed, level, ,
current, voltage, and other as well
as the on / off and PID control of many process
are completely modular and
each module can be . It used
Device Features Food, Iron Steel, , Metallurgy, Cement,
Ceram c, Petro-Chem stry, Ref ner es, Glass and other
are whose
standards, and ease of use have
been ensured at the stage.
1 pcs T
T, mA, mV, V)
1 pcs Analog Output (0/4-20mA.0/2-10V)

Input Types
100-240V AC/DC Supply Voltage
Sensor Type Standard Min. Max.
Type-T ( Cu-Const ) IEC60584 -200 °C 300 °C
Type-U ( Cu-Const ) IEC60584 -200 °C 600 °C
Auto-T Type-J ( Fe-Const ) IEC60584 -200 °C 800 °C
Type-L ( Fe-Const ) IEC60584 -200 °C 900 °C
Bumpless Transfer Type-K ( NiCr-Ni ) IEC60584 -200 °C 1200 °C
Type-E ( Cr-Const ) IEC60584 -200 °C 1200 °C
alue) Type-N ( Nicrosil-Nisil ) IEC60584 0 °C 1200 °C
Type-S ( Pt%10Rh-Pt ) IEC60584 0 °C 1500 °C
ON/OFF, P, PI, PD, PID Controls Type-R ( Pt%13Rh-Pt ) IEC60584 0 °C 1600 °C
Type-B ( Pt%18Rh-Pt ) IEC60584 0 °C 1800 °C
Standard MODBUS R Pt-100 DIN 43760 -200 °C 850 °C
0 / 4-20 mA 0 mA 20 mA
0 / 2-10 VDC 0 VDC 10 VDC

Device Dimensions

10 mm
48 mm 108 mm
48 mm

44 mm

44 mm

44 mm

Panel Cutting Dimensions = 45 ± 0,5 mm x 45 ± 0,5 mm

37
T Modular Structure and Connection Diagram
Power Supply ( PS ) 100-240 Vac/dc +10%-15% NO/NC Contact NO Contact
24 Vac/dc +10%-20%
4W, 6VA
Thermocouple = B, E, J, K, L, N, R, S, T, U
Two Wired Transmitter = 4-20mA
( S1 )
Resistance Thermometer = Pt-100
Current = 0/4-20mA
Voltage = 0-50mV, 0/2-10V
T 24Vdc ( Isc= 30mA )
R3 O1 LU
Thermocouple, mV = 10MΩ
Analog Input Impedance Current = 10Ω
Voltage = 1MΩ
Analog Output Current = 0/4-20mA ( RL≥500Ω )
( O1 ) Voltage = 0/2-10V ( RL≥1MΩ )
1 Relay Output
( R1,R2 )
Contact = 250VAC 10A
Logic Output = 24Vdc 20mA
No Load = 10.000.000 Switching
250V,10A Resistive Load = 1.000.000 Switching Module Description
Memory 100 Years, 100.000 Renewals Universal sensor input module (the sensor used to measure
Accuracy +/- 0,2% S1 process value should be connected to the terminals with
appropriate symbol on this module).
100 ms
RS485 communication unit and Analog Output Module(The content
Working = -10...+55°C O1,LU of this module is determined by the product code, function is
emperature
Storage = -20...+65°C selected from the configuration page).
Front Panel = IP54 Trunk = IP20 Relay output modules (The content of this module is determined by
R1,R2
Width = 48 mm the product code, function is selected from the configuration page).
Height = 48 mm Supply voltage input
Depth = 110 mm PS (Supply voltage is determined by product code).

45 +/- 0,5 mm x 45 +/- 0,5 mm


W 154 gr

Product Code

AC441 - _ _ / _ 0 / _ _ _ 0

Power Supply : PS
0 = 100-240V
1 = 24Vac/dc
LU
0 = N/A
3 = RS485 (MODBUS)

Analog Output Module : O1


0 = N/A
1 = 0/4-20mA Current Output
2 = 0/2-10Vdc Voltage Output

R1 Output Module : R1
0 = N/A
1 = NO Contact

3 = NO/NC Contact

R2,R3 Output Modules : R2-R3


0 = N/A
1 = NO Contact

Only one of these modules can be selected.