Professional Documents
Culture Documents
GuideToSynchronisingAndLoadSharing
GuideToSynchronisingAndLoadSharing
E-mail: Sales@Deepseaplc.com
Any reference to trademarked product names used within this publication is owned by their
respective companies.
Deep Sea Electronics Plc reserve the right to change the contents of this document without prior
notice.
1 BIBLIOGRAPHY
1. Diesel generator handbook. L.L.J.Mahon. ISBN 0-7506-1147-2
2. On-Site Power Generation. EGSA Education Committee. ISBN 0-9625949-3-8
Section Page
1 BIBLIOGRAPHY .............................................................................................. 2
2 INTRODUCTION .............................................................................................. 6
3 STEP BY STEP GUIDE.................................................................................... 6
3.1 CLARIFICATION OF NOTATION AND TERMINOLOGY USED WITHIN THIS
PUBLICATION. ...............................................................................................................................7
4 55X SYNCHRONISING AND LOAD SHARING SOLUTIONS......................... 8
4.1 SINGLE SET NO BREAK RETURN WITH MAINS .............................................................8
4.2 BASE LOAD PEAK LOPPING / PEAK SHAVING..............................................................9
4.2.1 SINGLE SET .................................................................................................................9
4.3 MULTIPLE SET PRIME POWER.......................................................................................10
4.4 MULTIPLE SET STANDBY TO MAINS SUPPLY .............................................................11
5 GENERATOR USES ...................................................................................... 12
5.1 STANDBY GENERATORS................................................................................................12
5.1.1 TRANSFER SWITCH..................................................................................................12
5.1.2 NO BREAK TRANSFER .............................................................................................12
5.2 CONTINUOUS PARALLEL OPERATION.........................................................................13
5.3 BASE LOAD PEAK LOPPING WITH 555 CONTROLLER...............................................13
5.3.1 PEAK LOPPING..........................................................................................................14
6 MULTIPLE GENERATORS ........................................................................... 15
6.1 MUTIPLE SET PRIME POWER.........................................................................................15
6.2 MULTIPLE SETS PROVIDING STANDBY TO THE MAINS SUPPLY .............................15
6.2.1 LOAD-SWITCHING USING 530 ATS .........................................................................15
6.3 MULTIPLE SETS (STANDBY) – NO BREAK TRANSFER ..............................................16
7 LOAD SHARING ............................................................................................ 17
7.1 ACTIVE POWER SHARING ..............................................................................................17
7.2 REACTIVE POWER SHARING .........................................................................................17
8 THE NEED FOR SYNCHRONISING.............................................................. 18
9 METHODS OF ADJUSTING VOLTAGE & FREQUENCY............................. 19
9.1 REMOTE SPEED / VOLTAGE POTENTIOMETERS........................................................19
9.2 DC VOLTAGE INPUT ........................................................................................................19
9.3 RAISE / LOWER PUSH BUTTONS...................................................................................19
10 REQUIREMENTS FOR SYNCHRONISATION AND LOAD SHARING ...... 20
10.1 GOVERNOR AND GOVERNOR INTERFACE ..................................................................20
10.1.1 ISOCHRONOUS ACTIVE LOAD SHARING...............................................................20
10.1.2 DROOP ACTIVE LOAD SHARING.............................................................................20
10.2 GENERATOR AND AVR ...................................................................................................21
10.2.1 DROOP REACTIVE LOAD SHARING........................................................................21
10.2.2 AUTOMATIC REACTIVE LOAD CONTROL...............................................................21
10.3 55X CONTROLLER ...........................................................................................................22
10.3.1 FUNCTION COMPARISON CHART...........................................................................22
10.3.2 CONNECTION DETAILS ............................................................................................23
10.3.3 AUTOMATIC SYNCHRONISING................................................................................24
10.3.4 DROOP LOAD SHARING ...........................................................................................24
10.3.5 ISOCHRONOUS LOAD SHARING.............................................................................25
11 LOAD SWITCHING DEVICES .................................................................... 26
11.1 CHOOSING A LOAD SWITCHING DEVICE .....................................................................26
11.1.1 CONTACTORS ...........................................................................................................26
11.1.2 CHARGED SPRING BREAKERS...............................................................................26
2 INTRODUCTION
This manual is intended to provide a guide to panel designers for interfacing the 550 / 555
Synchronising / Load Sharing Controller to many of the most popular engine speed governors and
automatic voltage regulators.
A general overview of generator uses is given including synchronising. This is only to be treated as
a guide to newcomers to this particular subject, and should not be treated as a total learning
package.
Connection diagrams included within this manual are intended as a guide only, Engineers must be
familiar with the AVR / Governor being used, and should always refer to the respective
manufacturers instructions.
If your AVR / Governor is not covered within this manual, please contact our technical support
department for advice using the contact details below.
• Identify your base application. Applications supported by the DSE 55x controllers are detailed
in the section headed ‘55x synchronising and load sharing solutions’.
• Identify your governor and AVR interface methods. Details of this are contained in the sections
headed ‘Interfacing to governors’ and ‘interfacing to Automatic voltage regulators’.
• Design your panel and system wiring. DSE can assist with your specific questions on this but
cannot design your panel for you. If you want a panel designing, please contact DSE Technical
Support Department who may be able to recommend a third party panel designer / builder
capable of producing a synchronising / load sharing system.
• Check / adjust the 55x module’s configuration using P810 for Windows. If it is a MultiSet
system, ensure that the settings for MultiSet Comms Link are correctly configured and the
MultiSet comms cable is of the correct specification.
• Commission each set in the system as a single standalone set. Before doing this, ensure the
governor/AVR interface is disabled as detailed in the section entitled ‘On site commissioning’.
• Set up the governor and AVR as detailed in their respective manufacturers handbooks.
• Before synchronising sets for the first time, double check that all the Bus wiring is correct and
that the controllers initial settings are suitable. This may include lowering the settings for ‘gain’
and ‘stability’ in the synchronising, voltage matching and load control sections. Details of ways
to verify these are included in the section entitled ‘55x controller commissioning adjustments’.
Should you have any queries arising from this manual please contact our Technical
Department:
INTERNATIONAL TEL: +44 (0) 1723 890099
INTERNATIONAL FAX: +44 (0) 1723 893303
E-mail: support@deepseaplc.com
Web: http://www.deepseaplc.com
Governor :
Droop 9
Interface 55x Raise/lower relays,
method P122 digital resistance
AVR :
Droop 9
Interface 55x Raise/lower relays,
method P122 digital resistance
Load Share
• No load share available.
options :
As no load sharing capability exists, no control
is made over the reactive / active load share. In
applications of this type, this is not normally a
requirement.
However, if load sharing is required during this
Description
short-term parallel, a load sharing 555 module
can be used. This will provide the additional
function of load ramping (soft transfer) during
“mains available” transfers. (see ‘base load
peak lopping’ example below for details of this)
Governor :
Droop 8
Interface P120 analogue governor
method interface
AVR :
Droop 9
Interface P121 analogue AVR
method interface
Load Share • KW control.
options : • Var/pf control (P121 interface only)
The set will produce a fixed amount of power
and will therefore export power to the mains
supply (utility) if the load falls below the
configured load control level.
Two or more sets are used to provide power to the load, sharing power equally as a percentage of
the sets full load rating. Sets are automatically started and stopped depending upon load levels
allowing economic use of the available generators.
Governor :
Droop 8
Interface P120 analogue governor
method interface
AVR :
Droop 9
Interface None, P121 analogue AVR
method interface
Load Share
• Load share kW
options :
Full control of the kW load share is possible,
the sets equally sharing the kW load between
them pro rata (i.e. same percentage of their
rating).
No control of VAr load sharing is made as the
AVR droop kits help to eradicate circulating
Description
currents.
The AVRs must be correctly set to keep the
voltages of the sets as close together as
possible.
The P121 AVR interface can be used if voltage
matching is required.
Governor :
Droop 8
Interface P120 analogue governor
method interface
Droop 9
AVR : None , P121 analogue AVR
Interface
interface (if voltage matching
method
is required)
• Load share kW.
• kVAr load sharing is achieved by the AVR
Load Share
droop function. The 550 controller will
options :
make no changes to alternator excitation
when the supplies are in parallel.
A DSE 530 controller will monitor the mains
supply and signal the sets to start should the
supply fail.
All available sets will start and after
successfully paralleling with each other will
signal their availability to the 530 transfer
switch controller. The 530 will then transfer the
load to the generator bus.
The generators will then share power using
Description
their load sharing communications link, sets
being stopped / started depending upon load
demands.
Upon mains restoration, the 530 controller will
change the load back to the mains supply, then
instruct the generating sets that they are no
longer required.
See Appendix 1 for further details of this
application.
Illustration Description
5.1.1 TRANSFER SWITCH The most common form of backup generator to the mains
supply is a single generator in “standby” mode. When the
mains supply fails, the load is left without power until the
generator is started. Once the set is “available”, the
transfer switch changes over so that the load is supplied by
the generator.
Typically, the “down time” will be around 15 seconds, but
may be longer depending upon the time taken to run the
engine to nominal speed and other application dependent
factors. When the mains supply returns, the load-switching
device (contactors/breakers) will momentarily remove
power from the load (typically 1 second) before transferring
the load back to mains supply power.
5.1.2 NO BREAK TRANSFER The break in supply when transferring back to the mains
can be eradicated by synchronising the generator supply to
the returned mains supply, and closing the supplies in
parallel with each other for a short period of time. Then, the
generator load switch is opened, returning the mains to
supply power to the load. There has been no break in
supply to the load during this return transfer process.
Terms often used for this procedure are “bumpless
transfer”, “no break return” and “no break transfer”.
Additionally, the same procedure can be used to transfer
from mains supply to generator supply enabling, for
instance, “on load” testing of the genset with no break in
supply to the load. This can also be performed if the supply
authority informs customers of a scheduled break in
supply.
Illustration Description
GENSET SUPPLY. During the time of high load level a single
(or multiple) generator(s) could be started,
then used to power the load using a ‘no
break’ transfer. This genset supply must be
capable of supplying the entire load during
this time of high usage.
5.3 BASE LOAD PEAK LOPPING WITH In this example, a 555 load-sharing
555 CONTROLLER controller is being used in a base load
peak lopping system. The controller has
been configured to start the generating set
at 10am, synchronise with the mains and
parallel the supplies. It will then export a
fixed amount of power (kW) to the load and
maintain a specified power factor (both
configured using P810 for Windows
software).
Illustration Description
6.1 MUTIPLE SET PRIME In this example, the site has four generating sets, used as
POWER the primary power source.
One genset will be running all the time, to provide power to
the site. If the load demand of the site increases, one or
more generators will be automatically called to start. They
will then synchronise onto the bus, and provide power in
parallel with the other set(s). At this point, the sets
connected to the bus will share the load, normally utilising
load sharing equipment.
Using multiple generating sets rather than one large set
allows for maintenance to be performed on one of the sets
while the other set(s) are still available for duty.
Additionally, if load demands are low, individual generators
can be started as required, rather than one large generator
being used at (for instance) only 25% of its full load rating.
If the overall size of the load increases, for instance due to
factory expansion another set can be added to increase
capacity with minimal disruption to the rest of the system.
6.2 MULTIPLE SETS If multiple gensets in parallel are used to backup the mains
PROVIDING STANDBY supply, care should be taken when designing the system.
In the example above for instance, should the mains supply
TO THE MAINS fail, two possibilities exist. Firstly, if only two generating
SUPPLY sets are providing power to the bus, they must be capable
of supplying the currently active load. Secondly, if none of
the sets are available, they will all start up simultaneously.
The first set will close onto the dead bus, and supply power
to the load. Again, the set must be capable of supplying
this power to the currently active load.
Two solutions exist :
a) Ensure each generating set is capable of supplying the
entire load so that the above situations will not occur.
b) Ensure before closing the load switch and powering
the load with the generating sets, that all of the
generating sets are available and synchronised onto
the generator bus. While running in this manner, not in
parallel with the mains supply, this is called ‘islanded
mode’.
6.2.1 LOAD-SWITCHING USING 530 ATS
The DSE 530 automatic transfer switch can be used to monitor the mains supply to ensure it is
within limits. Should the mains supply fail, the 530 can be used to ‘remote start on load demand’
the 550 controllers used in the example shown. All sets in the system will start together. The first
available set will close onto the dead bus, also closing it’s load switch auxiliary contact. The other
generating sets will synchronise onto the generator bus, and then close in parallel with it.
Connect all of the generating set load switch auxiliary contacts in series and connecting into the
auxiliary generator ready input (terminal 10) of the DSE 530 automatic transfer switch in
conjunction with further external relay logic to latch this signal. (Further details of this can be found
in Appendix 1 of this publication).
The DSE 530 module will sense the generator bus voltage and frequency, and once within limits
will ‘wait’ for the presence of the auxiliary generator ready input. This signifies the correct closure of
all sets in the system onto the generator bus. The mains – generator load transfer is then
performed by the 530 automatic transfer switch controller.
Consider firstly, two generators operating in droop, closed together in parallel. Providing that the
governors are set correctly, the ratios of the power supplied to the load by each generator will be
proportional to the ratio of governor droop in each system.
For instance for a load of 100kW, and two generators with 3% speed droop, the generators will
equally share the load, each one supplying 50kW.
Consider now one generator operating in droop, connected in parallel with the mains supply, with
the governor adjusted so that the mains and the generator are sharing the load between them.
“Backing off” the governor, decreasing the engine’s fuel supply, will result in the mains ‘motoring’
the alternator. The generator is being “reverse powered”, absorbing power from the mains supply
and not supplying any power to the load.
Instructing the governor to increase fuel to the engine will also have no effect on engine speed
because the generator is “tied” to the mains. Instead, the generator will begin to supply power to
the load. Further increasing the fuel supply increases the amount of power supplied by the
generator. This in turn decreases the amount of power supplied by the mains. This is known as
Kilowatt (kW) export.
This can be taken a step further, by paralleling multiple generating sets, all operating isochronously
(zero droop). Utilising an active load-sharing controller, precise changes can be made to the
amount of power supplied to the load by each generating set. This is achieved by altering the
amount of fuel supplied to the engine, and monitoring the amount of power supplied by the set.
Each controller can communicate with the others, passing information regarding load levels. This
can also be used to bring in or drop off other generating sets as load demands change.
Again, consider two identical generating sets closed together in parallel. Each generator has a
‘droop kit’ fitted to the AVR and the field current of each generator is the same. In this situation,
they will both supply equal reactive power (kVAr) to the load.
Adjusting the amount of field excitation in one of the generators has the effect of that generator
supplying more of the reactive power to the load, matched by an equal drop in the reactive power
supplied by the other generator.
Uses of reactive power control include:
1) Where multiple generators are used in parallel with each other, the AVRs droop kits will ensure
that the reactive power is equalised between the sets, removing circulating currents caused by
imbalance in the reactive power (VAr) supplied by the paralleled generating sets. This
circulating current generates heat in the alternator windings, which has the effect of limiting
active power (kW) output, reducing the efficiency of the generating set. If left unchecked,
excess circulating current can also damage the alternator windings.
2) Power factor control or VAr control. This feature maintains a specific power factor where one
generating set is used in parallel with the mains supply. This is normally used so that the
generator maintains its VArs to keep its output at the site load’s average power factor level, to
minimise demands on the mains supply.
WARNING! Attempting to close the supplies in parallel when they are not in
synchronism can result in damage to the generating set system.
For example: If synchronising (using two gensets) is effected 120° out of phase, the
coupling torque can be as high as 12 times full load torque, depending on the ratio of
engine and generator inertias (Source: Diesel Generator Handbook L.L.J. Mahon).
The actual synchronising process can be achieved through various methods. Put simply, each
method involves manipulating the engine governor to increase/decrease engine speed (which has
a direct relationship with generator frequency) and the Automatic Voltage Regulator (which
controls the alternator excitation field to produce voltage).
The engine governor determines engine speed, by sensing the speed of rotation of the flywheel
(normally using a magnetic pickup probe). The governor can then control the actuator to adjust the
amount of fuel into the engine, which changes engine speed (similar to the accelerator in a car).
Most governors are also fitted with a ‘remote speed adjust’ input to allow an external device to
increase or decrease the set speed of the engine.
The Automatic Voltage Regulator effects change in the generator output voltage by controlling the
alternator’s exciter field. The AVR adjusts the voltage output to the required set voltage. Most
AVRs are also fitted with a ‘remote volts adjust’ input to allow an external device to increase or
decrease the set voltage of the alternator.
Automatic synchronisers act upon the ‘remote speed adjust’ and ‘remote volts adjust’ inputs of the
governor and AVR to affect synchronism and voltage matching.
The method of interface between the automatic synchroniser and the governor/AVR depends upon
the type of governor and AVR being used, and are described in the section entitled “Methods of
Adjusting Voltage and Frequency”.
Illustration Description
RAISE / LOWER PUSH BUTTONS This diagram shows switched inputs to the
governor/AVR to raise/lower speed/voltage.
For synchronising purposes where active load sharing is employed, isochronous governors with
sync/load share DC analogue inputs should be used.
Isochronous active load sharing demands a fast response to variations in the measured
parameters. For this reason, we recommend the use of the P120 analogue governor interface
module in applications of this type.
Isochronous active load sharing is typically employed in mains peak lopping or multiple set prime
power applications.
Droop active load sharing is typically used in no-break changeover systems, where control of the
active load (kW) share is not made during the parallel time.
A droop governor must be fitted, with a small amount of droop configured (typically 3% to 5%).
Droop provides for a small lowering of engine speed, as the load on the set is increased.
NOTE: - Multiple identically rated sets running in parallel must have identical droop
settings on their governors to ensure equal load sharing between the generators. Non
identical droop settings will result in sharing of the load proportional to the droop ratios of
the sets.
NOTE: - Quadrature Droop Compensation (QDC or ‘Quad Droop’ for short) is also
sometimes referred to as Quadrature Current Compensation (QCC)
NOTE: - Multiple identically rated sets running in parallel must have identical droop
settings on their AVRs to ensure equal VAr sharing between the generators. Non identical
droop settings will result in VAr sharing proportional to the droop ratios of the sets.
Automatic reactive load control is typically used in peak lopping / peak shaving applications to
minimise the kVAr demands on the mains supply.
For voltage matching with the mains/utility supply, the generator must be fitted with a remotely
adjustable AVR (automatic voltage regulator).
The 55x Load sharing controller can take full control over the reactive power supplied by the
generating set. This can be used for exporting a fixed amount of power (VAr control)
WARNING: - Care should be taken with respect to the grounding methodology of the
generator neutrals, particularly where alternators with differing winding pitches are to be
paralleled.
For supply synchronising and paralleling purposes the 55x controller is available in a number of
different versions. The relative features of each version are detailed below:
550/555 non sync 555 auto sync 550 load share 555 load control
Power measurement
instrumentation
Only ‘enhanced’ (power
measurement) controllers. 9 9 9
Auto synchronising 8 9 9 9
Isochronous load
sharing / control 8 8 9 (see note) 9
MultiSet
communications 8 9 9 8
Automatic first set on
the bus determination 8 8 9 N/A
Auto start/stop on
changing load
demands
8 N/A
9 N/A
Reverse power
Only ‘enhanced’ (power
measurement) controllers. 9 9 9
Dead bus relay 8 9 9 9
Earth fault protection
Only ‘enhanced’ (power
measurement) controllers. 9 9 9
Details of connections to the 55x controller are contained within the 55x operators manual and the
Link500Plus Communications software manual. However, the following diagram is included to
clarify positions of the connectors for synchronising and load sharing applications.
P120/P121 analogue
governor/AVR connector
(load sharing versions only)
Connector B Connector C
NOTE: - All Load Sharing versions of the 55x controller are fitted with either an RS232
or an RS485 communications PCB (specified on ordering). For details of connections or
applications utilising the RS232 or RS485 connectors, please see the Link500Plus
software manual.
Automatic synchronising is the control over engine speed and generator output volts prior to the
actual paralleling of the supplies. All ‘auto-sync’ and ‘load-share’ versions of the 55x controller can
perform this function, although some governors/AVRs will require an external interface device (See
sections entitled P120/P121 analogue voltage module and P122 Digital resistance module).
Droop load sharing is synchronising and closing the generator supplies in parallel. Then, utilising
the relative droops of the systems to share power proportional to their droop ratios. No external
control is made over the power share, and hence it is not necessary to use the load-sharing
version of the 55x controller. The auto-synchronising version of the controller can be used to
control the governor and AVR to effect synchronism and close the supplies in parallel.
Using the auto synchronising 550 controller, it is possible to parallel multiple sets, and share the
load equally between them. No other control over the load sharing is necessary as this is taken
care of by the droop in the systems.
However, unless the governors are identically matched and set, the load share will not be equal. A
very small difference in governor characteristics will lead to a large difference in load shares.
Additionally as load levels increase though, the generators output frequency will lower due to the
governor droop. If these issues cannot be accepted, they can be eradicated by the use of the 550
load-sharing controller.
NOTE: - Multiple identically rated sets running in parallel must have identical droop
settings on their governors/AVRs to ensure equal load sharing between the generators.
Non identical droop settings will result in sharing of the load proportional to the droop
ratios of the sets.
The auto synchronising 555 controller (again without the load sharing option) can be used in “no
break return” duty with the mains supply. The supplies are only closed in parallel for a very short
time. The amount of power being supplied by the generator at this time is dependent upon the
governor setting. The 55x module has no control over the power sharing, but in this application, it
is not normally a requirement.
Isochronous load sharing is the use of isochronous (zero droop) governors, with full automatic
control over load sharing (i.e. the amount of power supplied by each set). When either off load, or
on load, the generators output frequency will remain the same (i.e. 50Hz).
The modules (when used in a MultiSet system) communicate to establish total system load. This
data is then used (when the controllers are suitably configured) to decide whether it is necessary to
call more sets for duty as the load levels increase. Additionally sets are automatically unloaded and
removed from the bus if the load level falls low enough to allow this. This allows the generating
sets to be used at a more economical level by ensuring the available (gensets currently running)
capacity is close to the actual demand. This reduces the amount of unloaded engines that are
running, hence improving efficiency and lowering fuel costs. The 555 load-control module can also
be used to maintain a specific VAr or pf level.
For isochronous load sharing, the governor must be controlled by the P120 analogue governor
interface module.
NOTE: - The closing time of any load switching device slave relays should also be
taken into account. For instance, plug in relays typically used in generating set control
panels have an operation time of 10-20mS.
NOTE: - If fitting a mains (utility) ‘Breaker’ with a trip position, it is recommended to fit
one equipped with auxiliary contacts to indicate the “tripped” position. This can be fed into
an input configured to “auxiliary mains failure” so that the module is ‘informed’ of mains
(utility) supply breaker tripping should this occur. This is particularly important when the
555 module is operating in parallel with the mains (utility) supply.
11.1.1 CONTACTORS
Contactors normally operate fast enough for paralleling applications but care should be taken to
choose a contactor that the manufacturer specifies be fast enough for use in paralleling
applications. (See above).
11.1.2 CHARGED SPRING BREAKERS
In general, charged spring breakers will operate much faster than contactors.
Charged spring breakers ‘pre charge’ a large spring device within the breaker, so that when
breaker operation is required, the spring is ‘released’ which operates the closing action of the
device.
Typically, the spring is charged when the undervolts input is energised, normally when the set is
first started. Once charged, the breaker is ready for the closing signal.
11.1.3 AIR CIRCUIT BREAKERS (ACBS)
A.C.B.’s normally operate fast enough for paralleling applications but care should be taken to
choose an A.C.B. that the manufacturer specifies be fast enough for use in paralleling applications.
(See above).
11.1.4 MOTOR OPERATED BREAKERS
Some types of motor operated breakers are not suitable for paralleling operations due to the
excessive amount of time that the breaker takes to motor into position before the closing process
can be completed. Care should be taken to choose a motor operated breaker that the
manufacturer specifies be fast enough for use in paralleling applications. (See above).
Description Photograph
The P120 analogue governor interface module provides an isolated,
adjustable DC voltage level to connect into the control inputs of many
governors. This replaces the manually operated or motorised
potentiometers used in many synchronising and load sharing
applications. The module is also suitable for connection to the load
sharing inputs of many popular engine speed governors.
The P120 interface is controlled directly by the 55x controller via its
P120/P121 analogue expansion port. This enables the 55x to adjust
the speed of the engine to match the mains / bus and hence get the
supplies into synchronism. The P120 module is especially suited for
use in active power sharing systems.
12.1 SPECIFICATIONS
Item Value
DC input Voltage range 8V – 35V DC continuous. Reverse polarity protected
Max operating current 75mA at 12V, 45mA at 24V.
Output type Optically isolated DC voltage level
Minimum output load 1000Ω
Operating temperature range -30°C to +70°C
Indications Combined DC power on / Link lost LED
Fixing TS32 32mm top hat din rail fixing (din rail not supplied)
IP protection IP30
Appropriate standards BS EN 60950, BS EN 50081-2, BS EN 50082-2
To further expansion
Aux1
+ve
Aux2
P121 analogue Generator
Aux3 AVR interface
A
Aux4
To controller B
AVR
NOTE: - The P120 analogue expansion port is only fitted to load sharing enabled 55x
controllers. Where this function is not fitted to the controller, it is not possible to use the
P120 interface modules.
Where a different method of interface to the governor is used, load sharing will not be
possible.
NOTE: - The length of cable between the P120 interface unit and the governor should
be kept as short as possible. Foil screened cable is recommended for this purpose to
ensure integrity of the control signal.
12.4.1 SW1
The SW1 selector sets the ‘centre’ point of the interface module’s output. For example: if the output
range required is 1V to 3V, with the ‘centre’ point being at 2V, then the position of the SW1 selector
would be 4, giving a voltage offset of 2V.
12.4.2 SW2
The SW2 selector sets the voltage output range of the interface module’s output. For example: if
the output range required is 1V to 3V, then the position of the SW2 selector would be 1, giving a
voltage range of ±1V from the ‘centre’ point of 2V
Typical wiring diagrams for many of the most popular governors are included within this manual
(See sections entitled Interfacing to Governors).
Where these diagrams include the P120 interface module, the switch positions required for both
SW1 and SW2 are given.
NOTE: - If the governor you are using is not listed within this manual, it may still be
possible to interface to it using the P120 module. Contact your governor manufacturer to
check if the product has a DC voltage input for connection to a synchroniser / load sharer,
and if so, what the ‘voltage range’ and ‘centre voltage’ is. You can then use the tables
above to determine settings for SW1 and SW2. P120 terminal A is the negative output
terminal and B is the positive output terminal (providing governor output reversed is not
selected in the 55x controller’s configuration).
If the ‘centre voltage’ and ‘voltage range’ are not available from the governor
manufacturer, providing the input is compatible with a DC voltage signal, it still may be
possible to interface to it using the P120 modules. Contact our Technical Support
Department for advice.
If the governor is not fitted with a DC voltage input for connection to synchroniser/load
share modules, then a different interface method will be required. See section entitled
Interfacing to governors.
Access to the selectors is gained by removing power to the interface module, then removing the
two screws that are used to secure the transparent cover. The selectors are positioned as shown
below:
Description Photograph
The P121 analogue AVR interface modules provide an
isolated, adjustable DC voltage level to connect into the control
inputs of many automatic voltage regulators. This replaces the
manually operated or motorised potentiometers used in many
synchronising and load sharing applications. The module is
also suitable for connection to the load sharing controller
inputs of many popular AVRs.
The P121 interface is controlled directly by the 55x controller
via its AVR analogue expansion port. This enables the 55x to
adjust the alternator voltage output to match the mains / bus
and hence get the supplies into synchronism. The P121
module is especially suited for use in reactive power sharing
systems.
13.1 SPECIFICATIONS
Item Value
AC input Voltage range 152 V AC to 305 V AC (+20%)
AC input frequency 50Hz to 75Hz at rated engine speed
Maximum burden 2VA
AC input isolation Double insulated transformer
Output type Optically isolated DC voltage level
Minimum output load 1000Ω
Operating temperature range -30°C to +70°C
Indications Combined AC power on / Link lost LED
Fixing TS32 32mm top hat din rail fixing (din rail not supplied)
IP protection IP30
Appropriate standards BS EN 60950, BS EN 50081-2, BS EN 50082-2
To further expansion
Aux1
+ve
Aux2
P121 analogue Generator
Aux3 AVR interface
A
Aux4
To controller B
AVR
AC supply Generator
output
NOTE: - The AVR analogue expansion port is only fitted to load sharing enabled 55x
controllers. Where this function is not fitted to the controller, it is not possible to use the
P121 interface modules.
Where a different method of interface to the governor is used, load sharing will not be
possible.
NOTE: - The length of cable between the P121 interface unit and the AVR should be
kept as short as possible. Foil screened cable is recommended for this purpose to ensure
integrity of the control signal.
13.4.1 SW1
The SW1 selector sets the ‘centre’ point of the interface module’s output. For example: if the output
range required is 1V to 3V, with the ‘centre’ point being at 2V, then the position of the SW1 selector
would be 4, giving a voltage offset of 2V.
13.4.2 SW2
The SW2 selector sets the voltage output range of the interface module’s output. For example: if
the output range required is 1V to 3V, then the position of the SW2 selector would be 1, giving a
voltage range of ±1V from the ‘centre’ point of 2V
For reference purposes, the switch positions perform the following functions:
SW1 setting ‘centre’ voltage of P121 SW2 setting Voltage range of P121
0 0V 0 ±0.5V
1 0.5V 1 ±1.0V
2 1.0V 2 ±1.5V
3 1.5V 3 ±2.0V
4 2.0V 4 ±2.5V
5 2.5V 5 ±3.0V
6 3.0V 6 ±3.5V
7 3.5V 7 ±4.0V
8 4.0V 8 ±4.5V
9 4.5V 9 ±5.0V
Typical wiring diagrams for many of the most popular AVRs are included within this manual (See
section entitled Interfacing to AVRs).
Where these diagrams include the P121 interface modules, the switch positions required for both
SW1 and SW2 are given.
NOTE: - If the AVR you are using is not listed within this manual, it may still be possible
to interface to it using the P121 modules. Contact your AVR manufacturer to check if the
product has a DC voltage input for connection to a synchroniser / load sharer, and if so,
what the ‘voltage range’ and ‘centre voltage’ is. You can then use the tables above to
determine settings for SW1 and SW2. P121 terminal A is the negative output terminal and
B is the positive output terminal (providing governor output reversed is not selected in the
55x controller’s configuration).
If the ‘centre voltage’ and ‘voltage range’ are not available from the AVR manufacturer,
providing the input is compatible with a DC voltage signal, it still may be possible to
interface to it using the P121 modules. Contact our Technical Support Department for
advice.
If the AVR is not fitted with a DC voltage input for connection to synchroniser/load share
modules, then a different interface method will be required. See section entitled
Interfacing to AVRs.
Access to the selectors is gained by removing power to the interface module, then removing the
two screws that are used to secure the transparent cover. The selectors are positioned as shown
below:
WARNING! Suitable steps should be taken to isolate the generator supply from the
P121 AVR interface module before removing the cover. The cover must not be removed
while the engine is running.
Ensure the cover is correctly refitted before reconnecting the power and attempting to
start the engine.
Description Photograph
The P122 digital resistance module is designed to connect to
the remote adjust inputs of many examples of automatic
voltage regulators and governors. The module replaces the
traditional “2 wire” variable resistor (rheostat). It is controlled
directly by the 55x controller via its expansion output port. This
enables the 55x to adjust the speed of the engine and voltage
of the generator to match the mains / bus and hence get the
supplies into synchronism.
14.1 SPECIFICATIONS
Item Value
DC input Voltage range 8V to 35V DC continuous. Reverse polarity protected.
Max operating current 250mA at 12V, 125mA at 24V
Standby current (output at datum resistance) 35mA at 12V, 23mA at 24V
Output resistance range 1KΩ, 5KΩ, 10KΩ, 100kΩ (specify on ordering)
Output rating 0.6W
Operating temperature range -30°C to +70°C
Indications DC power on LED. Separate Link Lost LED
Fixing TS32 32mm top hat din rail fixing (din rail not supplied)
IP protection IP30
Appropriate standards BS EN 60950, BS EN 50081-2, BS EN 50082-2
P122 Digital
55x module resistance Governor
Aux1
+ve To controller
Aux2
To further expansion
Aux3
Governor
Aux4
AVR
To controller
To 81157xx
relay or 81548xx
To further expansion
LED expansion
(if required)
Governor
AVR
NOTE: - Only Relay expansion and LED expansion modules with part numbers
81157xx, 81545xx and 81548xx can be used in conjunction with the P122 digital resistance
module.
Incorrect setting of the ‘mode select’ switch will result in incorrect behaviour of the synchronising
process and will prevent the 55x controller from being able to synchronise the supplies.
It is not necessary to remove the transparent cover of the P122 digital resistance module in order
to gain access to the mode selector switch.
The MSC Link is used by the 55x controllers advanced load share functions. Some examples of
this are:
• Determining which set is to be the first to close onto a dead bus, eliminating the need for
complex external relay logic as traditionally used to perform this function.
• Determining the level of the total system load for use in load sharing applications. This is the
digital equivalent of analogue load sharing lines.
• Identifying whether the set should start / stop based upon load levels when used in running on
load demand mode.
NOTE: - The MultiSet Communications link terminals (Mh, Ml & SCR) are only to be
connected to other DSE controllers as shown, and must not be connected to any other
device.
NOTE: - Do not connect the MSC cable screen (SCR) to earth at any point. Protection
from interference is provided within the module and may be compromised by earthing the
MSC cable screen.
The MSC link is a data transmission line, requiring that a 120Ω termination resistor is present at
the ends of the cable on the Mh and Ml lines. This termination resistor is provided within the 550
module and is enabled / disabled via a switch, located behind the module’s rear fascia plate.
To access the switch, remove the six small screws from the rear of the module and gently remove
the back plate. The switch is located above the MSC connection socket.
NOTE: - Only the “end” modules in the MSC link must have the 120Ω termination
resistor enabled (switch up). All other controllers must have the termination resistors
disabled (switch down).
Parameter Value
Connection type Twin conductors with screen. Ensure screen is connected to SCR
terminal of every controller on the bus.
Cable impedance 120Ω
Maximum cable resistance 0.050Ω/m
Maximum cable capacitance (between conductors) 75pF/m
Maximum cable capacitance (conductor to shield) 110pF/m
Termination resistors (one at each end of cable run) 120Ω 4W (switchable)
Max number of 55x controllers per bus 16 (only 3 shown above for clarity)
Max cable length 40m
Max Spur length (see note 2 below) 1m
Recommended cable BELDEN 9841 120Ω cable.
WARNING! 120Ω impedance cable must be used for the MultiSet Communications
Link.
Use of any other impedance cable may cause intermittent failures in communications,
indicated by MSC alarms although the system may function normally during engine / panel
testing.
NOTE 1: - The 120Ω terminator must be enabled on the first and last devices on the
communications bus. See section header MSC Settings for further details.
NOTE 2: - It is important that the MultiSet Communications Link cable is run from one
module to the next in a ‘bus’ fashion. ‘Spurs’ off this bus should be avoided where
possible, but where a spur is unavoidable; its length should be kept less than 1m from the
bus cable.
Several alarms are provided to warn the operator of possible problems with the communication link
between the gensets.
NOTE: - To avoid possible problems with spare modules it is suggested that units are
commissioned in the system starting with ID 1 and then 2,3… etc. Any modules used as
spares should be configured as number 16,15… etc. These can then be added to the
system without causing any conflicts with existing modules. Alternatively, use the P810
for Windows™ configuration software to reconfigure the module to suit.
CAUTION! - Care should be taken to ensure that correct wiring is used between the
modules, the MSC terminator is correctly enabled on only end units on the link and that
maximum cable run distances are not exceeded. Should data error alarms be apparent,
operation of the MultiSet system may not be possible.
If the number of modules communicating on the Multset communications link should rise, then any
existing ‘MSC failure’ warning alarm is cleared, and all communicating modules are automatically
reconfigured to ‘expect’ the increased number of sets on the bus.
Additionally, one of the module’s digital inputs can be configured so that the MSC failure alarm is
disabled when the input is active. The module can be configured to alert / remind the user of this
via an indication or warning alarm if required via the “Multiset comms alarm disabled action”
setting.
NOTE:- For details on the MSC failure alarm settings, you are referred to the section
entitled “5xx controller configuration for load sharing” elsewhere in this manual.
NOTE: - For details on configuring non-synchronising items within the 55x controller
you are referred to the P810 for Windows product manual.
The Multi-set settings page is used to configure the automatic starting and stopping of generators
based upon load level demands.
Running on load demand Description
This system is enabled by activating digital inputs on the
controllers that have been configured to Remote Start on
load demand. Every controller in the MultiSet system must
have a digital input configured and connected in this way.
This enables generating set(s) to be taken out of service
for maintenance, while still allowing the remainder of the
system to operate.
Upon activation of the Remote Start on load demand input,
all the sets in the system will start up. The first one to
become available will close onto the dead bus,
communicating with the other sets to instruct them to
synchronise onto the now live bus, before closing the load
switch in parallel with it.
If too much generating set capacity is available to supply
the current load, the sets that are not required will begin
their stop delay timers, after which they will drop off the bus
and stop.
Too few modules action : the action that will be taken if the
number of modules communication on the MSC link is less
than the “minimum modules on Multiset comms link” setting.
None : Too few modules on the MSC link will not generate an
alarm condition.
Warning: An alarm condition will be given, but the sets will
still be able to run and take load.
Electrical trip: An alarm condition will be given, the set will be
removed from the bus and shutdown after the cooling timer.
Minimum modules on Multiset comms link : The minimum
number of modules allowed on the MSC link before an alarm
is generated. The type of alarm can be configured using “Too
few modules action” detailed above.
Multiset comms alarms disabled action : The action that
will be taken if the Multiset comms alarms are disabled via
configurable input or external communications control.
None : Disabling the MSC link alarms will not generate an
alarm condition.
Indication : Disabling the MSC link alarms will generate an
‘indication’, but no alarm condition is generated.
Warning: An alarm condition will be given to remind the
user/operator that the MSC alarms have been disabled.
Load level for more sets to run: The load level at which the
550 controller decides that additional generating set capacity
is required to supply power to the load.
Once this load level is exceeded, the next highest priority set
in the sequence (determined using the Genset Run Priority)
will begin it’s start delay timer. Once this has expired, the set
will run up, synchronise and take load. Should the set fail to
take load, it will communicate this using the MultiSet
Communications Link which will signal the next generating set
in the sequence to take its place.
The starting sequence will be terminated should the load level
drop below the Load level for more sets to run while the start
delay timer is in progress. This allows for short term increases
in load.
‘Soft transfers’ of this type have many benefits, the most obvious of which are:
• When the generator is removed from the bus, other sets in the system are not suddenly loaded
with the load share that was being supplied by the generator being removed. Instead, the load
is slowly ramped, allowing time for the remaining sets to take up their share of the load.
• Opening of the load switch occurs at a much lower load level, helping to reduce arcing of the
contacts.
Options :
Disabled: No load sharing will take place.
Load Share (550 only): The load will be shared between all
the sets in the system.
kW fixed export (555 only): The generator will export a fixed
amount of active (kW) power.
Generator full load rating: The full load rating (in kW) of the
set.
Options :
Disabled: No reactive power (VAr/pf) sharing will take place.
VAr Share: Reactive power (VAr) will be shared between all
the sets in the system.
VAr fixed export: The generator will produce a fixed amount
of reactive power (VAr) for use when in parallel with the mains
supply (555 only)
Generator full VAr rating: The full load rating (in VAr) of the
set. This setting is used in conjunction with the full load rating
(VAr) of the other sets in the system to determine the load
share that this set will take (550 only).
NOTE:- The set will initially take load at the level set
by load ramp minimum and will then increase it’s load
share at this rate until either
• All the sets have an equal share of the load (550
module only)
or
• The generated power is equal to the setting for ‘load
parallel power’ (555 only)
NOTE: - The DC supply must be correctly connected to the P120 module when
performing this operation.
NOTE: - The AC supply must be correctly connected to the P121 module when
performing this operation.
NOTE: - The Link Lost LED will be extinguished until the generator begins to supply
voltage to the ‘AC supply’ terminals of the P121 module.
NOTE: - The DC supply must be correctly connected to the P122 module when
performing this operation.
NOTE: - When setting the off load speed and voltage, use the 55x’s built in
instrumentation to verify the settings. Adjusting voltage to an accuracy of ±1V and
frequency to an accuracy of ±0.1Hz between the different sets will ease the process of
setting up the load sharing parameters later.
Synchronising lamps
Modern electronic techniques ensure the correct operation of the ‘check sync’ and load switching
process, but this operation depends upon the correct wiring of the bus and incoming generator
supplies right through the system. This is the point that most errors are likely to creep in. It is very
important that wiring of the supplies is double and triple checked before the system is run for the
first time.
The inbuilt phase sequence / rotation protection goes some way to verify the wiring of the supplies
to the 55x controller. However, it is common practice to employ a secondary ‘sync check’ during
commissioning to double check the correct connection of the supplies.
The diagram to the left shows a busbar and
incoming generator supply. The synchronising
lamps can be used as a simple ‘check sync’
verification.
When the lamps are dim, the supplies are ready
for paralleling.
WARNING! Before re-enabling the load switching device double check ALL wiring
between the alternator output, the 55x controller and the synchronising lamps.
Additionally, verify the correct operation of the synchronising process.
NOTE: - When using the P120 interface to control the electronic governor controller, it
is easy to verify its connections. When the set is running ‘off load’, simply turn the P120s
SW1 switch clockwise one position. The engine speed should change slightly. Remember
to return the switch to its previous position before continuing.
This procedure can only be applied to the alternator output voltage where the P121 is
being used in conjunction with the AVR.
Setting up the synchroniser and voltage matcher is made easier by viewing the 55x Synchroscope
display. This can be viewed on the Generator Settings page of the 55x controller'’
instrumentation…
The display will display “Generator Settings” for a short time, before displaying the first generator
instrument.
The synchroscope display is the ‘last’ instrument in the list of generator instruments…
Display Detail
The Initial stage of the Synchronising
display will only show the difference
between the Mains/Bus Supply and the
Generator Output. Here the display is
showing a frequency difference of
+2.9Hz. The generating set frequency
is too high (indicated by the up arrow)
and will be automatically reduced. The
voltage is +0.2 volts high, but is within
the limits set for RMS check sync
voltage (shown by the tick symbol).
Once the difference between the
bus/mains supply and the Generator
output has been reduced, the
‘Synchroscope’ display will become
active. The moving indicator will roll
from left to right or right to left
depending on the polarity of the
difference between the Mains/bus
supply and the generator output. A
generator frequency greater than the
mains/bus frequency will cause the
indicator to move from left to right (and
vice-versa).
Synchronising will only occur when both
the frequency and the voltage
differences are within acceptable limits
– Indicated by ‘Tick’ marks on the top of
the display. Then the moving bar
display will show the phase of the
supplies. Synchronising will now
cease, as the voltage and frequency
are within the check synch window. As
the phase changes, the indicator will
move across the display.
The picture to the left shows the
position of the phase indicator relative
to the phase of the two supplies. For
instance when the phase is 0° or 360°
(supplies in synchronism), the indicator
dot is in the middle of the display, within
the check sync window. When the
phase is 180°, the indicator is at the
extreme left or right of the display, the
furthest point away from the check sync
window).
When the phase falls within the check
sync window, the indicator appears
‘locked’ between the bars of the phase
check sync window. At this time, the
command to close the contactor /
breaker is given. Should synchronism
be broken (i.e. the load switch does not
operate) then the indicator will pass out
of the synchronising window and the
‘locked’ indication will clear.
The method of setting up the 55x synchroniser depends upon the interface method between the
55x controller and the AVR/Governor.
If your interface method uses the internal 55x raise/lower relays or the P122 digital resistance
module, then you will use the ‘pulse’ scheme.
If your interface method uses the P120 / P121 analogue interface module, then you will use the
‘analogue’ scheme.
NOTE: - Start with gain and stability at the minimum settings. Increase gain until the
engine speed becomes unstable, then half the gain setting.
Now increase the stability setting until the engine speed again becomes unstable, then
lower a little.
You may need to perform the synchronising process a number of times to see the effect of
your changes. You can also ‘knock’ the governor actuator, or change the ‘slip frequency’
setting to disturb the engine speed and force the controller into making further changes.
NOTE: - Start with gain and stability at the minimum settings. Increase gain until the
generator voltage becomes unstable, then half the gain setting.
Now increase the stability setting until the voltage again becomes unstable, then lower a
little.
You may need to perform the voltage-matching process a number of times to see the effect
of your changes.
NOTE: - Start with gain and stability at the minimum settings. Increase gain until the
engine speed becomes unstable, then half the gain setting.
Now increase the stability setting until the engine speed again becomes unstable, then
lower a little.
You may need to change load levels a number of times to see the effect of your changes.
You can also ‘knock’ the governor actuator, or change the ‘load parallel power’ setting
(555 only) to disturb the load-share process and ‘force’ the controller into making further
changes.
Load parallel power: The amount of power that the set will
produce when used in ‘Load level control’ mode. (Only
available on 555 when Load Control Mode is set to Load Level
Control)
KVAr control: The amount of reactive power that the set will
produce when used in ‘load level control’ mode. . (Only
available on 555 when Reactive Load Control Mode is set to
Load Level Control)
Pf control: The power factor that the set will maintain when
used in ‘load level control’ mode. . (Only available on 555
when Reactive Load Control Mode is set to Load Level
Control)
In this situation, as reactive power sharing is controlled purely by the generator’s AVR, it is the
AVR voltage setting that must be adjusted to make any changes to the kVAr (reactive power)
share.
Example: With two sets in parallel, and one generator is supplying more VAr than the other. The
voltage setting of the AVRs must be adjusted slightly to transfer the share from one generator to
the other. Increasing the setting on one AVR has the effect of increasing that set’s share of the
reactive power, and decreasing the other set(s) share of reactive power.
As this will have slightly altered the generators output voltage, it should be checked to ensure that
it has not been altered by too much. This procedure may have to be conducted more than once,
possibly adjusting the other AVR(s) a little the following times to ensure a suitable reactive load
share between the sets, while maintaining a suitable off load generator voltage.
NOTE: - Many AVRs have only a single turn potentiometer for adjusting the output
voltage. This has the effect of making reactive power sharing adjustments very sensitive.
Care should be taken to make small changes to the adjustment, and to ensure that the
voltage / VAr is stable (i.e. not changing) before further changes are made.
NOTE: - Ensure the “Check voltage” window is suitably set to allow voltages to match
even when the generator(s) already on the bus are loaded. Remember that a loaded
generator with an AVR droop kit will give a lower voltage than an unloaded generator.
55x AVR/governor
analogue expansion
port
DYN1
P120 Analogue 10502/3/4/6
55x module governor interface
Aux1 To controller
+ve A 7 (+4V)
Aux2
To further expansion B 8 (In)
Aux3
SW1 SW2
Aux4
4 (2V) 3 (±2V)
NOTE: - The AVR/Governor analogue expansion port is only fitted to load sharing
enabled 55x controllers. Where this function is not fitted to the controller, it is not possible
to use the P120 interface module. A different method of interface to the governor must be
used.
NOTE: - If the 55x AVR/Governor expansion port is already in use, the data connection
to the P120 governor interface can be connected to the “To further expansion” socket of a
P121 AVR interface module.
Aux1 CW
+ve 6
Aux2 inc
8
dec
Aux3 (Interposing relay) CCW 7
(See note)
Aux4 5KΩ motorised potentiometer
NOTE: - Interposing relay should connect to recommended polarity and voltage for
potentiometer input. Refer to potentiometer manufacturer for details.
55x AVR/governor
analogue expansion
port
DYN1
P120 Analogue 10693/4/5
55x module governor interface 10752/3/4/6
Aux1 To controller
+ve A 7 (+4V)
Aux2
To further expansion B 9 (In)
Aux3
SW1 SW2
Aux4
4 (2V) 3 (±2V)
NOTE: - The AVR/Governor analogue expansion port is only fitted to load sharing
enabled 55x controllers. Where this function is not fitted to the controller, it is not possible
to use the P120 interface module. A different method of interface to the governor must be
used.
NOTE: - If the 55x AVR/Governor expansion port is already in use, the data connection
to the P120 governor interface can be connected to the “To further expansion” socket of a
P121 AVR interface module.
55x AVR/governor
analogue expansion
port
DYN1
P120 Analogue 10794
55x module governor interface
Aux1 To controller
+ve A 9
Aux2
To further expansion B 8
Aux3 120KΩ
SW1 SW
Aux4
4 (2V) 3 (±2.5V)
NOTE: - The AVR/Governor analogue expansion port is only fitted to load sharing
enabled 55x controllers. Where this function is not fitted to the controller, it is not possible
to use the P120 interface module. A different method of interface to the governor must be
used.
NOTE: - If the 55x AVR/Governor expansion port is already in use, the data connection
to the P120 governor interface can be connected to the “To further expansion” socket of a
P121 AVR interface module.
55x AVR/governor
analogue expansion
port
DYN1
P120 Analogue 10871
55x module governor interface
Aux1 To controller
+ve A 12
Aux2
To further expansion B 11
Aux3
SW1 SW2
Aux4
5 (2.5V) 4 (±2.5V)
NOTE: - The AVR/Governor analogue expansion port is only fitted to load sharing
enabled 55x controllers. Where this function is not fitted to the controller, it is not possible
to use the P120 interface module. A different method of interface to the governor must be
used.
NOTE: - If the 55x AVR/Governor expansion port is already in use, the data connection
to the P120 governor interface can be connected to the “To further expansion” socket of a
P121 AVR interface module.
(Interposing relay)
DYN1
10871
55x module 15
Aux1
+ve
Aux2
Aux3
(Interposing relay) 1 (+ve)
Aux4
16
55x AVR/governor
analogue expansion
port
DYNA 8000
P120 Analogue
55x module governor interface
Aux1 To controller
+ve A 7 (+4V)
Aux2
To further expansion B 9 (In)
Aux3
SW1 SW2
Aux4
4 (2V) 3 (±2V)
NOTE: - The AVR/Governor analogue expansion port is only fitted to load sharing
enabled 55x controllers. Where this function is not fitted to the controller, it is not possible
to use the P120 interface module. A different method of interface to the governor must be
used.
NOTE: - If the 55x AVR/Governor expansion port is already in use, the data connection
to the P120 governor interface can be connected to the “To further expansion” socket of a
P121 AVR interface module.
Aux1 CW
+ve 6
Aux2 inc
9
dec
Aux3 (Interposing relay) CCW 7
(See note)
Aux4 5KΩ motorised potentiometer
NOTE: - Interposing relay should connect to recommended polarity and voltage for
potentiometer input. Refer to potentiometer manufacturer for details.
19.2.1 EFC*
55x AVR/governor
analogue expansion
port
EFC
P120 Analogue
55x module governor interface
Aux1 To controller
+ve A 9 (+4v)
Aux2
To further expansion B 8 (In)
Aux3 120KΩ
SW1 SW2
Aux4 0 (0V) 2 (±1.5V)
NOTE: - The AVR/Governor analogue expansion port is only fitted to load sharing
enabled 55x controllers. Where this function is not fitted to the controller, it is not possible
to use the P120 interface module. A different method of interface to the governor must be
used.
NOTE: - If the 55x AVR/Governor expansion port is already in use, the data connection
to the P120 governor interface can be connected to the “To further expansion” socket of a
P121 AVR interface module.
55x AVR/governor
analogue expansion
port
QST30
P120 Analogue
55x module governor interface
Aux1
+ve To controller A 17(+5V ref)
Aux2
To further expansion B 16 (speed bias)
Aux3
SW1 SW2 19 (screen)
Aux4
0 (0V) 4 (±2.5V)
NOTE: - Ensure that the QST30 adjustable parameter Speed Bias Input Type is set to
‘Woodward’.
NOTE: - Setting the QST adjustable parameter Woodward scale factor to 60rpm/Volt
gives a ±300RPM window of adjustment to engine speed.
NOTE: - The AVR/Governor analogue expansion port is only fitted to load sharing
enabled 55x controllers. Where this function is not fitted to the controller, it is not possible
to use the P120 interface module. A different method of interface to the governor must be
used.
NOTE: - If the 55x AVR/Governor expansion port is already in use, the data connection
to the P120 governor interface can be connected to the “To further expansion” socket of a
P121 AVR interface module.
55x AVR/governor
analogue expansion
port
QSX15 /
P120 Analogue QSK45/60
55x module governor interface
Aux1
+ve To controller A 06(+5V ref)
Aux2
To further expansion B 11 (speed bias)
Aux3
SW1 SW2 20 (screen)
Aux4
0 (0V) 4 (±2.5V)
NOTE: - Ensure that the QSK45/60 adjustable parameter Speed Bias Input Type is set
to ‘Woodward’.
NOTE: - The AVR/Governor analogue expansion port is only fitted to load sharing
enabled 55x controllers. Where this function is not fitted to the controller, it is not possible
to use the P120 interface module. A different method of interface to the governor must be
used.
NOTE: - If the 55x AVR/Governor expansion port is already in use, the data connection
to the P120 governor interface can be connected to the “To further expansion” socket of a
P121 AVR interface module.
55x AVR/governor
analogue expansion
port
DDEC III
P120 Analogue
55x module governor interface
Aux1 To controller
+ve A C3 (Ref.)
Aux2
To further expansion B D1 (Speed)
Aux3
SW1 SW2
Aux4 5 (2.5V) 4 (±2.5V)
NOTE: - The AVR/Governor analogue expansion port is only fitted to load sharing
enabled 55x controllers. Where this function is not fitted to the controller, it is not possible
to use the P120 interface module. A different method of interface to the governor must be
used.
NOTE: - If the 55x AVR/Governor expansion port is already in use, the data connection
to the P120 governor interface can be connected to the “To further expansion” socket of a
P121 AVR interface module.
ESD5100 -
55x AVR/governor 5500 series
analogue expansion
port
P120 Analogue
55x module governor interface
Aux1 To controller
+ve
Aux2 A G (gnd)
To further expansion
B N (input)
Aux3
SW1 SW2
Aux4
9 (±4.5V) 2 (±1.5V)
NOTE: - The AVR/Governor analogue expansion port is only fitted to load sharing
enabled 55x controllers. Where this function is not fitted to the controller, it is not possible
to use the P120 interface module. A different method of interface to the governor must be
used.
NOTE: - If the 55x AVR/Governor expansion port is already in use, the data connection
to the P120 governor interface can be connected to the “To further expansion” socket of a
P121 AVR interface module.
Aux3 J
To further expansion
Aux4
Governor
NOTE: - If the 55x expansion port is already in use, the data connection to the P122
digital resistance module can be connected to the “To further expansion” socket of either
an 81157xx relay board, 81548xx annunciator, or another P122 digital resistance module.
NOTE: - Interposing relay should connect to recommended polarity and voltage for
potentiometer input. Refer to potentiometer manufacturer for details.
55x AVR/governor
analogue expansion
port
KG series
P120 Analogue
55x module governor interface
Aux1 To controller
+ve A C (gnd)
Aux2
To further expansion B B (input)
Aux3
SW1 SW2
Aux4
5 (2.5V) 4 (±2.5V)
NOTE: - The AVR/Governor analogue expansion port is only fitted to load sharing
enabled 55x controllers. Where this function is not fitted to the controller, it is not possible
to use the P120 interface module. A different method of interface to the governor must be
used.
NOTE: - If the 55x AVR/Governor expansion port is already in use, the data connection
to the P120 governor interface can be connected to the “To further expansion” socket of a
P121 AVR interface module.
55x AVR/governor
analogue expansion
port
MDEC 4000
P120 Analogue
55x module governor interface
Aux1 To controller
+ve A 7 (X1-BB REF +5V)
Aux2
To further expansion B 8 (X1-AA input)
Aux3
SW1 SW2
Aux4
0 (0V) 7 (±4.0V)
NOTE: - The range of speed adjustment possible is configurable within the MDEC 4000
controller. You are referred to the MDEC 4000 operating instructions for further details of
this function.
NOTE: - The AVR/Governor analogue expansion port is only fitted to load sharing
enabled 55x controllers. Where this function is not fitted to the controller, it is not possible
to use the P120 interface module. A different method of interface to the governor must be
used.
NOTE: - If the 55x AVR/Governor expansion port is already in use, the data connection
to the P120 governor interface can be connected to the “To further expansion” socket of a
P121 AVR interface module.
(Interposing relay)
MDEC 4000
Aux1 4 (X1-EE)
+ve
Aux2
Aux3
(Interposing relay) +24V (X5-A SPEED - )
Aux4
13 (X1-V)
NOTE: - Briefly activating the input for less than 1s increases or decreases the
nominal speed by 1 RPM.
When the input is activated for more than 1s, the nominal speed is adjusted automatically
at a configurable rate. Source mtu ELEKTRONIK ECU 4/G Documentation (Part 1)
19.7.1 873979*
This governor is manufactured by for Volvo by G.A.C. See section entitled G.A.C. 5100-5500
Series for connection details.
EDC III
55x AVR/governor
analogue expansion
port
P120 Analogue
55x module governor interface
Aux1 To controller
+ve
Aux2 A POT -
To further expansion
B POT SIGNAL
Aux3
SW1 SW2
Aux4
6 (3V) 2 (±1.5V)
NOTE: - The AVR/Governor analogue expansion port is only fitted to load sharing
enabled 55x controllers. Where this function is not fitted to the controller, it is not possible
to use the P120 interface module. A different method of interface to the governor must be
used.
NOTE: - If the 55x AVR/Governor expansion port is already in use, the data connection
to the P120 governor interface can be connected to the “To further expansion” socket of a
P121 AVR interface module.
55x AVR/governor
analogue expansion
port
721
P120 Analogue
55x module governor interface
Aux1
+ve To controller A 46 (-)
Aux2
To further expansion B 45 (+)
Aux3
SW1 SW2
Aux4
0 (0V) 9 (±4.5V)
NOTE: - The AVR/Governor analogue expansion port is only fitted to load sharing
enabled 55x controllers. Where this function is not fitted to the controller, it is not possible
to use the P120 interface module. A different method of interface to the governor must be
used.
NOTE: - If the 55x AVR/Governor expansion port is already in use, the data connection
to the P120 governor interface can be connected to the “To further expansion” socket of a
P121 AVR interface module.
(Interposing relay)
721
55x module 28
Aux1
+ve
Aux2
Aux3
(Interposing relay) 1 (+)
Aux4
27
55x AVR/governor
analogue expansion
port
2301A
P120 Analogue
55x module governor interface
Aux1
+ve To controller A 17 (Gnd)
Aux2
To further expansion B 15
Aux3
SW1 SW2
Aux4
5 (2.5V) 9 (±4.5V)
NOTE: - The AVR/Governor analogue expansion port is only fitted to load sharing
enabled 55x controllers. Where this function is not fitted to the controller, it is not possible
to use the P120 interface module. A different method of interface to the governor must be
used.
NOTE: - If the 55x AVR/Governor expansion port is already in use, the data connection
to the P120 governor interface can be connected to the “To further expansion” socket of a
P121 AVR interface module.
Governor
NOTE: - If the 55x expansion port is already in use, the data connection to the P122
digital resistance module can be connected to the “To further expansion” socket of either
an 81157xx relay board, 81548xx annunciator, or another P122 digital resistance module.
55x AVR/governor
analogue expansion
port
EPG
P120 Analogue
55x module governor interface
Aux1
+ve To controller A 12(-)
Aux2
To further expansion B 11 (+)
Aux3
SW1 SW2
Aux4
0 (0V) 4 (±2.5V)
NOTE: - The AVR/Governor analogue expansion port is only fitted to load sharing
enabled 55x controllers. Where this function is not fitted to the controller, it is not possible
to use the P120 interface module. A different method of interface to the governor must be
used.
NOTE: - If the 55x AVR/Governor expansion port is already in use, the data connection
to the P120 governor interface can be connected to the “To further expansion” socket of a
P121 AVR interface module.
Aux3 8
To further expansion
Aux4
Governor
NOTE: - If the 55x expansion port is already in use, the data connection to the P122
digital resistance module can be connected to the “To further expansion” socket of either
an 81157xx relay board, 81548xx annunciator, or another P122 digital resistance module.
(Interposing relay)
ProAct I / II
55x module 19
Aux1
+ve
Aux2
Aux3
(Interposing relay) 24 (+)
Aux4
18
20.1 BASLER
20.1.1 AVC63-4
NOTE: - If the 55x expansion port is already in use, the data connection to the P122
digital resistance module can be connected to the “To further expansion” socket of either
an 81157xx relay board, 81548xx annunciator, or another P122 digital resistance module.
(Interposing relay)
55x module DECS100
Aux1
+ve
6U
Aux2
7
Aux3 (Interposing relay)
6D
Aux4
20.2.1 COSIMAT N
55x AVR/governor
analogue expansion Cosimat N
port
P121 Analogue
55x module AVR interface
Aux1 To controller
+ve A n (-)
Aux2 B M/m (In)
To further expansion
Aux3
SW1 SW2
Aux4
9 (4.5V) 8 (±4.5V)
NOTE: - The AVR/Governor analogue expansion port is only fitted to load sharing
enabled 55x controllers. Where this function is not fitted to the controller, it is not possible
to use the P121 interface module. A different method of interface to the AVR must be used.
NOTE: - If the 55x AVR/Governor expansion port is already in use, the data connection
to the P120 governor interface can be connected to the “To further expansion” socket of a
P121 AVR interface module.
Aux3
To further expansion
Aux4
Governor
NOTE: - If the 55x expansion port is already in use, the data connection to the P122
digital resistance module can be connected to the “To further expansion” socket of either
an 81157xx relay board, 81548xx annunciator, or another P122 digital resistance module.
NOTE: - The remote adjust input on the AVR are terminals ST4. Polarity of the
connections between the terminals ST4 and the P122 is not important.
55x AVR/governor
analogue expansion R610 3F
port
P121 Analogue
55x module AVR interface
Aux1 To controller
+ve A 23 (-)
Aux2 B 22 (In)
To further expansion
Aux3
SW1 SW2
Aux4
0 (0V) 9 (±4.5V)
NOTE: - The AVR/Governor analogue expansion port is only fitted to load sharing
enabled 55x controllers. Where this function is not fitted to the controller, it is not possible
to use the P121 interface module. A different method of interface to the AVR must be used.
NOTE: - If the 55x AVR/Governor expansion port is already in use, the data connection
to the P120 governor interface can be connected to the “To further expansion” socket of a
P121 AVR interface module.
Aux1 CW
+ve 21
inc
Aux2 22
dec
Aux3 (Interposing relay) CCW 23
(See note)
Aux4 10KΩ motorised
potentiometer
NOTE: - Interposing relay should connect to recommended polarity and voltage for
potentiometer input. Refer to potentiometer manufacturer for details.
20.4.1 SE350
Governor
20.4.2 SE100A
Governor
NOTE: - If the 55x expansion port is already in use, the data connection to the P122
digital resistance module can be connected to the “To further expansion” socket of either
an 81157xx relay board, 81548xx annunciator, or another P122 digital resistance module.
Aux1
+ve
6U
Aux2
7
Aux3 (Interposing relay)
6D
Aux4
NOTE: - The Interposing relays must have contacts rated for 240V 1A AC. Care is
required because “input power” voltages are present between 6U & 7 and 6D & 7. (Source:
DVR ™
Marathon Electric Magnamax Technical Manual for Model DVR® 2000)
NOTE: - The MagnamaxDVR ™ AVR disables the voltage raise/lower inputs when in the
select mode. I.e. The 55x controller cannot ‘remotely adjust’ the generator’s output
voltage while the MagnamaxDVR ™ AVR is in Select mode.
55x AVR/governor
analogue expansion DVR 2000E
port
P121 Analogue
55x module AVR interface
Aux1 To controller
+ve A A
Aux2 B B
To further expansion
Aux3
SW1 SW2
Aux4 2 (±1.5)
0 (0V)
NOTE: - The AVR/Governor analogue expansion port is only fitted to load sharing
enabled 55x controllers. Where this function is not fitted to the controller, it is not possible
to use the P121 interface module. A different method of interface to the AVR must be used.
NOTE: - If the 55x AVR/Governor expansion port is already in use, the data connection
to the P120 governor interface can be connected to the “To further expansion” socket of a
P121 AVR interface module.
NOTE:- Setting SW2 to position 1 (1.5V) gives the possibility of +/- 10% adjustment in
voltage. This is normally considered enough for voltage matching. If more adjustment is
required, increase SW2. The Marathon DVR2000E’ s input can accept upto a maximum of
+/-3V to give +/- 30% adjustment range. This can be achieved by setting P121 SW2 = 6 (3V)
20.4.5 M40FA610A
55x AVR/governor
analogue expansion M40FA610A
port
P121 Analogue
55x module AVR interface
Aux1 To controller
+ve A 6
Aux2 B 8
To further expansion
Aux3
SW1 SW2
Aux4
0 (0V) 5 (±3.0V)
NOTE: - The AVR/Governor analogue expansion port is only fitted to load sharing
enabled 55x controllers. Where this function is not fitted to the controller, it is not possible
to use the P121 interface module. A different method of interface to the AVR must be used.
NOTE: - If the 55x AVR/Governor expansion port is already in use, the data connection
to the P120 governor interface can be connected to the “To further expansion” socket of a
P121 AVR interface module.
Aux3 Q
To further expansion
Aux4
Governor
NOTE: - If the 55x expansion port is already in use, the data connection to the P122
digital resistance module can be connected to the “To further expansion” socket of either
an 81157xx relay board, 81548xx annunciator, or another P122 digital resistance module.
Aux3 7
To further expansion
Aux4
Governor
Aux3
To further expansion
Aux4
Governor
NOTE: - If the 55x expansion port is already in use, the data connection to the P122
digital resistance module can be connected to the “To further expansion” socket of either
an 81157xx relay board, 81548xx annunciator, or another P122 digital resistance module.
55x AVR/governor
analogue expansion MA325,
port
P121 Analogue
MA327
55x module AVR interface
Aux1 To controller
+ve A A2 (-)
Aux2 B A1 (+)
To further expansion
Aux3
SW1 SW2
Aux4
0 (0V) 2 (±1.0V)
NOTE: - The AVR/Governor analogue expansion port is only fitted to load sharing
enabled 55x controllers. Where this function is not fitted to the controller, it is not possible
to use the P121 interface module. A different method of interface to the AVR must be used.
NOTE: - If the 55x AVR/Governor expansion port is already in use, the data connection
to the P120 governor interface can be connected to the “To further expansion” socket of a
P121 AVR interface module.
55x AVR/governor
analogue expansion MX321
port
P121 Analogue
55x module AVR interface
Aux1 To controller
+ve A A2 (-)
Aux2 B A1 (+)
To further expansion
Aux3
SW1 SW2
Aux4
0 (0V) 1 (±1.0V)
NOTE: - The AVR/Governor analogue expansion port is only fitted to load sharing
enabled 55x controllers. Where this function is not fitted to the controller, it is not possible
to use the P121 interface module. A different method of interface to the AVR must be used.
NOTE: - If the 55x AVR/Governor expansion port is already in use, the data connection
to the P120 governor interface can be connected to the “To further expansion” socket of a
P121 AVR interface module.
Governor
NOTE: - If the 55x expansion port is already in use, the data connection to the P122
digital resistance module can be connected to the “To further expansion” socket of either
an 81157xx relay board, 81548xx annunciator, or another P122 digital resistance module.
55x AVR/governor
analogue expansion MX341
port
P121 Analogue
55x module AVR interface
Aux1 To controller
+ve A A2 (-)
Aux2
To further expansion B A1 (+)
Aux3
SW1 SW2
Aux4
0 (0V) 1 (±1.0V)
NOTE: - The AVR/Governor analogue expansion port is only fitted to load sharing
enabled 55x controllers. Where this function is not fitted to the controller, it is not possible
to use the P121 interface module. A different method of interface to the AVR must be used.
NOTE: - If the 55x AVR/Governor expansion port is already in use, the data connection
to the P120 governor interface can be connected to the “To further expansion” socket of a
P121 AVR interface module.
Governor
NOTE: - If the 55x expansion port is already in use, the data connection to the P122
digital resistance module can be connected to the “To further expansion” socket of either
an 81157xx relay board, 81548xx annunciator, or another P122 digital resistance module.
55x AVR/governor
analogue expansion SX421,
port
P121 Analogue
SX440,
55x module AVR interface SX465-2
Aux1 To controller
+ve A A2 (-)
Aux2
To further expansion B A1 (+)
Aux3
SW1 SW2
Aux4
0 (0V) 2 (±1.0V)
NOTE: - Ensure the “VTrim” adjustment for the SX440’s voltage adjustment input is set
to accept a signal of ±1V DC.
NOTE:- Ensure that some droop is configured using the AVRs “Droop” adustment.
(typically 5%).
NOTE: - The AVR/Governor analogue expansion port is only fitted to load sharing
enabled 55x controllers. Where this function is not fitted to the controller, it is not possible
to use the P121 interface module. A different method of interface to the AVR must be used.
NOTE: - If the 55x AVR/Governor expansion port is already in use, the data connection
to the P120 governor interface can be connected to the “To further expansion” socket of a
P121 AVR interface module.
Governor
NOTE: - If the 55x expansion port is already in use, the data connection to the P122
digital resistance module can be connected to the “To further expansion” socket of either
an 81157xx relay board, 81548xx annunciator, or another P122 digital resistance module.
As this AVR has no provision for the addition of a ‘droop kit’, it is not suitable for use in
synchronising / load sharing applications.
20.7.1 GRT7-TH
55x AVR/governor
analogue expansion GRT7-TH
port
P121 Analogue
55x module AVR interface
Aux1 To controller
+ve A A (-)
Aux2 B B (-)
To further expansion
Aux3
SW1 SW2
Aux4
0 (0V) 9 (±4.5V)
NOTE: - Using a P121 for AVR interface gives approximately +/- 5% adjustment of
generator output voltage.
NOTE: - The AVR/Governor analogue expansion port is only fitted to load sharing
enabled 55x controllers. Where this function is not fitted to the controller, it is not possible
to use the P121 interface module. A different method of interface to the AVR must be used.
NOTE: - If the 55x AVR/Governor expansion port is already in use, the data connection
to the P120 governor interface can be connected to the “To further expansion” socket of a
P121 AVR interface module.
Aux1 CW
+ve 6
inc
Aux2 7
dec
Aux3 (Interposing relay) CCW
(See note)
Aux4 5KΩ 3W motorised
potentiometer
NOTE: - Interposing relay should connect to recommended polarity and voltage for
potentiometer input. Refer to potentiometer manufacturer for details.
NOTE: - When using version 3 or earlier model 550, the All available sets on bus output
source is not available, this feature is included in version 4 or higher model 550s. However
a similar function can be achieved using external logic derived from a module output
configured to System healthy and an auxiliary contact on each generator’s bus contactor /
breaker to indicate availability on the bus (see diagram below).
Load L