Professional Documents
Culture Documents
FB-DIAG
FB-DIAG
Data sheet
3238_en_A © PHOENIX CONTACT 2013-04-05
1 Description
The FB-DIAG/FF/NC field diagnostics module is a DIN rail- Features
mounted instrument that provides measurements and mon-
– Reads physical layer diagnostics on the H1 segment
itoring for the physical layer of an active Foundation Field-
bus™ fieldbus segment. – Powered from the H1 segment
– Communicates over the H1 segment
The FB-DIAG/FF/NC is for installation in the field in conjunc-
tion with an FB-ET module via T-bus connection. – Can be installed in the field or control cabinet
Critical process measurements, such as segment voltage, – Critical measurements, such as segment voltage, noise
device count, signal level, communication status and noise and signal, can be monitored
levels, can be realized on each segment using an FDM – Easy control system integration with DD, EDDL and
module. The use of device descriptor (DD), electronic de- DTM
vice description language (EDDL) and device type manager – Adjustable alarm condition thresholds allow for preci-
(DTM) allow seamless integration into any control system sion monitoring and trending
without the need for protocol or media conversion. – Capable of retrieving and transmitting diagnostic data
for up to 24 field devices
– Easy integration into Phoenix Contact systems using
the TBUS DIN rail bus system
– Wide input voltage of 9 to 32 V DC
– -40 to +85°C operating range
– ATEX and IECEx listed
This data sheet is valid for all products listed on the following page:
FB-DIAG/FF/NC
2 Ordering data
3 Technical data
General data
Ambient temperature (operation) -40 °C ... 85 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 95 % (no condensation)
Degree of protection IP20
Mounting On horizontal DIN rail NS 35 in acc. with EN 60715
Width 17.7 mm
Height 85 mm
Depth 70.4 mm
Weight 61 g
Connection data
Connection method TBUS
Electrical data
Supply voltage 9 V DC ... 32 V DC
Typical current consumption 27 mA
Max. current consumption 29 mA
Power dissipation 928 mW
Approvals
ATEX Sira 13ATEX4148X; II 3G Ex nA IIC T4 Gc
IECEx IECEx SIR 13.0059X; Ex nA IIC T4 Gc
4 Dimensional drawing
, , 85
70,4
Figure 1 Dimensions
5 Block diagram
MAU µC
F+ F- S
TBUS
6 Installation
6.1 Mounting
WARNING!
Never apply power directly to the ME 17,5
TBUS... connector. Supply voltage must be
from a Phoenix Contact FB-ET coupler for the
the FB-DIAG/FF/NC module.
6.2 Removal
1. Insert a suitable tool, e.g., screwdriver, into the release
latch and pull it down.
2. Pull the module slightly away from the mounting surface
by rotating it upward.
3. Lift the module from the rail.
7 Operation
7.1 LED indicators
LEDs on each module indicate operating status and basic
diagnostic information
Figure 4 DIN rail mounting Label Color/status Function
PWR Solid green Power is present
Off Power is not pres-
ent
DAT Solid green Communication
active
Flashing green Communication
errors
ERR Solid red System error
Flashing red Diagnostic alarms
are present