Data sheet
2736_en_D © PHOENIX CONTACT 2013-03-13
This data sheet is valid for all products listed on the following page:
FB-ET, FB-2SP, FB-ISO
2 Ordering data
Products
Description Type Order No. Pcs. / Pkt.
Device coupler, trunk module, external terminator, includes T-bus connector FB-ET 2316048 1
Device coupler, 2-spur, includes T-bus connector FB-2SP 2316051 1
Device coupler, 1-spur, isolated, intrinsically safe, includes T-bus connector FB-ISO 2316064 1
Accessories
Description Type Order No. Pcs. / Pkt.
Surge protective plug, for floating signal circuit PT 2X2-FF-ST 2800755 10
Base element, for four signal lines with floating ground PT 4+F-BE 2839415 10
Enclosure, 15 port, aluminum FB-15-AL 2316187 1
Enclosure, 15 port, stainless steel FB-15-SS 2316190 1
Enclosure, 8 port, aluminum FB-8-AL 2316200 1
Enclosure, 9 port, stainless steel FB-9-SS 2316213 1
3 Technical data
General data
Number of spurs/module
FB-2SP 2
FB-ISO 1
Number of spurs/segment
FB-2SP 24
FB-ISO 12
Operating temperature
FB-ET -401 to 85°C
FB-2SP see “Current and Temperature Ratings (FB-2SP, FB-ISO)”
FB-ISO -401 to 60°C
Storage temperature -40 to 85°C
Relative humidity <95% non-condensing, intermittent condensing
Degree of protection IP20
Flammability rating, UL V0
Dimensions (H x W x D) See page 6
Mounting NS35 (EN 60715)
Weight
FB-ET 66 g
FB-2SP 64 g
FB-ISO 96 g
Shock resistance 30g, 11 ms
Vibration resistance 5g, 10-150 Hz
Connection type Screw terminals, removable, for each spur/trunk
Core cross-section <2.5 mm² (24-12 AWG)
1
-50°C rated devices are available through special order
Electrical Data
Minimum supply voltage (input via FB-ET)
FB-2SP 10.3 V DC @ 0.5 A; 10.6 V DC @ 1.0 A
FB-ISO 16.5 V DC @ 0.5 A; 16.7 V DC @ 1.0 A
Maximum supply voltage (FB-ET) 32.0 V DC
Rated current
Trunk in to trunk out (FB-ET) <4.5 A
Trunk in to T-bus (FB-ET) <1.0 A
Voltage drop
Trunk in to trunk out (FB-ET) <0.2 V
Trunk in to spur out (FB-ET to FB-2SP) <1.3 V
Input to output isolation, routine test (FB-ISO) 500 V AC
Termination (FB-ET) 100 , external removable plug
Trunk voltage protection (FB-ET) Active if voltage exceeds 39 V (typical) or 41 V (max)
Current consumption at no load
FB-ET with terminator 12.0 mA
FB-ET without terminator 8.0 mA
FB-2SP 4.5 mA
FB-ISO 10.0 mA
Maximum power dissipation at maximum load and voltage
FB-ET with terminator 0.53 W
FB-2SP 0.15 W
FB-ISO 0.61 W
Rated voltage per spur
FB-2SP <32.0 V
FB-ISO >10.0 V
Conformance
Fieldbus Foundation™ (FB-ET and FB-2SP) FF-846
IEC IEC 60529, IEC 61158-2
NE NE21
EN EN 61326, EN 60068-2-27, EN 60068-2-6
Approval
ATEX
FB-2SP Sira 08ATEX4303X
II 3(3)G Ex nA [ic Gc] IIC T4 Gc FISCO ic / Entity spurs
II 3(3)G Ex nA [nL Gc] IIC T4 Gc FNICO / Entity spurs
II 3G Ex ic IIC T4 Gc, FISCO ic
II 3G Ex nL IIC T4 Gc, FNICO
FB-ET Sira 08ATEX4302X
II 3G Ex nA IIC T4 Gc
II 3G Ex ic IIC T4 Gc, FISCO ic
II 3G Ex nL IIC T4 Gc, FNICO
FB-ISO Sira 10ATEX2034X
II 3(1)GD Ex nA [ia Ga Da] IIC T4 Gc, FISCO power supply (spur)
Sira 10ATEX4035X
II 3(3)G Ex nA [nL Gc] IIC T4 Gc, FNICO power supply (spur)
IECEx
FB-2SP IECEx SIR 08.0110X
Ex nA [ic Gc] IIC T4 Gc FISCO ic / Entity spurs
Ex nA [nL Gc] IIC T4 Gc FNICO / Entity spurs
Ex ic IIC T4 Gc, FISCO ic
Ex nL IIC T4 Gc, FNICO
FB-ET IECEx SIR 08.0109X
Ex nA IIC T4 Gc
Ex ic IIC T4 Gc, FISCO ic
Ex nL IIC T4 Gc, FNICO
FB-ISO IECEx SIR 10.0015X
Ex nA [ia Ga Da] IIC T4 Gc, FISCO power supply (spur)
Ex nA [nL Gc] IIC T4 Gc, FNICO power supply (spur)
CSA (C/US)
FB-2SP Class I, Division 2, Groups A,B,C,D
Ex nA [nL] IIC T4 FNICO / Entity spurs
Ex nL IIC T4, FNICO
Class I, Zone 2, AEx nA [nL] IIC T4 FNICO / Entity spurs
Class I, Zone 2, AEx nL IIC T4, FNICO
FB-ET Class I, Division 2, Groups A,B,C,D
Ex nA IIC T4
Ex nL IIC T4, FNICO
Class I, Zone 2, AEx nA IIC T4
Class I, Zone 2, AEx nL IIC T4, FNICO
FB-ISO Install in:
Class I, Division 2, Groups A-D
Spur to:
Class I, Groups A-D; Class II, Groups E-G; Class III; I.S. and non-incendive
Ex nA [ia] IIC T4, FISCO/Entity power supply (spur)
Class I, Zone 2, AEx nA [ia] IIC T4, FISCO/Entity power supply (spur)
Ex nA [nL] IIC T4, FNICO/Entity power supply (spur)
Class I, Zone 2, AEx nA [nL] IIC, FNICO/Entity power supply (spur)
4 Dimensions 5 Schematics
TRUNK IN
85 17.65 7 Ti+ V
Ti-
TiS
TRUNK OUT
To+
70.4
To-
ToS
99.1
F+ F- S
92.7
SPUR 1
7 17.65 85
I S1+
S1-
S1S
SPUR 2
70.4
I S2+
S2-
S2S
F+ F- S
SPUR 1
89.7 DC I S1+
7 17.65 85 DC S1-
S1S
70.4
F+ F- S
A
PWR PWR PWR PWR PWR PWR PWR
FB-2SP
FB-2SP
FB-ISO
FB-ISO
FB-ISO
FB-ISO
FB-ISO
PWR
FB-ET
COM 15 15 15 15 15 15 15
45 25 45 25 25 25 25 25 25
SHIELD
35 35 35 35 35 35 35
IOUT (mA) IOUT (mA) IOUT (mA) IOUT (mA) IOUT (mA)
ERR2 ERR2
S1+ S1- S1S S1+ S1- S1S S1+ S1- S1S S1+ S1- S1S S1+ S1- S1S S1+ S1- S1S S1+ S1- S1S
S2+ S2- S2S S2+ S2- S2S
7 Installation
B
7.1 Mounting
The modules are installed using DIN rail and Figure 9 DIN rail mounting
ME 17,5 TBUS… (included) connectors.
3. Place the module onto the DIN rail from above. The
upper holding keyway must be hooked onto the top
edge of the DIN rail.
4. Push the module from the front towards the mounting
surface, making sure to align the module with the
ME 17,5 TBUS… connector.
7.2 Removal
Table 1 Connections
Connection Label Function
C Trunk TiS Trunk in shield
B Ti– Trunk in –
Ti+ Trunk in +
ToS Trunk out shield
To– Trunk out –
To+ Trunk out +
Spur SnS Spur n shield1
Sn– Spur n –
Sn+ Spur n +
1
n indicates the spur number. Couplers may have multiple spur
connectors.
Termination is required at each end of a trunk segment.
8 Connections
FOUNDATION fieldbus and Profibus PA network
configurations are bus-type networks. Each device coupler
includes removable connectors. Table 1 shows the trunk
and spur connections.
FB-2
The three positions are shown in Figure 12 and defined in
Table 2.
15
45 25
PWR
FB-2SP
1 35
FB
15
45 25
ToS To- To+
35
TiS Ti- Ti+
SHIELD
TRUNK IN/OUT
2
ERR1
Error 2 LED
SHIELD
3
Current level switch
Power LED
Communication LED Figure 13 FB-2SP switch and LEDs
Shield grounding switch
9.3 FB-ISO
The FB-ISO module provides a selectable current rating.
The current rating should be selected based on the
Figure 12 FB-ET switch and LEDs maximum current (mA) the field device requires. Three
positions (ratings) are available. The default position (rating)
Table 2 FB-ET Shield Switch Positions
is 35 mA.
Position Function
FB-2
35
IOUT (mA)
ERR
Power LED
S1+ S1- S1S
Error LED
Current level switch
10 Maintenance
10.1 LEDs
LEDs on each module indicate operating status.
Table 3 FB-ET LEDs
Label Color Function
PWR green With FB-ISO module:
On indicates power >18 V
Flashes to indicate voltage <18 V
Without FB-ISO module:
On indicates power >12 V
Flashes to indicate voltage <12 V
COM yellow On indicates network communication