LT/HT Power & Control Cables

Table - 9
TECHNICAL DETAILS FOR HAVELLS 1.1 KV, THREE & HALF CORE
ALUMINIUM/COPPER CONDUCTOR, PVC INSULATED, ARMOURED CABLE
Ref Specification : IS 1554 Part-1
Physical Parameters Cable Code : AYFY/YFY, AYWY/YWY
Flat Strip Armoured (AYFY/YFY) Round Wire Armoured (AYWaY/YWaY)
Size Minimum No. of Nominal Minimum Nominal Minimum Approx. Approx. Weight of Cable Nominal Minimum Approx. Approx. Weight of Cable
(Cross Strand in Conductor Insulation Inner Armour Outer Overall With Al'm With Cu Dia of Outer Overall With Al'm With Cu
Sectional Thickness Sheath Strip Sheath Dia of Cond. Cond. Armor Sheath Dia of Cond. Cond.
Area) Aluminium Copper Thickness Dimension Thickness Cable AYFY YFY Wire Thickness Cable AYWY YWY
Sqmm No's No's mm mm mm mm mm Kg/Km Kg/Km mm mm mm Kg/Km Kg/Km
3X 25 +16 6/6 6/6 1.20/1.00 0.30 4 X 0.80 1.40 23 900 1450 1.60 1.40 25 1150 1700
3X35 +16 6/6 6/6 1.20/1.00 0.30 4 X 0.80 1.40 25 1050 1800 1.60 1.40 27 1350 2050
3X 50+25 6/6 6/6 1.40/1.20 0.30 4 X 0.80 1.56 29 1350 2350 2.00 1.56 30 1650 2600
3X70+35 12/6 12/6 1.40/1.20 0.40 4 X 0.80 1.56 32 1700 3100 2.00 1.56 34 2200 3600
3X95 +50 15/6 15/6 1.60/1.40 0.40 4 X 0.80 1.56 36 2150 4050 2.00 1.72 39 2800 4750
3X120+70 15/12 18/12 1.60/1.40 0.50 4 X 0.80 1.72 40 2550 5050 2.00 1.88 42 3300 5750
3X150+70 15/12 18/12 1.80/1.40 0.50 4 X 0.80 1.88 44 3000 6000 2.00 1.88 46 3750 6700
3X 185+95 30/15 30/15 2.00/1.60 0.50 4 X 0.80 2.04 48 3650 7400 2.50 2.04 51 4850 8650
3X240+120 30/15 34/18 2.20/1.60 0.60 4 X 0.80 2.2 53 4500 9400 2.50 2.36 57 5850 10800
3X300+150 30/15 34/18 2.40/1.80 0.60 4 X 0.80 2.36 58 5450 11650 3.15 2.52 63 7600 13800
3X400+185 53/30 53/30 2.60/2.00 0.70 4 X 0.80 2.68 64 6750 14600 3.15 2.68 69 9000 16850
3X500+240 53/30 53/34 3.00/2.20 0.70 4 X 0.80 2.84 76 8550 18700 4 3.00 83 12400 22500
3X630+300 53/30 53/34 3.40/2.40 0.70 4 X 0.80 3.00 84 10600 23700 4 3.00 91 14750 27800
* Tabulated Approx. Weight of Cable are only for the purpose of guideline for transportation, loading & unloading purpose.
** Refer page no. 55 for normal delivery lengths & packing details.

Cross-sectional view
Conductor Material : Aluminium / Copper as per Class-2 of IS: 8130
Shape of Conductor : For Al'm Cond. - 4, 6 & 10 Sq.mm Solid / Stranded Non Compacted Circular,
16 Sq.mm and above - Stranded Compacted Shaped
For Cu Cond. - 4 & 6 Sq.mm Solid / Stranded Non Compacted Circular, 10 Sq.mm - Stranded Compacted Circular,
16 Sq.mm and above - Stranded Compacted Shaped
Insulation Material : PVC Type-A OR HR PVC Type-C as per IS: 5831; Colour : Red, Yellow, Blue & Black
Inner Sheath : PVC Type ST-1 as per IS: 5831; Options : PVC Type ST-2/FR Type/FRLS Type
Armouring : Single Layer of Galvanized Steel Round Wire / Flat Strip
Outer Sheath : PVC Type ST-1 as per IS: 5831; Options : PVC Type ST-2/FR Type/FRLS Type
Colour of Outer Sheath : Black or any other Colour as per requirement

Electrical Parameters
Normal Current Rating Short Circuit Current
Size Max. Conductor Approx. Conductor Reactance of Capacitance
Rating for 1 Second
(Cross D.C.Resistance at 20 °C A.C.Resistance at 70 °C Cable at 50 of Cable For Aluminium Conductor For Copper Conductor
Duration
Sectional Area) Hz (Approx.) (Approx.)
Aluminium Copper Aluminium Copper Ground Duct Air Ground Duct Air Aluminium Copper
Sqmm Ohm/Km Ohm/Km Ohm/Km Ohm/Km Ohm/Km μF/Km Amps Amps Amps Amps Amps Amps K.amps K.amps
3X25+16 1.20 0.727 1.44 0.87 0.083 0.42 76 63 70 99 81 90 1.90 2.88
3X35+16 0.868 0.524 1.04 0.63 0.082 0.48 92 77 86 120 99 110 2.66 4.03
3X50+25 0.641 0.387 0.769 0.464 0.082 0.49 110 95 105 145 125 135 3.80 5.75
3X70+35 0.443 0.268 0.532 0.322 0.076 0.56 135 115 130 175 150 165 5.32 8.05
3X95+50 0.320 0.193 0.384 0.232 0.076 0.58 165 140 155 210 175 200 7.22 10.90
3X120+70 0.253 0.153 0.304 0.184 0.075 0.63 185 155 180 240 195 230 9.12 13.80
3X150+70 0.206 0.1240 0.247 0.1488 0.074 0.63 210 175 205 270 225 265 11.40 17.30
3X185+95 0.164 0.0991 0.197 0.1189 0.074 0.64 235 200 240 300 255 305 14.10 21.30
3X240+120 0.125 0.0754 0.151 0.0912 0.073 0.67 275 235 280 345 295 355 18.20 27.60
3X300+150 0.100 0.0601 0.122 0.0733 0.073 0.68 305 260 315 385 335 400 22.80 34.50
3X400+185 0.0778 0.0470 0.0961 0.0580 0.072 0.70 335 290 375 425 360 435 30.40 46.00
3X500+240 0.0605 0.0366 0.0759 0.0459 0.072 0.70 370 320 425 470 390 520 38.00 57.50
3X630+300 0.0469 0.0283 0.0610 0.0368 0.072 0.70 405 350 480 555 470 675 47.90 72.50
Note: Normal current ratings are given in standard conditions (as given in page no 52, 53), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 52 - 54

20
LT/HT Power & Control Cables

Table - 10
TECHNICAL DETAILS FOR HAVELLS 1.1 KV
FOUR CORE, ALUMINIUM/COPPER CONDUCTOR, PVC INSULATED, ARMOURED CABLES
Ref Specification : IS 1554 Part-1
Physical Parameters Cable Code : AYFY/YFY, AYWY/YWY
Flat Strip Armoured (AYFY/YFY) Round Wire Armoured (AYWaY/YWaY)
Size Minimum No. of Nominal Minimum Nominal Minimum Approx. Approx. Weight of Cable Approx. Weight of Cable
Nominal Minimum Approx.
(Cross Strand in Conductor Insulation Inner Armour Outer Overall With Al'm With Cu Dia of Outer Overall With Al'm With Cu
Sectional Thickness Sheath Strip Sheath Dia of Cond. Cond. Armor Sheath Dia of Cond. Cond.
Area) Aluminium Copper Thickness Dimension Thickness Cable AYFY YFY Wire Thickness Cable AYWY YWY
Sqmm No's No's mm mm mm mm mm Kg/Km Kg/Km mm mm mm Kg/Km Kg/Km
4 1/3 1/3 1.00 0.30 N/A N/A N/A N/A N/A 1.40 1.24 17 520 620
6 1/3 1/3 1.00 0.30 N/A N/A N/A N/A N/A 1.40 1.24 19 610 770
10 1/7 6 1.00 0.30 4 X 0.80 1.40 19 600 850 1.60 1.40 21 790 1060
16 6 6 1.00 0.30 4 X 0.80 1.40 21 750 1100.0 1.60 1.40 23 950 1350
25 6 6 1.20 0.30 4 X 0.80 1.40 24 950 1550.0 1.60 1.40 25 1200 1800
35 6 6 1.20 0.30 4 X 0.80 1.40 26 1150 2000.0 1.60 1.56 28 1450 2300
50 6 6 1.40 0.40 4 X 0.80 1.56 30 1450 2550.0 2.00 1.56 32 2000 3100
70 12 12 1.40 0.40 4 X 0.80 1.56 33 1850 3450.0 2.00 1.56 35 2400 4000
95 15 15 1.60 0.40 4 X 0.80 1.72 38 2350 4600.0 2.00 1.72 40 3000 5250
120 15 18 1.60 0.50 4 X 0.80 1.88 41 2800 5650.0 2.00 1.88 44 3500 6350
150 15 18 1.80 0.50 4 X 0.80 1.88 45 3300 6800.0 2.50 2.04 49 4500 7950
185 30 30 2.00 0.60 4 X 0.80 2.04 50 4000 8350.0 2.50 2.20 54 5350 9700
240 30 34 2.20 0.60 4 X 0.80 2.36 57 5100 10800.0 2.50 2.36 60 6500 12250
300 30 34 2.40 0.70 4 X 0.80 2.52 64 6200 13300.0 3.15 2.68 69 8500 15700
400 53 53 2.60 0.70 4 X 0.80 2.84 71 7650 16750.0 3.15 2.84 75 10200 19350
500 53 53 3.00 0.70 4 X 0.80 3.00 79 9600 21300.0 4.00 3.00 85 13550 25300
630 53 53 3.40 0.70 4 X 0.80 3.00 89 11700 27050.0 4.00 3.00 95 16350 31450
* Tabulated Approx. Weight of Cable are only for the purpose of guideline for transportation, loading & unloading purpose.
** Refer page no. 55 for normal delivery lengths & packing details.

Cross-sectional view
Conductor Material : Aluminium / Copper as per Class-2 of IS: 8130
Shape of Conductor : For Al'm Cond. - 4, 6 & 10 Sq.mm Solid / Stranded Non Compacted Circular,
16 Sq.mm and above - Stranded Compacted Shaped
For Cu Cond. - 4 & 6 Sq.mm Solid / Stranded Non Compacted Circular, 10 Sq.mm - Stranded Compacted Circular,
16 Sq.mm and above - Stranded Compacted Shaped
Insulation Material : PVC Type-A OR HR PVC Type-C as per IS: 5831; Colour : Red, Yellow, Blue & Black
Inner Sheath : PVC Type ST-1 as per IS: 5831; Options : PVC Type ST-2/FR Type/FRLS Type
Armouring : Single Layer of Galvanized Steel Round Wire / Flat Strip
Outer Sheath : PVC Type ST-1 as per IS: 5831; Options : PVC Type ST-2/FR Type/FRLS Type
Colour of Outer Sheath : Black or any other Colour as per requirement

Electrical Parameters
Size Normal Current Rating Short Circuit Current
Max. Conductor Approx. Conductor Reactance of Capacitance
(Cross Rating for 1 Second
D.C.Resistance at 20 °C A.C.Resistance at 70 °C Cable at 50 of Cable For Aluminium Conductor For Copper Conductor
Sectional Duration
Hz (Approx.) (Approx.)
Area) Aluminium Copper Aluminium Copper Ground Duct Air Ground Duct Air Aluminium Copper
Sqmm Ohm/Km Ohm/Km Ohm/Km Ohm/Km Ohm/Km μF/Km Amps Amps Amps Amps Amps Amps K.amps K.amps
4 7.41 4.61 8.89 5.53 0.098 0.23 28 23 23 36 30 30 0.304 0.460
6 4.61 3.08 5.53 3.70 0.096 0.28 35 30 30 45 38 39 0.456 0.690
10 3.08 1.83 3.70 2.20 0.091 0.34 46 39 40 60 50 52 0.760 1.15
16 1.91 1.15 2.29 1.38 0.085 0.40 60 50 51 77 64 66 1.22 1.84
25 1.20 0.727 1.44 0.87 0.083 0.42 76 63 70 99 81 90 1.90 2.88
35 0.868 0.524 1.04 0.63 0.082 0.48 92 77 86 120 99 110 2.66 4.03
50 0.641 0.387 0.769 0.464 0.082 0.49 110 95 105 145 125 135 3.80 5.75
70 0.443 0.268 0.532 0.322 0.076 0.56 135 115 130 175 150 165 5.32 8.05
95 0.320 0.193 0.384 0.232 0.076 0.58 165 140 155 210 175 200 7.22 10.90
120 0.253 0.153 0.304 0.184 0.075 0.63 185 155 180 240 195 230 9.12 13.80
150 0.206 0.1240 0.247 0.1488 0.074 0.63 210 175 205 270 225 265 11.40 17.30
185 0.164 0.0991 0.197 0.1189 0.074 0.64 235 200 240 300 255 305 14.10 21.30
240 0.125 0.0754 0.151 0.0912 0.073 0.67 275 235 280 345 295 355 18.20 27.60
300 0.100 0.0601 0.122 0.0733 0.073 0.68 305 260 315 385 335 400 22.80 34.50
400 0.0778 0.0470 0.0961 0.0580 0.072 0.70 335 290 375 425 360 435 30.40 46.00
500 0.0605 0.0366 0.0759 0.0459 0.072 0.70 370 320 425 470 390 520 38.00 57.50
630 0.0469 0.0283 0.0610 0.0368 0.072 0.70 405 350 480 555 470 675 47.90 72.50
Note: Normal current ratings are given in standard conditions (as given in page no 52, 53), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 52 - 54