ELECTRICFIELD COMPANY, 75-81 INDUSTRIAL AREA, PHASE-II, GANGYAL, AMIMU-180010 J&K) INDIA. WEBSITE: wr lectin Routine Test Certificate (As per IS : 2705) Equipment Detail [:66 KV CURRENT TRANSFORMER Date: 1/2024 [: Mis DEVI POWERS PVT. LTD. ‘S.No : 28507 : DPPL/ZPL2023-24/1910, Dated. 19-10-2023. [: Out Door, Oil Cooled , Live Tank CT Core-l Core-It Coreiit Core-IV 100-5071 100-50/1A | _100-50/1A | _100-S0/1A 20VA 20VA = 02 P. PS [ALEASE <5 15 = = VKP eS = 250V at 100A | 250V at 100A [Rated Short time Thermal Current 31.5 KA for 3 Seconds. ;. Verification of terminal marking and polarity. Verified OK ‘withstood withstood ‘withstood tharge Value at 46KV: <10PC Metering Class Core : 1 HotPry 100% Burden Carrent | Ratio Error (%) [Phase Error (Min)| Ratio Error (%) 120% B02 065 0.02 100% 0.02 114 0.02 20% 0.14 2.18 oot 3% “022 5.19 0.03. 120% “0.01 043 0.04 100% “0.01 045 001 20% 0.03 151 ‘001 3% 70.06 2:36 0.01 Protection Class Core : %ofery 100% Burdea eid Current Ratio Error (%) Phase Error (Min) S0/A 100% 0.10 3a 00/1 100% 0.08 149 ‘Composite Error (%) 018 PS Class Core II Specified VKp(Vows]| Tex(mA) TA(VKp)_[_ 14 (lex mA) ‘Turn Ratio Error EN ont 250V 32 25v 2 as aa | PS Glass Core :1V Specified VKp(VoKsy]| _Tex(mA) TACVKp) | _11 (lexmA) ‘Turn Ratio Error SORA 0.03 fw fos fom | fae Tae ‘Tested By: iefield Co., Testing Engineer ELECTRICFIELD COMPANY, 75-81 INDUSTRIAL AREA, PHASE-II, GANGYAL, AMMU-IS0010 (U4) INDIA, WERSITR: wohl ia Routine Test Certificate (As per IS : 2705) [Equipment Detail [F665 KV CURRENT TRANSFORMER Date: 1/1/2024 [Customer's Name ‘Mis DEVI POWERS PVT. LTD. ‘S.No: 28508 [Order No. & Daie | DPPL/ZPI/2023-24/1910, Dated. 19-10-2023, [Type of Transformer [: Out Door, Oil Cooled, Live Tank CT Core Details Core Core-Il Coretit ‘Core-1V Ratio 100-S0/1A 100-501 100-5071 100-5071 [Burden 20VA 20VA, = = [Accuracy 02, SP PS PS [ALRASE <5, 15 = - VKP = = 250V at 100A [_250V at 100A [Rated Short time Thermal Current 31.5 KA for 3 Seconds. i Verification of terminal marking and polarity. fi, Power frequency dry withstand test on primary winding at 140 KV for one minute. iii. Power frequency dry withstand test on secondary winding at 3 KV for one minute. withstood iv. Over voltage interturn Test. (Withstood ok for one minute.) ‘withstood [v. Tan Delia Value = 0.243% lvi. Partial Discharge Value at 46KV: <10PC Metering Class Core : 1 aa % of Pry 100% Burden 25% Burden 2 Curreat _ | Ratio Error (%) [Phase Error (Min)| Ratio Error (%) [Phase Error (Min)] 120% 01 092 0.02 087 100% 0.02 4.45, 0.02 0.84 hea 20% 0.13 2.65 0.03 1.76 3% 024 494 "0.05 387 120% 0.01 0.53 0.02 0.35 100% 0.08 059 0.02 042 coe 20% 0.03 1.87, 0.01 1.29 5% 0.05 3.26 0.02 2.21 Protection Class Core : I ‘of Pry 100% Barden Ratio Current Ratio Error (%) Phase Error (Min) S0/1A 100% 0.06 3.62 100/14. 100% 0.01 1.32 Composite Error (%) 0.27 PS Class Core ? I Specified VKp(Volts]| Tex(mA) TACVKp) —_|_11 (lex mA) ‘Turn Ratio Error SO/1A 0.02 250V 28 28 37 me on PS Class Core : IV Specified VKp(Volls]| _fex(mA) TACK) _|_ 1 (lexma) Turn Ratio Error SO/LA 0.04 250V 30 28 a one oa Tested By: For Electriefield Co., ELECTRICFIELD COMPANY, 75-81 INDUSTRIAL AREA, PHASE-II, GANGYAL, JAMMCI8I010 (4K) INDIA. WERSTTE: ww ketrild.in Routine Test Certificate (As per IS = 2705) Equipment Detail ‘66 KV CURRENT TRANSFORMER Date: W72024 [Customer's Name Mis DEVI POWERS PVT. LTD. S.No : 28509 Order No. & Date DPPLIZPL/2023-24/1910, Dated. 19-10-2023, Type of Transformer ‘Out Door, Oil Cooled , Live Tank CT Core Details ‘Core-t Core-tI Corel CoreV, Ratio 100-5071 100-S071A 100-5071 100-50/1A Burden 20VA 20VA = = Accuracy 02 ? PS rs | JALE/SF, =5 15 = = VKP = = ‘350V at 100A | 250V at 100A Rated Short fime Thermal Current 31.5 KA for 3 Seconds. i. Verification of terminal marking and polarity. Verified OK Power frequency dry withstand test on primary winding at 140 KV for one minute. withstood ower frequency dry withstand test on secondary winding at 3 KV for one minute. withstood iv. Over voltage interturn Test, (Withstood ok for one minute.) withstood vy. Tan Deita Value = 0.227% [vi Partial Discharge Value at 46KV: <10PC Metering Class Cor Rath %ot Pry 100% Burden 25% Burden da Current __[ Ratio Error (%) [Phase Error (Min| Ratio Error (%) [Phase Error (Min) 120% “0.05 061 0.03 047 100% “0.06 065 “0.08 056 he 20% “0.16 244 “0.06 18 5% 0.32 567 0.08 365 120% 0.02 0.34 0.01 027 100% 0.02 0.39 0.01 0.36 Lckats 20% "0.05, 141 “0.02 1.15 5% 0.08 2.48 0.04 1.88 ‘of Pry a Current Burden Ratio Error (%) Phase Error (Min) ‘SOA 100% 0.09 4.06 100/14 100% “0.07 1.80 ‘Composite Error (%) PS Class Core = III 023 [Specified VKp(Vous)] _ Tex(mA) TLACVKp) _|_1-1 lex mA) Tura Ratio Error 250V 26 275 33 30/1A 0.08 100A 0.04 PS Class Core :1V Specified VKp(VoKS)] _lex(mA) TACVKp)__[ 1.1. dexmA) Tura Ratio Error 28 275 38 SO/A -0.07, 100A 0.03 For Electricfield Co., fii ff 8) ‘sting Engineer ELECTRICFIELD COMPANY, 75-81 INDUSTRIAL AREA, PHASE4I, GANGYAL, ” JAMAEU-189010 B&K) INDIA. WEBSITE: ww.clectrifiehin ROUTINE TEST CERTIFICATE FOR VOLTAGE TRANSFORMER (AS PER 1S:3156-1992) [Serial No. : 28515 [Date £01-01-2024 [Type : Outdoor, Oil Cooled, Single Phase No. OF winding 2 Rated Voltage : 66 KV JAccuracy Class 02, 0.2 Highest System Voltage : 72.5 KV Rated Output 250 VA, 5OVA Ratio : 66KV/V3/110V/V3-110V/V3, INo. Of Phase : Single insulation Level : 140/325KVp Rated VoltageFactor _: 1.2Cont. & 1 5Time for 30 Sec. [The following routine tests as stipulated in 1S:3156-1992 were conducted on PT. i. Verification of Terminal Marking and Polarity. oK ii. Power Frequency Dry withstand test on Primary Winding 3KV for one minute. iii. Power Frequency Dry withstand test on Secondary Winding 3KV for one minute. iv. Induced Over Voltage Withstand Test, on exciting from secondary side induced voltage on Primary Winding at 200Hz, 140KV for 30 Sec. \v. Partial Discharge Value at 46KV: <10PC vi. Accuracy Test for PT -Test results stated below. Metering Winding (1a-1n) % of Rated Voltage | % of Rated Burden | RE(%) | PE(Min)| %ofRated Burden | RE(%) | PE (Min) 120 100% 0.06 | 217 25% 012 | 1.44 100 100% 0.05 | 1.80 25% 012 | 132 80 100% 0.05 | 167 25% Og 07 Metering Winding (2a-2n} % of Rated Voltage | % of Rated Burden | RE(%) | PE(Min)| %ofRatedBurden | RE(%) | PE (Min) 120 400% ~o07 | 2.11 25% on | 143 100 100% 007 | 1.73 25% 012 | 1.24 80 100% -0.06 | 1.52 25% 042 | 412 Tested By : For Electricfield Co. pe =e Engineer ELECTRICFIELD COMPANY, 7581 INDUSTRIAL AREA, PHASE, GANGYAL, JAMMU-180010 (&K) INDIA. WEBSITE: ww clectriefitin ROUTINE TEST CERTIFICATE FOR VOLTAGE TRANSFORMER (AS PER 1S:3156-1992) [Serial No. : 28514 Date + 01-04-2024 HType : Outdoor, Oil Cooled, Single Phase NO. Of winding 2 Rated Voltage : 66 KV [Accuracy Class 202,02 Highest System Voltage : 72.5 KV Rated Output 250 VA, SOVA Ratio : 66KV/V3/110VAV3-110V/V3 No. Of Phase = Single insutation Level : 140/325KVp Rated VoltageFactor _: 1.2Cont. & 1.STime for 30 Sec. The following routine tests as stipulated in IS:3156-1992 were conducted on PT. i. Verification of Terminal Marking and Polarity. oK ii. Power Frequency Dry withstand test on Primary Winding 3KV for one minute. Withstood ii, Power Frequency Dry withstand test on Secondary Winding 3KV for one minute. Withstood iv. Induced Over Voltage Withstand Test, on exciting from secondary side induced voltage on Primary Winding at 200Hz, 140KV for 30 Sec. Withstood \. Partial Discharge Value at 46KV: <1OPC vi. Accuracy Test for PT -Test results stated below. Metering Winding (1a-1n) | % of Rated Voltage | % of Rated Burden | RE(%) | PE(Min)| %ofRated Burden | RE(%) | PE (Min) 420 100% 012 | 181 25% 0.07 | 0.95 100 100% 0.11 | 1.52 25% 008 | 074 80 100% 011 | 144 25% 008 | 0.58 ‘Metering Winding (2a-2n) | % of Rated Voltage | % of Rated Burden | RE(%) | PE(Min)| %ofRated Burden | RE(%) | PE (Min) 120 100% -0.09 | 1.89 25% ooo [4.11 100 100% -o09 | 1.62 25% oo9 | 083 80 100% -o.08 [1.19 25% oto | 075 Tested By : For Electricfield Co. we Testing Engineer ELECTRICFIELD COMPANY, 75-81 INDUSTRIAL AREA, PHASE.tI, GANGYAL, JAMIMU-180010 (&K) INDIA. WEBSITE: wwn.seetreildin ROUTINE TEST CERTIFICATE FOR VOLTAGE TRANSFORMER (AS PER IS:3156-1992) Serial No. : 28513 Date 2 01-01-2024 [Type : Outdoor, Oil Cooled, Single Phase INO. Of winding 22 Rated Voltage : 66 KV fAccuracy Class 20.2, 0.2 Highest System Voltage : 72.5 KV [Rated Output 50 VA, SOVA Ratio : G6KV/V3/110V/V3-110V/V3, INo. Of Phase : Single insulation Level : 140/325KVp Rated VoltageFactor = 1.2Cont. & 1.5Time for 30 Sec. The following routine tests as stipulated in IS:3156-1992 were conducted on PT. i. Verification of Terminal Marking and Polarity. oK Hi. Power Frequency Dry withstand test on Primary Winding 3KV for one minute. Withstood ii. Power Frequency Dry withstand test on Secondary Winding 3KV for one minute. Withstood liv. induced Over Voltage Withstand Test, on exciting from secondary side induced voltage on Primary Winding at 200Hz, 140KV for 30 Sec. Withstood \v. Partial Discharge Value at AGKV: <10PC Accuracy Test for PT -Test results stated below. Metering Winding (1a-1n) %of Rated Voltage | % of Rated Burden | RE(%) | PE(Min) | %ofRatedBurden | RE(X) | PE (Min) 120 100% 0.15 | 052 25% 04 | 043 100 100% 014 | 028 25% 00s | 0.14 80 100% 014 | 024 25% 005 | 0.09 Metering Winding (2a-2n) %of Rated Voltage | %ofRated Burden | RE(%) | PE(Min)| %ofRatedBurden | RE(%) | PE (Min) 420 100% -0.17 | 053 25% 0.05 | 0.52 100 100% -0.17 | 032 25% 005 | 0.43 80 100% 0.16 | 025 25% 006 | 034 For Electricfield Co. Testing Engineer ELECTRICFIELD COMPANY, 75-81 INDUSTRIAL AREA, PHASE.lI, GANGYAL, 4AMMU-180010 (48K) INDIA. WEBSITE: ww electrcfiedin ROUTINE TEST CERTIFICATE FOR VOLTAGE TRANSFORMER (AS PER 1S:3156-1992) [Serial No. : 28516, 28517 & 28518 Date : 01-04-2024 [Type : Outdoor, Oil Cooled, Single Phase INO. Of winding 2 Rated Voltage : 66 KV [Accuracy Class 20.2, 3P Rated Output 7:50 VA, SOVA 66KV/V3/110V/V3-110V/V3 INo. Of Phase = Single insulation Level :140/325KVp Rated VoltageFactor _: 1.2Cont. & 1.5Time for 30 Sec. The following routine tests as stipulated in 1S:3156 1992 were conducted on PT. Verification of Terminal Marking and Polarity. oK Power Frequency Dry withstand test on Primary Winding 3KV for one minute. Withstood Power Frequency Dry withstand test on Secondary Winding 3KV for one minute. Withstood . Induced Over Voltage Withstand Test, on exciting from secondary side induced voltage on Primary Winding at 200H2, 140KV for 30 Sec. Withstood v. Partial Discharge Value at 46KV: <10PC vi._Accuracy Test for PT -Test results stated below. [Serial No. : 28516 ‘Metering Winding (1a-in) % of Rated Voltage | % of Rated Burden | RE(%) | PE(Min)| %ofRated Burden | RE(%) | PE (Min) 420 100% 0.14 | 2.29 25% 006 | 1.52 400 400% 0.43 [477 25% 0.07125 80 100% “043 | 1.58 25% 0.07 | 1.06 Protection Winding (2a-2n) % of Rated Voltage | _% of Rated Burden Ratio Error (%) Phase Error (Min) 100 100% 0.15 241 [Serial No. : 28517 Metering Winding (fa-in) % of Rated Voltage | %ofRated Burden | RE(%) | PE(Min) | %ofRated Burden | RE(X) | PE (Min) 120 100% -0.07 | 2.25 25% 0.12 | 4.11 100) 100% -0.07 | 1.82 25% 013 | 0.98 80 100% -0.06 [1.15 25% 014 | 076 Protection Winding (2a-2n) % of Rated Voltage | % of Rated Burden Ratio Error (%) Phase Error (Min) 100 100% -0.09 3.14 [Serial No. : 28518 Metering Winding (fa-in) % of Rated Voltage | % of Rated Burden | RE (%) RE (%)_| PE (Min) 120 100% “0.11 015 | 1.18 400 100% 016 | 096 80 100% 0.16 | 0.74 Protection Winding (2a-2n) % of Rated Voltage |_% of Rated Burden Ratio Error (%) Phase Error (Min) 100 100% 0.12 2.68 Tested By : For Electricfield Co. ike Testing Engineer

You might also like