ELECTRICFIELD COMPANY,
75-81 INDUSTRIAL AREA, PHASE-II, GANGYAL,
AMIMU-180010 J&K) INDIA. WEBSITE: wr lectin
Routine Test Certificate (As per IS : 2705)
Equipment Detail [:66 KV CURRENT TRANSFORMER Date: 1/2024
[: Mis DEVI POWERS PVT. LTD. ‘S.No : 28507
: DPPL/ZPL2023-24/1910, Dated. 19-10-2023.
[: Out Door, Oil Cooled , Live Tank CT
Core-l Core-It Coreiit Core-IV
100-5071 100-50/1A | _100-50/1A | _100-S0/1A
20VA 20VA =
02 P. PS
[ALEASE <5 15 = =
VKP eS = 250V at 100A | 250V at 100A
[Rated Short time Thermal Current 31.5 KA for 3 Seconds.
;. Verification of terminal marking and polarity. Verified OK
‘withstood
withstood
‘withstood
tharge Value at 46KV: <10PC
Metering Class Core : 1
HotPry 100% Burden
Carrent | Ratio Error (%) [Phase Error (Min)| Ratio Error (%)
120% B02 065 0.02
100% 0.02 114 0.02
20% 0.14 2.18 oot
3% “022 5.19 0.03.
120% “0.01 043 0.04
100% “0.01 045 001
20% 0.03 151 ‘001
3% 70.06 2:36 0.01
Protection Class Core :
%ofery 100% Burdea
eid Current Ratio Error (%) Phase Error (Min)
S0/A 100% 0.10 3a
00/1 100% 0.08 149
‘Composite Error (%) 018
PS Class Core II
Specified VKp(Vows]| Tex(mA) TA(VKp)_[_ 14 (lex mA) ‘Turn Ratio Error
EN ont
250V 32 25v 2 as aa
| PS Glass Core :1V
Specified VKp(VoKsy]| _Tex(mA) TACVKp) | _11 (lexmA) ‘Turn Ratio Error
SORA 0.03
fw fos fom | fae Tae
‘Tested By: iefield Co.,
Testing EngineerELECTRICFIELD COMPANY,
75-81 INDUSTRIAL AREA, PHASE-II, GANGYAL,
AMMU-IS0010 (U4) INDIA, WERSITR: wohl ia
Routine Test Certificate (As per IS : 2705)
[Equipment Detail [F665 KV CURRENT TRANSFORMER Date: 1/1/2024
[Customer's Name ‘Mis DEVI POWERS PVT. LTD. ‘S.No: 28508
[Order No. & Daie | DPPL/ZPI/2023-24/1910, Dated. 19-10-2023,
[Type of Transformer [: Out Door, Oil Cooled, Live Tank CT
Core Details Core Core-Il Coretit ‘Core-1V
Ratio 100-S0/1A 100-501 100-5071 100-5071
[Burden 20VA 20VA, = =
[Accuracy 02, SP PS PS
[ALRASE <5, 15 = -
VKP = = 250V at 100A [_250V at 100A
[Rated Short time Thermal Current 31.5 KA for 3 Seconds.
i Verification of terminal marking and polarity.
fi, Power frequency dry withstand test on primary winding at 140 KV for one minute.
iii. Power frequency dry withstand test on secondary winding at 3 KV for one minute. withstood
iv. Over voltage interturn Test. (Withstood ok for one minute.) ‘withstood
[v. Tan Delia Value = 0.243%
lvi. Partial Discharge Value at 46KV: <10PC
Metering Class Core : 1
aa % of Pry 100% Burden 25% Burden
2 Curreat _ | Ratio Error (%) [Phase Error (Min)| Ratio Error (%) [Phase Error (Min)]
120% 01 092 0.02 087
100% 0.02 4.45, 0.02 0.84
hea 20% 0.13 2.65 0.03 1.76
3% 024 494 "0.05 387
120% 0.01 0.53 0.02 0.35
100% 0.08 059 0.02 042
coe 20% 0.03 1.87, 0.01 1.29
5% 0.05 3.26 0.02 2.21
Protection Class Core : I
‘of Pry 100% Barden
Ratio Current Ratio Error (%) Phase Error (Min)
S0/1A 100% 0.06 3.62
100/14. 100% 0.01 1.32
Composite Error (%) 0.27
PS Class Core ? I
Specified VKp(Volts]| Tex(mA) TACVKp) —_|_11 (lex mA) ‘Turn Ratio Error
SO/1A 0.02
250V 28 28 37 me on
PS Class Core : IV
Specified VKp(Volls]| _fex(mA) TACK) _|_ 1 (lexma) Turn Ratio Error
SO/LA 0.04
250V 30 28 a one oa
Tested By: For Electriefield Co.,ELECTRICFIELD COMPANY,
75-81 INDUSTRIAL AREA, PHASE-II, GANGYAL,
JAMMCI8I010 (4K) INDIA. WERSTTE: ww ketrild.in
Routine Test Certificate (As per IS =
2705)
Equipment Detail ‘66 KV CURRENT TRANSFORMER Date: W72024
[Customer's Name Mis DEVI POWERS PVT. LTD. S.No : 28509
Order No. & Date DPPLIZPL/2023-24/1910, Dated. 19-10-2023,
Type of Transformer ‘Out Door, Oil Cooled , Live Tank CT
Core Details ‘Core-t Core-tI Corel CoreV,
Ratio 100-5071 100-S071A 100-5071 100-50/1A
Burden 20VA 20VA = =
Accuracy 02 ? PS rs |
JALE/SF, =5 15 = =
VKP = = ‘350V at 100A | 250V at 100A
Rated Short fime Thermal Current 31.5 KA for 3 Seconds.
i. Verification of terminal marking and polarity. Verified OK
Power frequency dry withstand test on primary winding at 140 KV for one minute. withstood
ower frequency dry withstand test on secondary winding at 3 KV for one minute. withstood
iv. Over voltage interturn Test, (Withstood ok for one minute.) withstood
vy. Tan Deita Value = 0.227%
[vi Partial Discharge Value at 46KV: <10PC
Metering Class Cor
Rath %ot Pry 100% Burden 25% Burden
da Current __[ Ratio Error (%) [Phase Error (Min| Ratio Error (%) [Phase Error (Min)
120% “0.05 061 0.03 047
100% “0.06 065 “0.08 056
he 20% “0.16 244 “0.06 18
5% 0.32 567 0.08 365
120% 0.02 0.34 0.01 027
100% 0.02 0.39 0.01 0.36
Lckats 20% "0.05, 141 “0.02 1.15
5% 0.08 2.48 0.04 1.88
‘of Pry
a Current
Burden
Ratio Error (%)
Phase Error (Min)
‘SOA 100%
0.09
4.06
100/14 100%
“0.07
1.80
‘Composite Error (%)
PS Class Core = III
023
[Specified VKp(Vous)] _ Tex(mA)
TLACVKp) _|_1-1 lex mA)
Tura Ratio Error
250V 26
275 33
30/1A 0.08
100A 0.04
PS Class Core :1V
Specified VKp(VoKS)] _lex(mA)
TACVKp)__[ 1.1. dexmA)
Tura Ratio Error
28
275 38
SO/A -0.07,
100A 0.03
For Electricfield Co.,
fii
ff 8)
‘sting EngineerELECTRICFIELD COMPANY,
75-81 INDUSTRIAL AREA, PHASE4I, GANGYAL, ”
JAMAEU-189010 B&K) INDIA. WEBSITE: ww.clectrifiehin
ROUTINE TEST CERTIFICATE FOR VOLTAGE TRANSFORMER (AS PER 1S:3156-1992)
[Serial No. : 28515 [Date £01-01-2024
[Type : Outdoor, Oil Cooled, Single Phase No. OF winding 2
Rated Voltage : 66 KV JAccuracy Class 02, 0.2
Highest System Voltage : 72.5 KV Rated Output 250 VA, 5OVA
Ratio : 66KV/V3/110V/V3-110V/V3, INo. Of Phase : Single
insulation Level : 140/325KVp Rated VoltageFactor _: 1.2Cont. & 1 5Time for 30 Sec.
[The following routine tests as stipulated in 1S:3156-1992 were conducted on PT.
i. Verification of Terminal Marking and Polarity. oK
ii. Power Frequency Dry withstand test on Primary Winding 3KV for one minute.
iii. Power Frequency Dry withstand test on Secondary Winding 3KV for one minute.
iv. Induced Over Voltage Withstand Test, on exciting from secondary side induced
voltage on Primary Winding at 200Hz, 140KV for 30 Sec.
\v. Partial Discharge Value at 46KV: <10PC
vi. Accuracy Test for PT -Test results stated below.
Metering Winding (1a-1n)
% of Rated Voltage | % of Rated Burden | RE(%) | PE(Min)| %ofRated Burden | RE(%) | PE (Min)
120 100% 0.06 | 217 25% 012 | 1.44
100 100% 0.05 | 1.80 25% 012 | 132
80 100% 0.05 | 167 25% Og 07
Metering Winding (2a-2n}
% of Rated Voltage | % of Rated Burden | RE(%) | PE(Min)| %ofRatedBurden | RE(%) | PE (Min)
120 400% ~o07 | 2.11 25% on | 143
100 100% 007 | 1.73 25% 012 | 1.24
80 100% -0.06 | 1.52 25% 042 | 412
Tested By : For Electricfield Co.
pe
=e EngineerELECTRICFIELD COMPANY,
7581 INDUSTRIAL AREA, PHASE, GANGYAL,
JAMMU-180010 (&K) INDIA. WEBSITE: ww clectriefitin
ROUTINE TEST CERTIFICATE FOR VOLTAGE TRANSFORMER (AS PER 1S:3156-1992)
[Serial No. : 28514 Date + 01-04-2024
HType : Outdoor, Oil Cooled, Single Phase NO. Of winding 2
Rated Voltage : 66 KV [Accuracy Class 202,02
Highest System Voltage : 72.5 KV Rated Output 250 VA, SOVA
Ratio : 66KV/V3/110VAV3-110V/V3 No. Of Phase = Single
insutation Level : 140/325KVp Rated VoltageFactor _: 1.2Cont. & 1.STime for 30 Sec.
The following routine tests as stipulated in IS:3156-1992 were conducted on PT.
i. Verification of Terminal Marking and Polarity. oK
ii. Power Frequency Dry withstand test on Primary Winding 3KV for one minute. Withstood
ii, Power Frequency Dry withstand test on Secondary Winding 3KV for one minute. Withstood
iv. Induced Over Voltage Withstand Test, on exciting from secondary side induced
voltage on Primary Winding at 200Hz, 140KV for 30 Sec. Withstood
\. Partial Discharge Value at 46KV: <1OPC
vi. Accuracy Test for PT -Test results stated below.
Metering Winding (1a-1n) |
% of Rated Voltage | % of Rated Burden | RE(%) | PE(Min)| %ofRated Burden | RE(%) | PE (Min)
420 100% 012 | 181 25% 0.07 | 0.95
100 100% 0.11 | 1.52 25% 008 | 074
80 100% 011 | 144 25% 008 | 0.58
‘Metering Winding (2a-2n) |
% of Rated Voltage | % of Rated Burden | RE(%) | PE(Min)| %ofRated Burden | RE(%) | PE (Min)
120 100% -0.09 | 1.89 25% ooo [4.11
100 100% -o09 | 1.62 25% oo9 | 083
80 100% -o.08 [1.19 25% oto | 075
Tested By : For Electricfield Co.
we
Testing EngineerELECTRICFIELD COMPANY,
75-81 INDUSTRIAL AREA, PHASE.tI, GANGYAL,
JAMIMU-180010 (&K) INDIA. WEBSITE: wwn.seetreildin
ROUTINE TEST CERTIFICATE FOR VOLTAGE TRANSFORMER (AS PER IS:3156-1992)
Serial No. : 28513 Date 2 01-01-2024
[Type : Outdoor, Oil Cooled, Single Phase INO. Of winding 22
Rated Voltage : 66 KV fAccuracy Class 20.2, 0.2
Highest System Voltage : 72.5 KV [Rated Output 50 VA, SOVA
Ratio : G6KV/V3/110V/V3-110V/V3, INo. Of Phase : Single
insulation Level : 140/325KVp Rated VoltageFactor = 1.2Cont. & 1.5Time for 30 Sec.
The following routine tests as stipulated in IS:3156-1992 were conducted on PT.
i. Verification of Terminal Marking and Polarity. oK
Hi. Power Frequency Dry withstand test on Primary Winding 3KV for one minute. Withstood
ii. Power Frequency Dry withstand test on Secondary Winding 3KV for one minute. Withstood
liv. induced Over Voltage Withstand Test, on exciting from secondary side induced
voltage on Primary Winding at 200Hz, 140KV for 30 Sec. Withstood
\v. Partial Discharge Value at AGKV: <10PC
Accuracy Test for PT -Test results stated below.
Metering Winding (1a-1n)
%of Rated Voltage | % of Rated Burden | RE(%) | PE(Min) | %ofRatedBurden | RE(X) | PE (Min)
120 100% 0.15 | 052 25% 04 | 043
100 100% 014 | 028 25% 00s | 0.14
80 100% 014 | 024 25% 005 | 0.09
Metering Winding (2a-2n)
%of Rated Voltage | %ofRated Burden | RE(%) | PE(Min)| %ofRatedBurden | RE(%) | PE (Min)
420 100% -0.17 | 053 25% 0.05 | 0.52
100 100% -0.17 | 032 25% 005 | 0.43
80 100% 0.16 | 025 25% 006 | 034
For Electricfield Co.
Testing EngineerELECTRICFIELD COMPANY,
75-81 INDUSTRIAL AREA, PHASE.lI, GANGYAL,
4AMMU-180010 (48K) INDIA. WEBSITE: ww electrcfiedin
ROUTINE TEST CERTIFICATE FOR VOLTAGE TRANSFORMER (AS PER 1S:3156-1992)
[Serial No. : 28516, 28517 & 28518 Date : 01-04-2024
[Type : Outdoor, Oil Cooled, Single Phase INO. Of winding 2
Rated Voltage : 66 KV [Accuracy Class 20.2, 3P
Rated Output 7:50 VA, SOVA
66KV/V3/110V/V3-110V/V3 INo. Of Phase = Single
insulation Level :140/325KVp Rated VoltageFactor _: 1.2Cont. & 1.5Time for 30 Sec.
The following routine tests as stipulated in 1S:3156 1992 were conducted on PT.
Verification of Terminal Marking and Polarity. oK
Power Frequency Dry withstand test on Primary Winding 3KV for one minute. Withstood
Power Frequency Dry withstand test on Secondary Winding 3KV for one minute. Withstood
. Induced Over Voltage Withstand Test, on exciting from secondary side induced
voltage on Primary Winding at 200H2, 140KV for 30 Sec. Withstood
v. Partial Discharge Value at 46KV: <10PC
vi._Accuracy Test for PT -Test results stated below.
[Serial No. : 28516 ‘Metering Winding (1a-in)
% of Rated Voltage | % of Rated Burden | RE(%) | PE(Min)| %ofRated Burden | RE(%) | PE (Min)
420 100% 0.14 | 2.29 25% 006 | 1.52
400 400% 0.43 [477 25% 0.07125
80 100% “043 | 1.58 25% 0.07 | 1.06
Protection Winding (2a-2n)
% of Rated Voltage | _% of Rated Burden Ratio Error (%) Phase Error (Min)
100 100% 0.15 241
[Serial No. : 28517 Metering Winding (fa-in)
% of Rated Voltage | %ofRated Burden | RE(%) | PE(Min) | %ofRated Burden | RE(X) | PE (Min)
120 100% -0.07 | 2.25 25% 0.12 | 4.11
100) 100% -0.07 | 1.82 25% 013 | 0.98
80 100% -0.06 [1.15 25% 014 | 076
Protection Winding (2a-2n)
% of Rated Voltage | % of Rated Burden Ratio Error (%) Phase Error (Min)
100 100% -0.09 3.14
[Serial No. : 28518 Metering Winding (fa-in)
% of Rated Voltage | % of Rated Burden | RE (%) RE (%)_| PE (Min)
120 100% “0.11 015 | 1.18
400 100% 016 | 096
80 100% 0.16 | 0.74
Protection Winding (2a-2n)
% of Rated Voltage |_% of Rated Burden Ratio Error (%) Phase Error (Min)
100 100% 0.12 2.68
Tested By : For Electricfield Co.
ike
Testing Engineer