Professional Documents
Culture Documents
10.1109@TIA.2020.3004769
10.1109@TIA.2020.3004769
10.1109@TIA.2020.3004769
fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2020.3004769, IEEE
Transactions on Industry Applications
Abstract – A simplified arc-flash analysis technique that service-entrance equipment through the low-voltage switchgear
allows for determination of the settings of overcurrent protective or motor control centers (MCCs) in the facility. If the arc-flash
devices and selection of arc-rated PPE based on a reference study ends here, many locations where workers may be exposed
constant incident energy boundary area is presented in this to arc-flash hazards go “unanalyzed”—control panels,
paper. The reference areas are created based on the equations disconnect switches, junction boxes, etc. Extending the arc-flash
of IEEE Std. 1584™-2018 [1], taking into consideration potential study to cover these locations can cause field data collection
variation in the input parameters described in the standard. requirements and the analysis time required for the studies to
The method presented in this paper provides an efficient and grow tremendously, and can ultimately require several times the
straightforward means to simultaneously consider the effects of effort needed to execute the more traditional study work scope.
varying input parameters on arc-flash calculation results by Evaluation of arc-flash hazards in these areas can be aided by
plotting areas of constant incident energy on a time-current plot. application of simplified analysis methods.
Actual power distribution equipment may have multiple electrode Though constant energy lines are useful, changes to IEEE Std.
configurations, gaps between conductors, operating voltages, as 1584™-2018, made simple lines incapable of characterizing the
well as a range of available bolted short-circuit currents and incident energy levels. IEEE Std. 1584™-2018 adds several
variation in the size of equipment enclosures. The multiple input variables to the arc-flash calculation model and has
combinations require dozens of simulations to determine the enhanced the sensitivity of the incident energy calculations to the
worst-case incident energy levels. Unlike previous existing input parameters. Single-parameter C-lines are
implementations of incident energy curves, which were typically inadequate to represent the potential variation in the physical
single line representations of the incident energy, the plotting of electrical parameters of equipment such as low-voltage (LV)
bounded areas (C-area plots) allows for multiple parameter switchgear, MCCs, medium-voltage (MV) switchgear, etc. Power
sweeps to determine a band of variation within a defined set of system parameters required for the incident energy calculation
parameter combinations. may vary significantly because of equipment design and
operating conditions. The parameter variation can affect the
Index Terms — Arc fault currents, arc flash, arc-flash operating voltage, short-circuit current, arc current, gap between
boundary, arc-flash hazard analysis, IEEE 1584, incident energy, conductors, enclosure dimensions (height, width and depth),
working distance working distances, and finally, electrode orientation and
arrangement (Electrode Configurations VCB, VCBB, HCB) [1].
INTRODUCTION To help account for all these variables, the idea of constant
energy boundary area plots – the C-area plots – are introduced
Constant-energy lines, sometimes referred to as C-lines [2], C- to help reduce the analysis requirements and eliminate some of
curves or energy boundary curves [3], have been used over the the multiple analysis combinations caused by the parameter
last 12 to 15 years as a reference and aid for calculation of arc- variation.
flash incident energy levels. These curves were developed
based on the solution of the incident energy equation published BACKGROUND
in IEEE Std. 1584™-2002 [4]. The curves may be used for
practical or simplified arc-flash hazard analysis, such as when Arc-flash incident energy calculations are highly complex.
they are used as a guide for setting or selecting overcurrent According to [4], many variables must be considered, including
protective devices (OCPDs) during the protective device system voltage, available fault current, the duration of the arc,
coordination study conducted before the arc-flash hazard the length of the air gap between phase conductors or from
analysis. phase to ground, etc. Further complicating the analysis is the
Simplified analysis techniques supported by these types of relationship between variables. For example, the incident energy
curves also help make arc-flash analysis more efficient in some is based largely on the available fault current and the arcing
cases. According to [3], short-circuit and coordination studies in duration. However, the arcing duration, that is the clearing time
industrial facilities in the US have typically extended from the of the upstream OCPD, is dependent on the arcing fault current
0093-9994 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Exeter. Downloaded on July 01,2020 at 15:30:25 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2020.3004769, IEEE
Transactions on Industry Applications
0093-9994 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Exeter. Downloaded on July 01,2020 at 15:30:25 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2020.3004769, IEEE
Transactions on Industry Applications
12.552
The coefficients a1, a2, a3, b1, b2, b3 are of the form: 𝐸14300 = 𝑇 × 10(𝑐3) (9)
50
an = k1 + k 2lg I bf + k 3lg G The form of cn where n = 1 is shown below. The forms for c2
and c3 are similar, with the exception that Iarc 600 is replaced with
bn = k 4 I bf6 + k 5I bf5 + k 6 I bf4 + k 7 I bf3 + k 8I bf2 + k 9I bf + k10 Iarc_2700 and Iarc_14300, respectively.
Where: cn = k1 + k 2lg G +
I bf Bolted fault current (rms) (kA) k 3I arc_600
I arc_600 Ave. rms arc current at Voc = 600 V (kA) +
k 4 I + k 5I + k 6 I + k 7 I bf4 + k 8I bf3 + k 9 I bf2 + k10 I bf
7
bf
6
bf
5
bf
I arc_2700 Ave. rms arc current at Voc = 2700 V (kA)
1
I arc_14300 Ave. rms arc current at Voc =14 300 V (kA) k11lg I bf + k12lg D + k13lg I arc_600 + lg
CF
G Gap between electrodes (mm)
k1to k10 Coefficients provided in Table 1 of [1] Where:
lg log10 E600 Incident energy (IE) at Voc = 600 V (J/cm2)
E2700 IE at Voc = 2700 V (J/cm2)
Note that regardless of the actual voltage, it is necessary to E14300 IE at Voc = 14300 V (J/cm2)
determine intermediate arcing current values using (1), (2) and T Arc duration (ms)
(3) to derive the final arc current. The three intermediate
equations are processed through interpolation equations to apply
G Gap between conductors (mm)
the effect of voltage on the final current. The interpolation I arc_600 rms arc current for 600 V (kA)
process required to derive the final current is shown in (4), (5) I arc_2700 rms arc current for 2700 V (kA)
and (6).
I arc_14300 rms arc current for 14300 V (kA)
I arc_2700 - Iarc_600 I bf Bolted fault current (symm. rms) (kA)
I arc_1 = (Voc - 2.7)+ Iarc_2700 (4)
2.1 D Working distance (mm)
CF Enclosure size correction factor (see 4.6 and 4.8
I arc_14300 - Iarc_2700 of [1])
I arc_2 = (Voc - 14.3)+ Iarc_14300 (5) lg log10
11.6
k1to k13 Coefficients provided in Table 3, Table 4, and
I arc_1 (2.7 - Voc ) I arc_2 (Voc - 0.6) Table 5 of [1].
I arc_3 = + (6)
2.1 2.1 A final round of interpolation is required to obtain a final
incident energy as described in Section 4.9 of [1]. The previous
Where: equations (1) to (9) clearly show that in order to solve for both the
I arc_1 Interpolated term between 600 V and 2700 V (kA) final arc current and incident energy requires solving for six
intermediate values of current and energy. This situation is the
I arc_2 Interpolated term when Voc > 2700 V (kA) main reason why for MV systems, it is impossible to apply a direct
I arc_3 Interpolated term used when Voc < 2700 V (kA) solution to obtain the constant energy time required as described
in [3].
Voc System pre-fault voltage (kV)
When 0.600 < Voc ≤ 2.7, the final value of arcing current is I arc_3 B. Determination of MV C-lines
and when the voltage > 2.7 kV the final value of arcing current is
The MV C-line plot points for the new IEEE Std. 1584™-2018
I arc_2 . calculation model can be derived using an iterative approach.
The form of the incident energy equations for MV systems in The iterations can be made using time (arc duration) as the
(7), (8), and (9) also use interpolation, and are similar in form to solution parameter. We can setup a residual for the termination
(1), (2) and (3) for arcing current. of the iterative process based on the difference between the
constant energy setting and the estimated incident energy at
each step. Equations (10) and (11) illustrate the concept.
0093-9994 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Exeter. Downloaded on July 01,2020 at 15:30:25 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2020.3004769, IEEE
Transactions on Industry Applications
0093-9994 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Exeter. Downloaded on July 01,2020 at 15:30:25 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2020.3004769, IEEE
Transactions on Industry Applications
Fig. 5. Iarc versus Voc for 208 V to 1000 V (Fig G.32 of [1])
0093-9994 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Exeter. Downloaded on July 01,2020 at 15:30:25 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2020.3004769, IEEE
Transactions on Industry Applications
0093-9994 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Exeter. Downloaded on July 01,2020 at 15:30:25 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2020.3004769, IEEE
Transactions on Industry Applications
0093-9994 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Exeter. Downloaded on July 01,2020 at 15:30:25 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2020.3004769, IEEE
Transactions on Industry Applications
0093-9994 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Exeter. Downloaded on July 01,2020 at 15:30:25 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2020.3004769, IEEE
Transactions on Industry Applications
for VCB superimposed on the C-area plot for both VCBB and C-area plots rather than C-lines, could be used to identify
VCB combined. minimum arcing current levels for typical protective devices so
that the effect of differing system or equipment parameters can
be more readily assessed. This would be particularly useful
when a company operated many sites or installations that are
electrically similar – e.g., at oil well pumping units, cell phone
tower sites, etc., and desired to establish maximum incident
energy exposure levels at each location.
The case studies discussed in IV.A and IV.B illustrate the use
of the C-area plots in both MV and LV applications.
TABLE II
INPUT PARAMETER VARIATION FOR MV APPLICATION EXAMPLE
Pos. Neg.
Input parameter Value
var. (%) var. (%)
Voltage (kV) 4.16 5 5
Gap (mm) 102 30 30
Working Distance (mm) 914 10 10
Height (mm) 660 20 20
Width (mm) 660 20 20
Depth (mm) 660 20 20
Ibf Range (Min to Max) (kA) 2.5 to 5
Electrode Configurations VCB, HCB
Fig. 13. C-area plots for VCB and Mix of VCBB and VCB
0093-9994 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Exeter. Downloaded on July 01,2020 at 15:30:25 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2020.3004769, IEEE
Transactions on Industry Applications
The lower C-area plot is for a bus fault location and its circuit. To determine the required PPE at each piece of load
electrode configuration is VCB. The upper C-area plot is for a equipment, it is not necessary to solve for the exact incident
fault on the line side of the main circuit breaker “Main CBA”, and energy at each location. Instead, it may be sufficient to simply
it was determined that both VCB and HCB electrode determine if the maximum available incident energy falls below
configurations should be considered for this location. The C-line 12 cal/cm2 so that a worker can determine if that level of PPE is
shown in the middle of the upper C-area plot represents an 8 adequate. If the energy may be higher, then further analysis
cal/cm2 VCB line with no input parameter variation. would be required. The plot in Fig. 16 shows a 12 cal/cm2 C-area
For faults near the maximum short-circuit current, the plot along with the time-current curve for a 300 A class RK-5 LV
corresponding arc current and corresponding total clearing time fuse curve. The C-area plot is generated based on the data
of the upstream fuse (arc duration) is below the C-line. Based on provided in Table III.
the C-line, the incident energy for an arc flash on the line side of
“Main CBA” should be less than 8 cal/cm2. However, the fuse
curve clearly overlaps the C-area plot for the VCB/HCB
configuration C-area plot. The incident energy for a fault on the
line side of “Main CBA” is expected to release incident energy
higher than 8 cal/cm2 for the entire short-circuit current range.
The C-area curve clearly indicates that a different fuse size
selection is needed to ensure that the incident energy on the line
side is limited to the desired value (8 cal/cm2). It is determined
that a smaller fuse size can be used for this application and the
150 Amp fuse can be changed to 125 Amp. Since the
transformer primary amp rating is 100 Amps, the new size should
also protect the transformer better against other faults. After
making the adjustment, as shown in Fig. 15, the incident energy
calculated would once again be below 8 cal/cm2 at the indicated
Arc Current level as the fuse curve is fully below the C-area plot
at this point.
The VCB C-area plot in Fig. 14 shows that the relay operating
time is well below the lower portion of the C-area at the indicated
arc current level, as this point is well within the instantaneous
operating region of overcurrent relay “OCR A”. The energy is
clearly lower than 1.2 cal/cm2 even when adding circuit breaker
“Main CBA” opening time.
10
0093-9994 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Exeter. Downloaded on July 01,2020 at 15:30:25 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2020.3004769, IEEE
Transactions on Industry Applications
CONCLUSIONS
11
0093-9994 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Exeter. Downloaded on July 01,2020 at 15:30:25 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2020.3004769, IEEE
Transactions on Industry Applications
energy and arc-flash boundary distance. calculation standards which include ANSI and IEC short-circuit,
Finally, the C-area plots provide a more realistic and AC & DC arc flash and transient stability. Albert has participated
conservative method to account for variation in parameters not in several IEEE seminar and presentation for different IEEE
previously considered by IEEE Std. 1584™-2018 such as the communities including Orange County and San Francisco
enclosure opening height, width and depth. Actual equipment Industry Application Society.
such as MCCs include a variety of enclosure or “bucket”
dimensions and it may be impractical to otherwise consider all of Antony Parsons, P.E., (M’96) received the BSEE degree
the individual parameters in a study. from the University of Houston in 1995, then received the MSE
and Ph.D. degrees from the University of Texas at Austin in 1996
and 1999, respectively, all in electrical engineering. He then
REFERENCES joined Schneider Electric and is presently a Senior Staff Engineer
in the Power Systems Engineering group, where he is
[1] IEEE 1584-2018, IEEE Guide for Performing Arc-Flash responsible for providing analysis, design, and troubleshooting
Hazard Calculations, New York, NY: IEEE support to commercial and industrial facilities. Antony is a
[2] Tinsley, H.W. and Hodder, M., “A Practical Approach to Arc member of the IEEE Industry Applications Society and of the
Flash Hazard Analysis and Reduction,” IEEE Transactions IEEE P1584 working group on Arc Flash Hazard Calculations.
on Industry Applications, vol. 41, no. 1, 2005. He is a licensed engineer in the state of Texas.
[3] Parsons, A.C., Leuschner, W.B., and Jiang, K.X.,
“Simplified Arc-Flash Hazard Analysis Using Energy
Boundary Curves,” IEEE Transactions on Industry
Applications, vol. 44, no. 6, 2008.
[4] IEEE Std. 1584-2002, IEEE Guide for Performing Arc-Flash
Hazard Calculations, New York, NY: IEEE.
[5] NFPA 70E-2018, Standard for Electrical Safety in the
Workplace, Quincy, MA: NFPA
[6] IEEE 1584.1-2013, IIEEE Guide for the Specification of
Scope and Deliverable Requirements for an Arc-Flash
Hazard Calculation Study in Accordance with IEEE Std
1584™, New York, NY: IEEE
[7] A. Marroquin and A. Parsons, "Application of Incident
Energy Reference Boundary Area Plots in TCCS
Considering IEEE 1584-2018 Input Parameter Variability,"
2019 IEEE Petroleum and Chemical Industry Committee
Conference (PCIC), Vancouver, BC, Canada, 2019, pp.
369-380, doi: 10.1109/PCIC30934.2019.9074502.
VITAE
12
0093-9994 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Exeter. Downloaded on July 01,2020 at 15:30:25 UTC from IEEE Xplore. Restrictions apply.