khan2018

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

Investigation of the effects of critical incident energy

parameters using ETAP® to reduce arc flash hazards


Abeera Khan Mohammad Mohsin Aman
Department Of Electrical Engineering Department Of Electrical Engineering
NED University of Engineering and Technology NED University of Engineering and Technology
Karachi, Pakistan Karachi, Pakistan
abeera2014@gmail.com mohsinaman@neduet.edu.pk

Abstract— Arc flash is one of the major causes of injuries and the arc flash power, the distance of the person from the arc
death in electrical work related incidents. Arc flash risk flash source and the personal protective equipment (PPE) worn
assessment is required to protect the working personnel from the by the worker at the instant when arc flash event takes place.
hazards of an arc flash event. This paper conducts an Common injuries include broken bones, collapsed lungs,
investigation to analyze the effects of critical parameters that inhalation of toxic gases and effects on the eye sight and
influence incident energy level at different locations in a power hearing [4].
system. An electrical network, a representative of small industrial
facility, is modelled and in different scenarios, incident energy is Relating to the potential dangers and their prevention, many
determined by simulating an arc flash analysis based on IEEE codes and standards exist, which are updated with time. As per
1584 standard on Electrical Transient Analyzer Program the Occupational Safety and Health (OSH) act, it is the sole
(ETAP). The results of simulation are then presented, plotted and responsibility of the employers to provide a safe and healthful
discussed. Different mitigation techniques are also proposed to work place to the employees. Employers must ensure
reduce incident energy. The results could help the field personnel compliance with every applicable OSHA standards. For this
to know about the parameters that are crucial to incident energy. cause, the Code of Federal Regulations (CFR) is referred by
This will help them to explore different mitigation techniques the OSHA. Employers are responsible for assessing the
against arc flash event. workplace to determine if hazards exist or may exist and
should also make sure that every working personnel uses the
Keywords-arc flash analysis; incident energy; IEEE 1584
appropriate PPE for their protection [5]. Moreover, the workers
exposed to the energized equipment while working, must be
I. INTRODUCTION AND BACKGROUND qualified and well trained for the tasks, they are performing and
A rapid release of energy, caused by an arcing fault that must be using the appropriate PPE [6]. There must be adequate
results from a short circuit between two live conductors, can be PPE for specific body parts and when working around live
defined as an arc flash event. The electrical arc that occurs equipment, insulated tools are necessary to use [7].
between these energized conductors, with exception to laser, is National Fire Protection Association’s (NFPA 70®),
the hottest known substance on earth. The arc can reach National Electrical Code (NEC®) has laid the foundation for
temperatures up to and beyond 20,000 K, which is electrical safety in industrial, commercial facilities in the
approximately four times as hot as the sun’s surface [1][2]. It is United States and around the globe. In 2002, a new
a hazardous incident because of the release of energy due to an requirement was added as Article 110.16 to the 2002 edition of
electrical arc, which is the flow of current through the air the NEC which was the first arc flash hazard reference, NFPA
between two phase conductors or between a phase conductor had. It required that the equipment must be labeled to warn
and ground. Arc flash hazard is quantified in terms of incident qualified working personnel about electrical arc flash dangers
energy (calories per square centimeters, cal/cm2). A rapid [8].
heating of air, in the proximity of arc fault, takes place due to
the rise in pressure and temperature and consequently arc flash To have protection against electrical arc flash hazards,
produces. This releases intense heat, light and pressure waves PPEs are used. PPE is the clothing worn by the working
with a loud sound. Molten steel is spread out to large distances personnel and is necessary when working around live
and causes complete damage to equipment and severe injuries equipment (Fig. 1) because even though safe work practices
or even death of working personnel. The injuries may result and timely maintained equipment reduce the occurrence of an
from shock waves, radiations, gases inhaled, flying shrapnel arcing fault, the workers who are exposed to hazards need to be
and blinding light [3]. appropriately protected. If PPE rating is adequate with the
incident energy level then survivability from arc flash gets
The main cause of the arc flash event is the insulation increased [9]. For selecting proper PPE, the incident energy
failure occurs between two energized conductors which are at calculated at various system locations, provide basis. Based on
sufficient voltage level. The insulation failure can have many the incident energy level, PPE may include flame resistant
reasons like aging, overheat, treeing, loose connections and clothing, flash suits, arc hoods, hardhat, safety glasses, shoes,
human error etc. [2]. Degree of injury or burn is the function of gloves, face shield, etc. PPE should be appropriate means that
978-1-5386-5482-8/18/$31.00 ©2018 IEEE
empirical method and are true for a system having the
following specifications [10]:
x Voltage level: 208V-15kV.
x Frequency: 50Hz-60Hz.
x Bolted fault current: 700A-106kA.
x Gaps between conductors: 13mm-152mm.
x Three phase faults.
Following equations are used to calculate the arcing fault
current, normalized incident energy, the actual incident energy
and the boundary distance [10]:

Figure. 1 A workman wearing PPE


log Ia = K + 0.662 log Ibf + 0.0966 V + 0.000526 G

it should not be as little as to leave the personnel unshielded + 0.5588 V*log Ibf ̶ 0.00304 G*log Ibf (1)
and not much bulky as it could restrict movement or could
cause other problems like increased heat stress or increased risk where Ia represents the arcing fault current in kA. K equals
associated with a specific work. Unlike the previous editions of 0.153 for open configurations and -0.097 for box
NFPA 70E, where levels of PPE were determined as per hazard configurations. Ibf represent the bolted fault current in kA. V
risk category (HRC), the levels of PPE needed for different and G refers to the system voltage in kV and gap between the
tasks has been described as per arc rated PPE category in the conductors respectively.
latest edition. For actual requirements, it is advisable to look
for NFPA 70E.
Log En = K1 + K2 + 1.081 log Ia + 0.0011 G (2)
Arc flash study is necessary to find out the various system
locations, potentially exposed to arc flash hazards. The study is where K1 is -0.792 for open configurations and -0.0555 for
based on understanding the hazards, calculating the incident box configurations. K2 is taken as 0 for underground and high
energy values, protecting the equipment and personnel by resistance grounded system and -0.113 for grounded system.
reducing the incident energy levels which is a major concern in
industrial facilities that are in the design phase or already in
existence. For this purpose, it is essentially important to
investigate the different system parameters that are influencing E = Cf En ( )( ) (3)
the incident energy levels and then employ arc flash mitigation
techniques accordingly. where Cf is taken as 1.0 for voltages above 1 kV and 1.5
This paper attempts to investigate the parameters to which for voltages at or below 1 kV. t represents the arcing time. D
incident energy is sensitive at large, by modelling and represents the working distance in mm. x refers to the distance
simulating a small typical network using ETAP software. exponents that are defined in IEEE standard 1584.
Based on the simulated results, different methods to mitigate
the arc flash hazards are also briefly discussed.
(4)
The organization of the paper is as described. Section II
presents a mathematical model which helps to calculate the
arcing fault current, incident energy and the boundary distance. where DB is the boundary distance in mm and EB is the
Then in section III, test network is described, modeled and incident energy value at the boundary in cal/cm2.
simulated using the ETAP software. The simulated results are
presented and are discussed in detail, along with different III. NETWORK MODELLING AND SIMULATION
mitigation methods in section IV, followed by conclusion in
Network modelling and simulation is done on the ETAP
section V.
software which is an efficient software and a comprehensive
analysis platform for the simulation, design and protection of
II. INCIDENT ENERGY CALCULATIONS the distribution and industrial power systems. Many EPC
To provide the theoretical foundation and background for companies, consultancies and utilities use ETAP for load flow
the arc flash energy calculation, IEEE standard 1584 acts as an study, short circuit study, reliability analysis, harmonic
elaborate reference. It contains the formulations that can be analysis, arc flash analysis, protection coordination etc. to
used to calculate the incident energy in an arc flash event. Once determine the safe limits of the system.
the power system model is developed with all the required data The system is supplied by the utility at 13.8 kV with
defined, the ETAP software can perform the calculations. The available short circuit current as 7.949 kA and X/R ratio of 20.
formulations included in IEEE standard 1584 is based on an The system is fed through a delta-wye step down transformer
of 3 MVA, supplying a switchgear at 0.48 kV. The switchgear x The time (in sec) required to clear an arcing current (t).
bus (Swgr) feeds a Motor Control Center (MCC) and a
distribution power panel (Pwr_panel) at 208 V through a delta- The base value of every parameter is varied by the same
wye transformer of 0.75 MVA. The single line diagram is ratio: one-fourth, one-half, twice, quadruple and octuplet to get
shown in Fig 2. a fair enough comparison. The effects of the above mentioned
parameters are analyzed through simulation and results are
The parameters are set as per IEEE 1584 to model the tabulated and discussed as follows:
system and short circuit study is perform on the test system to
find out the available bolted fault current (Ibf) values at each A. Incident energy vs gap between conductors
bus in order to determine the arcing current (Ia) and incident
The base values of gap between conductors for BUS 1,
energy (E) along with arc flash boundaries (AFB). The results
Swgr, Pwr_panel and MCC are 153 mm, 32 mm, 30 mm and
are mentioned in Table I.
25 mm respectively. These values are changed with a defined
ratio and the results are simulated for incident energies. The
IV. RESULTS Table II shows the simulated incident energies of all equipment
In order to determine the effects of significant parameters that or buses with adjustment in gap between conductors. The
contributes in the incident energy levels, one parameter at a incident energies against variation in the gap between
time is varied, keeping the remaining unchanged while conductors for all buses are plotted in Fig. 3. As the gap
performing arc flash analysis. The effects of following four between conductors increases, the incident energy also
parameters related to incident energy are examined: increases. Likewise, as the gap decreases, the incident energy
also get reduced showing a direct relation between them.
x The gap between conductors or buses (in mm) of the However, incident energy of Swgr varies to a greater extent
electrically energized equipment (G) where an arc can with the variation in gap since its graph is steeper than that of
occur. BUS 1, Pwr_panel and MCC as shown in Fig. 3, implying that
x The distance of the working personnel (in inches) from the effect of change in gap has more impact on the incident
the arc flash source (D). energy of the Swgr bus. Additionally, it should be noted that
several of the ranges tested are outside of those recommended
x The available short circuit current (in kA) from the by IEEE 1584 “Equipment and Voltage Class Factors” [10]. It
utility. is to be mentioned here that once the gap between conductors
are set, it is difficult to adjust it to get reduced level of incident
energy. However, other methods can be considered for this
purpose which do not require adjustment in the conductor gaps.

TABLE II. INCIDENT ENERGY VALUES AT VARRYING GAPS BETWEEN


CONDUCTORS (G)

Incident energy (cal/cm2)

G G G 2G 4G 8G
Bus ID

BUS1 0.543 0.6 0.73 1.071 2.325 6.196


Swgr 13.093 13.361 13.914 15.088 17.744 24.538
Pwr_panel 5.857 5.962 6.19 6.682 7.778 10.541
MCC 4.554 4.636 4.77 5.091 5.778 7.444

Figure. 2 Single line diagram of network

TABLE I. BOLTED FAULT CURRENT, ARCING CURRENT, INCIDENT


ENERGY AND ARC FLASH BOUNDARY

Ibf Ia E AFB
Bus ID (kA) (kA) (cal/cm2) (ft)
BUS1 8.02 7.82 0.73 1.17
Swgr 51.49 24.66 13.91 10.55
Pwr_panel 27.81 8.92 6.11 4.05
MCC 51.49 26.59 4.78 3.48 Figure. 3 Simulated incident energy vs gaps between conductors for all buses.
B. Incident energy vs distance from energized equipment adjustment in the utility available short circuit current, at each
The base working distance from electrically energized bus is presented in Table IV, keeping all other parameters
equipment for BUS 1, Pwr_panel and MCC are 18 inches and unchanged. Fig. 5 shows the graph between simulated incident
24 inches for Swgr bus. The distances are varied and the results energies at different utility available short circuit current for
are simulated. The incident energy against the variation in the each bus.
working distances at each bus is tabulated in Table III. Fig. 4 As the utility available short circuit current gets increased,
shows the graph between simulated incident energies at the short circuit current level gets increased throughout the
different distances for each bus. network which increases the arcing current and so the incident
As the working distance from an exposed electrical energy. As the utility available short circuit current gets
equipment gets increased, the incident energy decreases; as the decreased, it decreases the short circuit current level
distance decreases, the incident energy increases showing an throughout the network which reduces the arcing current and
inverse relation between the two. hence incident energy also gets reduced.

Taking in to account the relation between incident energy Although the available short circuit current from the utility
level and the working distance of the worker, methods can be cannot be altered to get reduced incident energy levels, the
employed that allow the working personnel to work with simulated results in the Table IV shows that the reduced
increased distances. Remotely operated devices are available energy levels can still be achieved if short circuit current
from various manufactures for the safe operation of switching limiting methods can be used to reduce short circuit currents
and protection devices. Racking operation of breakers is much within the system at suitable locations. Fault current levels at
hazardous task and major proportion of electrical work related numerous locations in the system can be minimized with
injuries and accidents belong to this type of operation. The current limiting reactors but using current limiting reactors is
remote racking device enables the worker to stand aside and an expensive approach. The best method to reduce fault
the device perform racking function, resulting in reduced current is using the current limiting fuses or circuit breakers
energy due to increased working distance [11]. which functions by good protection schemes like relays
having less time delay, better security, sensitivity and also
with backup protection schemes. A fault current limiter (FCL)
C. Incident energy vs available short circuit current
or triggered current limiter (TCL) limits the fault current in
The network is supplied by the utility at 13.8 kV with 7.949 time and magnitude by operating in ¼ to ½ cycles, rendering
kA as available short circuit current. This short circuit current no resistance to the load current. With the help of fast fault
value is changed as per defined ratio and the results are clearance, the energy is much limited [3].
simulated. The effects on incident energy caused by the
The fault current can also be reduced by avoiding parallel
operation of transformers where possible. Parallel operation
TABLE III. INCIDENT ENERGY VALUES AT VARRYING WORKING restricts the working between the secondary side of
DISTANCES (W)
transformer and the downstream secondary breaker which is
one of the highest arc flash hazard area. This results due to the
Incident energy (cal/cm2) reason that the primary side breakers sense low value of
current passes through that area and would trip after a long
delay sensing low value of current at that side which results in
W W W 2W 4W 8W
Bus ID high arc flash energy [12].
BUS1 11.631 2.908 0.73 0.182 0.045 0.011
Swgr 107.221 38.625 13.91 5.012 1.806 0.65 D. Incident energy vs time required to clear the fault
Pwr_panel 60.236 19.314 6.11 1.988 0.637 0.204 To find out the effects of the time required by the
MCC 46.482 14.904 4.77 1.532 0.491 0.158 upstream over current protective device (FCT) to clear an
arcing fault, on the incident energy, the base values of them
are varied and the results are simulated. The base values are
0.048 sec, 0.249 sec, 0.208 sec and 0.05 sec for BUS 1, Swgr,
Pwr_panel and MCC respectively. The simulated results are
presented in Table V. Fig 6 shows the graph between different
values of FCTs and corresponding incident energy values of
each bus, tabulated in Table V. It can be observed that the
incident energy values for all buses are directly proportional to
the fault clearing time of their respective upstream protective
devices.
This suggest that if the fault clearing time can be reduced
by revising the protection settings of the devices or by
replacing the existing protective devices with efficient one,
this would result in reduced arc flash energies.
Figure. 4 Simulated incident energy vs distance from energized euipment This is also implemented on the test system under
for all buses
TABLE IV. INCIDENT ENERGY VALUES AT VARYING AVAILABLE SHORT long time pickup current of 2000 A, short time pickup current
CIRCUIT FROM UTILITY (I)
of 3200 A and instantaneous pickup current value of 6400 A.
With these pickup settings, LVCB_3 clears the associated
Incident Energy (cal/cm2) arcing fault current at Pwr_panel in 0.208 sec. This time can
be reduced by employing an overcurrent relay (excluding the
trip device of LVCB_3) having a wider range for pickup
I I I 2I 4I 8I values to select. The instantaneous pickup value of the OCR is
Bus ID
then set to be as 1600 A, while maintaining the security
BUS1 0.17 0.35 0.73 1.51 3.15 6.58 towards normal load current. As a result, the current values
Swgr 9.14 11.80 13.94 15.37 16.22 16.68
above 1600 A will get tripped instantaneously, causing a
Pwr_panel 5.53 5.9 6.11 6.22 6.28 6.31
MCC 3.10 4.03 4.78 5.29 5.59 5.75 reduced fault clearing time upto 0.066 sec and incident energy
at Pwr_panel reduced to 1.94 cal/cm2 as shown in Fig. 7.
Moreover, it can be noticed that the incident energy at
Swgr is 13.91 cal/cm2 with a fault clearing time of 0.249 sec,
which is substantially a long time to clear the arcing fault
current of 24.66 kA. The upstream protective device LVCB_1
has a solid state type trip device with 2000 A, 40000 A and
36000 A as long time, short time and instantaneous pickup
current values respectively. These settings of pickups are
adjusted and revised while taking care of the coordination
among the protective devices of the system, with 2000 A,
8000 A and 20000 A to be as long time, short time and
instantaneous pickup current values respectively, which
reduces the incident energy up to 3.34 cal/cm2 and fault
clearing time now limited to 0.06 sec as shown in Fig. 8.

Figure. 5 Simulated incident energy vs short circuit current for all buses
Furthermore, the digital relays currently available, allow
the time current curve to be custom-fit. This feature is very
consideration. The Pwr_panel has arcing current of 8.92 kA useful because it can help to achieve faster clearing time for
which is seen as 3.86 kA to the upstream protective device, fault current while keeping a coordination among devices [13].
installed at the primary side of the TRANSFORMER_2. The Such devices are more flexible in developing settings with
trip device of LVCB_3 is a solid state type trip device with

TABLE V. INCIDENT ENERGY VALUES AT VARYING FCTS OF THE


UPSTREAM PROTECTIVE DEVICES (T)

Incident Energy (cal/cm2)

T T T 2T 4T 8T
Bus ID

BUS1 0.18 0.36 0.72 1.45 2.89 5.79


Swgr 3.47 6.93 13.92 27.85 55.69 111.39
Pwr_panel 1.53 3.05 6.11 12.21 24.42 48.84
MCC 1.15 2.39 4.78 9.56 19.11 38.23

Figure. 7 Reduced incident energy at Pwr_panel

Figure. 8 Reduced incident energy at Swgr


Figure. 6 Simulated incident energy vs fault clearing time for all buses
selective curve shapes and adjustable delays to multiple [13] Kadri, K. Raahemifar and F. Mohammadi, “Impact of parameter
instantaneous element. Low arc flash circuit breakers are variation of arc flash on hazard mitigation in low voltage power
system”, 2016 IEEE Canadian Conference on Electrical and Computer
manufactured, which can open the contacts within time Engineering (CCECE), Vancouver, BC, 2016, pp. 1-6.
intervals comparable to FCLs [14]. [14] H. Wallace Tinsley, Michael Hodder, Aidan M. Graham, “Beyond the
calculations: life after arc flash analysis”, IEEE 2007
V. CONCLUSION [15] R. H. Lee, “The other electrical hazard: Electrical arc blast burns,” IEEE
Transactions on Industry Applications, vol. IA-18, no. 3, May/June
The arc flash events are much hazardous and causes severe 1982, pp. 246-251
injuries even death to the working personnel. The best strategy [16] Das, J., “Arc flash hazard analysis and mitigation”, Vol. 91. 2012: John
is to de-energize the equipment when possible. To find out the Wiley & Sons
effects of parameters to which incident energy is sensitive, a [17] <Arc Flash Hazard LV Circuit Breakers> ABB Inc •888-385-1221•
network representative of an industrial facility or electrical available at www.abb.com/lowvoltage.
plant was modeled and simulated to determine the effects. The [18] The Occupational Safety and Health Administration (OSHA), “Code of
incident energy has a direct relationship to the gap width. By Federal Regulations,” CFR 1910.132, General Requirements.
increasing the distance from equipment, incident energy [19] The Occupational Safety and Health Administration (OSHA), “Code of
reduces. By increasing utility available short-circuit current, Federal Regulations,” CFR 1910.333, Selection and Use of Work
Practices.
incident energy increases. As the time increases for each
[20] The Occupational Safety and Health Administration (OSHA), “Code of
protective device to clear the arcing fault current, the incident Federal Regulations,” CFR 1910.335, Safeguards for personnel
energy increases showing a direct relationship. protection.
Among the four parameters, the working distance and the [21] NFPA 70-2002, the “National Electrical Code” (NEC).
fault clearing time is influencing the incident energies to a [22] Parise G., L. Martirano, and M. Laurini, “Simplified arc-fault model:
greater extent. In order to mitigate the incident energies, The reduction factor of the arc current”, IEEE Transactions on Industry
Applications, 2013. 49(4): p. 1703-1710
different methods can be used. More attention is to be given to
[23] IEEE 1584-2002, “Guide for performing arc-flash hazard calculations.”
such methods that can enhance the working distances and
[24] Doan, D.R., J. Slivka, and C. Bohrer, “A summary of arc flash hazard
reduce the fault clearing time. assessments and safety improvements”, Petroleum and Chemical
Industry Technical Conference, 2007. PCIC’07. IEEE.
REFERENCES [25] H. Wallace Tinsley, Michael Hodder, Aidan M. Graham, “Beyond the
calculations: life after arc flash analysis”, IEEE 2007
[26] Rakan El-Mahayni, Jamal Bugshan, and Ritchie Pragale, “Arc-flash
[1] R. H. Lee, “The other electrical hazard: Electrical arc blast burns,” IEEE mitigation”, IEEE Industry Applications Magazine, may/june 2017.
Transactions on Industry Applications, vol. IA-18, no. 3, May/June
1982, pp. 246-251 [27] Nicolas Bardat, “IEC and CENELEC standards used to protect the
electrical worker against an Arc Flash”, 12th International Conference
[2] Nicolas Bardat, “IEC and CENELEC standards used to protect the on Live Maintenance (ICOLIM) 2017.
electrical worker against an Arc Flash”, 12th International Conference
on Live Maintenance (ICOLIM) 2017. [28] Kadri, K. Raahemifar and F. Mohammadi, “Impact of parameter
variation of arc flash on hazard mitigation in low voltage power
[3] Das, J., “Arc flash hazard analysis and mitigation”, Vol. 91. 2012: John system”, 2016 IEEE Canadian Conference on Electrical and Computer
Wiley & Sons Engineering (CCECE), Vancouver, BC, 2016, pp. 1-6.
[4] <Arc Flash Hazard LV Circuit Breakers> ABB Inc •888-385-1221•
available at www.abb.com/lowvoltage.
[5] The Occupational Safety and Health Administration (OSHA), “Code of
Federal Regulations,” CFR 1910.132, General Requirements. [1]
[6] The Occupational Safety and Health Administration (OSHA), “Code of [2]
Federal Regulations,” CFR 1910.333, Selection and Use of Work [3]
Practices. [4]
[7] The Occupational Safety and Health Administration (OSHA), “Code of [5]
Federal Regulations,” CFR 1910.335, Safeguards for personnel
[6]
protection.
[7]
[8] NFPA 70-2002, the “National Electrical Code” (NEC).
[8]
[9] Parise G., L. Martirano, and M. Laurini, “Simplified arc-fault model:
The reduction factor of the arc current”, IEEE Transactions on Industry
Applications, 2013. 49(4): p. 1703-1710
[10] IEEE 1584-2002, “Guide for performing arc-flash hazard calculations.”
[11] Rakan El-Mahayni, Jamal Bugshan, and Ritchie Pragale, “Arc-flash l: The reduction factor of the arc current”, IEEE Transactions on Industry
mitigation”, IEEE Industry Applications Magazine, may/june 2017. Applications, 2013. 49(4): p. 17
[12] Doan, D.R., J. Slivka, and C. Bohrer, “A summary of arc flash hazard
assessments and safety improvements”, Petroleum and Chemical
Industry Technical Conference, 2007. PCIC’07. IEEE.

You might also like