Professional Documents
Culture Documents
Sphp e Sphp Sphp Il Ns en 2011-02 v2.03
Sphp e Sphp Sphp Il Ns en 2011-02 v2.03
Sphp e Sphp Sphp Il Ns en 2011-02 v2.03
STERIVAP HP
®
STERIVAP HP IL
®
Steam sterilizer
Service instructions
The Instructions for use is protected by copyright law, the owner of the copyright being the
company BMT Medical Technology s.r.o. The Instructions for use is designed for personal use
only and it is not allowed to make it available to public in any way, as a whole or in parts. Breach
of the above stated regulations is considered to be a breach of the owner´s copyrights.
CONTENTS:
10. 2. 2011
1 INTRODUCTION.....................................................................................................................................3
SUPPLEMENTS:
2.2
1 introduction
steam generator
Service instructions
2.5 Elektrické zapojení
TT - heater elements
CHL - cooler. CONTACT
DOTYKOVÝ PANEL
PANEL
(vykládací strana)
(unloading side)
CONTACT
PANEL DIGIT.+ANALOG
VSTUPY
2.3.2
DOTYKOVÝ PANEL
(loading side) NPUTS
steam traps (vkládací strana) DIGIT. + ANALOG.
CPU BACK
CPU BACK
ETHERNET
Two steam traps Spirax-sarco types are used standardly in ETHERNET
CARD
KARTA CARD
KARTA
temperature/steam pressure balance) and it is therefore In the unloading side there is a smaller contact panel, which
2.5.2 Popis schématu elektrického zapojení
dedicated for traps connected to the outlet from the is controlled with the processor BACK.
sterilisation chamber (now newly also for the direct trap of Further the apparatus
Schéma elektrického contains
zapojení je v příloze tohoto the processor
návodu. SLAVE,
Následující číslování listů vwhich
odpovídá schématu Z468466 v.14 a schématu Z471105 v.4 (provedení UL). U vyšších verzí
textu
the steam/steam exchanger - FDD). processes the information from the digital (switches) and
se může číslování listů lišit.
This liner is not so much suitable for condensate draining analog (temperatures and pressures) of inputs and
V2.032 Ster_4-.doc
controls
STERIVAP HP_cz_ns
from jackets as the draining is too rapid, noisy... in some the outputs.
cases. In order to secure the safety as well as in the case of a
failure of the processor SLAVE, the apparatus contains a
The “E” type liner is set to “standard” (i.e. a little bit under the block of hardware protection, which is controlled with the
balanced state, than the previous type) and it is dedicated processor MASTER and some inputs (see the chapter of
for other traps, where the softer drain is required. E.g. the hardware protection).
condensate drain from the jackets, supply pipe etc.
This liner is not suitable for the chamber, as it drains the
condensate for this not enough purpose and it can cause 2.5.2 description of the electric
a distortion of the measured temperature on the main PT connection diagram
sensor, problems with the residual air, non-condensed gases
etc. The circuit layout is in the appendix attached to the
The liners are mechanically changeable and it is necessary, instructions for use. The following numbering of sheets
during the replacement, to replace them by a suitable type in the text corresponds to schemes Z468466 v.14 and
and with certain knowledge. Z471105 v.4 (the performance of UL). The numbering of
sheets for higher versions may be different.
2.4 coverage
2.5.2.1 network part
The unit is covered with stainless panels of 1.4301 material
quality. there is also a lockable service-door in the covering. The connection of the sterilizer’s network component is
illustrated in Sheets No. 1 and 2.
Sheet No. 3 shows the secondary voltage distribution of
2.5 electric connection Transformer T1 into individual electronic plates.
Meaning of the respective components is following: In SP HP E and SP HP S models, the mentioned LCD panel
consists of a touch panel with a 8.4“ display (one piece),
E1-E8 Heaters
VP_LVDS board, CCFL convertor (the display backlight) and
F501, Circuit breakers of heaters
F503, VP_CPUM processor board. On the back side of the front
F505, panel, there is the VP_KON connector board to which the
F507
chip reader, printer and servo are connected (for SP_HP
K1-K7 Contactors
and SP_HP_IL models).
Q1, Circuit breaker relay of motors
Q2, Q3 To the connectors XS1 and XS2 of this board it is led out
VY1 Vacuum pump motor the internal busbar RS485. If it is connected only the cable
C1 Pump motor - generator only to one of them, it is necessary that the both switches
C2 Pump motor - methylene S1 (beside the connectors XS1 and XS2) would be in
FL1 Fluorescent lamp with electronic position „ON“, otherwise both the switches S1 must be in
ballast
position OFF.
T1 Transformer
F1 Cut-out fuse for supply of T3,15A
electronics The connector XP8 serves for connecting of PC (recording
F2 Cut-out fuse for display backlight in T3,15A of bios).
the loading side The connectors XP3 and XP4 serve for interconnecting of
F3 Cut-out fuse for supply of alternate T6, 3A the sterilizers between them (control of consumption). If the
outputs and contract of the panel in
the unloading side cables are connected to both connectors, the switch S1-2
F4 Cut-out fuse for supply of the inputs T6, 3A must be in position „OFF“, if there is connected only one
and direct-current outputs connector, S1-2 must be in position „ON“.
F5 Fuse for T1 and FL1 T1A for 380-480 V
T2A for 220 V
T3A for 208 V (UL)
M5 Switchboard fan 2.5.2.4 rear panel (on the unloading
side)
Meaning of the respective components connected to the PT1.2 (MST) PT sensor – chamber MASTER
inputs and their function is following: PT2 PT sensor – water saving SLAVE
PT3.1 (SLV) PT sensor – solutions SLAVE
DIGITAL INPUTS PT3.2 (MST) PT sensor – solutions MASTER
Identification Meaning Function within PT4 PT sensor – generator SLAVE
switched
contact PT5 PT sensor - demiwater SLAVE
Q1 Thermal relay – vacuum pump motor PT6 PT sensor – detection of air SLAVE
overloaded
Q2 Thermal relay – generator pump motor
overloaded
Q3 Thermal relay – pump motor 2.5.2.6 outputs
methylene overloaded
B20 Pressure switch 1.5 Bar - slot under pressure The connection of the AC outputs is shown on the sheet No.
( BS)
B20.1 Pressure switch 1.5 Bar - slot under pressure 11 and of the DC outputs on the sheet No. 13.
( ES) The switching is indicated on the power board of the
B31 Pressure switch 3 Bar – without electronics VP_P… with appropriate LED diodes.
generator pressure
B86 Bottom lever gauge – flooded
demiwater Meaning of the respective components connected to the
B89 Upper level gauge - demiwaterr flooded outputs is following:
B90 (HW) Upper level gauge - generator flooded
Identification Meaning Note
B91 (NW) Bottom level gauge - generator flooded
Y03 Valve for filling the jacket I
B100 Upper level indicator - flooded
methylene Y103 Valve for filling the jacket II
B101 Bottom level indicator - flooded Y07 Valve for steam transfer into
methylene the chamber
B102 External level indicator - flooded Y09 Valve of the filling slot (entry
methylene door BS)
S11 Entry door (BS) closed closed Y09.1 Valve of the filling slot (output
door ES)
S11.1 Entry door (BS) opened opened
Y20 Valve for discharging of the
S11.2 Input service door (BS) (9x opened chamber
model)
Y23 Valve for discharging of the slot
S11.3 Input door (BS) closed (9x opened (entry door BS)
model)
Y23.1 Valve for discharging of the slot
S12 Safety strip – entry door (BS) not pressed (output door ES)
S13 Output door (ES) closed closed Y24 Cooling water valve for the air
S13.1 Output door (ES) opened opened detector
S13.2 Output service door (ES) (9x opened Y27 Air detector valve - condensate
model) Y28 Air detector valve - air
S13.3 Output door (ES) closed (9x opened Y30 Cooling water valve for vacuum
model) pump
S14 Safety strip – output door (ES) not pressed Y50 Valve for blocking of the
L1 Blocking – lack of electricity blocked condensate effluent conduit
ANALOG INPUTS Y80 Valve for vent
Identification Meaning Evaluated by Y81 Valve for vacuum breaking
processor of the vacuum pump
PE1.1 (SLV) Pressure transducer - chamber SLAVE Y81.1 Sterilizable aeration filter valve
PE1.2 (MST) Pressure transducer - chamber MASTER Y99 Valve for desludging
PE2 Pressure transducer - casing I. SLAVE Y150 Valve for degasification
PE20 Pressure transducer - casing II. SLAVE Y67 Valve for deaeration of the
jacket
PE3 Pressure transducer – SLAVE
generator Y70 Valve for jacket pressurizing
with air (counter-pressure)
PE101 Pressure transducer - air SLAVE
Y35 Valve for jacket spraying
PE102 Pressure transducer – entry SLAVE
steam Y21 Valve for discharging the
chamber
PE103 Pressure transducer – water for SLAVE
vacuum pump Y66 Valve for discharging the jacket
PE104 Pressure transducer – entry SLAVE Y02 Valve of waste steaming
demiwater Y501 Valve of water showering
PE105 Converter pressure – softened SLAVE Y502 Valve Methylene
water (EW)
Y503 Valve of chamber aerating
PE106 Pressure transducer – heating MASTER (methylene)
steam
PT1.1 (SLV) PT sensor – chamber SLAVE
Software of the apparatus has two main layers, BIOS (6) (6)
and APLIKACE. BIOS ensures the communication between
the appropriate processors. And further the upgrade (7) (7)
of the application.The application ensures the correct
function of the sterilizer. The processor master receives
(8) (8)
the instructions from the attendance for the requested
activity and at the same time for the control it assesses from (5) (5)
the processor slave the states of sensors, values
of measured variables and also the information regarding
to the fact, within which phase of sterilization cycle If you want to download the software, you have to start the
the process is found. “Loader.exe” program. A detailed procedure of firmware
Many of necessary data are obtained independently, or it downloading to the device from Hitachi Loader is described
compares them to the parallel obtained data from the slave. in the program-accompanying document (“HelpLoader_
If the attendance gives instruction to the commencement of cz.doc”). Use the mouse to select “File->Open file” from the
the activity, the master sends in direction to the slave menu and select the file you want to download. The file will
the packet of necessary parameters. be included automatically to the Process list panel.
The processor slave is entrusted the course (The files are named mnemonically, e.g. BiosMltMst…).
of the sterilization cycle on the basis of the information from Start the downloading procedure by the button “Start
the processor master. Slave has a direct access download” from the front panel “Process list”.
to the outputs (valves, contactor, ...) and to the inputs After the download is started, wait for the process
(thermal and pressure sensors, switches, ...). If the slave termination – see the legend “Current Process Status”.
detects the error, it notifies of the fact the processor master
and freezes its activity, i.e. all the action variables take up
the safe state and it is waiting. Only after deleting the error 2.7.1 loading of bios
by the attendance the slave receives the instruction to
transition to the initial state from the master, Bios is loaded into every processor board separately
i.e. in the chamber it is atmospheric pressure and the slot (VP_CPUM, VP_CPUS, VP_CPUB). For this purpose
will be de-sealed. each of these boards has a connector for connecting of
The processor back receives from the attendance a serial line RS232 (for VP_CPUM it is located on the
of the apparatus the instructions for the requested activity board VP_KON). With respect to the fact that the switches,
and hands over them to the processor master, which further which enable to load the Bios, are located on the boards of
processes them. electronics, before its loading it is necessary to uncover the
boards.
In loading the bios there is erased the processor memory, in
2.7 loading of bios, which there are stored all the information on the apparatus
aplications and languages (apart from the system version), therefore it is necessary,
before you record – load the bios on the boards of
“Loader.EXE” Version 9.1 and up is used for the software electronics VP_CPUM, to backup the following information
download to the sterilizer (hereinafter Loader.exe). Software (see. print,…):
is downloaded by a serial RS 232 link from a PC by means - Configuration of the device
of a transposed cable. - Setting of the device
- Offsets
Service instructions
V2.03 Ster_4-.doc
RESET
DIP
RESET
DIP
5. Wait until on the PC in the window „Listing of the process“ 2.7.3 rules for work with the
it is listed „End „ program loader.exe
- „Switch over the processor from the boot mode“
- Switch over the both switches DIP on the electronics Rule 1: If you want to close Hitachi Loader and it is not
board into position OFF possible, click on the button “Stop download” if you are in
- Reset the processor by the button RESET the panel “Process list”, or click to the button “Stop” if you
are in the panel “Process printout”.
After loading the bios it is necessary again: Rule 2: Do not close the window of the file that is just being
- To load the application downloaded!
- To perform the complete setting of the device including Rule 3: If any action fails, repeat it (even more times)!
the offsets
- To load the sterilization programs
2.7.2 loading of the application If within the automatics it is activated the generator, the
pump C1 refills with demineralised water into the generator
The device must be in the sleeping state (the process is not from the storage tank via the filter F7, back-flow valve V14
running) and there must not be selected the utility service and valve V7. Reaching the necessary level is secured by
„Download of programs“. When downloading the application the level switch B90. After starting the generator the heater
there is erased the RAM backup memory, therefore it is elements TT begin to heat. The boiler is brought onto the
necessary to record the user´s settings under the menu operating pressure, which is being scanned by the pressure
items „Setting of the display“, „Print“ and as well as the gauge PE3. The valve Y99 opens for approximately 2s after
number of the performed batches. every water refilling to decrease concentration of salt in the
When downloading the application, the PC is connected boiler. The level switch B91 secures protection of the heater
to the sterilizer via the connector RS232 on the electronics elements. The pressure switch B31 serves as protection
board VP_KON, and also for the electronics boards against overpressure. Valve V6 is used for manual mud
VP_CPUS and VP_CPUB. As to be first it must be
downloaded the application (including the languages) into discharge from the boiler. The generator is equipped with
the electronics board VP_CPUM. thermal degasification of the feed water. Water in the
storage tank is heated by a heating coil. Heating is regulated
The application is loaded in the following method: with the valve Y150. The temperature of demineralised
1. Start the Loader.exe water is scanned by the temperature sensor PT5. The
2. Open the file „VpsMltxxx.fls“ (so as it would have a blue minimal level of demineralised water in the storage tank is
bar) scanned by level gauge B86. In case of shortage of water
xxx: Mst pro VP_CPUM the feed pump C1 is blocked.
Slv pro VP-CPUS
Bck for VP_CPUB After selecting the sterilization program the steam of the
3. Select “Download->Start download”. heating jacket I is filled via the filter F2, valve Y03 for the
4. Wait till “End” is shown on the PC in the panel “Process pressure being set by the selected program. The pressure
list”. is scanned by the pressure gauge PE2. Into the jacket II the
5. When downloading to VP_CPUM electronics board, steam is filled via the valve Y103.
open the language file “VpsMltMstLng“. The language
file “VpsMltBckLng” shall be used for the electronics The pressure is scanned by the pressure gauge PE20. The
board VP_CPUB1 (black and white display 5.7“) back-flow valves V13 are fitted only within the version FED.
and “VpsMltBckcLng” shall be used for VP_CPUB2 After starting the sterilization program the door is sealed
electronics board (color display 5.7“). via the valve Y09. The pressure under the seal is checked
6. Select “Download->Start download.” by pressure switch B20. There is started the vacuum pump
7. Follow the directions on the screen: VY1, which via the valve Y20, filter F4, cooler CHL and
- Select maximum 4 languages – they must be equal both the back-flow valve V12 exhausts the air from the working
for Mst and Bck! space.
9. Wait till “End” is shown on the PC in the panel “Process
list”.
4
The pressure in the chamber is scanned by the pressure
gauge PE1.1 and PE1.2. After gaining the necessary under adjustent
pressure the valve Y 20 is closed and it is opened the valve
Y07, through which the steam is filled into the chamber. of the unit,
The condensate trap O2 realizes the condensate exhaust
from the chamberse. In an analogic way, the sterilization setting the
cycle proceeds till the phase of pressure releasing, when
the steam is intermittently discharged from the chamber parameters
via the cooler CHL. Cooling water is supplied into the
cooler via valve Y30, filter F6 and flow limiter P1. Water is The unit is adjusted and tested by the manufacturer.
further supplied into the cyclone and via an orifice plate it Selected adjustment and checking values of the STERIVAP®
feeds the vacuum pump VY1. Excess water flows away HP sterilizer:
via the overflow. The temperature of water in the cyclone is
Name Designa- Value Note
scanned by a PT2 temperature sensor. tion
In case that the water temperature is lower than the preset Door coupling 150N Door closing
value, the valve Y30 in some phases of the sterilization force
Set in upper third
cycle closes and the vacuum pump is then feeded from of the door lift
a closed circuit to save water. It is possible to set the Steam generator B31 +3,0 bar
controlling temperatures within the automatics. manostat
Valve Y80 opens when aerating the chamber. The air flows Float valve of the cca 80 mm Height of water
water storage tank level in the
into the chamber via bacteriological filter F1 and non-return storage tank
valve V10. Steam is sucked off the groove in the door by Sterilizer safety valve V1 3,2 bar
vacuum pump VY1 via opened valve Y23, filter F5 and non- Steam generator V2 3,2 bar
return valve V12. safety valve
Cooling water T1=27°C, Automatics
temperature T2= 33°C
Compressed air for pneumatic valves is reduced onto Compressed air V3 cca 5bar
approximately 5 bar pressure by the reduction valve reduction valve
V3. Temperature in the chamber is scanned by double Compressed air V40 cca 2,6
reduction valve
sensor PT1.1, PT1.2. The condensate from the jacket I
Compressed air V4 3,2 bar
is conducted via the filter F3, condensate trap O1. The reduction valve
condensate from the jacket II is conducted via the filter
F103, back-flow valve V111, condensate trap O101.
K60+K61 On
B31
Chamber: Jacket:
Steam source
For the period of storage the apparatus does not react to the
touch contact. If you are not sure that you have performed Chamber: Jacket: Generator:
the mentioned operation correctly, please, push the button Safety Devices Test
„Do not store“, by which you will arrive at the screen by one
level higher, or push possibly the button „Cancel“ for the - Press “K60+K61” to check the function of K60 and K61
return to the set screen. relays that will disconnect the power supply of outputs in
If it is possible to set the mentioned parameter only on case of a critical error (see the connection diagram).
certain limits, these limits are indicated in the brackets. The generator must be switched off to allow this test
functioning.
In order for the inactive buttons to become the functional - Function of the safety pressure switch B31, which
ones, it is necessary to log in the following manner: creates the independent protection of the generator, can
be checked by pushing the button „B31“. There appears
- To push the button the screen:
- The screen appears:
Generator:
Generator ++
Name: B31 Pressureless
Password: B90 Flooded
- into the line marked as “Jmeno”, write the name, Push the button „GENERATOR“ – the generator works in
assigned by the service BMT department, e.g. serv001 normal mode, i.e. it regulates the pressure within the set
(the line is activated by the touch) pressure values (see the setting of the apparatus). The
- into the line marked as “Heslo”, write the assigned actual pressure value is displayed by a colour column and
twelve-character password. concurrently in figures in the left upper part of the screen.
Pushing the button „OK“ you will arrive to the preceding All the displayed outputs can be controlled by touch,
screen se, in which there was changed the message „B31 however, in dependence on the process, which is just
without pressure“ to „B31 Under the pressure“. running, some outputs return to the state, which is required
by the given process.
In the case that B31 will not disconnect within nine seconds, Furthermore on the screen there are displayed all the
again push the button „GENERATOR“. analog and digital inputs related to the given block. Colour of
On the screen there are also the information on the fact, the digital inputs expresses, if the given input is connected
in which state there are the inputs and outputs being or disconnected (see „block the summary of digital inputs
necessary for the function of the generator. and outputs “), depends also on the selection of the colour
If it occurs that sooner than B31 activates the safety valve, palette.
it is necessary to adjust B31 to lower pressure, or to replace
the defected safety valve or the B31. The last block „the summary of digital inputs and outputs“
- Functionality of the bottom level gauge of the generator displays all the digital inputs and outputs, but these ones,
can be verified after pushing the button „B91“. Proceed which are not configured, have different colour and can be
according to the instructions described on the screen. inactive ones.
After confirming one step, the following one will
automatically highlight.
For the safety reasons, before the test the generator must 4.1.3 summary of inputs - outputs
be in cold state and without pressure.
- After pushing the button there appears the screen
“The summary of digital inputs and outputs”- see above.
4.1.2 display of blocks
4.1.4 configuration of the device You can pre-set the following options on the “Device
configuration 3/5” screen:
This service enables to configure the device according - Number of doors
to the fact, how it is manufactured. It is very important so - If the device is equipped with two doors, the unloading
as there would be configured only these parts, which are side display (Bck) must be selected from the following
contained in the device, otherwise the device may work options:
incorrectly and report errors. - LED panel
- LCD monochromatic touch panel 5.7“ (by 2010)
Press the button “Device configuration”. The screen “Device - LCD color touch panel 5.7“ (since 2011)
configuration 0/5” will be displayed and you can select the - LCD color touch panel 12.1“/8.4“
device type there. The content of other screens will be - This is Bck – this option shall be checked on the
modified depending on this selection. unloading side only and only if the device is equipped
with two large color displays 12.1“ or 8.4“
You can further pre-set the prefix of the device production - Chamber temperature at which the door can be opened
number there: If the production number has seven digits - Coupled or separate door sealing
(and starts with 5), “BMT” should be checked. If it has six - Duration of the door unsealing (period of time during
digits, “MMM” should be checked. which the vacuum pump evacuates the groove)
You can use arrows for switching between other screens. - Door sealing material used – either steam or air
- Door version – the right door version means that the
You can pre-set the following options on the “Device door on the loading side is positioned on the right side of
configuration 1/5” screen: the display
- Chamber volume - Internal steam generator – automatic switch-on –
- Steam supply such option is available only if the door is sealed
- External steam source FD, FDT (heating steam) independently by steam (there will not be any button for
- Internal steam generator ED (electrical) or FDD (steam- the generator switch-on on the main screen).
steam exchanger); presence of PT4 sensor shall be
pre-set in the generator 63 kW (and more) You can pre-set the following options on the “Device
- Safety valve V1 configuration 4/5” screen:
- Sensor B89 – upper level indicator in the demineralized - Chip card reader
water tank. - Sensors for the input media monitoring
- Output data configuration
You can use the “Device configuration 2/5” screen to set - Aeration filter type – if a sterilizable filter is used, we
whether (or not) the device includes: must find to which power board the Y 80.1 valve is
- Solutions – if yes, correct PT sensors must be selected connected; this information then must be pre-set in the
(PT 3.1 is a standard) device
- Bacteriological filter - Y 80 valve position.
- Jacket cooling
- Methylene H2O2 You can pre-set the following options on the “Device
- Air detector configuration 5/5” screen:
- Waste after-cooling - Energetic maximum watching. At first, the number of
- Ergonomically adjustable LCD panel interconnected sterilizers must be pre-se, followed by
- Memory card their production numbers and models.
- Audit trail The individual devices are interconnected by means
- Automatic start of a four-conductor UTP cable terminated by RJ
- Thermal degassing 14 connectors and connected 1:1. The first pair is
- Ultrasound level indicator S1 connected to the pins 1 and 2 while the second pair to
- Parameters modified by the user: the pins 3 and 4.
- None If two devices are selected, they are interconnected by
- Selected means of XS3 connectors on VP_CPUS boards. In the
- All – this option may only be pre-set for a competent third device, XS3 connector of its board VP_CPUS is
user who is fully aware of the danger of lack of batch connected to XS4 connector on the VP_CPUS board of
sterility and/or its damage in case the parameters are one of the first two devices.
modified wrongly - Daily batch counter
- PT31 and PT32 temperature sensors arrangement. - Internal 485 Bus Watching – this option is reserved for
research purposes
- Permissible range of high temperatures in the chamber –
if temperature exceeds this value, an error is announced.
4.1.5 setting the device pressure and temperature sensors will be set to the initial
values and to zero, respectively.
4.1.5.1 serial number and charges
counter After pushing the return button there appers the
screen „Summary of digital inputs and outputs“ – see above.
The serial number and charges counter are set during the It is recommended that pressure offsets are checked during
equipment production and the serviceman does not have the annual inspection of the instrument.
any right to change them. These data are stored on up to
nine independent places in the electronics and therefore
they are not lost in case of replacement of individual boards. 4.1.5.3 offset of temperatures
4.1.5.4 units
in the “Administrator” menu item to set the name of the The Preset button will reset the actual Next Maintenance page.
administrator to “admin” and password to “password”. The service activity can be defined on the individual lines in
The screen also shows the password to unblock the door. the field Service Activities Description. If all three description
The analogue variable that will be displayed on the third lines on the page remain empty, the page will be excluded
place of the digital output can also be pre-set there. from the service activities planning function.
• Press the button Menu / Device Setting / Next 12:59:21 Next Maitenance 1: 2008-06-24/000825:
Maintenance clean the door sealing groove
Program Download
Program Parameter Change
P1 Warm up
P2 Universal
P3 Universal Containers
4.1.7 programmes joining
P1 Warm up P1 Warm up
Now in the counter, please, confirm the data export. P8 Crash Test
Program was downloaded to the appropriate program P2 Universal
P2 Universal
P8 Crash Test
P5 Tools Fast
location and you have a possibility to confirm or to P5 Tools Fast
P6 Creutzfeld (J.)
P6 Creutzfeld (J.)
prohibit , In the other case the attendance will not be P7 Creutzfeld (J.)
P7 Creutzfeld (J.)
allowed to start it. Similarly it is possible to select, if the
program will be in the offer of a quick selection.
When you touch the touch screen at any point, you will
see a cross on the LCD panel showing the touched
place. Align the touched place with its image by means of
gradual pressing the “+” and “-” buttons both in vertical and
horizontal direction. The Redraw button renews the screen
without crosses displaying. Red button contours show the
with the information concerning the hardware and software button position on the touch panel stored in the device
Při dotyku v kterémkoliv místě dotykového panelu se na LCD panelu ob
versions of each boards, serial number of the equipment memory; the green contours show the position actually
zobrazuje místo dotyku. Pomocí postupného mačkání tlačítek „+“ a „-“ a
and the charge number. being set. It is recommended
tak i vertikálním to set the
směru, dosáhnete offset according
sesouhlasení to dotyku s jeho ob
místa
Automatics watches that in the device there would be fitted the central Test
„Překreslit“ button.
slouží k obnovení obrazovky bez křížků. Červené obrysy tla
the components mutually compatible in terms of hardware polohu na dotykovém panelu s offsetem uloženým v paměti přístroje, z
and software. In the case that some part of the hardware or Store the change
nastavovanou by pressing
polohu. the return button
Je doporučeno .
nastavovat offset podle středové
software is incompatible, this component is marked in red Po stisku návratového tlačítka změnu uložte.
colour.
Information about the version of hardware is downloaded on 4.1.10
4.1.10 SD Upgrade
sd upgrade
the boards at the time of debugging, so the spare parts have
this information in them.
Abbreviation meaning:
- Mst – board of electronics VP_CPUM
- Slv – board of electronics VP_CPUS
- Bck – board of electronics VP_CPUB
- Pwr – board of electronics VP_P (AC, DC see the
connection diagram).
There are five buttons in the upper part of the panels. bios, therefore it should be overwritten only if an older
The buttons are used for selection of the board to which version is stored on the board).
the firmware is to be downloaded. The buttons are set 3. After the replacing and programming the board VP_
automatically after a new FLS file is selected. An upgrade CPUM it is necessary to perform:
to two boards cannot be done at the same time. If there are - The setting of the device
more files to download, they must belong to one board, e.g. - Configuration of the device
the bckc application belongs to bckc with the languages. - Setting of the offsets
Insert the card in the sterilizer. Click on the button with If it was not possible to read it from the replaced
three dots in the upper right part of the panel and select the electronics board VP_CPUM, it is necessary to
FLS file for each line by means of the file manager. After obtain the information from the documentation for the
the file is opened, the number of the board to which the mentioned device.
module belongs will be indicated automatically. To download 4. After VP_CPUS and VP_CPUB2 board is replaced and
applications, UNICONFIG data, configuration or part of a programmed (model with a color display 5.7“), save
file, open “Application fls file” in the first line. the device configuration and pressure offsets (enter
The second line “language fls file” shall be used for the setting of one offset point and confirm its value).
languages and the third line “bios fls file” shall be used for Nothing will be pre-set during this action! By saving, the
bios. Bios cannot be downloaded separately but only with data from VP_CPUM board memory will be copied to
the correct version of applications and languages. Start the memories of VP_CPUS and VP_CPUB2 boards.
the upgrade by the “Start upgrade” button. If you download 5. In addition to it, save the programs in VP_CPUB2
the languages, the panel starts asking you for the desired board (in the Program download, for example, change
languages. Select them by means of “yes – no – cancel – the fast select of any program, then change it back and
end” (maximum four and minimum one language can be save the programs).
downloaded). To interrupt the download procedure, click on 6. If it is necessary to replace more boards, they must be
the “cancel” or “stop” button. To terminate the languages replaced gradually and the equipment must be turned
selection, click on the “end” button. Observe the blue on after the replacement of each board!.
downloading status bar. After 100 % is indicated and the
languages selection is terminated, the upgrade as such will
be started followed by the application reset. If you download 4.2.2 battery replacement
slave or bck, look for the error message “saving failed” after
the reset; if such message does not appear, the upgrade The battery is placed in the electronics board VP_CPUM.
was successful. It is necessary to replace it, if its voltage decreases to the
value of 2.7 V. Before its replacement, please, write down
the state of the batch counter.
4.2 replacement of the parts Set the date and time and all user settings (language, colour
of electronics palette, …) after the replacement.
4.2.4 replacement of the contact form of a full tree where all the program parameters can
panel - rear panel be seen. There are two tree types – a ”Full tree” showing
all parameters, or an “Applied tree” where the parameters
The contact panel is glued with bonding tape to the display. are presented according to the groups of switches setting.
When replacing it first it is necessary to separate by scalpel Each switch can display or hide a certain group of program
or a thin knife the old contact panel from the display and parameters. You can switch between the parameters in
then to glue a new contact panel so as the active surface of normal and tree displaying by holding the Shift key and
the contact panel would cover with the active surface of the clicking on any parameter by the left mouse button. You
display. can also edit here the user setting of each of the programs,
either a fast selection (program selection from the main
device menu), or an automatic door opening and cycle
4.3 definition of the program number setting.
parameters Then there are four columns with the program parameters,
the opened files manager on the left bottom side, and a text
4.3.1 the way of definition of the field on the right bottom side that displays the downloading
programme parameters events. The first column titled “Group” describes the
groups of the individual program parameters. The second
The automatics of the STERIVAP® HP unit is designed column “Field name” shows the edited parameter name
so that the actual courses of the individual sterilization and the parameter type icon. The third column “Field value”
programmes are defined in every ready made unit by means describes the edited parameter value. In the fourth column
of hardware and software tools. “Units”, units for each program parameter can be pre-
set. The individual parameters can be selected and then
Hardware tools: modified by means of the cursor arrows and/or the mouse.
computer compatible with the IBM PC Any changes of numerical and text values in the column
interconnecting cable “Field value” must be confirmed by the Enter key. If you
change any of the values in the editing field, you can return
Software aids: to the previous value by means of the Esc key. If the value
UNICONFIG.EXE of any parameter is limited, its range in which the value
Template file xxx.tpl can be changed is shown in the brackets together with the
- UniversalSter.tpl (for the sterilization and solutions name of the Limit to which the value belongs. If the given
sterilization data files *.ste) value has not been edited, this value is shown behind the
- AirDetector.tpl (for the AirDetector data files *.ade) parameter value. There are two types of Limits. The first
- VacuumTest.tpl (for the vacuum test data files *.vac) one marked with the symbol ? means that both the upper
- Unicrash.tpl (for the UNICRASH data files *.ucr) and lower limits of the Limit are equal and the range can be
- H2O2_SP-HP.tpl (for the data files H2O2*.h2o) changed from -3.4 * (10^10) to 3.4 * (10^10). The second
type of the Limit marked with the symbol ? means the Limit,
Data files the lower and upper limit of which can reach any value from
The templates must be saved in the “Templates” directory at -6000 to 6000 with one decimal point accuracy. Units, if
the same place where the UNICONFIG.exe file is located. there are any, can be bound separately to each parameter
The programs are placed (default) in the “Programs” (including the Limit). In the device, however, units displaying
directory; however, this is not a rule. according to the global setting can be pre-set. In the first
The program as such shall be defined in the following way: type of the Limit, you can only enter the range plus/minus
Follow the above mentioned procedure, select “Program the same value. For example, “4” means a limitation of the
download” from the menu and confirm. value x (x-4, x+4) where x is the defined default value of
the parameter in the device. There are two different ways
In PC, the following procedure shall be used: of the second Limit type recording, either in form of the
Start the UNICONFIG.EXE program. Select the menu “File- upper and (different) lower limit, e.g. “-5.2/1.2”, or in form
>Open file”, open the directory in which the appropriate data of one figure “5.2” where the upper and lower limit are
files are saved (default “Programs” directory), select the equal. The value of the Limit will limit each parameter in the
correct file type in the line “File type”, select the required file device (its value from the frost download of the program
(it must be shown in the line “File name”), and press “Open”. to the device). This means that, for example, the value 2.8
The PC screen will show a bar with the possible slots to which has a Limit 1.2 (both the value and the Limit are in
which the program will be downloaded. If “UNICONFIGslot the same units) will be limited in the device in the range
auto” has been pre-set, the program will be downloaded from 1.6 to 4.0. If any of the parameters is changed, the
to the first free slot. Then there is the button “Program name of the open program will be highlighted on the left
download” by which the program is sent to the device. bottom side in bold letters. You can save the program
The “Tree” button switches the parameters displaying in either through “File->Save” or by means of the shortcut key
Switch Air Turns on the air detector Period of 0,1s Exhaust of condensate by opening
detector exhaust of the valve Y20 during the heating
condensate
Switch Turns on the bacteriological filter heating-outlet
Bacteriological
filter Period of s Exhaust of condensate by opening
exhaust of the valve Y20 during the exposure
Switch Door 0 - through chamber, 1- non through condensate
logic chamber sterilization -
Number of Number of pressure lifts in the pause
steaming steaming phase Period of 0,1s Exhaust of condensate by opening
extrusions exhaust of the valve Y20 during the exposure
Time of s Duration time of sterilization condensate
sterilization/ Fo exposure/value of the parameter Fo heating-outlet
Temperature of °C Required temperature of sterilization Decrease kPa Controlled evacuation
sterilization speed
downwards of
Temperature °C Add to the required sterilization G-pressure
correction (reg. temperature and from the resulting
pressure) sterilization temperature it is Decrease s Controlled evacuation
determined the regulating pressure speed
downwards of
Temperature °C When starting at resulting G-time
overrun sterilization temperature the
minimum temperature will excess Rychlost kPa Controlled evacuation
by this value, subsequently the Decrease
sterilization exposure will start. speed
downwards of
Number of Parameter „n“, A-pressure
teeth when see annexe KV_202
keeping Decrease s Controlled evacuation
vacuum speed
downwards of
Pressure at the kPa see annexe KV_202 A-time
point B10
Vacuum pump kPa see annexe KV_202
Pressure at the kPa see annexe KV_202 switching
point B110 pressure
Pressure at the kPa see annexe KV_202 Jacket kPa Lower limit of the jacket pressure
point B16 pressure I regulation band in the program
Time T20 s see annexe KV_202 before phases before sterilization
sterilization
Number of Parameter „m“,
2.evacuations see annexe KV_202 Jacket kPa Lower limit of the jacket pressure
pressure II regulation band in the program
Pressure at the kPa see annexe KV_202 before phases before sterilization
point B11 sterilization
Pressure at the kPa see annexe KV_202 Control jacket kPa Control jacket hysteresis in all
point B111 hysteresis phases of the cycle
Time T21 s see annexe KV_202 Jacket kPa Lower limit of the jacket pressure
Pressure at the kPa see annexe KV_202 pressure I after regulation band in the program
point B15 sterilization phases after finishing sterilization
Pressure at the kPa see annexe KV_202 Jacket kPa Lower limit of the jacket pressure
point B17 pressure II after regulation band in the program
s see annexe KV_202 sterilization phases after finishing sterilization
Time T22
Delta of jacket kPa Pressure difference between
Increase speed kPa Pressure increase, speed controlling the chamber pressure and the
of J - pressure I
lower limit of the jacket pressure
Increase speed s Time increase, speed controlling regulation band = parallel working
of J - time of the chamber and jacket pressure.
Chamber pressure is primary, jacket
Increase speed kPa Pressure increase, speed controlling pressure is adapting by the constant
of D - pressure Delta P, see annexe KV_202
Increase speed s Time increase, speed controlling Delta of jacketII kPa Pressure difference between
of D - time the chamber pressure and the
Increase speed kPa Pressure increase, speed controlling lower limit of the jacket pressure
of H - pressure regulation band = parallel working
Increase speed s Time increase, speed controlling of the chamber and jacket pressure.
of H - time Chamber pressure is primary, jacket
pressure is adapting by the constant
Parallel stairs s Not used Delta P, see annexe KV_202
upwards-time
steam Delta of jacket kPa see annexe KV_202
I-S
Parallel stairs s Not used
upwards-time Delta of jacket kPa see annexe KV_202
pause II-S
Time stabilizer s Timeout before the sterilization Number of Parametr „k“, see annexe KV_202
exposure drying cycles
Period of s Exhaust of condensate by opening Pressure at the kPa see annexe KV_202
exhaust of the valve Y20 during the heating point B18
condensate Pressure at the kPa see annexe KV_202
heating - pause point B19
Time of drying - min. Time t5, see annexe KV_202
down
Time of drying
- up
s Time t5, see annexe KV_202 4.5 vacuum test
Maximum time s If the phase lasts longer, a fault
of pressure occurs The vacuum test is a special type of the sterilization
increase program. Its course is drawn in Fig.5.
in steam
generator
Maximum time s If the phase lasts longer, a fault
of pressure occurs Pressure in the chamber
increase in the
jacket
Maximum time s If the phase lasts longer, a fault
of filling the occurs. Function treats the filling
groove and evacuation of the groove. Atm. pressure
Maximum time s If the evacuation (pressure down,
of evacuation „n“ teeth, pressure up) lasts longer,
a fault occurs
Phase 1 Phase 2
Maximum time s If the steaming lasts longer, a fault
of steaming occurs
Maximum time s If the heating lasts longer, a fault
of heating occurs Testing
pressure
Maximum time s If pressure releasing lasts longer, Permitted
of pressure a fault occurs. change in
Prepara- Testing time pressure
releasing into tory time
atmosphere
Maximum time s If pressure releasing lasts longer, O Abs.
of drying - a fault occurs.
down
Maximum time s If aeration lasts longer, a fault
of drying up occurs Fig.5
P4 with a rubber charge cca 45 min. • Setting of the Air detector – setting of the air penetration
VT cca 18 min Close the door of the sterilizer.
BD test cca 18 min. Push the Start button.
Vacuum Test
Tools Fast
Press simultaneously the buttons for paper feed ◄ / ENTER / and the button marked ■ /NEXT/. The printer
enters the setting mode and prints information about the internal voltage of the printer (approx. 7, 8 V), firmware,
actual parameters setting, and procedure for these parameters modification.
Density: 30
Speed/Quality: med(104)/low
Interface: RS232/USB/Blue
Com: 115200, n, 8, Tx+
Sleep time: OFF
Font #: 1
Char.format: D0, W0, H0, S0, 104
Note:
The Com parameter shall be set in two steps: Baudrate: 115200 and Com-params: n, 8, Tx+. The Char. Format
parameter shall be set in three steps: Text orientat: Textmode (D0), Char. Size: W0/H0, and Char. Sparing: 0.
Drew Pleva
Date 23.07.2013
CONNECTION SP HP
Version 22 Page/pages
Revision 13/0713 Z468466 1/14
Drew Pleva
Date 23.07.2013
CONNECTION SP HP
Version 22 Page/pages
Revision 13/0713 Z468466 2/14
Drew Pleva
Date 23.07.2013
CONNECTION SP HP
Version 22 Page/pages
Revision 13/0713 Z468466 3/14
Drew Pleva
Date 23.07.2013
CONNECTION SP HP
Version 22 Page/pages
Revision 13/0713 Z468466 4/14
Drew Pleva
Date 23.07.2013
CONNECTION SP HP
Version 22 Page/pages
Revision 13/0713 Z468466 5/14
VP_CPUS- XS1
CHIP CARD
ETHERNET
SERVO
LED-LOGO
RS232
USB
K60/A2
X3/PE
T1/20
F1
F2
BLACK
BOARD VP_KON…
VP_CPUS XP9/5
VP_CPUS XP9/6
PRINTER
BOARD VP_CPUM…
SWITCH
FOR BIOS
Drew Pleva
Date 23.07.2013
CONNECTION SP HP
Version 22 Page/pages
Revision 13/0713 Z468466 6/14
PRINTER
VP_CPUS XP9/5
VP_CPUS XP9/6
SWITCH
FOR BIOS
RS232
ETHERNET
USB
F2
T1/20
F1
X3/PE
K60/A2
FOR LED
BACKLIGHT
CHIP CARD
INVERTER FOR
BACKLIGHT
TOUCHSCREEN
8,4“
CCFL
Drew Pleva
Date 23.07.2013
CONNECTION SP HP
Version 22 Page/pages
Revision 13/0713 Z468466 7/14
VP_KON(CPUME)-XS1
VP_CPUB(BE)-XS1
24V AC
1AC
BOARD
VP_PAC…
RS 232
BOARD VP_CPUS…
2AC
BOARD
VP_PAC…
SWITCH
FOR BIOS
3AC
BOARD
VP_PAC…
24V DC
Drew Pleva
Date 23.07.2013
CONNECTION SP HP
Version 22 Page/pages
Revision 13/0713 Z468466 8/14
T1/20
F1
BOARD
VP_CPUB2… VP_CPUS-XS2
RESET
SWITCH
FOR BIOS
CN1
TOUCHSCREEN
5,7“ COLOUR
BOARD
VP_CPUBE… VP_CPUS-XS2
SWITCH
FOR BIOS
Drew Pleva
Date 23.07.2013
CONNECTION SP HP
Version 22 Page/pages
Revision 13/0713 Z468466 13/14
* For independently sealed door
** For 9xx
Drew Pleva
Date 23.07.2013
CONNECTION SP HP
Version 22 Page/pages
Revision 13/0713 Z468466 14/14
ERROR REPORTING – STERIVAP HP
If on the display there repeatedly appears the error reporting, it is necessary, after setting the password for the error
confirmation, to switch off and again switch on the electricity supply. If the error continues to exist, please, proceed according to
the following table.
After pressing the button the service technician can suppress the errors for up to 999 seconds (repeated pressing).
Manufacturer: Distributor: