Material Abstract

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 19

Sokode

11kV
Line
S.No DESCRIPTION OF ITEMS UNIT QTY
73 11/0.433kV PMT 315kVA ea 0
74 11/0.433kV PMT 200kVA ea 1
76 11/0.433kV PMT 50kVA ea 14
Sokode- HO BSP- Pokuase
gborgame Sokode 33KV Line Total
PSS 33KV Line

0
1
14
S.No DESCRIPTION OF ITEMS UNIT QTY
Survey, Bush Clearing & Drawings
1 Bush Clearing - (Light Forest)-10m width km 10
Preparation of 'As Built Drawings' (3 hard copies and a Soft copy) for new construction
2 (1:2500) - given initial drawing by PDS for OHLs or UGC cct-km 20
3 Route Survey & Pegging by Contractor in readiness for construction cct-km 20
11kV Switchgear
11KV I/D Feeder Cubicle C/W 630A CB, Overcurrent and Earthfault Relays, Metering CTs,
Reclosing Relays and Sensitive Earthfault Relays, Earth Switch, Instanteneous and Max.
4 Demand Ammeter, KWhr and KVAhr Meter ea 0
Overhead Line Hardware (33kV)
33kV Intermediate X" arm angle section C/W Tie Straps(2), M20 x 40mm Bolts, Nuts &
5 Washers. ( 2 ) 2.6m (including 9No. Provisional) set 234
6 33kV Intermediate X"arm Angle Section (including 6No. Provisional) ea 64
7 33kV Polymeric Pin Type Insulator c/w fittings ea 766
8 33kV Polymeric Tension Type Insulator c/w fittings ea 204
Fittings for strain Insulator consisting of ball, Clevis, hook, Section Strap, and Anchor Clamp
9 for 265sq.mm set 0
Fittings for strain Insulator consisting of ball, Clevis, hook, Section Strap, and Anchor Clamp
10 for 120sq.mm set 204
Overhead Line Hardware (11kV)
11kV Intermediate angle iron crossarm (2.0m) C/W, Tie Straps(2No), M20 x 40mm Bolts, Nuts
11 & Washers(2No.). set 66
12 11kV Intermediate angle iron crossarm (2.0m Long) set 10
13 11kV Polymeric Pin Type Insulator c/w fittings ea 204
14 11kV Polymeric Tension Type Insulator c/w fittings ea 30
Fittings for strain Insulator consisting of ball, Clevis, hook, Section Strap, and Anchor Clamp
15 for 120sq.mm set 30
Low Voltage Overhead Line Hardware
16 D Iron C/W Pin (99mm x 120mm x 6mm) large ea 0
17 D-Iron Bracket Extension Strap C/W pins pair 0
18 LV Shackle Insulator - Porcelain (76mm height) ea 0
Overhead Line Conductors & Binding Wire
19 Hard drawn Aluminium bare stranded conductor (AAC) 265 sq.mm m 0
20 Hard drawn Aluminium bare stranded conductor (AAC) 120 sq.mm m 72600
21 Hard drawn Aluminium bare stranded conductor (AAC) 50 sq.mm m 0
22 Soft Aluminium Binding Wire m 970
23 Mid span joint for 120sq.mm AAC ea 25
24 Mid span joint for 265sq.mm AAC ea 0
25 Restringing of existing conductor - 120 sq.mm AAC m
ABC Low Voltage Overhead Line Hardware
Complete ABC Suspension Assembly including Bracket, Clamp, Straps etc. for (3x120mm2 +
26 1x70mm2) Al ABC ea 0
Complete ABC Dead End Assembly including Bracket, Clamp, Straps etc. for (3x120mm2 +
26 1x70mm2) Al ABC ea 0
Complete ABC Heavy Angle Assembly including Bracket, Clamp, Straps etc. for (3x120mm + 2

27 1x70mm2) Al ABC ea 0
28 `Q ea 0
ABC Insulation Piercing Connector for (3x120mm2+1x70mm2) to (3x120mm2+1x70mm2 ABC)
29 Connection connectors ea 0
30 ABC Insulation Caps for (3x120mm2+1x70mm2) ABC . ea 0
31 Pre-Insulated Compression Junction suitable for (3x120mm 2+ 1x70mm2)ABC ea 0
32 LV PVC Aerial Bundled Al. conductor (ABC)3x120+1 x 70sq. mm m 0
Poles & Trenches
33 Wood pole 9m ea 0
34 Wood pole 10m ea 0
36 Wood pole 11m ea 80
37 Wood pole 12m ea 0
38 Wood Pole - 14m ea 0
39 Steel Tubular Pole - 11m ea 290
40 Steel Tubular Pole - 12m ea 0
41 Steel Tubular Pole - 14m ea 0
42 Trench excavation & backfilling in normal soil for 9m pole ea 0
43 Trench excavation & backfilling in normal soil for 10m pole ea 0
44 Trench Excavation and Filling in normal soil for 11m pole ea 370
45 Trench Excavation and Filling in normal soil for 12m pole ea 0
46 Trench excavation & backfilling in normal soil for 14m pole ea 0
Trench excavation & backfilling in water logged soil for 9m pole with 0.1m thick concrete and
47 0.2m above ground ea 0
Trench excavation & backfilling in water logged soil for 10m pole with 0.1m thick concrete
48 and 0.2m above ground ea 0
Trench excavation & backfilling in water logged soil for 11m pole with 0.1m thick concrete
49 and 0.2m above ground ea 0
Trench excavation & backfilling in water logged soil for 12m pole with 0.1m thick concrete
50 and 0.2m above ground ea 0
Trench excavation & backfilling in water logged soil for 14m pole with 0.1m thick concrete
51 and 0.2m above ground ea 0
Reinforcement of foundation in normal soil for 10m pole with 0.1m thick concrete ea 0
Reinforcement of foundation in normal soil for 11m pole with 0.1m thick concrete (for
existing poles at the end of tilted portions that will remain during recostruction) ea 0
Reinforcement of foundation in normal soil for 12m pole with 0.1m thick concrete ea 0
Stay Equipments
52 LV Stay Insulator ea 0
53 11kV Stay Insulator ea 20
54 33kV Stay Insulator ea 102
Stay Equipment C/W Rod & Plate, Bow, 1NO. Brackets & 2nO. thimbles and M16 X 40mm bolt
55 & nuts. (inclding 10% of existing ones to be replaced - Provisional) set 114
56 Stay Wire 7/ 4 SWG m 1368
57 Wooden Stay Block ea 114
Substation Equipments and Materials (11kV)
58 800kVA GMT full package ea 0
59 500kVA GMT full package ea 0
60 315 kVA GMT full package ea 0
61 200 kVA GMT full package ea 0
62 800kVA partial package without HV RMU ea 0
63 500kVA partial package without HV RMU ea 0
67 315 kVA partial package without HV RMU ea 0
68 200 kVA partial package without HV RMU ea 0
69 11/0.433kV GMT 800kVA ea 1
70 11/0.433kV GMT 500kVA ea 0
71 11/0.433kV GMT 315kVA ea 0
72 11/0.433kV GMT 200kVA ea 0
73 11/0.433kV PMT 315kVA ea 0
74 11/0.433kV PMT 200kVA ea 1
75 11/0.433kV PMT 100kVA ea 14
76 11/0.433kV PMT 50kVA ea 14
77 11kV Expulsion type fusegear - single pole ea 90
78 Lightning Arrestor - 11kV ea 90
79 11kV Metering Cubicle c/w 3N0. CTs ea 0
80 11kV expulsion type fuselink 3A ea 42
81 11kV expulsion type fuselink 6A ea 42
82 11kV expulsion type fuselink 15A ea 3
83 11kV expulsion type fuselink 20A ea 0
84 11kV expulsion type fuselink 30A ea 0
85 11kV expulsion type fuselink 63A ea 0
86 Ancilliary Channel crossarm for 11kV 1.6m Long ea 174
87 Distribution Panel 4-Way ea 0
88 Distribution Panel 6-Way ea 0
89 Distribution Panel 8-Way ea 0
Substation Equipments and Materials (33kV)
90 33/0.433kV PMT 315kVA ea 0
91 33/0.433kV PMT 200kVA ea 3
92 33/0.433kV PMT 100kVA ea 3
93 33/0.433kV PMT 50kVA ea 2
101 33/0.433kV 100 kVA GMT ea 0
102 33/0.433kV 200 kVA GMT ea 0
103 33/0.433kV 315 kVA GMT ea 0
33/0.433kV 500 kVA GMT (Including 1No. To replace existing 400kVA) - To be procured from
104 open market ea 1
105 33/0.433kV 800 kVA GMT - To be procured from open market ea 0
106 33/0.433kV 1MVA GMT - To be procured from open market ea 0
107 33/0.433kV 1.25MVA GMT - To be procured from open market ea 0
94 33kV Expulsion type fusegear - single pole ea 27
95 Lightning Arrestor - 33kV ea 27
96 33kV expulsion type fuselink 1A ea 6
97 33kV expulsion type fuselink 2A ea 9
98 33kV expulsion type fuselink 5A ea 9
99 33kV expulsion type fuselink 6A ea 0
108 33kV Expulsion Type Fuselink 10A ea 3
116 33kV Expulsion Type Fuselink 20A ea 0
100 Ancilliary Channel crossarm for 33kV (Including 15No. Provisional) ea 0
117 33kV Metering Cubicle c/w 3N0. CTs ea 0
Substation Accessories including LV Materials
118 Transformer Mounting Bracket pr 37
119 L-Bracket Attachment to Fusegear/Lighting Arrestor ea 234
LV pvc insulated, pvc sheathed Al. Conductor 120 sq. mm (Including provision for 10 No.
120 PMTs) m 0
121 400A Pole mounted service cut out (Including provision for 10 No. PMTs) ea 0
Low Voltage HRC Type J Fuselink With Non-Slotted Tag - 63A - 92mm (Including provision for
124 10 No. PMTs) ea 0
109 Low Voltage HRC Type J Fuselink With Non-Slotted Tag - 100A - 92mm ea 0
110 Low Voltage HRC Type J Fuselink With Non-Slotted Tag - 200A - 92mm ea 0
111 Substation chain link fencing with gates ea 1
112 11kV GIS Pole Mounted Load Isolator c/w support structure ea 0
113 33kV GIS Pole Mounted Load Isolator c/w support structure ea 0
114 11kV 400A Pole Mounted Auto Recloser c/w support structure ea 0
115 33kV 400A Pole Mounted Auto Recloser c/w support structure ea 0
Switches and Accessories
122 11kv Non-extensible Ring Main Unit Type FRMU MK IA ea 0
123 11kV Extensible GIS/Oil Switch - Lucy & Co. ea 0
125 11kV Extensible GIS/Oil Fused Switch - Lucy & Co. ea 0
126 Busbar coupling Kit for EOS & EFS (Lucy) Switches ea 0
127 Busbar End Cap Kit for EOS &EFS Switches ea 0
133 Transformer Oil - 205L dr 0
134 Plinth for Transformer in normal soil (300mm above ground) ea 1
135 Plinth for Transformer - Partial Package S/S in normal soil (300mm above ground) ea 0
136 Plinth for Transformer - Full Package S/S in normal soil (300mm above ground) ea 0
137 Plinth for Feeder /Fused Switch in normal soil (300mm above ground) ea 0
138 Plinth for Ring Main Unit in normal soil (300mm above ground) ea 0
139 Plinth for Metering Unit in in normal soil (300mm above ground) ea 0
Plinth for DP in normal soil (300mm above ground) ea 0
11kV Cables, Terminations & Joints
140 11kV XLPE/SWA/PVC Al. cable 3 x 185 sq.mm m. 500
141 Trench excavation & backfilling for 3x185sqmm 11kV single circuit m 500
142 Trench excavation & backfilling for 3x185sqmm 11kV double circuit m 0
143 11kV XLPE/SWA/PVC Al. cable 1 x 240 sq.mm m 5000
144 Trench excavation & backfilling for 1x240sqmm 11kV single circuit m 2000
#REF! 11kV XLPE/SWA/PVC Al. cable 3 x 95 sq.mm m 0
#REF! Trench excavation & backfilling for 3x95sqmm 11kV single circuit m 0
#REF! Outdoor Termination for 3 x (1 x 240sq.mm) XLPE Cable ea 0
#REF! Indoor Termination for 3 x (1 x 240sq.mm) XLPE Cable ea 0
#REF! Straight Joint for 3 x (1 x 240) XLPE (Heat Shrink) set 0
145 Outdoor Termination for 3 x 185sq.mm XLPE Cable ea 0
146 Indoor Termination for 3 x 185sq.mm XLPE Cable with Straight boot set 0
147 Indoor Termination for 3 x 185sq.mm XLPE Cable with Rt. Angle boot set 0
148 Straight Joint for 3 x 185 XLPE (Heat Shrink) set 1
149 Outdoor Termination for 3 x 95sq.mm XLPE Cable set 0
150 Indoor Termination for 3 x 95sq.mm XLPE Cable set 0
151 Straight Joint for 3 x 95 XLPE (Heat Shrink) set 0
153 11kV Cable Marker ea 3329
154 Trench excavation & backfilling for LV single circuit m 0
155 LV XLPE/SWA/PVC Al. cable 4 x 185 sq.mm m. 0
156 Outdoor Termination for 4 x 185sq.mm XLPE LV Cable set 0
157 Indoor Termination for 4 x 185sq.mm XLPE LV Cable set 0
158 Straight Joint for 4 x 185 XLPE (Heat Shrink) set 0
159 LV XLPE/PVC Cu. cable 1 x 500 sq.mm m. 0
160 Cu. Compression cable lug 500 sq.mm ea 0
LV XLPE/PVC Cu. cable 1 x 185 sq.mm m 0
Cu. Compression cable lug 185 sq.mm ea 0
33kV Cables, Terminations & Accessories
161 33kV XLPE/SWA/PVC Al. cable 1 x 630sq.mm (Cable handling) m 5000

162 Trench excavation & backfilling for 1x 630 Al single circuit (0.6m width x 0.9m depth) m 2000
Trench excavation & backfilling for 1x 630 Al double circuit including sand bedding (0.6m
163 width x 0.9m depth) m 2000
Trench excavation & backfilling for (1x 630 Al) four circuits including sand bedding (1.2m
164 width x 0.9m depth) m 0
165 33kV Cable Marker ea 2
166 Indoor Termination for 1 x 630 XLPE ea 0
167 Straight Through Joint for 1 x 630 XLPE ea 0
168 Outdoor Termination for 1 x 630 XLPE ea 0
169 Compression cable lug 70 sq.mm Cu - for earthing of cables to the indoor panels ea 0
170 630sq.mm Aluminium cable lug for outdoor termination ea 0
Cable Laying Accessories, PVC Pipes, etc.
171 Cable Cover Tile ea 200
172 Cable warning tape for both HV & LV circuits m 100
173 HV Insulating Tape (Rotunda) roll 1
174 LV Insulating Tape roll 0
175 10.16cm x 304.8cm Ordinary PVC Pipe ea 0
176 10.16cm x 609.6cm High Presure PVC Pipe ea 3
177 15.0cm x 609.6cm High Presure PVC Pipe ea 0
178 22.0cm x 609.6cm High Pressure PVC Pipe ea 0
181 Plastic staple for 1x240sq.mm Cables @ 1m intervals ea 0
182 Plastic staple for 1x630sq.mm Cables @ 1m intervals ea 215
183 Construction of 12.0m Space Truss (including material) ea 0
Road Crosings
Launching pit for thrust boring (2m x 3m x2m deep for take-off & 1m x 2m x 2m deep for
184 receiving end) m3 0
185 4 - inch Thrust boring - asphalt & tared road crossing m 15.0
186 6 - inch Thrust boring - asphalt & tarred road crossing m 0.0
187 8 - inch Thrust boring - asphalt & tarred road crossing m 0.0
188 Removal and Reinstatement of pavement blocks (0.6m x 0m) m2 0.00
189 Removal and Reinstatement of concrete surfaces (0.6mx0.1m x 12m) m3 0.00
190 Removal and Reinstatement of grassed surfaces (0.6m x 0m) m2 120.00
Bolts, Nuts, Washers and Connectors
191 Bimetallic tap-off clamp (bolted type) 120Al/16Cu ea 0
192 Al. tap-off clamp (bolted type) 120 /120 ea 271
193 Al. tap-off clamp (bolted type) 265/265 ea 0
194 Bolt,Nut & Washers M20 x 280mm ea 880
195 Bolt,Nut & Washers M16 X 300mm (Double Arm) ea 0
196 Bolt,Nut & Washers M16 x 220mm ea 0
35 sq.mm Copper compression cable lug (Including provisional for 30% of existing substations
197 and lightning arrestors) ea 47
198 120 sq.mm Aluminium compression cable lug ea 0
199 185 sq.mm Aluminium compression cable lug ea 0
200 240 sq.mm Aluminium compression cable lug ea 0
201 300 sq.mm Aluminium compression cable lug ea 0
202 70 / 95 Bimetal compression lug ea 0

203 150 /185 Bimetal compression lug (Including provisional for 30% of existing substations) ea 389
204 185/240 Bimetal compression lug ea 0
205 630sq.mm Bimetalic cable lug. ea 0
Earthing Materials
PMT Earthing inclusive of surge divertor earthing {10rods + 35m(35Cu) + 20m(16Cu) +
205 10m(16pvc) } (Including provisonal fo 30% of existing substations) ea 11
GMT stand alone Earthing {5rods + 25m(35Cu)} (Including provisonal fo 30% of existing
206 substations) ea 1
207 Partial Package (DP together with Transformer) {5 rods + 25m(35Cu} ea 0
208 Full Packaged Earthing (Transformer, DP and RMU) {5rods + 25m(35Cu) } ea 0
209 DP Earthing {5rods + 25m(35Cu)} ea 0
210 Surge Arrestor Earthing {5rods + 25m(35Cu)} ea 1
211 LV Earthing {1rod + 10m(16pvc)} ea 0
212 RMU/EOS/EFS/Metering Unit Earthing {5rods + 25m(35Cu)} ea 0
213 Steel tubular pole earthing {1 rod + 3m(35Cu)} ea 290
214 Copper Earth Rod C/W Clamp ea 0
215 Hard drawn Copper bare stranded conductor 35 sq.mm ea 0
216 Hard drawn Copper bare stranded conductor 16 sq.mm ea 0
217 LV pvc insulated, pvc sheathed Copper Conductor 16sq. mm ea 0
Retiring of RMUs, Conductors and Poles
218 Hard drawn Copper bare stranded conductor, 16 sq.mm m 0
219 Hard drawn Aluminium bare stranded conductor (AAC) 25 sq.mm m 0
220 Hard drawn Copper bare stranded conductor, 35 sq.mm m 0
221 Hard drawn Aluminium bare stranded conductor (AAC) 50 sq.mm m 0
222 Hard drawn Aluminium bare stranded conductor (AAC) 120 sq.mm m 0
223 Dismantling of LV PVC aerialBundled Al. conductor (ABC) 3x50+1 x 50sq. mm m 0
Dismantling of LV line structure, any type or size including all brackets, poles, steelwork and
224 insulators Lot. 0
Dismantling of HV wood line structure, any type or size including all brackets, poles, steelwork
225 and insulators Lot. 0
Dismantling of HV concrete line structure, any type or size including all brackets, poles,
226 steelwork and insulators Lot. 0
227 Dismantling of 11kv Non-extensible Ring Main Unit Type FRMU MK IA ea 0
228 Dismantling of 11KV GIS Pole Mounted Load Isolator ea 0
229 Dismantling of 33KV Load Isolator Three pole c/w bar ea 0

230 Dismantling of 11kV 50kVA PMT substation (including 11kV fusegear and lightning arrestors) ea 14

231 Dismantling of 11kV 100kVA PMT substation (including 11kV fusegear and lightning arrestors) ea 14

232 Dismantling of 11kV 200kVA PMT substation (including 11kV fusegear and lightning arrestors) ea 4

233 Dismantling of 11kV 315kVA PMT substation (including 11kV fusegear and lightning arrestors) lot 0

Dismantling of 11kV 100kVA GMT substation (including 11kV fusegear and lightning arrestors) lot 0

234 Dismantling of 11kV 200kVA GMT substation (including 11kV fusegear and lightning arrestors) lot 0

235 Dismantling of 11kV 315kVA GMT substation (including 11kV fusegear and lightning arrestors) lot 0

Dismantling of 11kV 400kVA GMT substation (including 11kV fusegear and lightning arrestors) lot 0

236 Dismantling of 11kV 500kVA GMT substation (including 11kV fusegear and lightning arrestors) lot 1

237 Dismantling of 11kV 800kVA GMT substation (including 11kV fusegear and lightning arrestors) lot 1
238 Dismantling of 11kV Pin Insulator (Glass) c/w fitting ea 0
239 Dismantling of 11kV Pin Insulator (Porcelain) c/w fitting ea 0
240 Dismantling of 11kV Pin Insulator (Polymer) c/w fitting ea 0
241 Dismantling of 11kV Strain Insulator (Glass)c/w fitting -set of three (3) discs set 0
242 Dismantling of 11kV Strain Insulator (Porcelain)c/w fitting-- set of three (3) discs set 0
243 Dismantling of 11kV Strain Insulator (Polymer)c/w fitting ea 0
Dismantling of 11kV Extensible GIS/Oil Switch - Lucy & Co. with coupling and other
244 accessories ea 0
Dismantling of 11kV Extensible GIS/Oil Fused Switch - Lucy & Co.with coupling and other
245 accessories ea 0
246 Dismantling of 11kV Metering Cubicle c/w 3N0. CTs ea 0
247 Dismantling of 11kV XLPE/SWA/PVC Al. cable 3 x 95 sq.mm m
248 Dismantling of 11kV XLPE/SWA/PVC Al. cable 3 x 185 sq.mm m
249 Dismantling of 11kV XLPE/SWA/PVC Al. cable 1 x 240 sq.mm m
Reinstallation of LV headgear
250 Reinstallation dimantled LV headgear on relocated & reconstructed PMTs Lot 0
Metering Service Installation Costs
LV Metering Cubicle & connecting accessories for 800/5A ,1000/5A AMR metering (10m
circuit length of1x500sq.mmCu. LV PVC cable, 2m of 16sq.mm Cu LV PVC conductor,
2No.11KV Intermediate Angle cross arms,8No. 500sqmm compression Cu. lugs, 1No. copper
earth rod, 4No.M40 X 300bolts & nuts, 4No.M8 X 40bolts & nuts, 2No. LV insulating tape, 1
251 pack of cable tie) Lot. 0
252 Meter Installation fee for MV SLT metring (11kV) ea 0
253 Meter Installation fee for HV SLT metring (33kV) ea 0
ENGINEERING DESIGN, PRELIMINARIES, PROJECT SUPPORT
Engineering and Design services Lot 1
Pre-Commissioning Test Lot 1
Preliminaries Lot 1
Local Transportation of MateriaLot from Port to Project Site Lot 1
Project Support Lot 1
TOTAL OF MATERIAL & INSTALLATION (TOTAL 1)
MATERIAL SCHEDULE FOR THE PRIMARY DISTRIBUTION SUNSTATION & 33KV DOUBLE CCT STEEL LATICE TOWER LINES BETWEEN H
BSP & PRIMARY DISTRIBUTION SUBSTATION AT SOKODE GBOGAME
S.No ITEM DESCRIPTION
33kV Indoor Single Bus Switchgear 2000A GIS

33kV I/D Feeder Panel, c/w 1250A CB, 600/1200/5/5A 2-Core CTs, AC Directional over current and AC
Directional Earth fault relay (67/67N), Instantaneous over current and AC Time delay overcurrent relay (50/51),
Instantaneous earth fault and AC time earth fault relay (50N/51N), AC reclosing relay (79) and Distance Relay
1 (21) : the isolators should be motorised and the switchgear should be SCADA ready (with all Intelligent Electronic
Devices being IEC 61850 compliant). The switchgear should come complete with 2No of cable termination slots
per phase

33kV I/D Busbar Coupler Cubicle c/w 2000A CB & 2400/1200/5/5A 2-core CTs, Instantaneous over current and
AC Time overcurrent relay (50/51), Instantaneous earth fault and AC time earth fault relay (50N/51N),: the
2 isolators should be motorised and the switchgear should be SCADA ready ((with all Intelligent Electronic Devices
being IEC 61850 compliant).

33kV I/D Transformer Cubicle c/w 1250A CB, 1200/600/5/5/5A 3-core CTs, Instantaneous over current and AC
Time delay overcurrent relay (50/51), Instantaneous earth fault and AC time earth fault relay (50N/51N) and
3 Transformer differential relay (87T): the isolators should be motorised and the switchgear should be SCADA
ready ((with all Intelligent Electronic Devices being IEC 61850 compliant). The switchgear should come complete
with 2No of cable termination slots per phase

33kV I/D Feeder Panel, c/w 1250A CB, VTs & 600/1200/5/5A 2-Core CTs, AC Directional over current and AC
Directional Earth fault relay (67/67N), Instantaneous over current and AC Time delay overcurrent relay (50/51),
5 Instantaneous earth fault and AC time earth fault relay (50N/51N), AC reclosing relay (79) and Distance Relay
(21) : the isolators should be motorised and the switchgear should be SCADA ready (with all Intelligent Electronic
Devices being IEC 61850 compliant). The switchgear should come complete with 2No of cable termination slots
per phase

11kV Indoor Switchgear - 2500A Busbar Rating AIS


11KV I/D Feeder Cubicle C/W 630A CB,3-core CTs, Instantaneous over current and AC Time delay overcurrent
relay (50/51), Instantaneous earth fault and AC time earth fault relay (50N/51N), Metering CTs, Reclosing Relays
13 and Sensitive Earthfault Relays, Earth Switch, Instanteneous and Max. Demand Ammeter, KWhr and KVAhr
Meter: the isolators should be motorised and the switchgear should be SCADA ready (with all Intelligent
Electronic Devices being IEC 61850 compliant).

11KV I/D Transformer Cubicle, C/W 2000A CB & 2500-1500/5/5/5A ,VTs, Instantaneous over current and AC
Time delay overcurrent relay (50/51), Instantaneous earth fault and AC time earth fault relay (50N/51N),
14 Metering CTs, Reclosing Relays and Sensitive Earthfault Relays, Earth Switch, Instanteneous and Max. Demand
Ammeter, KWhr and KVAhr Meter: the isolators should be motorised and the switchgear should be SCADA ready
(with all Intelligent Electronic Devices being IEC 61850 compliant). The switchgear should come complete with
4No of cable termination slots per phase

11kV I/D Bus Coupler C/W 2000A CB, Protection and Metering CTs, Instantaneous over current and AC Time
delay overcurrent relay (50/51), Instantaneous earth fault and AC time earth fault relay (50N/51N): the isolators
15 should be motorised and the switchgear should be SCADA ready (with all Intelligent Electronic Devices being IEC
61850 compliant).

11kV Auxilliary Transformer Cubicle equipped with 630A CB, 25/5A 2-core CTs, Instantaneous over current and
AC Time overcurrent relay (50/51), Instantaneous earth fault and AC time earth fault relay (50N/51N),: the
isolators should be motorised and the switchgear should be SCADA ready ((with all Intelligent Electronic Devices
being IEC 61850 compliant).
Power Transformer, OLTC Panel, NGRs & Cable Support Structures
16 20/26 MVA ONAN/ONAF 33/11KV Power Transformer with indoor bushings (for indoor stations)

On-load Tap Changer Control Panel for the 20/26MVA Power Transformer (note: Annunciation facility for the
17 Power Transformer is to be incorporated into the OLTC Panel with a minimum of three (3) spare windows)

11kV Neutral Earth Resistor, Isolator & 1600-800/5A Current Transformer, Instantaneous earth fault and AC time
18 earth fault relay (50N/51N), 6.35 ohms, 1000A per 30sec
Auxiliary Power Supply Equipment
19 100KVA Aux. Transformer 11kV/400V/230V for indoor stations
20 LV AC Distribution Board
110V DC System including 2no battery banks, 2no. battery chargers, distribution panel Lot and manual and
21 automatic transfer switches and fuses and all accessories deemed necessary to ensure that the system is fit for
purpose
110V DC System including 2no battery banks, 2no. battery chargers, distribution paneLot and manual and
22 automatic transfer switches and fuses and all accessories deemed necessary to ensure that the system is fit for
purpose
23 Substation Lighting System - Outdoor /Compound Lighting as required
24 Substation Lightning Mast c/w support structures & connecting accessories as required
25 Fire Extinguishers (CO2 and Powder types, 10kg each) 4no.
26 Automatic Fire detection, protection and Fire Extingushing (wall mounted) for control house building
27 Substation Automation System (SAS) - ECG Specification E-91
Intelligent pump of rating 2.2kW/3Hp, Vp 220/230V, VI 415, 50Hz shall be provided at the station for the
28 collection of rain water in the transformer bund area (4No. Required: 2no for basement & 1no each for Power
Transformer)
Complete Network Communication Equipment to integrate with existing ECG communication System and
29 existing ECG network management syetem (NMS)
30 Complete security cameras and access control system for the station
31 30kW Solar System c/w all required accessories
Power & Control Cables
32 Power and Control cables for 400/240V AC auxiliary services including all distribution boards
All auxilliary cabling for each relevant indoor substation equipment using average length (cabling between power
33 trafo & OLTC panel, OLTC panel to trafo switchgear, AC&DC supply to all the switchgear (11kV & 33kV), DC
Emergency lighting system connection to the DC board)
1x630sq.mm XLPE(33kV) Copper Cable for the connection of the Power Transformers to the 33kV Transformer
34 Cubicle (2 run per phase)
35 Indoor Terminations Kit for 1x500sq.mm XLPE (33kV) Al Cable
Indoor Terminations Kit (Plug in type) for 1x500sq.mm XLPE (33kV) Cu Cable/1x630sq.mm XLPE (33kV) Al
36 Cable/Cu Cable
37 Blinding plugs for 33kV Switchgear

1x240sq.mm XLPE(11kV) Aluminium Cable for the connection of the Power Transformers to the 11kV
38 Transformer Cubicle (4 runs per phase)plus connection of Auxiliary Transformer to Auxiliary Transformer Cubicle

39 Indoor Terminations Kit for 1x500sq.mm XLPE (11kV) Cu Cable


40 4 x 95sq.mm XLPE (LV) Al Cable for connection between auxilliary transformer and LV AC Distribution Board
41 I/D Termination (heat shrink) for 4 x 95sq.mm LV Cable
42 Hard Drawn Bare Stranded Copper Conductor - 150sq.mm
43 Copper Earth Rod:- 16mm diameter earth rod of 1.5m length - equipment earth plus earth grid
44 Earthing materiaLot for cadweld connections/joints
Substation Equipment & Support Structure Earthing (70sq.mm Cu conductor, copper earth rods and other
45 accessries) - standard indoor station
Substation Control Building and Switchyard

Construction of Control Building complete with all finishes , fixtures , furnishes and building services ready for
installation of electromechanical equipment. (Include Mechanised borehole, Security Gate and Transit Qtrs
46 Complete, Road provision in the switching station and at the entrance up to ......., swicthing station yard fencing,
switching station drainage system, manholes, masonry fencewalls with concrete columns at 3m intervals, steel
metallic gates for vehicles & pedestrians and Landscaping

ENGINEERING DESIGN, PRELIMINARIES, PROJECT SUPPORT


47 Engineering and Design services for Substations
48 Pre-Commissioning Test of the Substation
49 Preliminaries for Substations
50 Local Transportation of MateriaLot from Port to Project Site for Substation
51 Project Support
TOTAL OF MATERIAL & INSTALLATION (TOTAL 1)
TOWER LINES BETWEEN HO

UNIT QTY

No. 5

No. 1

No. 2

Set 2

No. 6

No. 2

No. 1

No. 1

No. 2

No. 2

No. 2
No. 1
No. 1

Set 1

Set 1
Lot 1
Lot 1
Lot 1
Lot 1
Lot 1

Lot 1

Lot 1
Lot 1
Lot 1

Lot 1

Lot 1

m 1,000
No. 15

No. 72
No. 30

m 1,500
No. 28
m 50
Set 2
m 4,140
No 254
No 2,116

Lot 1

Lot 1

Lot 1
Lot 1
Lot 1
Lot 1
Lot 1
S.No Material Description Unit Qty
Bush Clearing and Survey
Detailed survey of tower line route, line profile and detailed design (spotting), Pegging of
1 Tower Positions and Geotechnical Survey km 15
2 Bush Clearing - Light Forest km 11
TOWER LINE PORTION
3 Double Circuit Tower Type SS (Suspension) of basic height for 265sq.mm AAC. No 100
4 Double Circuit Tower Type SS (Suspension) with 3M extension for 265sq.mm AAC. No 8
5 Double Circuit Tower Type SS (Suspension) with 6M extension for 265sq.mm AAC. No 4
6 Double Circuit Tower Type AC of basic height for 265sq.mm AAC. No 20
7 Double Circuit Tower Type AC with 3M Extension for 265sq.mm AAC. No 2
8 Double Circuit Tower Type AC with 6M Extension for 265sq.mm AAC. No 1
9 Double Circuit Tower Type DE of basic height for 265sq.mm AAC. No 14
Double Circuit Tower Type Specially designed for 90o Angle for 265sq.mm AAC - basic
10 height No 1
11 265sqmm hard Drawn All Aluminium conductors. km 100
Fibre-Optic cables & accessories
12 Optical Ground Wire (OPGW) 4000m per drum - to be laid as skywire. km 16
13 48 core underground fibre optic cable (4000m per drum) km 2
14 Vibration Dampers for skywire (OPGW) No 300
15 Suspenson Fitting to suit OPGW No 195
16 Tension Fitting to suit OPGW No 88
17 Joint Box OPGW/OPGW No 4
18 Joint Box OPGW/UGFOC No 2
19 Joint Box UGFOC/UGFOC No 0
20 ODF (to install at Substation) No 2
21 Down Lead Clamp No 74
22 Coil Clamp No 37
23 PLB Tube for UGFOC km 2
24 Pre-Installtion Testing of OPGW & UGFOC Drum 5
25 Vibration dampers for 265sq.mm AAC No 3396

26 33kV Polymeric tension insulator set including fittings and hardware for 265sq.mm AAC Set 528
33kV Polymeric suspension insulator sets including fittings and hardware for 265sq.mm
27 AAC Set 1170
28 Tower footing earthing (2rods +10m(35sq.mm Cu. Bare) + accessories) Lot. 240
29 Counterpoise grounding for towers (1 rod + 2m(35sq.mm Cu Bare) + accessories) Lot 24
30 33kV Surge Divertor (Set of 3No) Lot. 4
31 Surge
the Divertor
tower typesEarthing (5rods +35m
are as follows: (35sq.mm
.(The cost Cu. Bare) + also
of the foundation accessories)
includes supply & placement of Lot. 8
reinforced concrete (1:2:4) and steel)
Foundation in normal /Laterite/Good soil for SS Double Circuit Tower (Excavation of
32 required hole dimension & casting of concrete to fill) - 400AAC Tower Type No 75
Foundation in poor/wet soil for SS Double Circuit Tower (Excavation of required hole
33 dimension & casting of concrete to fill) - 400AAC Tower Type No 18
Foundation in submerged soil for SS Double Circuit Tower (Excavation of required hole
34 dimension & casting of concrete to fill) - 400AAC Tower Type No 5
Foundation in Rocky for SS Double Circuit Tower of basic height - 400AAC Tower Type
35 (Excavation of required hole dimension & casting of concrete to fill) No 2
Foundation in normal /Laterite/Good soil for SS Double Circuit Tower with 3M Extension -
36 400AAC Tower Type (Excavation of required hole dimension & casting of concrete to fill) No 6
Foundation in poor/wet soil for SS Double Circuit Tower with 3M Extension - 400AAC
37 Tower Type (Excavation of required hole dimension & casting of concrete to fill) No 1

Foundation in submerged soil for SS Double Circuit Tower with 3M Extension - 400AAC
38 Tower Type (Excavation of required hole dimension & casting of concrete to fill) No 1
Foundation in Rocky for SS Double Circuit Tower with 3M Extension - 400AAC Tower Type
39 (Excavation of required hole dimension & casting of concrete to fill) No 0

Foundation in normal /Laterite/Good soil for SS Double Circuit Tower with 6M Extension -
40 400AAC Tower Type (Excavation of required hole dimension & casting of concrete to fill) No 3
Foundation in poor/wet soil for SS Double Circuit Tower with 6M Extension - 400AAC
41 Tower Type (Excavation of required hole dimension & casting of concrete to fill) No 1

Foundation in submerged soil for SS Double Circuit Tower with 6M Extension - 400AAC
42 Tower Type (Excavation of required hole dimension & casting of concrete to fill) No 0
Foundation in Rocky for SS Double Circuit Tower with 6M Extension - 400AAC Tower Type
43 (Excavation of required hole dimension & casting of concrete to fill) No 0
Foundation in normal /Laterite/Good soil for AC Double Circuit Tower (Excavation of
44 required hole dimension & casting of concrete to fill) - 400AAC Tower Type No 10
Foundation in poor/wet soil for AC Double Circuit Tower (Excavation of required hole
45 dimension & casting of concrete to fill) - 400AAC Tower Type No 5
Foundation in Submerged soil for AC Double Circuit Tower (Excavation of required hole
46 dimension & casting of concrete to fill) - 400AAC Tower Type No 4
Foundation in Rocky for AC Double Circuit Tower of basic height - 400AAC Tower Type
47 (Excavation of required hole dimension & casting of concrete to fill) No 1

Foundation in normal /Laterite/Good soil for AC Double Circuit Tower with 3M Extension -
48 400AAC Tower Type (Excavation of required hole dimension & casting of concrete to fill) No 2
Foundation in poor/wet soil for AC Double Circuit Tower with 3M Extension - 400AAC
49 Tower Type (Excavation of required hole dimension & casting of concrete to fill) No 0

Foundation in submerged soil for AC Double Circuit Tower with 3M Extension - 400AAC
50 Tower Type (Excavation of required hole dimension & casting of concrete to fill) No 0
Foundation in Rocky for AC Double Circuit Tower with 3M Extension - 400AAC Tower Type
51 (Excavation of required hole dimension & casting of concrete to fill) No 0

Foundation in normal /Laterite/Good soil for AC Double Circuit Tower with 6M Extension -
52 400AAC Tower Type (Excavation of required hole dimension & casting of concrete to fill) No 1
Foundation in poor/wet soil for AC Double Circuit Tower with 6M Extension - 400AAC
53 Tower Type (Excavation of required hole dimension & casting of concrete to fill) No 0
Foundation in normal /Laterite/Good soil for DE Double Circuit Tower - 400AAC Tower
54 Type (Excavation of required hole dimension & casting of concrete to fill) No 10
Foundation in poor/wet soil for DE Double Circuit Tower - 400AAC Tower Type (Excavation
55 of required hole dimension & casting of concrete to fill) No 2
Foundation in submerged soil for DE Double Circuit Tower - 400AAC Tower Type
56 (Excavation of required hole dimension & casting of concrete to fill) No 2
Foundation in Rocky for DE Double Circuit Tower - 400AAC Tower Type (Excavation of
57 required hole dimension & casting of concrete to fill) No 0
Foundation in normal /Laterite/Good soil for Double Circuit Tower Type Specially designed
for 90o Angle for 400sq.mm AAC - basic height (Excavation of required hole dimension &
58 casting of concrete to fill) - 400AAC Tower Type No 0
Foundation in poor/wet soil for Double Circuit Tower Type Specially designed for 90o Angle
for 400sq.mm AAC - basic height (Excavation of required hole dimension & casting of
59 concrete to fill) - 400AAC Tower Type No 1
Foundation in submerged soil for Double Circuit Tower Type Specially designed for 90o
Angle for 400sq.mm AAC - basic height (Excavation of required hole dimension & casting of
45 concrete to fill) - 400AAC Tower Type No 0
60 Hard Rock Excavation (Provisional) - 400AAC Tower Type cum 0
CABLE PORTION
61 1 x 630sq.mm XLPE (33kV) Al cable km 6
62 1 x 500sq.mm XLPE (33kV) Cu cable for take-off at both ends of the line km 0
63 Cable laying accessories such as cover tiles,warning tape, etc. Lot. 1
64 Supply of concrete for Road crossing (Provisional) Cum 0
65 Supply of 6"class C 6m High Pressure PVC Pipe (Provisional) m 0
66 Outdoor Termination Kit for 1 x 630sq.mm XLPE (33kV) Al cable ea 60
67 Indoor Termination Kit for 1 x 630sq.mm XLPE (33kV) Al cable ea 12
68 Straight through joint for 1 x 630sq.mm XLPE (33kV) Al cable ea 18
74 Outdoor Termination Kit for 1 x 500sq.mm XLPE (33kV) Cu cable ea 0
75 Indoor Termination Kit for 1 x 500sq.mm XLPE (33kV) Cu cable ea 0
76 Straight through joint for 1 x 500sq.mm XLPE (33kV) Cu cable ea 0
77 15.0cm x 609.6cm Ordinary PVC Pipe - CABLE RISERS ea 48
78 Provision for support for cable risers - 12 cables on a single DE Tower ea 4
79 Local Transportation of bonded warehouse to project site Lot 1
Preliminaries & Mobilisation:- Provision for Site Establisment, Site Offices, Storage Facilities,
80 Hiring of Tools and equipment etc for a tower line Lot 1
81 Project Support Lot 1
TOTAL OF MATERIAL & INSTALLATION (TOTAL 1)
CONSTRUCTION OF 2X60MVA 33kV DOUBLE CIRCUIT MONOPOLE LINES FROM POKUASE BSP TO
ADENTA DISTRIBUTION SUBSTATION

S.No Material Description Unit Qty


Bush Clearing and Survey
Detailed survey of monopole line route, line profile and detailed design (spotting)
1 and Pegging of pole Positions km 15
2 Bush Clearing - (Light Forest/grassland) - 15m width for tower line works km 5
Double Circuit Monopole Line Portion
3 Double Circuit suspension type (0-3deg) for 400sq.mm AAC No 100
4 Double Circuit light angle type (30deg) for 400sq.mm AAC No 33
5 Double Circuit medium angle type (60deg) for 400sq.mm AAC No 13
6 Double Circuit end pole type (90deg) for 400sq.mm AAC No 4
7 400sqmm Hard Drawn All Aluminium conductors km 99
Fibre-Optic cables & accessories
8 Optical Ground Wire (OPGW) 4000m per drum - to be laid as skywire. km 16.0
9 48 core underground fibre optic cable (4000m per drum) km 2.00
10 Vibration Dampers for skywire (OPGW) No 200
11 Suspenson Fitting to suit OPGW No 145
12 Tension Fitting to suit OPGW No 0
13 Joint Box OPGW/OPGW No 4
14 Joint Box OPGW/UGFOC No 2
15 Joint Box UGFOC/UGFOC No 0
16 ODF (to install at Substation) No 2
17 Down Lead Clamp No 74
18 Coil Clamp No 37
19 PLB Tube for UGFOC km 2.00
20 Pre-Installtion Testing of OPGW & UGFOC Drum 5
21 Vibration Dampers for 400sqmm AAC No 1800
33kV Polymeric tension insulator set including fittings and hardware for 400sq.mm
22 AAC No 300

33kV Polymeric suspension insulator sets including fittings and hardware for
23 400sq.mm AAC No 600
24 Mono Pole earthing (2rods +10m(35sq.mm Cu. Bare) + accessories) No 150
25 Counterpoise grounding for Mono Pole (1 rod + 2m(35sq.mm Cu Bare) + accessories) Lot 15
26 33kV Surge Divertor (Set of 3No) Lot. 4
27 Surge Divertor Earthing (5rods +35m (35sq.mm Cu. Bare) + accessories) Lot. 4
Monopole Foundations: Reinforced concrete foundations, including all associated
work as design, excavations, soil investigations and foundations tests and finishing.
The average excavation volumes of the tower types are as follows: .(The cost of the
foundation also includes supply & placement of reinforced concrete (1:2:4) and
steel)
Foundation in normal /Laterite/Good soil for Double Circuit Suspension Monopole
28 type (0-3deg) - 20m No 70

Foundation in Poor soil for Double Circuit Suspension Monopole type (0-3deg) -
29 20m No 20

Foundation in Rocky soil for Double Circuit Suspension Monopole type (0-3deg) -
30 20m No 10

Foundation in normal /Laterite/Good soil for Double Circuit Suspension Monopole


31 type (30deg) - 20m No 20

32 Foundation in Poor soil for Double Circuit Suspension Monopole type (30deg) - 20m No 10

Foundation in Rocky soil for Double Circuit Suspension Monopole type (30deg) -
33 20m No 5
Foundation in normal /Laterite/Good soil for Double Circuit Suspension Monopole
34 type (60deg) - 20m No 10

35 Foundation in Poor soil for Double Circuit Suspension Monopole type (60deg) - 20m No 2

Foundation in Rocky soil for Double Circuit Suspension Monopole type (60deg) -
36 20m No 1

Foundation in normal /Laterite/Good soil for Double Circuit Suspension Monopole


37 type (90deg) - 20m No 2

38 Foundation in Poor soil for Double Circuit Suspension Monopole type (90deg) - 20m No 1

Foundation in Rocky soil for Double Circuit Suspension Monopole type (90deg) -
39 20m No 1
Cable Portion & Local Transportation
40 1 x 630sq.mm XLPE (33kV) Al cable km 1
41 1 x 500sq.mm XLPE (33kV) Cu cable for take-off at both ends of the line km 0
42 Cable laying accessories such as cover tiles,warning tape, etc. Lot 1
43 Supply of concrete for Road crossing (Provisional) Cu.m 0
44 Supply of 6"class C 6m High Pressure PVC Pipe (Provisional) m
45 Outdoor Termination Kit for 1 x 630sq.mm XLPE (33kV) Al cable ea 30
46 Indoor Termination Kit for 1 x 630sq.mm XLPE (33kV) Al cable ea 30
47 Straight through joint for 1 x 630sq.mm XLPE (33kV) Al cable ea 12
48 Outdoor Termination Kit for 1 x 500sq.mm XLPE (33kV) Cu cable ea 0
49 Indoor Termination Kit for 1 x 500sq.mm XLPE (33kV) Cu cable ea 0
50 Straight through joint for 1 x 500sq.mm XLPE (33kV) Cu cable ea 0
51 15.0cm x 609.6cm Ordinary PVC Pipe - CABLE RISERS ea 30
52 Provision for support for cable risers - 12 cables on a single DE Tower ea 0
53 Project Support Lot 1
Prelimiaries, Mobilisation:- Provision for Site Establishment, Site Office, Storage
54 Facilities, Hiring of Tools and Equipment etc for a tower line construction Lot 1
55 Local Transportation of Materials from Tema Port to Project Site Lot 1