SS-20 AHU-01A/B:

Need to confirm the root cause for rubber bushes damage in spring isolators.
As all the parts of spring isolators are fixed, Petra to confirmed that how load/vibration is going to transfer to spring,Its look like that
enough vibration is not transferred to spring and due to that reason rubber bushes of all AHUs are damaged so early

AHU Cooling coils distribution lines were found to be out of drain pan. During operation sweating
drops / condensate water will come in AHU blower section and water will be carried to AHU base.
Need to confirm. SS-AHU-01A-01B
SS-20 AHU 01 A and 01 B Drain pan was found to be rusted. Need to verify the root cause from
rust stain only,
Petra.

Need to clean the pain with chemical

Improper coating on internal surface of copper coils in AHUs

SS-020-AHU-01A-01B