1354 Vapour Pressure Analyser 2014 OIM Iss. 6 (With Drawings)

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 50

Vapour Pressure

Analyser
ATEX Vapour Pressure Analyser

OPERATING AND MAINTENANCE


MANUAL
Analytical Technology & Control Limited.
Broadway, Market Lavington
Devizes, Wiltshire
SN10 5RQ
United Kingdom

Tel. No.: +44 (0)1380 818411

Fax No.: +44 (0)1380 812733

E-Mail: info@atacgroup.com

Website: http://www.atacgroup.com

Please note that this manual covers both of ATAC’s ATEX certified 1354 Analysers
(IIB & IIB+H2)

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 2


Issue 6, 18/02/2015
CONTENTS
CONTENTS .......................................................................................................................... 3
1 LIST OF FIGURES ................................................................................................. 5
2 LIST OF TABLES .................................................................................................. 6
3 SAFETY PRECAUTIONS ...................................................................................... 7
3.1 SAFETY WARNING .............................................................................................................................. 7
3.1.1 SYMBOLS........................................................................................................................................... 7

4 INTRODUCTION .................................................................................................... 8
4.1 FUNCTION ............................................................................................................................................ 8
4.2 SAFETY ................................................................................................................................................ 8
4.3 OPTIONS .............................................................................................................................................. 9
4.3.1 VOLTAGE ........................................................................................................................................... 9
4.3.2 SAMPLE PRESSURE ......................................................................................................................... 9
4.3.3 PRESSURE TRANSMITTER .............................................................................................................. 9
4.3.4 RANGE ............................................................................................................................................... 9

5 PRINCIPLE OF OPERATION .............................................................................. 10


5.1 SUMMARY OF DATA ......................................................................................................................... 11
5.1.1 RANGE ............................................................................................................................................. 11
5.1.2 SAMPLE ........................................................................................................................................... 11
5.1.3 INLET PRESSURE ........................................................................................................................... 11
5.1.4 DISCHARGE PRESSURE ................................................................................................................ 11
5.1.5 OIL BATH ......................................................................................................................................... 11
5.1.6 TEMPERATURE ............................................................................................................................... 11
5.1.7 ELECTRICAL .................................................................................................................................... 12
5.1.8 AIR.................................................................................................................................................... 12
5.1.9 COOLING WATER............................................................................................................................ 12
5.1.10 TRANSMITTER................................................................................................................................. 12
5.1.11 MATERIAL IN CONTACT.................................................................................................................. 12
5.1.12 DIMENSIONS ................................................................................................................................... 12
5.1.13 WEIGHT ........................................................................................................................................... 12
5.1.14 ENVIRONMENTAL CONDITIONS .................................................................................................... 13

6 TECHNICAL DESCRIPTION................................................................................ 14
6.1 SAMPLE FLOW PATH ........................................................................................................................ 14
6.2 GENERAL MECHANICAL DESCRIPTION ......................................................................................... 14
6.2.1 MOTOR ............................................................................................................................................ 14
6.2.2 HEATER ........................................................................................................................................... 14
6.2.3 COOLING COIL ................................................................................................................................ 15
6.2.4 HEAT EXCHANGER ......................................................................................................................... 16
6.2.5 STIRRERS ........................................................................................................................................ 16
6.2.6 TRANSMITTER................................................................................................................................. 16
6.2.7 PRESSURE GAUGES AND GAUGE SAVER ................................................................................... 16
6.2.8 NOZZLE ASSEMBLY AND SENSING DEVICE................................................................................. 17
6.3 ELECTRICAL POWER........................................................................................................................ 18
6.4 TEMPERATURE CONTROLLER ........................................................................................................ 18
6.4.1 INTRODUCTION............................................................................................................................... 18
6.4.2 MECHANICAL DESCRIPTION.......................................................................................................... 18
6.4.3 ON/OFF OPERATION....................................................................................................................... 19
6.4.4 PROPORTIONAL OPERATION (TABLE 1)....................................................................................... 19
6.4.5 RESET-INTEGRAL (TABLE 2) .......................................................................................................... 19
6.5 PRESSURE ........................................................................................................................................ 19

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 3


Issue 6, 18/02/2015
7 INSTALLATION AND COMMISSIONING ............................................................ 21
7.1 PART 1 - INSTALLATION ................................................................................................................... 21
7.2 MOUNTING THE INSTRUMENT ........................................................................................................ 22
7.2.1 LOCATION........................................................................................................................................ 22
7.2.2 HOUSING ......................................................................................................................................... 22
7.3 SERVICE CONNECTIONS ................................................................................................................. 22
7.3.1 MAINS POWER SUPPLY ................................................................................................................. 22
7.3.2 SIGNAL INTERCONNECTIONS ....................................................................................................... 22
7.3.3 COOLING WATER............................................................................................................................ 23
7.3.4 SAMPLE ........................................................................................................................................... 23
7.3.5 RESPONSE TIME............................................................................................................................. 23
7.4 PRESSURE SETTINGS...................................................................................................................... 23

8 PART 2 - COMMISSIONING ................................................................................ 24


8.1 PREPARATION .................................................................................................................................. 24
8.2 SETTING UP ....................................................................................................................................... 25
8.2.1 PRELIMINARY OPERATIONS .......................................................................................................... 25
8.2.2 ADJUSTMENT OF BATH OPERATING TEMPERATURE................................................................. 26
8.3 CALIBRATON CHECK ........................................................................................................................ 26

9 NORMAL OPERATION ........................................................................................ 28


9.1 START-UP PROCEDURE .................................................................................................................. 28
9.2 SHUT-DOWN PROCEDURE .............................................................................................................. 28

10 ROUTINE MAINTENANCE .................................................................................. 30


10.1 DAILY CHECKS .................................................................................................................................. 30
10.2 MONTHLY CHECKS ........................................................................................................................... 30
10.2.1 NOZZLE............................................................................................................................................ 30
10.2.2 FILTER SCREENS ........................................................................................................................... 30

11 FAULT FINDING AND REPAIR ........................................................................... 31


11.1 SAFETY .............................................................................................................................................. 31
11.2 FAULT LOCATION ............................................................................................................................. 31
11.3 REMOVAL AND FITTING OF RESISTANCE THERMOMETER ........................................................ 33
11.4 REMOVAL OF HEATER, COOLING COIL & HEAT EXCHANGER UNIT........................................... 33
11.5 RENEWAL OF THERMAL FUSE ........................................................................................................ 33

12 SPARE PARTS AND REPAIRS ........................................................................... 34


12.1 REPAIRS ............................................................................................................................................ 35
12.2 SPARE PARTS TABLES .................................................................................................................... 36
12.2.1 OVERALL ASSEMBLY ..................................................................................................................... 36
12.2.2 TEMPERATURE CONTROL UNIT .................................................................................................... 37
12.2.3 NOZZLE HOUSING .......................................................................................................................... 38
12.2.4 COIL ASSEMBLY ............................................................................................................................. 38

13 DOCUMENTS AND DRAWINGS FOR THIS MANUAL ....................................... 39

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 4


Issue 6, 18/02/2015
1 LIST OF FIGURES
FIGURE 1 – COIL ASSEMBLY ........................................................................................................... 15

FIGURE 2 – NOZZLE ASSEMBLY ..................................................................................................... 17

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 5


Issue 6, 18/02/2015
2 LIST OF TABLES
TABLE 1 – PROPORTIONAL BAND SELECTED BY GAIN SWITCH ................................................ 20

TABLE 2 – RESET TIME SELECTED BY RESET SWITCH ............................................................... 20

TABLE 3 – FAULT FINDING ............................................................................................................... 32

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 6


Issue 6, 18/02/2015
3 SAFETY PRECAUTIONS

3.1 SAFETY WARNING


ELECTRICAL APPARATUS FOR USE IN POTENTIALLY EXPLOSIVE ATMOSPHERES.
ANY MODIFICATION TO THIS PRODUCT CAN JEOPARDISE THE SAFETY CLASSIFICATION
OF THIS PRODUCT.
IF THE EQUIPMENT IS NOT USED IN THE MANNER DESCRIBED IN THIS MANUAL THE
PROTECTION PROVIDED BY THE EQUIPMENT MAY BE IMPAIRED.
ONLY BONAFIDE SPARE PARTS SUPPLIED BY ANALYTICAL TECHNOLOGY & CONTROL
LIMITED (ATAC) ARE ALLOWED TO BE FITTED. MODIFICATIONS OR SUBSTITUTE PARTS
CAN JEOPARDISE THE SAFETY CLASSIFICATION OF THIS PRODUCT.
WHERE THIS INSTRUMENT IS INSTALLED IN AN AREA CLASSIFIED ZONE 1 OR 2, POWER
MUST NOT BE APPLIED WHEN ANY COVER OR DOOR HAS BEEN REMOVED OR OPENED
UNLESS SPECIFIC PERMISSION HAS BEEN OBTAINED.
THE INSTRUMENT MUST BE INSTALLED USING ELECTRICAL GLANDS OR CONDUIT
APPROPRIATE TO THE HAZARDOUS AREA CLASSIFICATION
THIS EQUIPMENT IS CERTIFIED FOR USE IN RESPECT OF HAZARDOUS LOCATIONS UP
TO AND INCLUDING GROUP IIC. UNAUTHORISED MODIFICATION OR ACCIDENTAL
DAMAGE MAY INVALIDATE THE CERTIFICATION.
THIS INSTRUMENT INCLUDES APPARATUS USING VOLTAGES THAT CAN ENDANGER
LIFE. IT IS THE DUTY OF ALL PERSONS WHO MAY BE CONCERNED WITH OPERATION OR
WORK UPON THE APPARATUS TO COMPLY WITH CURRENT ELECTRICITY SAFETY
REGULATIONS AND TO BE THOROUGHLY CONVERSANT WITH ALL REGULATIONS
GOVERNING THE WORK THEY UNDERTAKE.
DISCONNECTION OF THE PROTECTIVE EARTH INSIDE OR OUTSIDE THE APPARATUS
WILL MAKE IT DANGEROUS. INTENTIONAL DISCONNECTION IS PROHIBITED.
DO NOT USE FUSES OF A TYPE OR RATING DIFFERING FROM THOSE SPECIFIED.
SOME COMPONENTS ON THE PRINTED CIRCUIT BOARDS MAY BE SUBJECT TO DAMAGE
FROM STATIC ELECTRICITY. ANTI-STATIC PRECAUTIONS SHOULD BE TAKEN WHEN
HANDLING THE COMPONENTS OR BOARDS
CERTAIN RELAYS AND SIGNAL LINES WITHIN THE INSTRUMENT MAY BE SUPPLIED WITH
DANGEROUS VOLTAGES CONTROLLED OR SUPPLIED FROM OUTSIDE THE INSTRUMENT
AND NOT CUT OFF BY THE INSTRUMENT'S ISOLATOR.
ALL INCOMING LIVE CONNECTIONS INTO THE EX P ENCLOSURE (THE ELECTRICAL
ENCLOSURE) MUST BE PROTECTED BY A SUITABLY RATED EX IB SAFETY DEVICE SO
THE RISK OF IGNITION ON LOSS OF PRESSURISATION IS REMOVED.
IF TESTING REQUIRES WORK ON LIVE EQUIPMENT, IT MUST BE UNDERTAKEN BY
QUALIFIED STAFF WHO ARE AWARE OF THE HAZARDS INVOLVED.

3.1.1 SYMBOLS
The following symbols appear in the manual, their meanings are listed below;

Caution, risk of electric shock.

Caution, risk of danger.

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 7


Issue 6, 18/02/2015
4 INTRODUCTION

4.1 FUNCTION
The Model 1354 Vapour Pressure Analyser is a process instrument that continuously
measures the vapour pressure of liquid streams. The vapour pressure information may be
indicated directly or transmitted for automatic blending and injection control of various
hydrocarbon process streams. The Monitor is intended for use with liquids having
viscosities up to a maximum of 10 centipoise (cP).

The Vapour Pressure Analyser provides consistent and accurate readings by measuring
the vapour pressure of the sample under standardised conditions. The incoming sample
stream is heated or cooled and regulated accurately to a temperature of 100oF
(37.8oC). If reinsertion of the sample into the process stream is desired, a suitable
pump may be required. The nominal sample flow rate in the instrument is about 55 to
230 litres per hour depending upon the back pressure and the type of sample.

4.2 SAFETY
The Vapour Pressure Analyser is component certified to meet ATEX requirements for
installation in potentially hazardous environments. The following certificates apply:

Vapour Pressure Analyser Overall Certificate Of Conformity


ITS09ATEX16356X Exd IIB T6
ITS09ATEX16357X Exd IIB+H2 T6

Vapour Pressure Analyser Temperature Controller


08ATEX2411X EN 60079-0 & EN 60079-1 Exd IIB T6
06ATEX2129X EN 60079-0 & EN 60079-1 Exd IIB+H2 T6
Motor
L.C.I.E. 00ATEX 6036 EN 50014 & EN 50018 Exd IIB/IIC T4/T5/T6
OR SUITABLY CERTIFIED ATEX EQUIPMENT FOR HAZARDOUS AREAS
Heater
ITS02ATEX1021X EN 50014 & EN50018 Exd e IIC T3

Resistance Thermometer
07ATEX2226 EN 60079-0 & EN 60079-1 Exd IIC T3/T4/T5/T6

NOTE: The Absolute Pressure Transmitter, which is fitted to the customer’s


requirements, must have appropriate ATEX certification.

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 8


Issue 6, 18/02/2015
4.3 OPTIONS

4.3.1 VOLTAGE
The Monitor is available to suit 100-125V or 200-250V supplies. Change of voltage range
involves replacement of a solid-state relay, fuses, neon lamps, the motor overload cut-out
and the heater. Changes must be made to the Temperature Controller mains transformer
tappings.

4.3.2 SAMPLE PRESSURE

The minimum sample pressure is 7 bar (100 lbf/in2). Sample preparation systems can be
offered for lower inlet pressures and for sample return.

4.3.3 PRESSURE TRANSMITTER


Most makes and types of absolute pressure transmitter can be accommodated. Note that
the overall certification provides for a limited number of models.

4.3.4 RANGE
The standard model reads vapour pressures up to 1.6 bars absolute (22 psia). Units for
higher vapour pressures are available upon request.

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 9


Issue 6, 18/02/2015
5 PRINCIPLE OF OPERATION

The measuring principle of the instrument can be compared to that employed in the
laboratory eductor air pump. The sample is brought to a standard temperature of 100 oF
(37.8oC) and forced through a jet orifice in which the increase in fluid velocity creates a
pressure drop sufficient to induce incipient vaporisation of the sample. The minimum
absolute pressure reached in a jet orifice occurs when the static pressure of the liquid at the
nozzle exit reaches the effective vapour pressure of the sample.

The Analyser reads Kinetic vapour pressure which is defined as the pressure exerted when
a solid or liquid is at equilibrium with its own vapour. The industry standard test is the ASTM
method D-323-58 which determines the Reid vapour pressure. This is not true vapour
pressure since it includes a factor depending upon the expansion of a volume of air. Good
correlation between the Monitor reading and the laboratory reading is achieved.

The relationship between the fluid velocity and pressure is given by the flow energy
equation:
(V1)2 + P1 = (V2)2 + P2 + F2

V1 and V2 are the fluid velocities at the inlet and outlet respectively of the jet orifices.

P1 and P2 are the inlet and outlet pressure.

F2 is the fluid friction loss.

It is evident that if the outlet velocity V2 can be made sufficiently large while V1 and P1 are
held constant then, ignoring friction, the pressure of the fluid out of the nozzle can be
reduced to the effective vapour pressure of the sample. Since the fluid temperature is held
constant and the pressure at the nozzle inlet maintained at a level that causes vaporisation
of the sample, the pressure in the measuring chamber is an accurate measurement of the
effective vapour pressure.

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 10


Issue 6, 18/02/2015
5.1 SUMMARY OF DATA

5.1.1 RANGE

Standard 0 to 1.4 bar (0 to 20 lbf/in2) absolute.

Maximum 0 to 10 bar (0 to 150 lbf/in2) absolute. For higher ranges refer to


factory.

Repeatability +0.007 BAR (0.1 lbf/in2)


Response time better than 50 sec at normal flow rates.

5.1.2 SAMPLE

Temperature Within the range 25oC to 50oC but fluctuations must not exceed 5oC.

5.1.3 INLET PRESSURE

Maximum 60 bar (900 lbf/in2)


Operation 2.5 times the discharge pressure + 7 bar

Minimum 7 bar (100 lbf/in2)

5.1.4 DISCHARGE PRESSURE


Discharge Pressure should be sufficient to prevent gassing
Flow Rate 55 to 230 1/h (12 to 50 imp. gal/h) depending upon back pressure.
Viscosity 10cP MAX

5.1.5 OIL BATH


Capacity 11 litres (2.5 gal imp)
Oil Oxidation resistant, good heat-transfer

Flash point Closed cup flash point 220oC MIN (Certification requirement)

Vapour pressure 0.2mm Hg MAX at 180oC (Certification requirement)

5.1.6 TEMPERATURE

Ambient 0oC to 55oC nominal

Sample 100oF (37.8oC) at measurement point

Oil bath 100oF (37.8oC)

Thermal fuse 130oC nominal

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 11


Issue 6, 18/02/2015
5.1.7 ELECTRICAL
Voltage 100V MIN/125V MAX or 200V MIN/250V MAX. The ABSOLUTE
MAXIMUM values are 10% more than the stated values.
Frequency 50Hz + 5% or 60HZ + 5%
Power 200W + Heater, typically 1.5kW
Connections M25 x 1.5

5.1.8 AIR

1.4 bar (20 lbf/in2) required for pneumatic transmitters only

5.1.9 COOLING WATER


Flow rate 135l/h (30 imp. gal/h) MAX, dependent upon heat input

Temperature 30oC MAX


Pressure 7 bar g. MAX

5.1.10 TRANSMITTER
Pneumatic or electric as specified.

5.1.11 MATERIAL IN CONTACT


Sample path is stainless steel, PTFE and Viton.

5.1.12 DIMENSIONS
Overall length 900mm
Overall width 500mm
Overall height 1420mm excluding transmitter

5.1.13 WEIGHT
180kg approximately

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 12


Issue 6, 18/02/2015
5.1.14 ENVIRONMENTAL CONDITIONS

The Vapour Pressure Analyser is free-standing and provide that it is sheltered from direct
sun, rain and strong winds. It will operate satisfactory indoors/outdoors
Ambient Temperature range conditions 0 Deg C to +55 Deg C
Altitude 2000m
Relative humidity not to exceeding 80%
Main supply fluctuations not exceeding +/- 10%
Over voltage category II IEC 60364-4-443
Pollution degree 2

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 13


Issue 6, 18/02/2015
6 TECHNICAL DESCRIPTION

6.1 SAMPLE FLOW PATH


Sample enters the Monitor at the sample inlet connector. To obtain reliable readings the
temperature of the incoming sample must be between 25°C - 50°C. It is preferable that the
sample temperature is maintained on one side or the other of the set-point temperature.
The flow then passes a 100 mesh Y-type filter which removes most contaminants. A
bypass line from the filter to the sample-out line permits cleaning of the filter. Flow in the
bypass line is prevented by closing the flush valve during normal operation.

Sample then flows to a pressure reducing regulator that produces a constant downstream
pressure; from there it passes through a heat exchanger comprising 4 coils of stainless
steel pipe in series-parallel immersed in an oil bath held at a constant temperature. A
resistance thermometer in the bath provides a signal enabling the temperature controller to
regulate the oil bath temperature. The sample temperature is controlled at 37.8 oC (100oF)
+ 0.01oC and can be checked by a standard mercury-in-glass thermometer fitted into a well
in the oil bath. The set point temperature is adjusted by means of dials mounted on the
front of the temperature controller enclosure.

The sample is applied at constant pressure to the measurement nozzle, the pressure being
controlled by a pressure regulator and displayed using a pressure gauge. It flows into a jet
orifice in the sensing device at the outlet of which vaporisation of the sample occurs. The
vapour pressure is indicated by a pressure gauge and then converted for remote monitoring
and control purposes by an absolute pressure transducer. Any possible back surge of
pressure resulting from downstream variations is prevented by a back pressure regulator.

6.2 GENERAL MECHANICAL DESCRIPTION


The major components, apart from the Temperature Controller, are mounted on a main
plate. An oil bath is screwed to the underside of the main plate and is mounted on two
angles welded to sleeves which ride on vertical pipe-stand legs. Two eye-bolt stop pins are
used to hold the sleeves in position when lowering or raising the oil bath, which is done
manually. Both the oil bath and the main plate are thermally insulated and enclosed in
heavy gauge steel. The Temperature Controller Box is mounted on housing brackets
bolted to the front legs of the stand.

6.2.1 MOTOR
A flameproof induction motor is flange mounted on the oil bath cover. The motor shaft
extends through the cover to drive the stirrer paddles. Voltages applied to the motor must
not exceed the rated value + 10%.

6.2.2 HEATER
In order to minimise the bath time-constant, a single, thin wall, stainless steel, low wattage
density, oil bath immersion heater is provided. The heater is connected to a non-resettable
thermal fuse. The heater is normally rated at 1.5kW at nominal mains voltage.

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 14


Issue 6, 18/02/2015
6.2.3 COOLING COIL

A 1/4in, stainless steel cooling coil is provided in the oil bath for constant circulation of
cooling water when a measurement temperature less than that of the process stream is
desired or high ambient temperature is expected.

Figure 1 – Coil Assembly

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 15


Issue 6, 18/02/2015
6.2.4 HEAT EXCHANGER
A 1/4in. EXT, stainless steel heat-exchanger is immersed in the oil bath. The sample flows
through 4 heat exchanger coils using 1/4in tubing connected in series-parallel. This
increases the heat transfer surface while at the same time reducing the pressure dropped
across the exchanger. A spiralled strip of metal is inserted inside along the length of all the
heat exchanger tubes to ensure that the sample is well mixed. This improves the heat
transfer by preventing streaming of the hot sample down the centre of the tubes.

6.2.5 STIRRERS
Two Hallikainen Size 1 stainless steel jet-stir impellers are used to agitate the bath oil,
minimising the overall bath time-constant and temperature gradients. The hollow stirrer
blades cause the bath oil to flow radically out through the blades at a high velocity as well
as in directions normal and tangential to the blade surfaces. The two stirrers have different
flow patterns defined by the angle of set of the impeller blades; this further improves the
efficiency of the mixing of the bath oil.

6.2.6 TRANSMITTER
The vapour pressure of the sample is transmitted, either electronically or pneumatically. It is
essential that the transmitter measure’s absolute pressure to avoid errors caused by
variations in atmospheric pressure.

6.2.7 PRESSURE GAUGES AND GAUGE SAVER


Gauges are provided that indicate inlet, outlet and nozzle pressures. The Gauge saver
protects the nozzle pressure gauge and the transmitter against damaging overpressures.

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 16


Issue 6, 18/02/2015
6.2.8 NOZZLE ASSEMBLY AND SENSING DEVICE
The sensing device on the nozzle assembly is adjusted, with a standard sample, to allow
final on site calibration to within the limits of ASTM D-323-58

Figure 2 – Nozzle Assembly

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 17


Issue 6, 18/02/2015
6.3 ELECTRICAL POWER
The electrical system provides power for the heater, the stirrer motor and the Temperature
Controller. The latter is protected by a quick-blow fuse located on its chassis; take care
that fluctuations of the incoming power supply do not interfere with its performance. The
Temperature Controller can accept variations of +10% in its power supply voltage provided
that the period of fluctuation is greater than the reset time to which the Controller has been
adjusted.
Since the maximum reset time is 100sec, this is the minimum permissible time in which the
incoming power may vary by more than 3%. If the period of variation is less, the operation
of the Temperature Controller may be upset. The resistance of the power supply lines must
be low enough to prevent step voltage changes, such as might be caused by switching the
heater load on and off, from exceeding 3%. The heater is protected by a non-resettable
thermal fuse that breaks the electrical circuit at a temperature of 130oC. If the fuse
requires renewal, see Section 7.5.

6.4 TEMPERATURE CONTROLLER

6.4.1 INTRODUCTION
A 100 ohm platinum sensing element used in conjunction with a 100 ohm fixed low
temperature-coefficient resistor is used as standard input to the Controller.

The Controller can be operated in any one of three modes as follows:


(1) On-off
(2) Time proportional
(3) Time proportional with reset (integral)
Modes (1) and (2) are used for test purposes only.

6.4.2 MECHANICAL DESCRIPTION

The Temperature Controller is housed in the electronic box. It comprises two printed circuit
boards, the Pre-Amplifier and the Main Amplifier. It has two controls and two indicator
lamps, designated as follows:
(1) Coarse
A 10-turn potentiometer is used to adjust the control temperature. The potentiometer
is adjusted by means of a two scale vernier dial which is calibrated in whole turns
(10) on the inner scale and in a percent of a turn on the outer scale. Readings on
these scales are expressed in terms of the smallest division on the scale (1% of a
turn); thus for two turns and 83% of a turn the potentiometer setting is quoted as
283. A lock is provided on the dial to prevent accidental movement.

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 18


Issue 6, 18/02/2015
(2) Fine
A 10-turn potentiometer is used to obtain fine control of set point in a similar
manner to the coarse control.
(3) Heater ON
A red neon lamp, mounted on the front panel lights when the heater is energised.
(4) Mains ON
Other controls are three internal PCB mounted switches which provide the
following:
(a) S1 - Gain
(b) S2 - Reset time
(c) S3 - On-off/proportional (OPTION)

6.4.3 ON/OFF OPERATION


In this mode, the heater is turned on when the oil bath temperature falls below set point and
is turned off when set point is reached. S3 is used to select this mode of operation of the
temperature control circuit.

6.4.4 PROPORTIONAL OPERATION (TABLE 1)


The heat input to the oil bath is controlled so that it is proportional to the difference between
the set point and the actual temperature. Using this method there is less likelihood of
over-shoot caused by residual heat contained in the heater element after the heater is
turned off.

The heater remains fully on or fully off until the temperature approaches the set-point. The
difference between the temperature at which the heater is turned off and the set-point
temperature is determined by the setting of S1, GAIN. The temperature bands
corresponding to the GAIN switch settings are listed in Table 1. Over the proportional band
the heat input the heater is on for one second, then off for one second.

6.4.5 RESET-INTEGRAL (TABLE 2)


In temperature control systems using proportional control only, the controlled temperature
is always a little below the set-point temperature. This error or droop can be affected by
external influences. The Reset facility introduces a correcting signal proportional to the
magnitude and duration of the temperature difference. The droop can thus be reduced to
zero.

6.5 PRESSURE
For most applications the calculated inlet pressure will not exceed the safe working
pressure of 40 bars. LPG represents a special case with an inlet pressure approaching the
safe maximum pressure of 40 bars.

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 19


Issue 6, 18/02/2015
GAIN SETTING PROPORTIONAL BAND TEMPERATURE DIFFERENTIAL deg. C.

T 1 0.036
a
b 2 0.056
l
e 3 0.08
1 4 0.12
– 5 0.18
P 6 0.25
r
o 7 0.35
p
o
r
8 0.45
t
i
9 0.6
o
n 0 0.73
a
l Band Selected by Gain Switch

RESET SWITCH
RESET TIME (seconds)
SETTING

1 NO RESET
2 100
3 66
4 45
5 32
6 22
7 15
8 10
9 6.6
0 4.5

Table 2 – Reset Time Selected by Reset Switch

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 20


Issue 6, 18/02/2015
7 INSTALLATION AND COMMISSIONING

7.1 PART 1 - INSTALLATION

ANALYTICAL TECHNOLOGY & CONTROL can advise users on the installation and system
design and undertake to supply and commission the necessary equipment.
For users wishing to design their own installation, the following information is intended as a
guide and, as such, cannot include detail of every possible configuration.
WARNING

ELECTRICAL APPARATUS FOR USE IN POTENTIALLY EXPLOSIVE ATMOSPHERES

ANY MODIFICATION TO THIS PRODUCT CAN JEOPARDISE THE SAFETY


CLASSIFICATION OF THIS PRODUCT

Where This Instrument Is Installed In An Area Classified Zone 1 Or 2, Power Must Not Be
Applied When Any Cover Or Door Has Been Removed Or Opened Unless Specific
Permission Has Been Obtained.
THE INSTRUMENT MUST BE INSTALLED USING ELECTRICAL GLANDS OR CONDUIT APPROPRIATE
TO THE HAZARDOUS AREA CLASSIFICATION
THIS EQUIPMENT IS CERTIFIED FOR USE IN RESPECT OF HAZARDOUS LOCATIONS UP TO AND
INCLUDING GROUP IIB OR IIB+H2. UNAUTHORISED MODIFICATION OR ACCIDENTAL DAMAGE MAY
INVALIDATE THE CERTIFICATION.
THIS INSTRUMENT INCLUDES APPARATUS USING VOLTAGES THAT CAN ENDANGER LIFE. IT IS
THE DUTY OF ALL PERSONS W HO MAY BE CONCERNED W ITH OPERATION OR W ORK UPON THE
APPARATUS TO COMPLY W ITH CURRENT ELECTRICITY SAFETY REGULATIONS AND TO BE
THOROUGHLY CONVERSANT W ITH ALL REGULATIONS GOVERNING THE W ORK THEY UNDERTAKE.
DISCONNECTION OF THE PROTECTIVE EARTH INSIDE OR OUTSIDE THE APPARATUS W ILL MAKE IT
DANGEROUS. INTENTIONAL DISCONNECTION IS PROHIBITED.
DO NOT USE FUSES OF A TYPE OR RATING DIFFERING FROM THOSE SPECIFIED.

Installed Equipment Must Be Certified To the ATEX Directive (94/9/EC)


And Installed In Accordance With EN60079-14 & EN13463-1

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 21


Issue 6, 18/02/2015
7.2 MOUNTING THE INSTRUMENT

7.2.1 LOCATION
Locate the Monitor as near as possible to the sample point.
For adequate access, prepare a firm level site 3m x 2m. Access for routine operations is
required only on the two shortest sides. Access to the other long side is required when
lowering the bath.
Four fixing holes 5/8in diameter are located in the support stand on which the Monitor is
mounted.
Run all services from the end furthest from the Temperature Controller.

7.2.2 HOUSING
The Monitor is designed to operate satisfactorily when exposed to normal ambient
temperature variations, draughts, etc. Protection should be provided from rain or snow and
exposure to extreme wind and direct heat from the sun. The Monitor may be housed in an
existing building such as a pump house, or a specially built shelter. In either case it is
essential to take adequate precautions regarding safety classification.
The location should include ample lighting for inspection and servicing.

7.3 SERVICE CONNECTIONS

7.3.1 MAINS POWER SUPPLY


Provide a flameproof isolating switch near to the equipment to enable the power to be
turned off for servicing.
Wire from the isolating switch to terminals L (LIVE), N (NEUTRAL) and E (EARTH) of TB2
in the temperature controller via approved 20mm glands.

7.3.2 SIGNAL INTERCONNECTIONS


Connect a clean and dry instrument air supply to the transmitter (or provide appropriate
electrical connections if an electrical transmitter is used). For details of the transmitter see
the separate manufacturer's handbook.

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 22


Issue 6, 18/02/2015
7.3.3 COOLING WATER

The sample temperature should fall within the range of 25 - 50oC with fluctuations not
exceeding 5oC. The function of cooling water is to reduce the oil bath temperature so that
the heater is required to maintain the temperature and thus to exercise control.

Water cooling is only required when the sample inlet temperature is about 30oC. Connect
the cooling water lines to the 1/4in ANPT female cooling water inlet and outlet elbows. To
prevent excessive temperature fluctuations in the oil bath install a water flow control valve
in the water line; to maintain a reasonably constant flow rate (up to a maximum of 50 l/h), it
is preferable to include a flowmeter.

7.3.4 SAMPLE
(a) Sample In
Connect the Sample In lines to the 1/4in ANPT male "IN" port. The maximum
permissible pressure on this line is 60 bar (900 lbf/in2). Allowance must be made
for the pressure drop in the incoming sample line at flow rates of up to 230 l/h.
(b) Sample Out
Connect the Sample Out lines to the 1/4in ANPT male "OUT" port. The sample out
is normally returned to the process line. If the outlet pressure is less than the
pressure of the line to which the stream is to be returned, a suitable pump must be
provided. (See 4.3)

7.3.5 RESPONSE TIME


The Analyser has a response time of about 40 seconds to a step change in sample vapour
pressure. This is mainly determined by the volume of sample in the heat exchanger and
the sample flow rate. If the Analyser is to be used to control injection of volatiles into a
hydrocarbon stream. The piping between the sampling point and the instrument should be
such that a change in vapour pressure of the blended stream is detected, and corrective
measures initiated rapidly after a change at the injection point. The sampling point can be
a minimum distance of 12 pipeline diameters downstream from the volatiles injection point
but only if the manner of injection ensures maximum mixing.

7.4 PRESSURE SETTINGS


Pressure settings are determined as follows:
(a) Measure or calculate the maximum pressure at the sample outlet connection on the
basis of the return line pressure, the pressure drop in the outlet line to the return line and
anticipated return line pressure fluctuations.
(b) To obtain the correct pressure setting for the back pressure regulator add one bar to the
value obtained in (a) above.
(c) Calculate the minimum inlet pressure by multiplying the value obtained in (a) above by
2.5 and increasing it by 7 bar.
NOTE: For most applications the calculated inlet pressure will not exceed the safe working
pressure of 40 bars. LPG represents a special case with an inlet pressure approaching the
safe maximum operating pressure of 40 bars. A properly designed sample system allows
considerable flexibility in respect of operating conditions.
ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 23
Issue 6, 18/02/2015
8 PART 2 - COMMISSIONING

WARNING

THIS INSTRUMENT INCLUDES APPARATUS USING VOLTAGES THAT CAN


ENDANGER LIFE. IF IT IS THE DUTY OF ALL PERSONS WHO MAY BE CONCERNED
WITH OPERATION OR WORK UPON THE APPARATUS TO COMPLY WITH CURRENT
ELECTRICITY SAFETY REGULATIONS AND TO BE THOROUGHLY CONVERSANT
WITH ALL REGULATIONS GOVERNING THE WORK THEY UNDERTAKE.
SWITCH OFF THE POWER BEFORE RAISING OR LOWERING THE OIL BATH. WEAR
GLOVES.
THE FLAMEPROOF CONTROL UNIT MUST BE OPENED FOR CIRCUIT CHECKING,
WHICH CAN ONLY BE PERFORMED WITH THE POWER SWITCHED ON. WHERE THE
INSTRUMENT IS INSTALLED IN AN AREA CLASSIFIED ZONE 1 OR ZONE 2 SPECIAL
PERMISSION MUST BE OBTAINED FOR THE TESTS.
DISCONNECTION OF THE PROTECTIVE EARTH INSIDE OR OUTSIDE THE
APPARATUS WILL MAKE IT DANGEROUS. INTENTIONAL DISCONNECTION IS
PROHIBITED.
DO NOT USE FUSES OF A TYPE OR RATING DIFFERING FROM THOSE SPECIFIED.

8.1 PREPARATION

(1) Insert the thermometer provided into the well directly above the sample outlet T. A
hook in the thermometer well cap is used to rotate the thermometer for ease of
reading and removal.
(2) Fill the oil bath housing up to the middle of the oil-fill elbow with oil having the following
properties:
(a) Good heat transference.
(b) Resistance to oxidation

(c) A closed-cup flash point of not less than 220oC (Mandatory)

(d) A vapour pressure at 180oC not more than 0.2mm Hg. (Mandatory)
NOTE: Filling is easier with the oil-bath dropped; if this is done, fill to 10mm below the filler
elbow. When the oil-bath is raised, sufficient oil will be displaced by the pipe-work to raise
the oil to the correct level.

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 24


Issue 6, 18/02/2015
(3) Fill the thermometer well with the same oil.
(4) Set the COARSE multi turn temperature-setting dial for the required operating
temperature. Set the FINE dial to mid-position (500).
(5) Set the following valves and controls:
(a) Close the external sample inlet valve.
(b) Close the filter flush valve
(c) Close the inlet pressure reducing regulator (fully counter-clockwise).
(d) Open the outlet pressure reducing regulator (minimum pressure).
(e) Switch the power OFF
(f) Switch the external air supply (if any) OFF

8.2 SETTING UP

8.2.1 PRELIMINARY OPERATIONS


Proceed as follows:
(1) Close the mains isolator. Switch on MOTOR and POWER.
(2) Open the cooling water valve.

(3) Wait until the oil bath temperature is within 5oC of the normal operating temperature.
(4) Set both pressure regulators to minimum pressure. (See 4.4, step 5)
(5) Open the outlet and then the inlet valve.
(6) Slowly increase the nozzle pressure by means of the inlet pressure regulator until the
nozzle pressure gauge reads about 1.7 bar gauge.
(7) Adjust the output regulator to give a reading on the output gauge of about 1 bar gauge
above the expected vapour pressure of the sample.
(8) By means of the inlet pressure regulator, raise the nozzle pressure gradually. The
vapour pressure gauge reading will rise until the sample starts to vaporise and will then
remain constant with rising nozzle pressure.
(9) Set the nozzle pressure to a value about 1 bar above the pressure at which
vaporisation commenced.
(10) The general operating conditions of the Monitor are now roughly set.

(11) Determine pressure settings as follows:


(a) Measure or calculate the maximum pressure at the sample outlet connection on
the basis of the return line pressure, the pressure drop in the outlet line to the
return line and anticipated return line pressure fluctuations.
(b) To obtain the correct pressure setting for the back pressure regulator add one bar
to the value obtained in (a).
(c) Calculate the minimum inlet pressure by multiplying the value obtained in (a) by
2.5 and increasing it by 7 bar.

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 25


Issue 6, 18/02/2015
8.2.2 ADJUSTMENT OF BATH OPERATING TEMPERATURE
The control unit is set during manufacture for optimum performance at the temperature
specified on the Data Sheet, which also lists the gain and reset dial settings. Load changes
(variation of ambient or sample fluid temperature) do not require changes in the optimum
settings. Ensure that sample is flowing before making any adjustments to the temperature.
To adjust the settings for a different operating temperature, proceed as follows.

WARNING
THE FLAMEPROOF UNIT MUST BE OPENED FOR THESE OPERATIONS SO POWER
MUST BE SWITCHED OFF AT EACH STOP, OR SPECIAL PERMISSION OBTAINED TO
WORK WITH THE ENCLOSURE OPEN AND POWER ON.

(1) Set the Gain switch (S1 on PA0333) to position 1 (maximum gain)

(2) Set the Re-set switch (S3 on PA0333) to ON. (ON/OFF control ON).

(3) Set the Coarse and Fine temperature dials so that the bath operates at the required
temperature. [see Calibration Curve Dwg #12833 for reference / Data Sheet]

(4) When the amber light starts to flash on and off, this show that the bath is at the
required temperature (check on thermometer). Measure the time in seconds for the
complete temperature on-off cycle i.e. time from amber light going off at the end of
one long ON period to the same point after the next long ON period. Repeat this
measurement several times to check.

(5) Set the Re-set switch (S3 on PA0333) to OFF (Proportional control ON) and set the
gain switch S1 to 0 (minimum gain), then increase the Gain setting to the maximum
value possible without producing hunting. Correct operation is when the amber lamp
flashes on and off steadily about once per second and a half. Hunting is when the
lamp periodically increases and decreases its percentage ON time. Hunting may also
be observed on the indicator or recorder as a regular cyclic fluctuation in the test
sample viscosity.

(6) Set the Re-set switch following Table 2 to the nearest value above the number of
seconds measured as the cycle period in step 4. This completes the adjustment. The
new dial settings should be recorded in the instrument log or Test Certificate.

8.3 CALIBRATON CHECK


The Monitor, as supplied, was calibrated using a standard reference liquid and it should not
normally require adjustment. If it is necessary to check the readings obtained, proceed as
follows:
(1) Confirm that the temperature of the oil bath is accurately set to the specified value
(normally 37.8oC + 0.01oC).
(2) Ensure that the plant is running normally and producing a sample having a steady
vapour pressure.

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 26


Issue 6, 18/02/2015
NOTE: If a sample is not available from the plant to the Monitor, the input must be derived
from a Test System incorporating a pump giving adequate pressure and flow (7 bar, 3 1/m),
and a storage container holding a sample. Ensure that there is no change in composition of
the re-cycled sample arising from evaporation of the light ends. This is particularly
relevant in hot climates and with volatile samples. A single component sample such as
Hexane would avoid light end losses.
(3) Check that the transmitter calibration is correct. (Check the reading on the pressure
gauge, if fitted, and adjust to give the same reading as the transmitter.)
(4) Record the reading on the Monitor and immediately take a sample of the oil at the
input to the Monitor. This sample should be taken in a container designed to minimise
losses through vapourisation. Carry out several laboratory tests to ensure that results
are within the limits of the ASTM D-323-58 test.
(5) If the Monitor output is the same as the laboratory test and falls within the ASTM limits,
no further action is necessary.
(6) If it is necessary to adjust the instrument, a change of the reading may be obtained by
altering the spacing between the nozzle and the aspirator in the measuring chamber.
(Items 11 and 12 of Fig 6.) This may be done, by inserting shims on the shoulder
between the two piece parts. To do this it is necessary to switch off the sample input
and output lines using the appropriate valves in the sample system.

WARNING
WHEN OPERATING ON HIGH VAPOUR PRESSURE SAMPLES THE ANALYSER
SHOULD BE VENTED TO ATMOSPHERE BEFORE REMOVING THE NOZZLE
ASSEMBLY.

(7) Remove the filter to gain access to the nozzle assembly. After ensuring that the oil
pressure in the instrument is zero, remove the nozzle assembly by unscrewing the
handle and carefully removing the assembly from its holder.

(8) Unscrew item 11 and fit a shim washer of 0.040in on the shoulder of the part (refer to
Fig. 6).

(9) Re-assemble the assembly and check that the O-rings are undamaged. Smear them
with silicone grease to prevent damage during re-insertion. Refit the assembly in the
Monitor.

(10) Open the isolation valves and repeat the above checks, adjusting the shim thickness to
give a result that falls within the limits of the ASTM Test.

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 27


Issue 6, 18/02/2015
9 NORMAL OPERATION

9.1 START-UP PROCEDURE

(1) Open any external sample outlet valves and then the inlet valves and any sampling
system valves, which are not part of the instrument.
(2) Close any external power isolator (supplied by the user).
(3) Switch on any sample re-insertion pump.
(4) Switch on the power and motor switches on the front of the Temperature Controller.
The red (left-hand) signal lamp turns on indicating that the oil bath heaters are
energised.
(5) When the amber (right-hand) signal begins to blink off and on, the bath is approaching
operating temperature; when the on-period is roughly equal to the off-period, the bath
has reached the set operating temperature.
(6) With sample flowing, use the mercury thermometer to check that the operating
temperature is 100oF (37.8oC)
(7) Check that the pressure-reducing regulator is not leaking by listening for chattering
or other noises.
(8) Switch on the transmitter
(9) Open the air supply valve, (if pneumatic transmitters are used).
(10) The instrument is now operational.

9.2 SHUT-DOWN PROCEDURE

(1) Shut off the incoming sample stream


(2) Turn off the mains and motor power supply switches
(3) Close the external air supply valve (if applicable).
(4) Switch OFF the power isolator
NOTE: If the Monitor is to be shut down for a protracted period and the sample stream is
liable to coagulate, it may be advisable to flush it out.

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 28


Issue 6, 18/02/2015
This Page has been intentionally left blank.

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 29


Issue 6, 18/02/2015
10 ROUTINE MAINTENANCE
WARNING
THIS INSTRUMENT INCLUDES APPARATUS USING VOLTAGES THAT CAN
ENDANGER LIFE. IT IS THE DUTY OF ALL PERSONS WHO MAY BE CONCERNED
WITH OPERATION OR WORK UPON THE APPARATUS TO COMPLY WITH CURRENT
ELECTRICITY SAFETY REGULATIONS AND TO BE THOROUGHLY CONVERSANT
WITH ALL REGULATIONS GOVERNING THE WORK THEY UNDERTAKE.
THE FLAMEPROOF CONTROL UNIT MUST BE OPENED FOR CIRCUIT CHECKING,
WHICH CAN ONLY BE PERFORMED WITH THE POWER SWITCHED ON. WHERE THE
INSTRUMENT IS INSTALLED IN AN AREA CLASSIFIED ZONE 1 or ZONE 2, SPECIAL
PERMISSION MUST BE OBTAINED FOR THE TESTS.
SWITCH OFF THE POWER BEFORE OPENING OR LOWERING THE OIL BATH. WEAR
GLOVES.

10.1 DAILY CHECKS


(1) Check that the amber signal lamp is switching on and off at approximately 2 sec.
intervals.
(2) Check the oil level by removing the pipe from the oil-fill elbow. The oil level should not
be permitted to drop below the mid point of the elbow. Change the oil if it becomes
viscous and dirty.

(3) Read the temperature indicated on the mercury thermometer. This should be 100oF
(37.8oC)
(4) The inlet filter screen may be removed for cleaning and replacing by disconnecting the
flush valve line. The filter screen holder may be unscrewed from the pipe plug so
that the filter screen cartridge can be removed.

Experience will indicate which of the above procedures may be performed at longer
intervals or even omitted.

10.2 MONTHLY CHECKS

NOTE: If the sample stream is volatile and leaves no sediment, the following operations
may be carried out at longer intervals.

10.2.1 NOZZLE
Remove the nozzle; dismantle and clean it.

10.2.2 FILTER SCREENS


Remove and dismantle the inlet filter; clean the filter screen

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 30


Issue 6, 18/02/2015
11 FAULT FINDING AND REPAIR

11.1 SAFETY
WARNING
SWITCH OFF THE POWER BEFORE OPENING OR LOWERING THE OIL BATH. WEAR
GLOVES.
THE FLAMEPROOF CONTROL UNIT MUST BE OPENED FOR CIRCUIT CHECKING,
WHICH CAN ONLY BE PERFORMED WITH THE POWER SWITCHED ON. WHERE THE
INSTRUMENT IS INSTALLED IN AN AREA CLASSIFIED ZONE 1 OR ZONE 2, SPECIAL
PERMISSION MUST BE OBTAINED FOR THE TESTS.
THIS INSTRUMENT INCLUDES APPARATUS USING VOLTAGES THAT CAN
ENDANGER LIFE. IT IS THE DUTY OF ALL PERSONS WHO MAY BE CONCERNED
WITH OPERATION OR WORK UPON THE APPARATUS TO COMPLY WITH CURRENT
ELECTRICITY SAFETY REGULATIONS AND TO BE THOROUGHLY CONVERSANT
WITH ALL REGULATIONS GOVERNING THE WORK THEY UNDERTAKE.

11.2 FAULT LOCATION

To locate a fault proceed in the sequence given overleaf, but first check:
(1) that the gauges show their normal readings;
(2) the Temperature Controller indicator lamps; in the normal operation, the red
temperature controller lamp (left-hand lamp) should be on continuously and the amber
lamp (right-hand lamp) should be flashing;

(3) the mercury thermometer reads normally (100oF, 37.8oC).


NOTE: The Temperature Controller switches the heater power by means of a solid-state
relay mounted on the inside of the lid of the Temperature Controller Box. This relay is
powered by the load current; thus if the heater is not connected, the relay does not
work and no reading will be obtained across the output terminals.

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 31


Issue 6, 18/02/2015
FAULT SYMPTOM RECOMMENDED CHECKING SEQUENCE AND ACTION
Mercury thermometer reads a) Heater not functioning.
below 36°C All other b) Temperature control unit inoperative (not panel lamps)
gauges about normal c) No sample flow.
Heater functions but does a) Sample flow rate too high due to wear on nozzle assembly.
not raise sample to proper b) Incoming sample temperature too low. Use pre-heaters on
temperature. incoming sample line.
c) Excessive or unnecessary cooling water flow.

Nozzle pressure gauge a) Line stoppage prior to sensing device.


reads zero. b) Clogged filter
c) Pressure reducing regulator defective
d) Incoming sample line stoppage outside Monitor.
Nozzle inlet pressure a) Stoppage in nozzle sensing device
gauge indicates b) Clogged thermometer well.
recommended pressure. c) Clogged pressure transmitter connections.
Vapour pressure gauges
read about 1 bar abs
Vapour pressure gauge a) Defective back pressure regulator
reading is excessively high b) Stoppage outside Monitor
(outlet side)
Temperature Controller a) Supplies (check at terminal)
indicator lamp does not b) Check voltage to neon at TB3/2&3 adjusting the
light temperature setting control to turn the Controller fully on
and off. The neon should be switched on and off at the
mains supply of the instrument.
c) Check the voltage to RLF1 at terminal TBM1, adjusting
temperature controls as in (b); the voltage should swing
from +6V to -8V.

Heater remains a) Check the voltage to the heater at TB2/4 adjusting the
continuously on or off. temperature setting to turn the Controller fully on and
off.
Controller not responding to a) Check that the resistance thermometer and balancing
the temperature settings resistor are each approximately 100 ohms.
b) Check all terminal block connections for security.
c) With the supply connected check that the mains
transformer T1 input and output voltages are correct.
d) Check that 2.3Vac is available at TBP1/11 and
TBP1/12,
e) Check the output of the pre-amplifier at TB1/3; at bridge
balance, it should be 5mV peak-to-peak.
f) Check the output of the controller at TBM1/7&8, while
varying the temperature setting control to turn the
Controller fully on and fully off. The output should swing
between +6Vdc and -8Vdc. Adjust the temperature
controls to balance the bridge; the output should
continually switch between the two levels.

Bath temperature fluctuates a) If the bath temperature is fluctuating outside the control
limits, refer to the section on adjustment of bath
operating temperature.

Table 3 – Fault Finding

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 32


Issue 6, 18/02/2015
11.3 REMOVAL AND FITTING OF RESISTANCE THERMOMETER

Proceed as follows.
(1) Disconnect the resistance thermometer terminations at the controller end and remove
all securing clips;
(2) Unscrew the gland at the controller end and carefully pull the cable through to the
outside;
(3) Carefully straighten the cable so that it lies vertically above the resistance
thermometer;
(4) Unscrew the resistance thermometer from the bath, allowing the cable to rotate with
the thermometer.
WARNING:
Do not attempt to disconnect the cable at the resistance thermometer end. This would
destroy the assembly.
Refit in reverse order.

11.4 REMOVAL OF HEATER, COOLING COIL & HEAT EXCHANGER UNIT


NOTE: This operation requires two persons

(1) Unscrew the socket-head screws securing the heater cover and remove the cover;
disconnect the wires from the immersion heater terminals.

(2) Unscrew the large socket head screw holding the immersion heater to the top flange.

(3) Unscrew the connection nuts holding the cooling coil in place.

(4) Disconnect the sample line from the inlet elbow and from the sensing device holder.

(5) Loosen the stirrers on the motor shaft. The complete heat exchanger, heater and
cooler can now be withdrawn and dismantled as required.

11.5 RENEWAL OF THERMAL FUSE

The thermal cut-off fuse is situated inside the tube next to the heater element. To replace
the thermal fuse, proceed as follows.
(1) Disconnect the back socket-head screws securing the heater cover and remove the
cover.
(2) Disconnect the wires from the heater to the back fuse terminal.
(3) Pull the fuse out of the tube.
(4) Fit a new fuse in reverse order to removal.

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 33


Issue 6, 18/02/2015
12 SPARE PARTS AND REPAIRS

For Technical Assistance Contact:


Analytical Technology & Control Limited
Broadway
Market Lavington
Devizes
Wiltshire
SN10 5RQ
Tel : 01380 - 818411
Fax : 01380 – 812733
E-mail : Atac@atacgroup.com
www : atacuk .com

Warning :

ELECTRICAL APPARATUS FOR USE IN POTENTIALLY EXPLOSIVE ATMOSPHERES

ANY MODIFICATION TO THIS PRODUCT CAN JEOPARDISE THE SAFETY


CLASSIFICATION OF THIS PRODUCT

ONLY BONAFIDE SPARE PARTS PURCHASE FROM ANALYTICAL TECHNOLOGY &


CONTROL LIMITED (ATAC) ARE ALLOWED TO BE FITTED, MODIFICATION OR
SUBSTITUTES PARTS CAN JEOPARDISE THE SAFETY CLASSIFICATION OF THIS
PRODUCT
Important components are listed in this section under the following headings.

SECTION TITLE

6.2 Overall Assembly


6.4 Temperature Control Unit
6.2.7 Nozzle Housing
6.2.3 Coil Assembly
Many components are unlikely to fail during the life of the Monitor but they may be
damaged accidentally. Others have a finite life and it is recommended that spares are held
on site.
The quantities listed should cover normal requirements for about a year. Where more than
one analyser is used on the same site, it is advisable to hold an additional one each of the
items marked X.

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 34


Issue 6, 18/02/2015
12.1 REPAIRS

Repairs should be addressed to our Customer Services Supervisor. It is helpful to our


Repairs Department to note the reason for the part being returned, including a brief
description of the failure or malfunction.
To ensure prompt and accurate processing of your order, we ask that the following
information always be included.
(1) Serial number of the instrument for which parts are being supplied.
(2) The ATAC Part Number, (listed in this Section).
(3) Description of the part.
(4) Chassis or assembly number where applicable.
(5) Method of shipment required.
(6) Your purchase order number.
(7) State whether item is for stock or breakdown.

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 35


Issue 6, 18/02/2015
12.2 SPARE PARTS TABLES

12.2.1 OVERALL ASSEMBLY


QTY Per
No: Description ATAC Part No:
Instrument

1 Transmitter See The Test Certificate


2 Inlet Pressure Regulator XXB0585 1
3 'Y' strainer XXB1942 1
4 100 mesh SS screen XXB0921 1

Gauge Saver 2-50psia XXB0049 1


5 OR
Gauge Saver 50-8000psia XXB0050 1
6 Valve Needle (Flush) XXB1943 1
7 Resistance Thermometer XXB0108 1
8 Back Pressure Regulator 0-250 psi XXB0912 1
9 Stirrer Impellor L.H XXB0889 1
10 Stirrer Impellor R.H XXB0890 1
Back Pressure Regulator 0-10 barg XXB0047 1
11 Back Pressure Regulator 0-16 barg OR XXB0970 1
Back Pressure Regulator 0-1 MPag XXB2072 1
Nozzle Pressure Gauge 0-40 barg XXB0048 1
12 Nozzle Pressure Gauge 0-60 barg OR XXB0944 1
Nozzle Pressure Gauge 0-4 MPag XXB2073 1
13 Nozzle Housing XXB0841 1
Vapour Pressure Gauge 0-1.6 bara XXB0044 1
Vapour Pressure Gauge 0-2.5 bara XXB0045 1
14 OR
Vapour Pressure Gauge 0-10 bara XXB0046 1
Vapour Pressure Gauge 0-160 kPaa XXB2071 1
Heater 100/120V 1.0kW XXB0107 1
Heater 100/120V 1.5kW XXB0172 1
Heater 100/120V 2.0kW XXB4145 1
15 OR
Heater 220/250V 1.0kW XXB0170 1
Heater 220/250V 1.5kW XXB0171 1
Heater 220/250V 2.0kW XXB5375 1
16 Thermal fuse 128 Deg. C XXB0106 1

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 36


Issue 6, 18/02/2015
12.2.2 TEMPERATURE CONTROL UNIT
QTY Per
No: Description ATAC Part No:
Instrument

1 Main amplifier PCB XPA0333 1


2 Pre-amplifier PCB XPA0335 1
3 Transformer (power) XXB0447 1
The following items mounted on the door
Relay, solid state 230V XXB0415 1
4 OR
Relay, solid state 115V XXB0416 1
5 Potentiometer RV2 FINE XXB0449 1
6 Potentiometer RV3 COARSE XXB0431 1
7 Fuse 150mA XFS0064 5
Neon Indicator Red 230V XXB0411 1
8 OR
Neon Indicator Red 115V XXB0413 1
Neon Indicator Amber 230V XXB0412 1
9 OR
Neon Indicator Amber 115V XXB0414 1
10 Toggle switch on/off (MAINS) XXB0408 1
11 Toggle switch on/off (MOTOR) XXB0408 1
Motor overload cut out 230V XXB0963 1
12 OR
Motor overload cut out 115V XXB0964 1
Order to suit mains input voltage

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 37


Issue 6, 18/02/2015
12.2.3 NOZZLE HOUSING
QTY Per
No: Description ATAC Part No:
Instrument

1 Nozzle Assembly Complete XXB0763 1


2 Sensing Nozzle Assembly XXB0758 1
3 Thermometer, Mercury See Data Sheet
4 Thermometer Guard XXB0765 1
5 Shims, Derating XXB0392 1 (set)
6 Kit of Spares, (for Nozzle Assembly) XXB0388 1
Comprising:
1 Viton O-ring BS No.113 XOR0008 1
2 Viton O-ring BS No.012 XOR0017 6
3 Viton O-ring BS No.009 XXB0389 2
4 30 mesh filter screen XXB0391 2

12.2.4 COIL ASSEMBLY


QTY Per
No: Description ATAC Part No:
Instrument

Heat exchanger, rectangular XXB0847 1


Heat exchanger, circular XXB0848 3

Water cooling coil assembly (St. St.) XXB0051 1


Water cooling coil assembly (Monel) XXB0053 1
Water cooling coil assembly (Hastelloy) XXB0052 1
Swagelok 1/4 in. back and front ferrules XFC0499 8

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 38


Issue 6, 18/02/2015
13 DOCUMENTS AND DRAWINGS FOR THIS MANUAL

Drawing Iss
Description Date
No .
XPA0382 Temperature Controller Pre-Amplifier PCB 4 24/02/2015
12883 Calibration Curve 2 24/02/2015
12886 Mains Voltage Connections On TBC1 3 24/02/2015
Electrical Schematic For Main Temperature 24/02/2015
12896 3
Controller PCB
13273 Model 1354 Overall Assembly 3 24/02/2015
13290 Vapour Pressure Analyser Wiring Circuit 6 24/02/2015
13330 Installation Details For Vapour Pressure Analyser 4 24/02/2015
13349 Flow Diagram 4 24/02/2015
15719 Principle Of Operation 1 24/02/2015
Vapour Pressure Analyser Temperature
990-0016 2 20/04/2008
Controller Certification Label Drawing

ATAC 1354 Vapour Pressure Analyser Operating and Maintenance Manual 39


Issue 6, 18/02/2015

You might also like