Protection Relays

NA60
FEEDER PROTECTION RELAY
THE COMPREHENSIVE SOLUTION FOR FEEDERS AND
TRANSFORMERS PROTECTION
— Application
The relay type NA60 can be typically used in radial or meshed MV and LV networks as feeder or power trans-
former protection:
• On radial, ring and parallel feeders of any length in solidly grounded, ungrounded, Petersen coil and/or resis-
tance grounded systems.
• On parallel connected generators and transformer on the same Busbar.
Moreover undervoltage and overvoltage functions are provided as protections or voltage controls.
The relay type NA60 can be can be provided with circuits for input phase current suitable for traditional CTs and
VTs, or combined ThySensor devices.

NA60
52

74TCS

- Protective & control functions


27 59

27 Undervoltage
67 49 50/51 74VT
49 Thermal image (for lines and transformers)
50/51 Phase overcurrent
74CT 50N/51N Residual overcurrent
59N 59 Overvoltage
BF 59N Residual overvoltage
67 Phase directional overcurrent
67N 50N/51N
67N Ground directional overcurrent
BF Circuit breaker failure
Alternative 74CT CTs monitoringMonitoraggio TA di fase
74TCS Trip circuit supervision

27 59

I 67 49 50/51 74VT Control functions COMMUNICATION


- USB
74CT METERING
- I L1..I L3,I E - Modbus RS485
59N
- Oscillography - Modbus TCP/IP
BF
- IEC 870-5-103/DNP3
- Events & Faults log
67N 50N/51N

NA60 - Flyer - 10-2021


— Measuring inputs with traditional CTs and VTs — Measures
• Three phase current inputs and one residual current input, NA60 provides metering values for phase and residual currents,
with nominal currents independently selectable at 1 A or 5 A phase and residual voltage, making them available for reading
through DIP-switches. on a display or to communication interfaces.
• Three phase voltage inputs with programmable nominal volt- The input signals can be acquired through the traditional CTs
ages within range 50...130 V (UR =100 V) or 200...520 V (UR =400 V) and VTs, or through combined sensors ThySensor including cur-
and one residual voltage input, with programmable nominal rent, voltage measures, standardized lamp voltage presence
voltage within range 50...130 V (UER =100 V). and isolated in the same component.
For residual current measurement (protection 50N/51N and 67N)
— Measuring inputs with ThySensor devices the installation of a balance current transformer is required,
• Three phase current inputs, with 630 A nominal current (pri- while the residual voltage is derived through vector calculus on
mary). the three phase voltages using the sensors ThySensor, or is se-
• One residual current input, with nominal currents indepen- lectable from the above calculation and the broken Delta VT in
dently selectable at 1 A or 5 A through DIP-switches. versions with traditional VT inputs.
• Three phase voltage inputs with nominal voltage 20/√3 kV (pri- Input signals are sampled 24 times per period and the RMS value
mary); the residual voltage has been obtained by vector calcu- of the fundamental component is measured using the DFT (Dis-
lation measures of phase voltages crete Fourier Transform) algorithm and digital filtering.
With DFT the RMS value of 2nd, 3rd, 4th and 5th harmonic of
— Firmware updating phase current are also measured.
The use of flash memory units allows on-site firmware updating. On the basis of the direct measurements, several calculated
(min, max, average,...), phase, sequence, power, harmonic, de-
— Construction mand and energy measures are processed.
According to the hardware configurations, the NA60 protec- Measures can be displayed with reference to nominal values or
tion relay can be shipped in various case styles suitable for the directly expressed in amperes and volts.
required mounting options (flush, projecting mounting, rack or
with separate operator panel) and with connections to input sig-
nals suitable for traditional VTs and CTs ( screw terminals) or
— Blocking input/outputs
One output blocking circuit and one input blocking circuit are
combined sensors ThySensor (RJ45 connectors for connecting
provided.
embedded cables)
The output blocking circuits of one or several Pro_N relays,
— Modular design shunted together, must be connected to the input blocking cir-
In order to extend I/O capability, the NA60 hardware can be cus- cuit of the protection relay, which is installed upstream in the
tomized through external auxiliary modules: electric plant. The output circuit works as a simple contact,
• MRI - Output relays and LEDs whose condition is detected by the input circuit of the upstream
• MID16 - Binary inputs protection relay.
• MCI - 4...20 mA converter Use of suitable pilot wire to fiber optic converters (BFO) allows
• MPT - Pt100 probe inputs. to perform fast and reliable accelerated logic selectivity on ra-
dial and closed ring networks.

— Output relays
Six output relays are available (two changeover, three make and
one break contacts); each relay may be individually programmed
as normal state (normally energized, de-energized or pulse) and
reset mode (manual or automatic).
A programmable timer is provided for each relay (minimum
pulse width). The user may program the function of each relay
according to a matrix (tripping matrix) structure.

— Communication
Multiple communication interfaces are implemented:
• One USB local communication front-end interface for commu-
nication with ThyVisor setup software.
• Two back-end interfaces for communication with remote mon-
itoring and control systems by:
— Binary inputs - RS485 port using ModBus® RTU, IEC 60870-5-103 or DNP3
Two binary inputs are available with programmable active state protocol.
(active-ON/active-OFF) and programmable timer (active to OFF/ - Ethernet port (RJ45 or optical fiber) using ModBus/TCP pro-
ON or ON/OFF transitions). tocol.
Several presettable functions can be associated to each input.

ThySensor
Insulator
VT

CT
Voltage divider for
voltage-detector lamps

2 NA60 - Flyer - 10-2021


— MMI (Man Machine Interface) as a warning for a possible short circuit in the pilot wire or in the
The user interface comprises a membrane keyboard, a backlight output circuit of the downstream protection.
LCD alphanumeric display and eight LEDs. The logic selectivity function can be realized through any com-
The green ON LED indicates auxiliary power supply and self di- bination of binary inputs, output relays and/or committed pilot
agnostics, two LEDs are dedicated to the Start and Trip (yellow wires circuits.
for Start, red for Trip) and five red LEDs are user assignable. — Self diagnostics
All hardware and software functions are repeatedly checked
and any anomalies reported via display messages, communica-
tion interfaces, LEDs and output relays. Anomalies may refer to:
• Hw faults (auxiliary power supply, output relay coil interrup-
tions, MMI board...).
• Sw faults (boot and run time tests for data base, EEPROM
memory checksum failure, data BUS,...).
• Pilot wire faults (break or short in the wire).
• Circuit breaker faults.
— Event storage
Several useful data are stored for diagnostic purpose; the events
are stored into a non volatile memory.
They are graded from the newest to the older after the “Events
reading”command (ThyVisor) is issued:
• Sequence of Event Recorder (SER).
The event recorder runs continuously capturing in circular
mode the last three hundred events upon trigger of binary in-
— Control and monitoring put/output.
Several predefined functions are implemented: • Sequence of Fault Recorder (SFR).
• Activation of two set point profiles The fault recorder runs continuously capturing in circular
• Phase CTs and VTs monitoring (74CT and 74VT) mode the last twenty faults upon trigger of binary input/output
• Logic selectivity and/or element pickup (start-trip).
• Cold load pickup (CLP) with block or setting change • Settings recording
• Trip circuit supervision (74TCS) Following some setting changes the last eight changes are re-
• Second harmonic restraint (inrush) corded in circular mode (Data Logger CEI 0-16)
• Remote tripping • Trip counters.
• Circuit Breaker commands and diagnostic
User defined logic may be customized according to IEC 61131-3 — Digital Fault Recorder (Oscillography) [1]
standard protocol (PLC). Upon trigger of tripping/starting of each function or external sig-
nals, the relay records in COMTRADE format:
Circuit Breaker commands and diagnostic • Oscillography with instantaneous values for transient analysis.
Several diagnostic, monitoring and control functions are provided: • RMS values for long time periods analysis.
• Health thresholds can be set; when the accumulated duty • Logic states (binary inputs and output relays).
(SI or SI2t), the number of operations or the opening time ex- Note - A license for Digital Fault Recorder function is required, for purchase
ceeds the threshold an alarm is activated. procedure please contact Thytronic.
• Breaker failure (BF); breaker status is monitored by means The records are stored in nonvolatile memory
52a-52b and/or through line current measurements.
• Trip Circuit Supervision (74TCS). — Programming and settings
• Breaker control; opening and closing commands can be car- All relay programming and adjustment operations may be per-
ried out locally or remotely. formed through MMI (Keyboard and display) or using a Personal
Computer with the aid of the ThyVisor software.
Cold Load Pickup (CLP) The same PC setup software is required to set, monitor and con-
The Cold Load Pickup feature can operate in two following figure all Pro_N devices.
modes: Two session level (User or Administrator) with password for sen-
• Each protective element can be blocked for a adjustable time. sible data access are provided.
• Each threshold can be increased for a programmable time.
It is triggered by the circuit breaker closing.

Second harmonic restraint


To prevent unwanted tripping of the protective functions on
transformer inrush current, the protective elements can be
blocked when the ratio between the second harmonic current
and the relative fundamental current is larger than a user pro-
grammable threshold.
The function can be programmed to switch an output relay so
as to cause a blocking protection relays lacking in second har-
monic restraint.
Logic selectivity
With the aim of providing a fast selective protection system
some protective functions may be blocked (pilot wire accelerat-
ed logic). To guarantee maximum fail-safety, the relay performs a
run time monitoring for pilot wire continuity and pilot wire short-
ing. Exactly the output blocking circuit periodically produces a
pulse, having a small enough width in order to be ignored as an
effective blocking signal by the input blocking circuit of the up-
wards protection, but suitable to prove the continuity of the pilot
wire. Furthermore a permanent activation (or better, with a dura-
tion longer than a preset time) of the blocking signal is identified,
NA60 - Flyer - 10-2021 3
SPECIF ICAT IONS
GENERAL INPUT CIRCUITS
— Mechanical data — Auxiliary power supply Uaux
Mounting: flush, projecting, rack or separated operator panel Nominal value (range) 24...48 Vac/dc, 115...230 Vac/110...220 Vdc
Mass (flush mounting case) 2.0 kg Operative range (each one of the above nominal values)
19...60 Vac/dc - 85...265 Vac/75...300 Vdc
— Insulation tests Power consumption:
Reference standards EN 60255-5 • Maximum (energized relays, Ethernet TX) 10 W (20 VA)
High voltage test 50Hz 2 kV 60 s • Maximum (energized relays, Ethernet FX) 15 W (25 VA)
Impulse voltage withstand (1.2/50 ms) 5 kV
Insulation resistance >100 MW — Phase current inputs with traditional CTs
• Nominal current In 1 A or 5 A selectable by DIP Switches
— Voltage dip and interruption • Permanent overload 25 A
Reference standards EN 61000-4-29 • Thermal overload (1 s) 500 A
• Rated consumption (for any phase) ≤ 0.002 VA (In = 1 A)
— EMC tests for interference immunity ≤ 0.04 VA (In = 5 A)
1 MHz damped oscillatory wave EN 60255-22-1 1 kV-2.5 kV • Connections M4 terminals
Electrostatic discharge EN 60255-22-2 8 kV
Fast transient burst (5/50 ns) EN 60255-22-4 4 kV — Residual current input
Conducted radio-frequency fields EN 60255-22-6 10 V • Nominal current IEn 1 A or 5 A selectable by DIP Switch
Radiated radio-frequency fields EN 60255-4-3 10 V/m • Permanent overload 25 A
High energy pulse EN 61000-4-5 2 kV • Thermal overload (1 s) 500 A
Magnetic field 50 Hz EN 61000-4-8 1 kA/m • Rated consumption ≤ 0.006 VA (IEn = 1 A), ≤ 0.012 VA (IEn = 5 A)
Damped oscillatory wave EN 61000-4-12 2.5 kV — Voltage inputs with traditional VTs
Ring wave EN 61000-4-12 2 kV Reference voltage UR 100 V or 400 V selectable on order
Conducted common mode (0...150 kHz) EN 61000-4-16 10 V Nominal voltage Un 50...130 V or 200...520 V adjustable via sw
Permanent overload / 1s overload 1.3 UR / 2 UR
— Emission Rated consumption (for any phase) ≤ 0.5 VA
Reference standards EN 61000-6-4 (ex EN 50081-2)
Conducted emission 0.15...30 MHz Class A — Residual voltage input with traditional VTs
Radiated emission 30...1000 MHz Class A Reference voltage UER 100 V
Nominal voltage UEn 50...130 V adjustable via sw
— Climatic tests Permanent overload / 1s overload 1.3 UER / 2 UER
Reference standards IEC 60068-x, ENEL R CLI 01, CEI 50 Rated consumption ≤ 0.5 VA

— Mechanical tests — Phase inputs with ThySensors


Reference standards EN 60255-21-1, 21-2, 21-3 Secondary voltage (Inp = 630 A) 200 mV
Secondary voltage (Unp = 20/√3 kV) 1.0 V
— Safety requirements Connections RJ45 clamp
Reference standards EN 61010-1
Pollution degree 3 — ThySensors primary inputs
Reference voltage 250 V Primary nominal current Inp 630 A
Overvoltage III Extended primary current 50 A...1250 A
Pulse voltage 5 kV Permanent thermal nominal current 1.2 Inp
Reference standards EN 60529 Max primary current 22.5 kA
Protection degree: Thermal overload (3 s) 16 kA
• Front side IP52 Dynamic overload (half cycle) 40 kA
• Rear side, connection terminals IP20 Primary nominal voltage Unp 20/√3 kV
Permanent overload factor 1.8
— Environmental conditions
Ambient temperature -25...+70 °C — Binary inputs
Storage temperature -40...+85 °C Quantity and type 2 dry inputs
Relative humidity 10...95 % Max permissible voltage 19...265 Vac/19...300 Vdc
Atmospheric pressure 70...110 kPa Max consumption, energized 3 mA

— Certifications — Block input (Logic selectivity)


Product standard for measuring relays EN 50263 Quantity and type 1 powered by internal isolated supply
CE conformity Max consumption, energized 5 mA
• EMC Directive 89/336/EEC
• Low Voltage Directive 73/23/EEC OUTPUT CIRCUITS
Type tests IEC 60255-6 — Output relays K1...K6
Quantity 6
COMMUNICATION INTERFACES • Type of contacts K1, K2 changeover (SPDT, type C)
Local PC USB Type B • Type of contacts K3, K4, K5 make (SPST-NO, type A)
Network: • Type of contacts K6 break (SPST-NC, type B)
• RS485 1200...57600 bps Nominal current 8A
• Ethernet 100BaseT 100 Mbps Nominal voltage/max switching voltage 250 Vac/400 Vac
Protocol ModBus® RTU/IEC 60870-5-103/DNP3, TCP/IP Breaking capacity:
• Direct current (L/R = 40 ms) 50 W
• Alternating current (l = 0,4) 1250 VA
Make 1000 W/VA
Short duration current (0,5 s) 30 A
4 NA60 - Flyer - 10-2021
Block output (Logic selectivity) — Undervoltage - 27
Quantity 1 Common configuration:
Type optocoupler • Voltage measurement type for 27 (Utype27) [1] U ph-ph /U ph-n
• 27 Operating logic (Logic27) AND/OR
— LEDs
Quantity 8 U< Element
• ON/fail (green) 1 • U< Curve type (U<Curve) DEFINITE, INVERSE [2]
• Start (yellow) 1 Definite time
• Trip (red) 1 • 27 First threshold definite time (U <def) 0.05...1.10 U n /E n
• Allocatable (red) 5 • U<def Operating time (t U<def ) 0.03...100.0 s
Inverse time
GENERAL SETTINGS • 27 First threshold inverse time (U <inv) 0.05...1.10 U n /E n
• U<inv Operating time (t U<inv) 0.10...100.0 s
— Rated values (traditional CTs an VTs versions)
Relay nominal frequency (f n) U<< Element
50, 60 Hz Definite time
Relay phase nominal current (In) 1 A, 5 A • 27 Second threshold definite time (U <<def) 0.05...1.10 U n /E n
Phase CT nominal primary current (Inp) 1 A...10 kA • U<<def Operating time (t U<<def ) 0.03...100.0 s
Relay residual nominal current (IEn) 1 A, 5 A Note [1] - With U ph-ph setting all threshold are in p.u. U n
Residual CT nominal primary current (IEnp) 1 A...10 kA With U ph-n setting all threshold are in p.u. E n
Relay nominal voltage (phase-to-phase) (Un) 50...130 V or 200...520 V Note [2] - The mathematical formula for INVERSE curves is:
Relay nominal voltage (phase-to-ground) En= Un/√3 t = 0.75 ∙ t U < inv / [1 - (U/U< inv)], where:
Line VT primary nominal voltage (phase-to-phase) (Unp) 50 V..500 kV t = trip time (in seconds)
Relay residual nominal voltage (direct measure) (UEn) 50...130 V t U< inv = operating time setting (in seconds)
Residual primary nominal voltage (phase-to-phase) · √3 (UEnp) U = input voltage
50 V...500 kV U<inv = threshold setting
— Rated values (ThySensor input versions)
Relay nominal frequency (f n) 50, 60 Hz — Thermal image - 49
Phase CT nominal primary current (Inp)[1] 1 A...10 kA Common configuration:
Relay residual nominal current (IEn) 1 A, 5 A • Initial thermal image DqIN (Dth IN ) 0.0...1.0 DqB
Residual CT nominal primary current (IEnp) 1 A...10 kA • Reduction factor at inrush (KINR) 1.0...3.0
Relay nominal voltage (phase-to-phase) (Un) 50...130 V or 200...520 V • Thermal time constant t (T ) 1...200 min
Relay nominal voltage (phase-to-ground) En= Un/√3 • DthCLP Activation time (t DthCLP) 0.00...100.0 s
Line VT primary nominal voltage (phase-to-phase) (Unp) 50 V..500 kV DthAL1 Element
Relay residual nominal voltage (calculated) UECN = Un · √3 = 3 · En • 49 First alarm threshold DqAL1 (Dth AL1) 0.3...1.0 DqB
Note [1] - It represents the reference value to which they are expressed all DthAL2 Element
the settings and corresponds to the rated primary current sensors • 49 Second alarm threshold DqAL2 (Dth AL 2 ) 0.5...1.2 DqB
Dth> Element
— Binary input timers • 49 Trip threshold Dq (Dth>) 1.100...1.300 DqB
ON delay time (IN1 tON, IN2 tON) 0.00...100.0 s
OFF delay time (IN1 tOFF, IN2 tOFF) 0.00...100.0 s — Phase overcurrent - 50/51 (traditional CTs versions)
Logic Active-ON/Active-OFF I> Element
• I> Curve type (I>Curve) DEFINITE
— Relay output timers IEC/BS A, B, C, ANSI/IEEE MI, VI, EI, RECTIFIER, I2t or EM
Minimum pulse width (t TR) 0.000...0.500 s • ICLP > Activation time (t CLP>) 0.00...100.0 s
• I> Reset time delay (t > RES) 0.00...100.0 s
PROTECTIVE FUNCTIONS Definite time
• 50/51 First threshold definite time (I> def ) 0.100...40.0 In
— Base current IB (traditional CTs versions) • I> def within CLP (ICLP>def ) 0.100...40.0 In
Base current (IB) • I> def Operating time (t > def ) 0.04...200 s
0.10...2.50 In Inverse time
Note - The base current IB represents the rated current of the component • 50/51 First threshold inverse time (I>inv) 0.100...20.00 In
of the protected (line, transformer ,...), expressed in relation to the CT • I>inv within CLP (ICLP>inv) 0.100...20.00 In
rated current. Since usually the secondary current rating of the line CT • I>inv Operating time (t >inv) 0.02...60.0 s
coincides with the current rating of the relay, the IB value must be set to
the ratio of the nominal current of the protected equipment and the CT I>> Element
primary rated current. • Type characteristic DEFINITE or I2t
• ICLP >> Activation time (t CLP>>) 0.00...100.0 s
— Base current IB (ThySensor versions) • I>> Reset time delay (t >> RES) 0.00...100.0 s
Base current (IB) Definite time
0.10...2.50 In • 50/51 Second threshold definite time (I>> def ) 0.100...40.0 In
Note - The base current IB represents the rated current of the component of • I>> def within CLP (ICLP>>def ) 0.100...40.0 In
the protected (line, transformer ,...), expressed in relation to the CT rated • I>> def Operating time (t >> def ) 0.03...10.00 s
current. The IB value must be set to the ratio of the nominal current of the Inverse time
protected equipment and the ThySensor primary current (630 A). • 50/51 Second threshold inverse time (I>>inv) 0.100...20.00 In
• I>>inv within CLP (ICLP>>inv) 0.100...20.00 In
— Thermal protection with RTD thermometric probes - 26 • I>>inv Operating time (t >>inv) 0.02...10.00 s
Alarm
• Alarm threshold qALx (x=1...8) 0...200 °C I>>> Element
• Operating time t qALx (x=1...8) 0....100 s • ICLP >>> Activation time (t CLP>>>) 0.00...100.0 s
Trip • I>>> Reset time delay (t >>> RES) 0.00...100.0 s
• Trip threshold q>x (x=1...8) 0...200 °C Definite time
• Operating time t q >x (x=1...8) 0....100 s • 50/51 Third threshold definite time (I>>> def ) 0.100...40.0 In
Note: The element becomes available when the MPT module is enabled and • I>>>def within CLP (ICLP>>>def ) 0.100...40.0 In
connected to Thybus • I>>>def Operating time (t >>> def ) 0.03...10.00 s
NA60 - Flyer - 10-2021 5
— Phase overcurrent - 50/51 (ThySensor versions) Inverse time
I> Element • 59 First threshold inverse time (U >inv) 0.50...1.50 U n /E n
• I> Curve type (I>Curve) DEFINITE, IEC/BS A, B, C, • U>inv Operating time (t U>inv) 0.10...100.0 s
ANSI/IEEE MI, VI, EI,, RECTIFIER, I2t or EM U>> Element
• ICLP > Activation time (t CLP>) 0.00...100.0 s Definite time
• I> Reset time delay (t > RES) 0.00...100.0 s • 59 Second threshold definite time (U >>def) 0.50...1.50 U n /E n
Definite time • U>>def Operating time (t U>> def ) 0.03...100.0 s
• 50/51 First threshold definite time (I> def ) 0.010...30.0 In
Note [1] - With U ph-ph setting all threshold are in p.u. U n
• I> def within CLP (ICLP>def ) 0.010...30.0 In
With U ph-n setting all threshold are in p.u. E n
• I> def Operating time (t > def ) 0.04...200 s
Inverse time Note [2] - The mathematical formula for INVERSE curves is:
• 50/51 First threshold inverse time (I>inv) 0.010...20.00 In t = 0.5 ∙ t U > inv / [(U/U> inv)-1], where:
• I>inv within CLP (ICLP>inv) 0.010...20.00 In t = trip time (in seconds)
• I>inv Operating time (t >inv) 0.02...60.0 s t U> inv = operating time setting (in seconds)
U = input voltage
I>> Element U>inv = threshold setting
• Type characteristic DEFINITE or I2t
• ICLP >> Activation time (t CLP>>) 0.00...100.0 s — Residual overvoltage - 59N (traditional VTs versions)
• I>> Reset time delay (t >> RES) 0.00...100.0 s Common configuration:
Definite time • Residual voltage measurement for 59N- direct/calc. U E /U EC
• 50/51 Second threshold definite time (I>> def ) 0.010...30.0 In • 59N Operating mode from 74VT internal (74VTint59N) OFF/Block
• I>> def within CLP (ICLP>>def ) 0.010...30.0 In • 59N Operating mode from 74VT external (74VText59N) OFF/Block
• I>> def Operating time (t >> def ) 0.03...10.00 s U E > Element
Inverse time • U E > Curve type (U E >Curve) DEFINITE, INVERSE [1]
• 50/51 Second threshold inverse time (I>>inv) 0.010...20.00 In • U E> Reset time delay (t UE>RES) 0.00...100.0 s
• I>>inv within CLP (ICLP>>inv) 0.010...20.00 In Definite time
• I>>inv Operating time (t >>inv) 0.02...10.00 s • 59N First threshold definite time (U E >def) 0.01...0.70 U En
• U E>def Operating time (t UE >def) 0.07...100.0 s
I>>> Element
Inverse time
• ICLP >>> Activation time (t CLP>>>) 0.00...100.0 s
• 59N First threshold inverse time (U E >inv) 0.01...0.50 U En
• I>>> Reset time delay (t >>> RES) 0.00...100.0 s
• U E>inv Operating time (t UE >inv) 0.10...100.0 s
Definite time
• 50/51 Third threshold definite time (I>>> def ) 0.010...30.0 In U E >> Element
• I>>>def within CLP (ICLP>>>def ) 0.010...30.0 In • U E>> Reset time delay (t UE>>RES) 0.00...100.0 s
• I>>>def Operating time (t >>> def ) 0.03...10.00 s • 59N Second threshold definite time (U E >>def) 0.01...0.70 U En
• U E>>def Operating time (t UE >>def) 0.07...100.0 s
— Residual overcurrent - 50N/51N Note [1] - The mathematical formula for INVERSE curves is:
IE> Element t = 0.5 ∙ t UE > inv / [(UE /UE > inv)-1 where:
• IE> Curve type (IE>Curve) DEFINITE, t = trip time (in seconds)
IEC/BS A, B, C, ANSI/IEEE MI, VI, EI, EM t UE> inv = operating time setting (in seconds)
• IECLP > Activation time (t ECLP>) 0.00...100.0 s UE = residual input voltage
• IE> Reset time delay (t E> RES) 0.00...100.0 s U E> inv = threshold setting
Definite time — Residual overvoltage - 59N (ThySensor versions)
• 50N/51N First threshold definite time (I E>def) 0.002...10.00 IEn Common configuration:
• IE>def within CLP (IECLP>def ) 0.002...10.00 IEn • Residual voltage measurement for 59N- calculated U EC
• IE>def Operating time (t E> def) 0.04...200 s • 59N Operating mode from 74VT internal (74VTint59N) OFF/Block
Inverse time • 59N Operating mode from 74VT external (74VText59N) OFF/Block
• 50N/51N First threshold inverse time (IE >inv) 0.002...2.00 IEn
• IE>inv within CLP (IECLP>inv) 0.002...2.00 IEn U E > Element
• IE>inv Operating time (t E>inv) 0.02...60.0 s • U E > Curve type (U E >Curve) DEFINITE, INVERSE [1]
• U E> Reset time delay (t UE>RES) 0.00...100.0 s
IE>> Element Definite time
• IECLP >> Activation time (t ECLP>>) 0.00...100.0 s • 59N First threshold definite time (U E >def) 0.01...0.70 U En
• IE>> Reset time delay (t E>> RES) 0.00...100.0 s • U E>def Operating time (t UE >def) 0.07...100.0 s
Definite time Inverse time
• 50N/51N Second threshold definite time (IE>>def) 0.002...10.00 IEn • 59N First threshold inverse time (U E >inv) 0.01...0.50 U En
• IE>>def within CLP (IECLP>>def ) 0.02...10.00 IEn • U E>inv Operating time (t UE >inv) 0.10...100.0 s
• IE>>def Operating time (t E>> def ) 0.03...10.00 s U E >> Element
• U E>> Reset time delay (t UE>>RES) 0.00...100.0 s
IE>>> Element
• 59N Second threshold definite time (U E >>def) 0.01...0.70 U En
• IECLP >>> Activation time (t ECLP>>>) 0.00...100.0 s
• U E>>def Operating time (t UE >>def) 0.07...100.0 s
• IECLP >>> Reset time delay (t E>>> RES) 0.00...100.0 s
Definite time Note [1] - The mathematical formula for INVERSE curves is:
• 50N/51N Third threshold definite time (I E>>>def) 0.002...10.00 IEn t = 0.5 ∙ t UE > inv / [(UEC /UE > inv)-1 where:
• IECLP >>> def within CLP (IECLP>>>def ) 0.002...10.00 IEn t = trip time (in seconds)
• IECLP >>> def Operating time (t E>>> def ) 0.03...10.00 s t UE> inv = operating time setting (in seconds)
UEC = residual input voltage (calculated)
U E> inv = threshold setting
— Overvoltage - 59
Common configuration: — Phase directional overcurrent - 67 (CTs and VTs versions)
• Voltage measurement type for 59 (Utype59) [1] U ph-ph /U ph-n Common configuration:
• 59 Operating logic (Logic59) AND/OR • 67 Operating mode (Mode67) I /I ∙cos
U> Element • 67 Operating logic (Logic67) 1/3 / 2/3
• U> Curve type (U>Curve) DEFINITE, INVERSE [2] • 67 Operating mode from 74VT internal (74VTint67)
Definite time OFF/Block/Not directional
• 59 First threshold definite time (U >def) 0.50...1.50 U n /E n • 67 Operating mode from 74VT external (74VText67)
• U>def Operating time (t U> def ) 0.03...100.0 s OFF/Block/Not directional
6 NA60 - Flyer - 10-2021
IPD> Element IPD>> Element
• IPD> Curve type (IPD>Curve) DEFINITE, • IPD> Curve type (IPD>>Curve) DEFINITE,
IEC/BS A, B, C, ANSI/IEEE MI, VI, EI, RECTIFIER, I2t or EM IEC/BS A, B, C, ANSI/IEEE MI, VI, EI
• IPDCLP > Activation time (t PDCLP>) 0.00...100.0 s RECTIFIER, I2t or EM
• IPD> Reset time delay (t PD > RES) 0.00...100.0 s • IPDCLP >> Activation time (t PDCLP>>) 0.00...100.0 s
Definite time • IPD>> Reset time delay (t PD >> RES) 0.00...100.0 s
• 67 First threshold definite time (IPD > def ) 0.100...40.0 In Definite time
• IPD > def characteristic angle (ThetaPD>def ) 0...359° • 67 Second threshold definite time (IPD >> def ) 0.010...30.0 In
• IPD > def within CLP (IPDCLP>def ) 0.100...40.0 In • IPD >> def characteristic angle (ThetaPD>>def ) 0...359°
• IPD > def Operating time (t PD > def ) 0.05...200 s • IPD >> def within CLP (IPDCLP>>def ) 0.010...30.0 In
Inverse time • IPD >> def Operating time (t PD >> def ) 0.04...200 s
• 67 First threshold inverse time (IPD >inv) 0.100...10.0 In Inverse time
• IPD >inv characteristic angle (ThetaPD>inv) 0...359° • 67 Second threshold inverse time (IPD >>inv) 0.010...10.00 In
• IPD >inv within CLP (IPDCLP>inv) 0.100...10.0 In • IPD >>inv characteristic angle (ThetaPD>>inv) 0...359°
• IPD >inv Operating time (t PD >inv) 0.02...60.0 s • IPD >>inv within CLP (IPDCLP>>inv) 0.010...10.00 In
IPD>> Element • IPD >>inv Operating time (t PD >>inv) 0.02...60.0 s
• IPD> Curve type (IPD>>Curve) DEFINITE,
IPD>>> Element
IEC/BS A, B, C, ANSI/IEEE MI, VI, EI, RECTIFIER, I2t or EM
• IPDCLP >>> Activation time (t PDCLP>>>) 0.00...100.0 s
• IPDCLP >> Activation time (t PDCLP>>) 0.00...100.0 s
• IPD>>> Reset time delay (t PD >>> RES) 0.00...100.0 s
• IPD>> Reset time delay (t PD >> RES) 0.00...100.0 s
Definite time
Definite time
• 67 Third threshold definite time (IPD >>> def ) 0.010...30.0 In
• 67 Second threshold definite time (IPD >> def ) 0.100...40.0 In
• IPD >>> def characteristic angle (ThetaPD>>>def ) 0...359°
• IPD >> def characteristic angle (ThetaPD>>def ) 0...359°
• IPD >>> def within CLP (IPDCLP>>>def ) 0.010...30.0 In
• IPD >> def within CLP (IPDCLP>>def ) 0.100...40.0 In
• IPD >>> def Operating time (t PD >>> def ) 0.04...10.00 s
• IPD >> def Operating time (t PD >> def ) 0.04...200 s
Inverse time IPD>>>> Element
• 67 Second threshold inverse time (IPD >>inv) 0.100...10.0 In • IPDCLP >>>> Activation time (t PDCLP>>>>) 0.00...100.0 s
• IPD >>inv characteristic angle (ThetaPD>>inv) 0...359° • IPD>>>> Reset time delay (t PD >>>> RES) 0.00...100.0 s
• IPD >>inv within CLP (IPDCLP>>inv) 0.100...10.0 In Definite time
• IPD >>inv Operating time (t PD >>inv) 0.02...60.0 s • 67 Fourth threshold definite time (IPD >>>> def ) 0.010...30.0 In
IPD>>> Element • IPD >>>> def characteristic angle (ThetaPD>>>>def ) 0...359°
• IPDCLP >>> Activation time (t PDCLP>>>) 0.00...100.0 s • IPD >>>> def within CLP (IPDCLP>>>>def ) 0.010...30.0 In
• IPD>>> Reset time delay (t PD >>> RES) 0.00...100.0 s • IPD >>>> def Operating time (t PD >>>> def ) 0.04...10.00 s
Definite time
• 67 Third threshold definite time (IPD >>> def ) 0.100...40.0 In — Directional earth fault overcurrent - 67N (traditional CTs)
• IPD >>> def characteristic angle (ThetaPD>>>def ) 0...359° Common configuration:
• IPD >>> def within CLP (IPDCLP>>>def ) 0.100...40.0 In • 67N Operating mode (Mode67N) I /I ∙cos
• IPD >>> def Operating time (t PD >>> def ) 0.04...10.00 s • Residual voltage measurement type for 67N - direct/calculated
(3VoType67N) U E / U EC
IPD>>>> Element • 67N Multiplier of threshold for insensitive zone (M) 1.5...10.0
• IPDCLP >>>> Activation time (t PDCLP>>>>) 0.00...100.0 s • 67N Operating mode from 74VT internal (74VTint67N)
• IPD>>>> Reset time delay (t PD >>>> RES) 0.00...100.0 s OFF/Block/Not directional
Definite time • 67N Operating mode from 74VT external (74VText67N)
• 67 Fourth threshold definite time (IPD >>>> def ) 0.100...40.0 In OFF/Block/Not directional
• IPD >>>> def characteristic angle (ThetaPD>>>>def ) 0...359° IED> Element
• IPD >>>> def within CLP (IPDCLP>>>>def ) 0.100...40.0 In • IED> Curve type DEFINITE,
• IPD >>>> def Operating time (t PD >>>> def ) 0.04...10.00 s IEC/BS A, B, C, ANSI/IEEE MI, VI, EI, EM
• IEDCLP > Activation time (t EDCLP>) 0.00...100.0 s
— Phase directional overcurrent - 67 (ThySensor versions) • IED> Reset time delay (t ED > RES) 0.00...100.0 s
Common configuration: Definite time
• 67 Operating mode (Mode67) I /I ∙cos 67N First threshold definite time (IED > def - UED > def )
• 67 Operating logic (Logic67) 1/3 / 2/3 • Residual current pickup value 0.002...10.00 IEn
• 67 Operating mode from 74VT internal (74VTint67) • Residual voltage pickup value 0.004...0.500 UEn
OFF/Block/Not directional • Characteristic angle 0...359°
• 67 Operating mode from 74VT external (74VText67) • Half operating sector 1...180°
OFF/Block/Not directional • IED > def within CLP (IEDCLP>def ) 0.002...10.00 IEn
• IED > def Operating time (t ED > def ) 0.05...200 s
IPD> Element
• IPD> Curve type (IPD>Curve) DEFINITE, Inverse time
IEC/BS A, B, C, ANSI/IEEE MI, VI, EI, 67N First threshold inverse time (IED >inv - UED >inv)
RECTIFIER, I2t or EM • Residual current pickup value 0.002...2.00 IEn
• IPDCLP > Activation time (t PDCLP>) 0.00...100.0 s • Residual voltage pickup value 0.004...0.500 UEn
• IPD> Reset time delay (t PD > RES) 0.00...100.0 s • Characteristic angle 0...359°
• Half operating sector 1...180°
Definite time • IED >inv within CLP (IEDCLP >inv) 0.002...2.00 IEn
• 67 First threshold definite time (IPD > def ) 0.010...30.0 In • IED >inv Operating time (t ED >inv) 0.02...60.0 s
• IPD > def characteristic angle (ThetaPD>def ) 0...359°
• IPD > def within CLP (IPDCLP>def ) 0.010...30.0 In IED>> Element
• IPD > def Operating time (t PD > def ) 0.05...200 s • IED> Curve type (IED>>Curve) DEFINITE,
Inverse time IEC/BS A, B, C, ANSI/IEEE MI, VI, EI, EM
• 67 First threshold inverse time (IPD >inv) 0.010...10.00 In • IEDCLP >> Activation time (t EDCLP>>) 0.00...100.0 s
• IPD >inv characteristic angle (ThetaPD>inv) 0...359° • IED>> Reset time delay (t ED >> RES) 0.00...100.0 s
• IPD >inv within CLP (IPDCLP>inv) 0.010...10.00 In Definite time
• IPD >inv Operating time (t PD >inv) 0.02...60.0 s 67N Second threshold definite time (IED >> def - UED >> def )

NA60 - Flyer - 10-2021 7


• Residual current pickup value 0.002...10.00 IEn Definite time
• Residual voltage pickup value 0.004...0.500 UEn 67N Second threshold definite time (IED >> def - UED >> def )
• Characteristic angle 0...359° • Residual current pickup value 0.002...10.00 IEn
• Half operating sector 1...180° • Residual voltage pickup value 0.004...0.500 UEn
• IED >> def within CLP (IEDCLP >> def ) 0.002...10.00 IEn • Characteristic angle 0...359°
• IED >> def Operating time (t ED >> def ) 0.05...10.00 s • Half operating sector 1...180°
Inverse time • IED >> def within CLP (IEDCLP >> def ) 0.002...10.00 IEn
67N Second threshold inverse time (IED >>inv - UED >>inv) • IED >> def Operating time (t ED >> def ) 0.05...10.00 s
• Residual current pickup value 0.002...2.00 IEn Inverse time
• Residual voltage pickup value 0.004...0.500 UEn 67N Second threshold inverse time (IED >>inv - UED >>inv)
• Characteristic angle 0...359° • Residual current pickup value 0.002...2.00 IEn
• Half operating sector 1...180° • Residual voltage pickup value 0.004...0.500 UEn
• IED >inv within CLP (IEDCLP>>inv) 0.002...2.00 IEn • Characteristic angle 0...359°
• IED >inv Operating time (t ED >>inv) 0.02...10.00 s • Half operating sector 1...180°
• IED >inv within CLP (IEDCLP>>inv) 0.002...2.00 IEn
IED>>> Element • IED >inv Operating time (t ED >>inv) 0.02...10.00 s
• IEDCLP >>> Activation time (t EDCLP>>>) 0.00...100.0 s
• IED>>> Reset time delay (t ED >>> RES) 0.00...100.0 s IED>>> Element
Definite time • IEDCLP >>> Activation time (t EDCLP>>>) 0.00...100.0 s
67N Third threshold definite time (IED >>> def - UED >>> def ) • IED>>> Reset time delay (t ED >>> RES) 0.00...100.0 s
• Residual current pickup value 0.002...10.00 IEn Definite time
• Residual voltage pickup value 0.004...0.500 UEn 67N Third threshold definite time (IED >>> def - UED >>> def )
• Characteristic angle 0...359° • Residual current pickup value 0.002...10.00 IEn
• Half operating sector 1...180° • Residual voltage pickup value 0.004...0.500 UEn
• IED >>> def within CLP (IEDCLP >>> def ) 0.002...10.00 IEn • Characteristic angle 0...359°
• IED >>> def Operating time (t ED >>> def ) 0.05...10.00 s • Half operating sector 1...180°
• IED >>> def within CLP (IEDCLP >>> def ) 0.002...10.00 IEn
IED>>>> Element • IED >>> def Operating time (t ED >>> def ) 0.05...10.00 s
• IEDCLP >>>> Activation time (t EDCLP>>>>) 0.00...100.0 s
• IED>>>> Reset time delay (t ED >>>> RES) 0.00...100.0 s IED>>>> Element
Definite time • IEDCLP >>>> Activation time (t EDCLP>>>>) 0.00...100.0 s
67N Fourth threshold definite time (IED >>>> def - UED >>>> def ) • IED>>>> Reset time delay (t ED >>>> RES) 0.00...100.0 s
• Residual current pickup value 0.002...10.00 IEn Definite time
• Residual voltage pickup value 0.004...0.500 UEn 67N Fourth threshold definite time (IED >>>> def - UED >>>> def )
• Characteristic angle 0...359° • Residual current pickup value 0.002...10.00 IEn
• Half operating sector 1...180° • Residual voltage pickup value 0.004...0.500 UEn
• IED >>>> def within CLP (IEDCLP >>>> def ) 0.002...10.00 IEn • Characteristic angle 0...359°
• IED >>>> def Operating time (t ED >>>> def ) 0.05...10.00 s • Half operating sector 1...180°
• IED >>>> def within CLP (IEDCLP >>>> def ) 0.002...10.00 IEn
— Directional earth fault overcurrent - 67N (Thysensor) • IED >>>> def Operating time (t ED >>>> def ) 0.05...10.00 s
Common configuration:
• 67N Operating mode (Mode67N) I /I ∙cos — Selective block - BLOCK2
• Residual voltage measurement U EC Selective block IN:
• 67N Multiplier of threshold for insensitive zone (M) 1.5...10.0 • BLIN Max activation time for phase protections (tB-IPh)0.10...10.00 s
• 67N Operating mode from 74VT internal (74VTint67N) • BLIN Max activation time for earth protections (tB-IE) 0.10...10.00 s
OFF/Block/Not directional
• 67N Operating mode from 74VT external (74VText67N) Selective block OUT:
OFF/Block/Not directional • BLOUT Dropout time delay for phase protections (tF-IPh) 0.00...1.00 s
IED> Element • BLOUT Drop-out time delay for phase protections (tF-IE) 0.00...1.00 s
• IED> Curve type DEFINITE, • BLOUT Drop-out time delay for phase and earth protections (tF-IPh/IE)
IEC/BS A, B, C, ANSI/IEEE MI, VI, EI, EM 0.00...1.00 s
• IEDCLP > Activation time (t EDCLP>) 0.00...100.0 s — Internal selective block - BLOCK4
• IED> Reset time delay (t ED > RES) 0.00...100.0 s • Output internal selective block dropout time for phase protec-
Definite time tions (t F-IPh) 0.00...10.00 s
67N First threshold definite time (IED > def - UED > def ) • Output internal selective block dropout time for ground protec-
• Residual current pickup value 0.002...10.00 IEn tions (t F-IE ) 0.00...10.00 s
• Residual voltage pickup value 0.004...0.500 UEn
• Characteristic angle 0...359° — Breaker failure - BF
• Half operating sector 1...180° BF Phase current threshold (IBF >) 0.05...1.00 In
• IED > def within CLP (IEDCLP>def ) 0.002...10.00 IEn BF Residual current threshold (IEBF >) 0.01..2.00 IEn
• IED > def Operating time (t ED > def ) 0.05...200 s BF Time delay (t BF) 0.06...10.00 s
Inverse time
67N First threshold inverse time (IED >inv - UED >inv) — Second Harmonic Restraint - 2ndh-REST
• Residual current pickup value 0.002...2.00 IEn Second harmonic restraint threshold (I2ndh>) 10...50 %
• Residual voltage pickup value 0.004...0.500 UEn I2ndh> Reset time delay (t 2ndh>RES) 0.00...100.0 s
• Characteristic angle 0...359°
• Half operating sector 1...180° — VT supervision - 74VT
• IED >inv within CLP (IEDCLP >inv) 0.002...2.00 IEn 74VT Negative sequence overvoltage threshold (U2VT>) 0.05...0.50 En
• IED >inv Operating time (t ED >inv) 0.02...60.0 s 74VT Negative sequence overvoltage threshold (I2VT>) 0.05...0.50 In
74VT Phase undervoltage threshold (U VT< ) 0.05...0.50 En
IED>> Element
74VT Minimum change of current threshold 74VT (DIVT<) 0.05...0.50 In
• IED> Curve type (IED>>Curve) DEFINITE,
IEC/BS A, B, C, ANSI/IEEE MI, VI, EI, EM 74VT Undercurrent inhibition threshold (IVT< ) 0.100...40.0 In
• IEDCLP >> Activation time (t EDCLP>>) 0.00...100.0 s 74VT Alarm time delay (t V T-A L ) 0.0...10.0 s
• IED>> Reset time delay (t ED >> RES) 0.00...100.0 s

8 NA60 - Flyer - 10-2021


— CT supervision - 74CT 5th harmonic:
74CT Threshold (S<) 0.10...0.95 • Fifth harmonic phase currents I L1-5th , I L 2-5th , I L 3-5th
74CT Overcurrent threshold (I * ) 0.10...1.00 I n
S< Operating time (t S <) 0.03...200 s Demand phase currents:
• Phase fixed currents demand I L1FIX , I L 2FIX , I L 3FIX
— Circuit Breaker supervision • Phase rolling currents demand I L1ROL , I L 2ROL , I L 3ROL
Number of CB trips (N.Open) 0...10000 • Phase peak currents demand I L1MA X , I L 2MA X , I L 3MA X
Cumulative CB tripping currents (SumI) 0...5000 In • Phase minimum currents demand I L1MIN , I L 2MIN , I L 3MIN
CB opening time for I^2t calculation (t break ) 0.05...1.00 s Demand power:
Cumulative CB tripping I^2t (SumI^2t) 0...5000 I n2.s • Fixed active power demand P FIX
CB max allowed opening time (t break >) 0.05...1.00 s • Fixed reactive power demand Q FIX
• Rolling active power demand P ROL
— Pilot wire diagnostic • Rolling reactive power demand Q ROL
BLOUT1 Diagnostic pulses period (PulseBLOUT1) • Peak active power demand P MA X
OFF - 0.1-1-5-10-60-120 s • Peak reactive power demand Q MA X
BLIN1 Diagnostic pulses control time interval (PulseBLIN1) • Minimum active power demand P MIN
OFF - 0.1-1-5-10-60-120 s • Minimum reactive power demand Q MIN
METERING & RECORDING Energy:
• Positive active energy EA +
— Measured parameters • Negative active energy EA-
Direct: • Total active energy EA
• Frequency f • Positive reactive energy EQ+
• Fundamental RMS phase currents I L1, I L 2 , I L 3 • Negative reactive energy EQ-
• Fundamental RMS phase voltages U L1, U L 2 , U L 3 • Total reactive energy EQ
• Fundamental RMS residual current IE
• Fundamental RMS residual voltage (Traditional VTs) UE
— Fault recording (SFR)
Calculated: Number of faults 20
• Thermal image DTheta Recording mode circular
• Fundamental RMS phase-to-phase voltages U 12 , U 23 , U 31 Trigger:
• Fundamental RMS calculated residual voltage U EC • Output relays of enabled protection or control element (OFF-ON)
• Maximum current between I L1-I L 2 -I L 3 I Lmax • External trigger (binary inputs) IN1...INx
• Minimum current between I L1-I L 2 -I L 3 I Lmin Data recorded:
• Average current between I L1-I L 2 -I L 3 IL • Counter (resettable by ThyVisor) 0...10 9
• Maximum voltage between U L1-U L 2 -U L 3 U Lmax
• Time stamp Date and time
• Average voltage between U L1-U L 2 -U L 3 UL
• Cause tripped element
• Maximum voltage between U 12 -U 23 -U 31 U max
• Fundamental RMS phase currents I L1r, I L 2r, I L 3r
• Average voltage between U 12 -U 23 -U 31 U
• Fundamental RMS residual current I Er
Phase: • Fundamental RMS phase voltages U L1r, U L 2r, U L 3r
• Displacement angle of I L1 respect to U L1 PhiL1 • Fundamental RMS phase-to-phase voltages U 12r, U 23r, U 31r
• Displacement angle of I L 2 respect to U L 2 PhiL2 • Fundamental RMS residual voltages (measured and calculated)
• Displacement angle of I L 3 respect to U L 3 PhiL3 U Er, U ECr
• Displacement angle of I L1 respect to U 23 Alpha1 • Displacement angles (IL1-UL1, IL2-UL2, IL3-UL3) PhiL1r, PhiL2r, PhiL3r
• Displacement angle of I L 2 respect to U 31 Alpha2 • Displacement angles (IL1-U23, IL2-U31, IL3-UL3) Alpha1r, Alpha2r, Alpha3r
• Displacement angle of I L 3 respect to U 12 Alpha3 • Displacement angle UE-IE (traditional VTs) PhiEr
• Displacement angle of U E respect to I E (traditional V Ts) PhiE • Displacement angle UEC-IE PhiECr
• Displacement angle of U EC respect to I E PhiEC • Thermal image DTheta- r
• Binary inputs state IN1, IN2...INx
Sequence: • Output relays state K1...K6...K10
• Positive sequence current I1 • Fault cause info (operating phase) L1, L2, L3
• Negative sequence current I2
• Negative sequence current/positive sequence current ratio I 2 /I 1 — Event recording (SER)
• Negative sequence voltage U2 Number of events 300
Recording mode circular
Power:
• Total active power P Trigger:
• Total reactive power Q • Start/Trip of enabled protection or control element
• Total apparent power S • Binary inputs switching (OFF/ON or ON/OFF) IN1...INx
• Power factor cosPhi • Setting changes
• Phase active powers P L1, P L 2 , P L 3 • Auxiliary supply Power UP/Power DOWN
• Phase reactive powers Q L1, Q L 2 , Q L 3 Data recorded:
• Power factors cosPhiL1, cosPhiL2, cosPhiL3 • Counter (resettable by ThyVisor) 0...10 9
• Cause binary input/trip/setting change/Power ON/OFF
2nd harmonic: • Time stamp Date and time
• Second harmonic phase currents I L1-2nd , I L 2-2nd , I L 3-2nd
• Maximum of the second harmonic phase currents/fundamen- — Settings recording
tal component percentage ratio I -2nd /I L Number of setting changes 8
3rd harmonic: Recording mode circular
• Third harmonic phase currents I L1-3rd , I L 2-3rd , I L 3-3rd Data recorded:
• Setting counter 0...109
• Third harmonic residual current I E-3rd
• Third harmonic residual voltage (traditional VTs) U E-3rd • Setting data description and parameter
• Time stamp Date and time
4th harmonic:
• Fourth harmonic phase currents I L1-4th , I L 2-4th , I L 3-4th
NA60 - Flyer - 10-2021 9
— Digital Fault Recorder (Oscillography) [1] Note 1- A licence for the digital fault recorder function is required.
File format COMTRADE The oscillography records are stored in non-volatile memory.
Records depending on setting [2]
Recording mode circular Note [2] - For instance, with following setting:
Sampling rate > 1 kHz • Pre-trigger time 0.25 s
• Post-trigger time 0.25 s
Trigger setup: • Sampled channels i L1, i L2 , i L3 , i E
• Analog channels I L1, I L2 , I L3 , I E
• Pre-trigger time 0.05...1.00 s
• Digital channels K1, K2, K3, K4, K5, K6, IN1, IN2
• Post-trigger time 0.05...60.00 s
• Trigger from inputs IN1, IN2...INx up to 180 records can be stored
• Trigger from outputs K1...K6...K10
• Communication ThyVisor

Set sample channels:


• Instantaneous currents i L1, i L2, i L3, i E
• Instantaneous voltages u L1, u L2, u L3, u E
Set analog channels (Analog 1...12):
• Frequency f
• Fundamental RMS phase currents I L1, I L 2 , I L 3
• Fundamental RMS residual current IE
• Fundamental RMS phase voltages U L1, U L 2 , U L 3
• Fundamental RMS residual voltage UE
• Fundamental RMS phase-to-phase voltages U 12 , U 23 , U 31
• Fundamental RMS calculated residual voltage U EC
• Displacement angles IL1-UL1, IL2-UL2, IL3-UL3 PhiL1, PhiL2, PhiL3
• Displacement angles IL1-U23, IL2-U31, IL3-UL3 Alpha1, Alpha2, Alpha3
• Displacement angle UE-IE (traditional VTs) PhiE
• Displacement angle UEC-IE PhiEC
• Second harmonic phase currents I L1-2nd , I L 2-2nd , I L 3 -2nd
• Maximum of the second harmonic phase currents/fundamen-
tal component percentage ratio I -2nd /I L
• Temperature T1...T8

Set digital channels (Digital 1...12):


• Output relays state K1...K6...K10
• Binary inputs state IN1, IN2...INx

Oscillography (DFR)

10 NA60 - Flyer - 10-2021


— Protective elements

L1
L2 BUSBAR
L3

NA60
(*) Antiferrorisonance
dn da
dn db B7
dn dc (*) UE 59N
B8

A N n a B1
B N n b UL1
B2
C N n c
B3
UL2
B4
B5 27
UL3
B6
59

74VT

67

49

P1 C1
50/51
S1
IL1
S2 C2
P2 74CT
C3 50BF
IL2
C4
C5
IL3
C6

P1 C7
OPERATION (**)

S1
IE 50N/51N 67N
S2 C8
P2
BINARY INPUTS

CB position

LOAD (***)

(**) OPERATION FOR:


- 67 elements with characteristic angle adjusted within 0°... 90° or 270° ...359° ranges
- 67N elements for insulated neutral systems and characteristic angle setting = 90°
(***) MEASUREMENTS:
- Positive sign for measurement of active power and energy with passive load
- Negative sign for measurement of active power and energy with generators
NA60-fun.ai

NA60 - Flyer - 10-2021 11


— Connection diagram example with CTs and VTs inputs

L1
L2 BUSBAR
L3

D1
dn
NA60 A1
da A2
C1 C2
A3 F1
A4 RX F2
n A3
A5 F3
K1 A6 F4
A4 A7
TX
F5
a B1 A5 A8 C3 C4

U L1 K2 A6 A9
A10
B1
B2
B2 A7 A11 B3

OUTPUT RELAYS
B3
VOLTAGE INPUTS
A8 A12 B4
A13 B5
U L2 K3 A9 A14 C5 C6 B6
B4 A15 B7
B5 K4 A10 A16 B8

A17
U L3
B6 A11 A18

B7 K5 A12 A19
A20 C7 C8

R (*) B8 UE A13
A21
K6 A22

A14 E1
(*) Antiferroresonance

F1
P1 C1
S1 F2
I L1
F3
RS485

S2 C2
P2 F4
C3 B-
Supervision
CURRENT INPUTS

F5
C4
I L2 A+
unit
C5
I L3
C6
P1 C7
ETHERNET

S1
IE D1
S2 C8 HUB
P2

E1
54 53 52 51 50 49 48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 32 31 30 29 28
THYBUS
OPERATION (**)

A1 
UAUX OUTPUT INPUT
67, 67N

A2
RUN
BUS
ON

MODULO 4 RELE’ + 8 INGRESSI DIGITALI


1
2
3
4
5

MRI
4 RELAYS + 8 BINARY INPUTS MODULE

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27
BLOCK OUT
BLOCK IN

BLOUT-
A17 A15
BLOUT+
A18 A16
BINARY INPUTS

A19
IN1
A20
USB

LOAD (***) A21


IN2
A22

(**) OPERATION FOR:


- 67 elements with characteristic angle adjusted within 0°... 90° or 270° ...359° ranges
- 67N elements for insulated neutral systems and characteristic angle setting = 90°
(***) MEASUREMENTS:
- Positive sign for measurement of active power and energy with passive load
- Negative sign for measurement of active power and energy with generators

12 NA60 - Flyer - 10-2021


— Connection diagram example with ThySensor inputs

L1
L2 SBARRE
L3

NA60

K1 A3
A4
A5
P1
K2 A6
IL1-UL1 A7
A8

ThySensor INPUTS

OUTPUT RELAYS
P2
K3 A9
IL2-UL2
K4 A10
A11
IL3-UL3 K5 A12
D1
K6 A13

A1 A14
A2
C1 C2
A3 F1
A4
A5
RX F2
F3
F1
A6 TX F4 F2

RS485
A7 F5
A8 F3
Residual current

B-
A9 B1 P1 C1 F4
INPUT

A10 B2 S1 A+
F5
A11 B3 IE
A12 B4 S2 C2
A13 B5 P2
A14 B6
L1 B7
A15
A16 B8
ETHERNET

A17
L2
A18
D1
A19
A20
L3
A21
A22

E1
A1 
THYBUS

UAUX E1
A2
BLOCK OUT
BLOCK IN

BLOUT-
A17 A15
OPERATION (*)

BLOUT+
A18 A16
67, 67N

A19
BINARY INPUTS

IN1
A20
USB

A21
IN2
A22
LINEA (**)

(*) OPERATION FOR:


- 67 elements with characteristic angle adjusted within 0°... 90° or 270° ...359° ranges
- 67N elements for insulated neutral systems and characteristic angle setting = 90°
(**) MESUREMENTS:
- Positive sign for measurement of active power and energy with passive load
- Negative sign for measurement of active power and energy with generators

NA60 - Flyer - 10-2021 13


— ThySensor

Ø 110
Ø 100
50

Mounting hole M10 Mounting hole M10


Cable gland

Spacer 8mm M4

P2 P1
104

225
96
25

Capacitive divider output


14
Ø 110
42
62

P1

Busbar mounting Busbar mounting


20
Ø

hole M12 Ø hole M12


20

14 NA60 - Flyer - 10-2021


DIMENSIONS
FRONT VIEW REAR VIEW
128.5
107 120 101 ø 4.5 110

D1 D1

A1 A1
A2 A2

ø 4.5
C1 C2 C1 C2
A3 F1 A3 F1
A4 RX F2 A4 RX F2
A5 F3 A5 F3
A6 TX F4 A6 TX F4
A7 F5 A7 F5
A8 C3 C4 A8 C3 C4
A9 B1 A9 B1
A10 B2 A10 B2
177

171
149

200
168
A11 B3 A11 B3
A12 B4 A12 B4
ON 1 2 3 4 5 START ON 1 2 3 4 5 START
A13 B5 A13 B5
80

TRIP TRIP A14 C5 C6 B6 A14 C5 C6 B6


A15 B7 A15 B7
A16 B8 A16 B8

A17 A17
A18 A18
A19 A19
A20 C7 C8 A20 C7 C8

A21 A21
A22 A22
31

E1 E1

20
FLUSH MOUNTING PROJECTING MOUNTING FLUSH MOUNTING PROJECTING MOUNTING
(Separate operator panel)

SIDE VIEW

212.5 275
25 15
205 30 5 30 ø 4.5
170

FLUSH MOUNTING SEPARATE PROJECTING MOUNTING PROJECTING MOUNTING


OPERATOR PANEL (Separate operator panel) (Stand alone)

RACK MOUNTING FLUSH MOUNTING CUTOUT

482.6 102.5 ±0.3


465 70
177 (4U)

161
101.6

154

ON 1 2 3 4 5 START ON 1 2 3 4 5 START ON 1 2 3 4 5 START ON 1 2 3 4 5 START

TRIP TRIP TRIP TRIP

N.4 holes ø 3.5

NA60 - Flyer - 10-2021 15


Headquarter: 20139 Milano - Piazza Mistral, 7 - Tel. +39 02 574 957 01 ra - Fax +39 02 574 037 63
Factory: 35127 Padova - Z.I. Sud - Via dell’Artigianato, 26 - Tel. +39 049 894 770 1 ra - Fax +39 049 870 139 0