Professional Documents
Culture Documents
Barrio Rivadavia Oeste_Project.VC1-Report
Barrio Rivadavia Oeste_Project.VC1-Report
PVsyst TRIAL
PVsyst - Simulation report
Grid-Connected System
PVsyst TRIAL
Barrio Rivadavia Oeste - Argentina
PVsyst TRIAL
PVsyst TRIAL
Author
PVsyst TRIAL
Project: segovia tapia diplomatura
Variant: Nueva variante de simulación
PVsyst V7.4.7
VC1, Simulation date:
20/06/24 23:27
PVsyst TRIAL
with V7.4.7
Project summary
Geographical Site Situation Project settings
Barrio Rivadavia Oeste Latitude -31.54 °S Albedo 0.20
Argentina Longitude -68.59 °W
Altitude 680 m
Time zone UTC-3
Weather data
Barrio Rivadavia Oeste
Meteonorm 8.1 (2010-2019), Sat=100% - Sintético
System summary
PVsyst TRIAL
Grid-Connected System No 3D scene defined, no shadings
System information
PV Array Inverters
Nb. of modules 272 units Nb. of units 8 units
Pnom total 29.92 kWp Pnom total 24.00 kWac
Pnom ratio 1.247
Results summary
Produced Energy 46959 kWh/year Specific production 1569 kWh/kWp/year Perf. Ratio PR 78.19 %
PVsyst TRIAL
Project and results summary
Main results
Loss diagram
Predef. graphs
Table of contents
PVsyst TRIAL
PVsyst TRIAL
20/06/24 PVsyst Evaluation mode Page 2/7
Project: segovia tapia diplomatura
Variant: Nueva variante de simulación
PVsyst V7.4.7
VC1, Simulation date:
20/06/24 23:27
PVsyst TRIAL
with V7.4.7
General parameters
Grid-Connected System No 3D scene defined, no shadings
PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane No 3D scene defined Transposition Perez
Tilt/Azimuth 30 / 90 ° Diffuse Perez, Meteonorm
Circumsolar separate
PVsyst TRIAL
PV Array Characteristics
PV module Inverter
Manufacturer Generic Manufacturer Generic
Model Poly 110 Wp 72 cells Model 3 kWac inverter
(Original PVsyst database) (Original PVsyst database)
Unit Nom. Power 110 Wp Unit Nom. Power 3.00 kWac
Number of PV modules 272 units Number of inverters 8 units
Nominal (STC) 29.92 kWp Total power 24.0 kWac
Modules 34 string x 8 In series Operating voltage 125-440 V
At operating cond. (50°C) Pnom ratio (DC:AC) 1.25
Pmpp 26.91 kWp
U mpp 248 V
I mpp 108 A
PVsyst TRIAL
Total PV power Total inverter power
Nominal (STC) 30 kWp Total power 24 kWac
Total 272 modules Number of inverters 8 units
Module area 244 m² Pnom ratio 1.25
Cell area 215 m²
Array losses
Thermal Loss factor DC wiring losses Module Quality Loss
Module temperature according to irradiance Global array res. 38 mΩ Loss Fraction 1.5 %
Uc (const) 20.0 W/m²K Loss Fraction 1.5 % at STC
Uv (wind) 0.0 W/m²K/m/s
PVsyst TRIAL
PVsyst TRIAL
20/06/24 PVsyst Evaluation mode Page 3/7
Project: segovia tapia diplomatura
Variant: Nueva variante de simulación
PVsyst V7.4.7
VC1, Simulation date:
20/06/24 23:27
PVsyst TRIAL
with V7.4.7
Main results
System Production
Produced Energy 46959 kWh/year Specific production 1569 kWh/kWp/year
Perf. Ratio PR 78.19 %
PVsyst TRIAL
Balances and main results
PVsyst TRIAL
February 195.8 68.59 26.23 183.4 179.0 4346 4196 0.765
March 186.7 55.60 23.18 175.3 170.2 4223 4077 0.778
April 144.0 35.73 17.72 139.0 133.7 3457 3337 0.802
May 116.9 26.82 12.25 110.9 105.9 2848 2749 0.829
June 108.4 16.98 8.34 103.1 97.8 2674 2583 0.837
July 113.5 17.67 7.67 106.2 101.1 2764 2668 0.839
August 144.9 21.34 10.95 137.8 132.2 3516 3393 0.823
September 170.0 41.10 14.78 160.5 155.7 4028 3889 0.810
October 213.1 59.46 19.99 197.1 192.0 4767 4601 0.780
November 230.3 65.11 23.50 211.6 206.4 4968 4795 0.757
December 259.7 69.35 26.87 242.8 237.4 5587 5395 0.743
Year 2140.9 539.41 18.27 2007.3 1945.5 48645 46959 0.782
PVsyst TRIAL
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings
PVsyst TRIAL
20/06/24 PVsyst Evaluation mode Page 4/7
Project: segovia tapia diplomatura
Variant: Nueva variante de simulación
PVsyst V7.4.7
VC1, Simulation date:
20/06/24 23:27
PVsyst TRIAL
with V7.4.7
Loss diagram
2141 kWh/m² Global horizontal irradiation
-2.10%
-1.17%
-11.70% PV loss due to temperature
PVsyst TRIAL
PVsyst TRIAL
20/06/24 PVsyst Evaluation mode Page 5/7
Project: segovia tapia diplomatura
Variant: Nueva variante de simulación
PVsyst V7.4.7
VC1, Simulation date:
20/06/24 23:27
PVsyst TRIAL
with V7.4.7
Predef. graphs
Diagrama entrada/salida diaria
PVsyst TRIAL
PVsyst TRIAL
PVsyst TRIAL
20/06/24 PVsyst Evaluation mode Page 6/7
PVsyst V7.4.7
VC1, Simulation date:
20/06/24 23:27
PVsyst TRIAL
with V7.4.7
PVsyst TRIAL
PVsyst TRIAL
PVsyst TRIAL
PVsyst TRIAL