FOUNDATION -PILE

4
335

Fully Galvanized Leg

300

500

250

550
2150
1900
ELVATION : STRUCTURE WITH FOUNDATION

R0 29.07.15 FOR CLIENT APPROVAL VB RC RC


REV. DATE DESCRIPTION DRAWN CHKD. APPR.
PROJECT CODE:
PACKAGE ID: CHKD. APPR. DRAWN CHKD. APPR.
THIRD ANGLE DO NOT SCALE TPS-023 SHEET
CS5711-004-9 PROJECTION THIS DRAWING IF TITLE 1 OF 1
NAME OF THE PROJECT:
TITLE IN DOUBT ASK PROJECT: VB RC RC
250MW SOLAR POWER (S) IN ANANTAPUR Foundation and Sectional details REV.
250MW SOLAR POWER (S) IN ANANTAPUR Foundation and Sectional details DATE DATE COPYRIGHT:-
DATE DATE DATE

DISTRICT OF ANDHRA PRADESH-DCR THIS DRAWING IS PROPERTY OF TATA POWER DISTRICT OF ANDHRA PRADESH-DCR
04.08.15 04.08.15 04.08.15 R0
for 24 Module mounting structure SOLAR SYSTEMS LTD,AND MAY NOT BE COPIED
UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE IN mm for 24 Module mounting structure
NAME OF THE PACKAGE:
DWG NUMBER-
(IN WHOLE OR IN PART) USED FOR MANUFACTURE
OR DISCLOSED WITHOUT PRIOR CONSENT TATA TOLERANCES
SCALE PART/DWG SHEET SIZE

DEVELOPMENT OF 250 MW (5 x 50 MW) NUMBER-


SOLAR PV PROJECT IN ANANTAPUR DISTRICT (AP) 5711-004-P2-PVC-V-017
POWER SOLAR SYSTEMS LTD OR AN AUTHORIZED
AGENT.
NO D.P.

± 1mm
ONE D.P.

± 0.5mm
TWO D.P.

± 0.25mm
ANGLES

± 0.5°
NTS
TPS023-CV-203-R1
A3
Embedment length for 96 x 48mm leg into the pile foe both uplift and Bending Moment

Uplift force =16.3KN


The above uplift force will be resisted by all the faces of the leg, bonded with concrete. Hence 1/3rd of the
total uplift force will be resisted by 96mm length face & 1/6th of the total uplift force will be resisted by
48mm length face

Force carried by 48mm f a c e (16.3/6) = 2.72kN

Bending moment = 2.7 kN-m

Tensile force exerted on 48mm face due to moment = Moment /Lever arm
Lever arm in the present case = distance between the 48mm face = 96mm

Hence additional tensile force exerted on 48mm face = 2.7 / 0.096

= 28.12 kN

Hence total ultimate tensile force acting on 48mm face = (2.72+28.12) x 1.5

= 46.26 kN

Allowable bond stress for M25 grade concrete = 1.4 N/mm2

Considering uplift resistance in both sides of the 48mm face


Force resisted by 550mm embedded length of the leg = 48 x 550 x 2 x 1.4
= 73.92kN > 46.26 kN

Hence Safe
However, in order to take care for the uncertainties in ensuring the compacted concrete inside
the tube, an additional 12mm dia bar projected 75mm from the face of the pipe is proposed.