UBW Technical Manual

US.UBW.Tech.Manual.2018
Table of Contents

UBW Technical Manual

General Description..............................................................................................................................3
Part Number Description.......................................................................................................................4
Interrupt Capacity Ratings.....................................................................................................................5
UBW 225 Trip Curves (15 - 225A).........................................................................................................6
UBW 250 Trip Curves..........................................................................................................................33
UBW 400 Trip Curves..........................................................................................................................35
UBW 600 Trip Curves..........................................................................................................................37
UBW 800 Trip Curves..........................................................................................................................39
UBW 1200 Trip Curves........................................................................................................................40
UBW 2500 Trip Curves........................................................................................................................42
Let Thru Curves..................................................................................................................................46
UBW Dimensions................................................................................................................................49

2 | 1-800-ASK-4WEG | www/weg/met Data subject to change without notice.


Molded-Case Circuit Breakers
General Description
General Circuit
Breaker Information
WEG’s molded-case circuit breakers are Because bimetals are responsive to the heat
designed to provide circuit protection for low emitted by the current flow, they allow a long- 2. Operating Mechanism
voltage distribution systems. They are time delay on light overloads, yet they have a The function of the operating mechanism is to
described by NEMA as, “. . . a device fast response on heavier overloads. provide a means of opening and closing the
for closing and interrupting a circuit between breaker contacts. All mechanisms are of the
separable contacts under both normal and Magnetic trip action is achieved through the quick-make, quick-break type and are “trip
abnormal conditions,” and further- more as, use of an electromagnet in series with the free.” “Trip free” mechanisms are designed
“. . . a breaker assembled as an integral load current. This provides an instantaneous so that the contacts cannot be held closed
unit in a supporting and enclosing housing of tripping action when the current reaches a against an abnormal circuit condition and are
insulating material.” The NEC® describes predetermined value. Front-adjustable sometimes referred to as an “overcenter
them as, “A device designed to open and magnetic trip elements are supplied as toggle mechanism.” In addition to indicating
close a circuit by non-automatic means, and standard on 250 A frame circuit breakers and whether the breaker is “on” or “off,” the
to open the circuit automatically on a above 225 are fixed thermal and magnetic operating mechanism handle indicates when
predetermined overload of current, without the breaker is “tripped” by moving to a
injury to itself when properly applied within Electronic RMS Trip Breakers position midway between the extremes. This
its rating.” WEG electronic trip breakers are generally distinct trip point is particularly advantageous
So designed, WEG circuit breakers protect applied for applications where high levels of where breakers are grouped, as in
conductors against overloads and conductors system coordination are called for. Available panelboard applications, because it clearly
and connected apparatus, such as motors from 500–2500 A, today’s electronic trip indicates the faulty circuit. The operating
and motor starters, against short circuits. breakers can provide superior protection and mechanism contains a positive on feature. In
coordination as well as additional protection the normal switching operation, the handle of
Circuit Breaker Components and features. Both the overload trip action and the the circuit breaker will not be capable of
short-circuit trip action of breakers with being left readily at or near the off position
Functions when the main contacts are closed.
Being essentially high interrupting capacity Digitrip electronic trip units are achieved by
switches with repetitive elements, WEG’s the use of current transformers and solid-
state circuitry that monitors the current and 3. Arc Extinguishers
circuit breakers are comprised of three main
initiates tripping through a flux shunt trip The function of the DE-ION® arc extinguisher
functional components. These are:
when an overload or a short circuit is present. is to confine, divide
1. Trip elements (thermal-magnetic or
All multiple-pole circuit breakers have trip extinguish the arc drawn between opening
electronic)
elements in each pole and a common trip bar. breaker contacts. It consists of specially
2. Operating mechanism
An abnormal circuit condition in any one pole shaped steel grids isolated from each other
3. Arc extinguishers
will cause all poles to open simultaneously. and supported by an insulating housing.
When the contacts are opened, the arc drawn
1. Trip Elements induces a magnetic field in the grids, which in
The function of the trip element is to trip the Electronic RMS trip breakers can include trip
turn draws the arc from the contacts and into
operating mechanism in the event of a features such as:
the grids. The arc is thus split into a series of
prolonged overload or short-circuit current. To smaller arcs and the heat generated is quickly
accomplish this, a thermal- magnetic trip • Adjustable long-time pickup dissipated through the metal. These two
action is provided. • Adjustable short-time pickup actions result in a rapid removal of ions from
• Adjustable long delay time the arc, which hastens dielectric build- up
Thermal-Magnetic Breakers • Adjustable short delay time between the contacts and results in
WEG thermal-magnetic breakers are general • Adjustable instantaneous pickup rapid extinction of the arc.
purpose devices suitable for the majority of
breaker applications and are considered the Trip unit adjustments are made by setting
industry standard. Available from 15–800 A, switches on the front of the trip unit or by
thermal-magnetic breakers provide accurate programming the trip unit electronically.
reliable overload and short- circuit protection All electronic RMS trip breakers are equipped
for conductors and connected apparatus. with a manual push-to-trip mechanism.
Thermal trip action is achieved through the
use of a bimetal heated by the load current.
On a sustained over- load, the bimetal will
deflect, causing the operating mechanism to
trip.

Data subject to change without notice. UBW Technical Manual | 3


Molded-Case Circuit Breakers

Description UBW Breakers Frames 225 to 2500

Selective trip over a smaller range of fault currents within the interrupting rating (low short-time
Select trip
ratings). Typically 10–13 times the frame size

Operator type Types of operators: mechanically operated over-center toggle or motor operator
Closing speed Greater than 5-cycle closing for electrically operated devices
Mounting Typically fixed-mounted but large frame sizes may be available in drawout construction
Interrupting rating Interrupting duty at 480 Vac: 22–100 kA
Current limiting Current limiting available with and without fuses up to 200 kA
Relative cost Low
Available frame sizes Large number of frame sizes available. Typical 15–2500 A
Maintenance Very limited maintenance possible on larger frame sizes
Enclosure types Used in enclosures, panelboards, switchboards, MCCs and control panels
Series ratings Available in series ratings
Enclosed rating 80% continuous-current rated
Standards NEMA AB1/AB3 UL 489

UBW Part Number Sequence

4 | 1-800-ASK-4WEG | www/weg/met Data subject to change without notice.


Molded-Case Circuit Breakers

Interupting Capicity Ratings


225 Frame
Type Poles 240ac 480ac 600ac 250dc
N 3 65K 35K N/A 10K
H 3 100K 65K N/A 22K
L 3 200K 100K N/A 22K
250 Frame
Type Poles 240ac 480ac 600ac 250dc
N 3 65K 35K 18K 10K
H 3 100K 65K 25K 22K
L 3 200K 100K N/A 22K
400 Frame
Type Poles 240ac 480ac 600ac 250dc
N 3 65K 35K 18K 10K
H 3 100K 65K 35K 22K
L 3 200K 100K 65K 22K
600 Frame
Type Poles 240ac 480ac 600ac 250dc
N 3 65K 35K 25K 22K
H 3 100K 65K 35K 25K
L 3 200K 100K 50K 30K
800 Frame
Type Poles 240ac 480ac 600ac 250dc
S 3 65K 50K 25K 22K
H 3 100K 65K 35K 25
1200 Frame
Type Poles 240ac 480ac 600ac DC Rated
S 3 85K 50K 25K NO
H 3 100K 65K 35K NO
L 3 N/A 100K 65K NO
2500 Frame
Type Poles 240ac 480ac 600ac DC Rated
H 3 125K 65K 50K NO
L 3 200 100K 65K NO

Data subject to change without notice. UBW Technical Manual | 5


Molded-Case Circuit Breakers

UBW Time Current Curves


225N/H 15A
CURRENT IN AMPERES

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000
Circuit breaker time/current curves

2 HOURS
2 HOURS

F-frame circuit breakers


5,000 Catalog types ED, EHD, FDB, FD and HFD circuit breakers, two-, three- 5,000

1 HOUR
1 HOUR

and four-poles.
Circuit breaker time/current curves
For application and coordination purposes only.
3,000 Series 225 frame circuit breakers
Based on 40˚C ambient, cold start. Connected with four (4) feet of 3,000
rated wire (60˚C
Tested in open air with current in allpole.
2,000 2,000
For application
Maximum andVac: coordination
600 at 50/60 Hz purposes only . Based on 40°C ambient, cold start .
Connected
MaximumwithVdc:
four250
(4) feet of rated wire (60°C up to 125A, 75°C above 125A) per
terminal . Tested in open air .
Breaker rating
1,000 Continuous amperes Instantaneous trip amperes 1,000
15A Vac: 600 at 50/60 Hz
Maximum See curve
Maximum Vdc: 250
Interrupting Rating (UL/CSA Listed)
Breaker Symmetrical Rms amperes (KA) Amps (KA)
500 Breaker
type rating
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vac 125V 500
EHD 18 14 — 10 —
Continuous
FDB amperes
18 14 Instantaneous
14 10trip, amperes

300 FD 65 35 18 10 — 300
15A HFD 100 65 See curve
25 22
ED 65 — — — 10
200 1 Single-pole test data at 25˚C based on NEMA procedures 200
Interrupting
(AB 4-2003Rating (UL/CSA
) for verifying Listed)
performance of molded case
circuit breakers.
Symmetrical RMS amperes (kA)
Breaker Type @240Vac @480Vac @600Vac 250Vac
100 Maximum single- 100
pole trip times N 65 35 18 10
at 25°C 1 H 50
1 MINUTE

100 65 25 22

50

30
Notes:

20 1 Single-pole test data at 25°C based on NEMA procedures (AB


20 4-2003) for verifying
performance of molded case circuit breakers .

10 10

Minimum Maximum

5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03
Maximum interrupting time
.02 .02

.01 .01

Interrupting
.005 rating .005
determines
end of curve
.003 (see above) .003

.002 .002

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
500

1000

2000

3000

4000
5000
6000

8000
9000
700
200

300

400

600

800
900
100

CURRENT IN AMPERES

6 | 1-800-ASK-4WEG | www/weg/met Data subject to change without notice.


Molded-Case Circuit Breakers
Effective September 2015

UBW Time Current Curves


225 L 15A
CURRENT IN AMPERES

1000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000

2 HOURS
2 HOURS

Circuit breaker time/current curves


®
Series C F-frame circuit breakers
Series C F-frame circuit breakers
5,000 Catalog type FDC circuit breaker, two-, three- and four-poles. 5,000

1 HOUR
1 HOUR

For application and coordination purposes only.


For application
Based and coordination
on 40˚C ambient, purposes
cold start. Connected withonly .
four Based on 40°C ambient, cold start .
(4) feet of
3,000 Connected with
rated wire (60˚C upfour (4) feet
to 125A, of rated
75˚C above wire
125A) per(60°C up to 125A, 3,000
terminal. 75°C above 125A) per
Tested in open air with current in all poles.
terminal . Tested in open air .
2,000 Maximum Vac: 600 at 50/60 Hz 2,000
Maximum 600 at 50/60 Hz
Vac:250
Maximum Vdc:
Maximum Vdc: 250
Breaker rating
Continuous amperes Instantaneous trip amperes
1,000 Breaker
15A rating See curve 1,000

Continuous amperes
Interrupting rating Instantaneous trip, amperes
(UL/CSA listed)
Breaker Symmetrical Rms amperes (KA) Amps (KA)
15A
type @ 240 Vac @ 480 Vac See@curve
600 Vac 250 Vdc
500 500
FDC 200 100 35 22
Interrupting Rating (UL/CSA Listed)
Single-pole test data at 25˚C based on NEMA procedures
1

300
Symmetrical
(AB 4-2003) for verifying performanceRMS amperes
of molded case (kA) 300
Amps (KA)
Breaker Type
circuit breakers. @240Vac @480Vac @600Vac 250Vdc
200 L 200 100 35 200 22

Notes:

100 1 Single-pole test data at 25°C based on NEMA procedures100


(AB 4-2003) for verifying
Maximum single- performance of molded case circuit breakers .
pole trip times

1 MINUTE
1 MINUTE

at 25°C 1
50 50

30 30

20 .02 20

600V

10 .01 10
480V
Minimum Maximum
5 .005 5
240V

3 .003 3

TIME IN SECONDS
2 .002 2
100,000

200,000
10,000

20,000

30,000

40,000
50,000
60,000
70,000
80,000
90,000

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03
Maximum interrupting time
.02 .02

.01 .01

.005 .005

Interrupting
.003
rating
.003
determines
end of curve
.002 (see above) .002

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
1000

2000

3000

4000
5000
6000

8000
9000
500

700
200

300

400

600

800
900
100

CURRENT IN AMPERES

Figure 46. Type FDC 15A—Curve Number SC-5516-93A


Data subject to change without notice. UBW Technical Manual | 7
EATON www.eaton.com 49
Proof 1 — October 20, 2015 10:24 PM
Molded-Case Circuit Breakers

UBW Time Current Curves


225N/H CURRENT IN AMPERES
20A

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000
time/current curves

2 HOURS
2 HOURS

®
Series C F-frame circuit breakers
5,000 Catalog types ED, EHD, FDB, FD and HFD circuit breakers, two-, three- 5,000
Circuit Breaker time/current curves

1 HOUR
1 HOUR

3,000
Series 225 circuit breakers 3,000
Based on 40˚C ambient, cold start. Connected with four (4) feet of

Tested
2,000 2,000
For application and coordination purposes only . Based on 40°C ambient, cold start .
Maximum Vac: 600 at 50/60 Hz
Connected
Maximumwith four250
Vdc: (4) feet of rated wire (60°C up to 125A, 75°C above 125A) per
terminal . Tested in open air .
Breaker rating
1,000 Continuous amperes Instantaneous trip amperes 1,000
20A Vac: 600 at 50/60 Hz
Maximum See curve
Maximum Vdc: 250
Interrupting rating (UL/CSA listed)
Breaker Symmetrical Rms amperes (KA) Amps (KA)
500 Breaker
type rating
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc 500
EHD 18 14 — 10 —
Continuous
FDB amperes14
18 Instantaneous
14 10 trip, —amperes
300 FD 65 35 18 10 — 300
20A HFD 100 65 See curve
25 22 —
ED 65 — — — 10
200 1 Single-pole test data at 25˚C based on NEMA procedures 200
Interrupting
(AB 4-2003Rating (UL/CSA
) for verifying Listed)
performance of molded case
circuit breakers.
Symmetrical RMS amperes (kA)
Breaker Type @240Vac @480Vac @600Vac 250Vac
100 Maximum single- 100
pole trip times N
at 25°C 1 65 35 18 10
1 MINUTE

H 50
100 65 25 22
50

30 Notes: 30

20 1 Single-pole test data at 25°C based on NEMA procedures (AB


20 4-2003) for verifying
performance of molded case circuit breakers .

10 10

Minimum Maximum

5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03
Maximum interrupting time
.02 .02

.01 .01

Interrupting
.005 rating .005
determines
end of curve
.003 (see above) .003

.002 .002

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
500

1000

2000

3000

4000
5000
6000

8000
9000
700
200

300

400

600

800
900
100

CURRENT IN AMPERES

8 | 1-800-ASK-4WEG | www/weg/met Data subject to change without notice.


Proof 1 — October 20, 2015 10:24 PM
Series C
Molded-Case Circuit F-Frame
Breakers
UBW Time Current Curves
225 L CURRENT IN AMPERES
20A

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000
time/current curves

2 HOURS
2 HOURS

Series C F-frame circuit breakers

5,000 Catalog type FDC circuit breaker, two-, three- and four-poles. 5,000
Circuit breaker time/current curves

1 HOUR
1 HOUR

For application and coordination purposes only.


Series C40˚C
Based on F-frame circuit
ambient, cold breakers
start. Connected with four (4) feet of
3,000 rated wire (60˚C up to 125A, 75˚C above 125A) per terminal. 3,000

2,000 ForMaximum
application
Vac: and
600coordination
at 50/60 Hz purposes only . Based on 40°C ambient, cold start .
2,000
Connected with four
Maximum Vdc: 250 (4) feet of rated wire (60°C up to 125A, 75°C above 125A) per
terminal . Tested in open air .
Breaker rating
Continuous amperes Instantaneous trip amperes
1,000 Maximum
20A Vac: 600 at 50/60 Hzcurve
See 1,000
Maximum Vdc: 250
Interrupting rating (UL/CSA listed)
Breaker Symmetrical Rms amperes (KA) Amps (KA)
Breaker
type rating
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc
500 500
FDC 200 100 35 22
Continuous amperes Instantaneous trip, amperes
1 Single-pole test data at 25˚C based on NEMA procedures
300 20A See curve
(AB 4-2003) for verifying performance of molded case 300
circuit breakers.

200
Interrupting Rating (UL/CSA Listed)
200
Symmetrical RMS amperes (kA) Amps (KA)
Breaker Type @240Vac @480Vac @600Vac 250Vdc
L 200 100 35 22
100 Maximum single- 100
pole trip times
at 25°C 1 Notes:

1 MINUTE
1 MINUTE

1 Single-pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying
50 50
performance of molded case circuit breakers .

30 30

20 .02 20

600V

10 .01 10

Minimum Maximum 480V

5 .005 5
240V

3 .003 3

TIME IN SECONDS
2 .002 2
100,000

200,000
10,000

20,000

30,000

40,000
50,000
60,000
70,000
80,000
90,000

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03
Maximum interrupting time
.02 .02

.01 .01

.005 .005

.003 Interrupting .003


rating
.002
determines
.002
end of curve
(see above)

.001 .001
10000
7000
1000

2000

3000

4000
5000
6000

8000
9000
500

700
200

300

400

600

800
900
100

5 6 7 8 9 10 20 30 40 50 60 70 8090

CURRENT IN AMPERES

Figure 47. Type FDC 20A—Curve Number SC-5517-93A

Data subject to change without notice. UBW Technical Manual | 9


50 EATON www.eaton.com
Molded-Case Circuit Breakers

Time Current Curves


225 N., H.
CURRENT IN AMPERES
30A

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000
Circuit breaker time/current curves

2 HOURS
2 HOURS

®
Series C F-frame circuit breakers
5,000 Catalog types ED, EHD, FDB, FD and HFD circuit breakers, two-, three- 5,000
Circuit
andbreaker
four-poles. time/current curves

1 HOUR
1 HOUR

3,000
225 circuit breakers and coordination purposes only.
For application
3,000
Based on 40˚C ambient, cold start. Connected with four (4) feet of
125A, 75˚C above 125A) per terminal.
Tested in open air with current in all poles.
2,000 2,000
For application and coordination purposes only . Based on 40°C ambient, cold start .
Maximum Vac: 600 at 50/60 Hz
Connected withVdc:
Maximum four 250
(4) feet of rated wire (60°C up to 125A, 75°C above 125A) per
terminal . Tested in open air .
Breaker Rating
1,000 Continuous amperes Instantaneous trip amperes 1,000
30A Vac: 600 at 50/60 HzSee curve
Maximum
Maximum Vdc: 250
Interrupting rating (UL/CSA listed)
Breaker Symmetrical RMS amperes (KA) Amps (KA)
500 Breaker
typerating
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc 500
EHD 18 14 — 10 —
Continuous
FDB amperes
18 14 Instantaneous
14 10 trip, amperes

300 FD 65 35 18 10 — 300
30A HFD 100 65 See curve25 22 —
ED 65 — — — 10
200 1 Single-pole test data at 25˚C based on NEMA procedures 200
Interrupting Rating
(AB 4-2003 (UL/CSA
) for verifying Listed)
performance of molded case
circuit breakers.
Symmetrical RMS amperes (kA)
Breaker Type @240Vac @480Vac @600Vac 250Vac
100 Maximum single- 100
pole trip times N 65 35 18 10
at 25°C 1

1 MINUTE
1 MINUTE

50
H 100 65 25 22
50

30 Notes: 30

20 1 Single-pole test data at 25°C based on NEMA procedures (AB


20 4-2003) for verifying
performance of molded case circuit breakers .

10 10

Minimum Maximum

5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

Maximum interrupting time


.02 .02

.01 .01

Interrupting
.005 rating .005
determines
end of curve
.003 (see above) .003

.002 .002

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
500

1000

2000

3000

4000
5000
6000

8000
9000
700
200

300

400

600

800
900
100

CURRENT IN AMPERES

10 | 1-800-ASK-4WEG | www/weg/met Data subject to change without notice.


Proof 1 — October 20, 2015 10:24 PM
Series C
Molded-Case Circuit Breakers
F-Frame

UBW Time Current Curves CURRENT IN AMPERES


30A
225 L

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000
time/current curves

2 HOURS
2 HOURS

Series C F-frame circuit breakers

5,000 Catalog type FDC circuit breaker, two-, three- and four-poles. 5,000
Circuit breaker time/current curves

1 HOUR
1 HOUR

For application and coordination purposes only.


Series
BasedC onF-frame
40˚C ambient,circuit
cold start.breakers
Connected with four (4) feet of
3,000 rated wire (60˚C up to 125A, 75˚C above 125A) per terminal. 3,000

2,000 For application


Maximum Vac:and600coordination
at 50/60 Hz purposes only . Based on 40°C 2,000
ambient, cold start .
Connected
Maximumwith
Vdc: four
250(4) feet of rated wire (60°C up to 125A, 75°C above 125A) per
terminal . Tested in open air .
Breaker rating
Continuous amperes Instantaneous trip amperes
1,000 Maximum
30A Vac: 600 at 50/60 See
Hz curve 1,000
Maximum Vdc: 250
Interrupting rating (UL/CSA listed)
Breaker Symmetrical Rms amperes (KA) Amps (KA )
Breaker
type
rating
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc
500 500
Continuous
FDC 200amperes100 Instantaneous
35 trip,22amperes
1 Single-pole test data at 25˚C based on NEMA procedures
30A See curve
(AB 4-2003) for verifying performance of molded case
300 300
circuit breakers.
Interrupting Rating (UL/CSA Listed)
200 200
Symmetrical RMS amperes (kA) Amps (KA)
Breaker Type @240Vac @480Vac @600Vac 250Vdc
L 200 100 35 22
100 Maximum single- 100
pole trip times Notes:
at 25°C 1

1 MINUTE
1 MINUTE

1 Single-pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying
50 performance of molded case circuit breakers . 50

30 30

20 .02 20

600V

10 .01 10
480V
Minimum Maximum

5 .005 5
240V

3 .003 3

TIME IN SECONDS
2 .002 2
100,000

200,000
10,000

20,000

30,000

40,000
50,000
60,000
70,000
80,000
90,000

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03
Maximum interrupting time
.02 .02

.01 .01

.005 .005

.003 .003
Interrupting
rating
.002 determines .002
end of curve
(see above)

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
1000

2000

3000

4000
5000
6000

8000
9000
500

700
200

300

400

600

800
900
100

CURRENT IN AMPERES

Figure 49. Type FDC 30A—Curve Number SC-5519-93A

Data subject to change without notice. UBW Technical Manual | 11


52 EATON www.eaton.com
Molded-Case Circuit Breakers

Time Current Curves


225 N/H CURRENT IN AMPERES
40A

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000
Circuit breaker time/current curves

2 HOURS
2 HOURS

5,000 Catalog types ED, EHD, FDB, FD and HFD circuit breakers, two-, three - 5,000

1 HOUR
1 HOUR

Circuit breaker time/current curves


and four-poles.

For application and coordination purposes only.


3,000 Series C F-frame circuit breakers
Based on 40˚C ambient, cold start. Connected with four (4) feet of 3,000
rated wire (60˚C up to 125A, 75˚C above 125A) per terminal.
Catalog Types: ED, HED FDB, FD and HFD circuit breakers, two-, three- and four-pole .
Tested in open air with current in all poles.
2,000 2,000
For application and 600
Maximum Vac: coordination
at 50/60 Hz purposes only . Based on 40°C ambient, cold start .
Connected
Maximum with
Vdc:four
250(4) feet of rated wire (60°C up to 125A, 75°C above 125A) per
terminal . Tested in open air .
Breaker Rating
1,000 Continuous amperes Instantaneous trip amperes 1,000
Maximum
40A Vac: 600 at 50/60 See
Hz curve
Maximum Vdc: 250
Interrupting rating (UL/CSA listed)
Breaker Symmetrical Rms amperes (KA) Amps (KA)
500 Breaker
type rating
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc 500

EHD 18 14 — 10 —
Continuous
FDB 18amperes 14 Instantaneous
14 10 trip, amperes

300 FD 65 35 18 10 — 300
40A HFD 100 65 See curve
25 22 —
ED 65 — — — 10
200 1 Single-pole test data at 25˚C based on NEMA procedures 200
Interrupting
(AB 4-2003Rating (UL/CSA
) for verifying Listed)
performance of molded case
circuit breakers.
Symmetrical RMS amperes (kA)
Maximum single- Breaker Type @240Vac @480Vac @600Vac 250Vac
100 100
pole trip times
at 25°C 1 N 65 35 18 10

1 MINUTE
1 MINUTE

50
H 100 65 25 22
50

30 30
Notes:

20 1 Single-pole test data at 25°C based on NEMA procedures 20


(AB 4-2003) for verifying
performance of molded case circuit breakers .

10 10

Minimum Maximum

5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

Maximum interrupting time


.02 .02

.01 .01

Interrupting
.005 rating .005
determines
end of curve
.003 (see above) .003

.002 .002

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
500

1000

2000

3000

4000
5000
6000

8000
9000
700
200

300

400

600

800
900
100

CURRENT IN AMPERES

Figure 33. Types ED, EHD, FDB, FD, and HFD 40A—Curve Number SC-4139-87B
12 | 1-800-ASK-4WEG | www/weg/met Data subject to change without notice.
36 EATON www.eaton.com
Molded-Case Circuit Breakers

UBW Time Current Curves


225 L CURRENT IN AMPERES
40A

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000
time/current curves

2 HOURS
2 HOURS

Series C F-frame circuit breakers

5,000 Catalog type FDC circuit breaker, two-, three- and four-poles. 5,000
Circuit breaker time/current curves

1 HOUR
1 HOUR

225 circuit breaker cold start. Connected with four (4) feet of
3,000 75˚C above 125A) per terminal. 3,000

2,000
For application and coordination purposes only . Based on 40°C 2,000
ambient, cold start .
Maximum Vac: 600 at 50/60 Hz
Connected
MaximumwithVdc: four
250 (4) feet of rated wire (60°C up to 125A, 75°C above 125A) per
terminal . Tested in open air .
Breaker rating
Continuous amperes
1,000 Maximum Vac: 600 at 50/60 Instantaneous
Hz trip amperes
1,000
40A See curve
Maximum Vdc: 250
Interrupting rating (UL/CSA listed)
Breaker
Breaker rating
Symmetrical Rms amperes (KA) Amps (KA)
type @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc
500 Continuous
FDC 200 amperes100 Instantaneous
35 trip,22amperes500

40A1 See curve


Single-pole test data at 25˚C based on NEMA procedures
300 (AB 4-2003) for verifying performance of molded case 300
circuit breakers.
Interrupting Rating (UL/CSA Listed)
200 Symmetrical RMS amperes (kA) Amps
200 (KA)
Breaker Type @240Vac @480Vac @600Vac 250Vdc
L 200 100 35 22
Maximum single-
100 100
pole trip times Notes:
at 25°C 1

1 MINUTE
1 MINUTE

1 Single-pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying
performance of molded case circuit breakers .
50 50

30 30

20 .02 20

600V

10 .01 10
480V
Minimum Maximum

5 240V .005 5

3 .003 3

TIME IN SECONDS
2 .002 2
100,000

200,000
10,000

20,000

30,000

40,000
50,000
60,000
70,000
80,000
90,000

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03
Maximum interrupting time
.02 .02

.01 .01

.005 .005

.003 .003
Interrupting
rating
.002
determines .002
end of curve
(see above)

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
1000

2000

3000

4000
5000
6000

8000
9000
500

700
200

300

400

600

800
900
100

CURRENT IN AMPERES

Data subject to change without notice. UBW Technical Manual | 13


Figure 51.Type FDC 40A—Curve Number SC-5521-93A
Molded-Case Circuit Breakers

Time Current Curves


225 N., H.
CURRENT IN AMPERES
50A

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000
time/current curves

2 HOURS
2 HOURS

circuit breakers
5,000 Catalog types ED, EHD, FDB, FD and HFD circuit breakers, two-, three- 5,000
Circuit breaker time/current curves

1 HOUR
1 HOUR

and four-poles.

225 Circuit breaker


3,000 Based on 40˚C ambient, cold start. Connected with four (4) feet of 3,000

Tested in open air with current in all poles.


2,000 2,000
For application and coordination purposes only . Based on 40°C ambient, cold start .
Maximum Vac: 600 at 50/60 Hz
Connected
Maximum Vdc:with250four (4) feet of rated wire (60°C up to 125A, 75°C above 125A) per
terminal . Tested in open air .
Breaker rating
1,000 Continuous amperes Instantaneous trip amperes 1,000
Maximum
50A
Vac: 600 at 50/60 Hz
See curve
Maximum Vdc: 250
Interrupting rating (UL/CSA listed)
Breaker Symmetrical Rms amperes (KA) Amps (KA)
500 Breaker
type @ 240rating
Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc 500
EHD 18 14 -- 10 —
Continuous
FDB 18
amperes
14 14
Instantaneous
10 —
trip, amperes
300 FD 65 35 18 10 — 300
50A
HFD 100 65 25See curve 22 —
ED 65 — — — 10
200 1 Single-pole test data at 25˚C based on NEMA procedures 200
Interrupting Rating
(AB 4-2003) for verifying (UL/CSA
performance Listed)
of molded case
Maximum single-
pole trip times circuit breakers. Symmetrical RMS amperes (kA)
at 25°C 1 Breaker Type @240Vac @480Vac @600Vac 250Vac
100 100
FD 65 35 18 10

1 MINUTE
1 MINUTE

H 100 65 25 50 22
50

30 Notes:

20 1 Single-pole test data at 25°C based on NEMA procedures


20 (AB 4-2003) for verifying
performance of molded case circuit breakers .
Minimum Maximum
10 10

5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

Maximum interrupting time


.02 .02

.01 .01

Interrupting
.005 rating .005
determines
end of curve
.003 (see above) .003

.002 .002

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
500

1000

2000

3000

4000
5000
6000

8000
9000
700
200

300

400

600

800
900
100

CURRENT IN AMPERES

14 | 1-800-ASK-4WEG | www/weg/met Data subject to change without notice.


Proof 1 — October 20, 2015 10:24 PM
Series C
Molded-Case Circuit Breakers
F-Frame

UBW Time Current Curves


CURRENT IN AMPERES
225L 50A

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000
Circuit breaker time/current curves

2 HOURS
2 HOURS

circuit breakers

5,000 Catalog type FDC circuit breaker, two-, three- and four-poles. 5,000
Circuit breaker time/current curves

1 HOUR
1 HOUR

For application and coordination purposes only.


225 circuit breakers cold start. Connected with four (4) feet of
3,000 rated wire (60˚C up to 125A, 75˚C above 125A) per terminal. 3,000

2,000 ForMaximum
application
Vac:and
600coordination
purposes only . Based on
at 50/60 Hz cold start . 2,000
40°C ambient,
Maximum Vdc: 250
Connected with four (4) feet of rated wire (60°C up to 125A, 75°C above 125A) per
terminal .
BreakerTested
rating in open air .
Continuous amperes Instantaneous trip amperes
1,000 1,000
50A
Maximum Vac: 600 at 50/60See
Hzcurve
Maximum Vdc: 250 (UL/CSA listed)
Interrupting rating
Breaker Symmetrical Rms amperes (KA) Amps (KA)
type @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc
Breaker rating 500
500
FDC 200 100 35 22
Continuous amperes Instantaneous trip, amperes
1 Single-pole test data at 25˚C based on NEMA procedures
300 50A (AB 4-2003) for verifying performance of molded case
See curve 300
circuit breakers.

200 Interrupting Rating (UL/CSA Listed) 200


Maximum single- Symmetrical RMS amperes (kA) Amps (KA)
pole trip times Breaker Type @240Vac @480Vac @600Vac 250Vdc
at 25°C 1
100 L 200 100 35 100 22

Notes:

1 MINUTE
1 MINUTE

50 1 Single-pole test data at 25°C based on NEMA procedures 50


(AB 4-2003) for verifying
performance of molded case circuit breakers .

30 30

20 .02 20

600V
Minimum Maximum
10 .01 10
480V

5 .005 5
240V

3 .003 3

TIME IN SECONDS
2 .002 2
100,000

200,000
10,000

20,000

30,000

40,000
50,000
60,000
70,000
80,000
90,000

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03
Maximum interrupting time
.02 .02

.01 .01

.005 .005

.003 Interrupting .003


rating
determines
.002 end of curve .002
(see above)

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
1000

2000

3000

4000
5000
6000

8000
9000
500

700
200

300

400

600

800
900
100

CURRENT IN AMPERES

Figure 53. Type FDC 50—Curve Number SC-5523-93A

Data subject to change without notice. UBW Technical Manual | 15


56 EATON www.eaton.com
Molded-Case Circuit Breakers

Time Current Curves


225 N., H. CURRENT IN AMPERES
60A

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000
2 HOURS Circuit beake time/current curves

2 HOURS
5,000 Catalog types ED, EHD, FDB, FD and HFD circuit breakers, two-, three- 5,000
1 HOUR

Circuit
and breaker time/current curves
four-poles.

1 HOUR
3,000
225 circuit breakers 3,000
Based on 40˚C ambient, cold start. Connected with four (4) feet of
125A, 75˚C above 125A) per terminal.
oen air with current in all poles.
2,000 2,000
For application
Maximum Vac: 600and coordination
at 50/60 Hz purposes only . Based on 40°C ambient, cold start .
Connected
Maximum Vdc: with
250 four (4) feet of rated wire (60°C up to 125A, 75°C above 125A) per
terminal . Tested in open air .
Breaker rating
1,000 Continuous amperes Instantaneous trip amperes 1,000
Maximum Vac:
60A 600 at 50/60 Hz
See curve
Maximum Vdc: 250
Interrupting rating (UL/CSA listed)
Breaker Symmetrical Rms amperes (KA) Amps (KA)
500 Breaker
type rating
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc 500
EHD 18 14 — 10 —
Continuous
FDB 18 amperes
14 14 Instantaneous
10 —trip, amperes
300 FD 65 35 18 10 — 300
60A 100
HFD 65 25See curve 22 —
ED 65 — — — 10
200 1 Single-pole test data at 25˚C based on NEMA procedures 200
Maximum single-
Interrupting Rating
(AB 4-2003) for verifying (UL/CSA
performance Listed)
of molded case
pole trip times circuit breakers. Symmetrical RMS amperes (kA)
at 25°C 1 Breaker Type @240Vac @480Vac @600Vac 250Vac

1 MINUTE
100 100
N 65 35 18 10
H 50
1 MINUTE

100 65 25 22

50

30 Notes: 30

20 1 Single-pole test data at 25°C based on NEMA procedures


20 (AB 4-2003) for verifying
performance of molded case circuit breakers .
Minimum Maximum
10 10

5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

Maximum interrupting time


.02 .02

.01 .01

Interrupting
.005 rating .005
determines
end of curve
.003 (see above) .003

.002 .002

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
500

1000

2000

3000

4000
5000
6000

8000
9000
700
200

300

400

600

800
900
100

CURRENT IN AMPERES

16 | 1-800-ASK-4WEG | www/weg/met Data subject to change without notice.


Proof 1 — October 20, 2015 10:24 PM
Series C Molded-Case Circuit Breakers
F-Frame Effective September 2015

UBW Time Current Curves CURRENT IN AMPERES


60A
225L

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000
Circuit breaker time/current curves

2 HOURS
2 HOURS

®
Series C F-frame circuit breakers

5,000 Catalog type FDC circuit breaker, two-, three- and four-poles. 5,000
Circuit breaker time/current curves

1 HOUR
1 HOUR

For application and coordination purposes only.


UBW 225L circuit breakers
cold start. Connected with four (4) feet of
3,000 rated wire (60˚C up to 125A, 75˚C above 125A) per terminal. 3,000

2,000 For application and 600


Maximum Vac: coordination
at 50/60 Hz purposes only . Based on 40°C 2,000
ambient, cold start .
Connected
Maximum with
Vdc:four
250(4) feet of rated wire (60°C up to 125A, 75°C above 125A) per
terminal . Tested in open air .
Breaker rating
Continuous amperes Instantaneous trip amperes
1,000 Maximum
60A Vac: 600 at 50/60 Hz
See curve 1,000
Maximum Vdc: 250
Interrupting rating (UL/CSA listed)
Breaker Symmetrical Rms amperes (KA) Amps (KA)
Breaker
type rating
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc
500 500
FDC 200
Continuous amperes 100 35
Instantaneous trip,22amperes
1 Single-pole test data at 25˚C based on NEMA procedures
300
60A See curve of molded case
(AB 4-2003) for verifying performance 300
circuit breakers.
Maximum single- Interrupting Rating (UL/CSA Listed)
200 200
pole trip times Symmetrical RMS amperes (kA) Amps (KA)
at 25°C 1
Breaker Type @240Vac @480Vac @600Vac 250Vdc
L 200 100 35 22
100 100
Notes:

1 MINUTE
1 MINUTE

1 Single-pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying
50 performance of molded case circuit breakers . 50

30 30

Minimum Maximum
20 .02 20

600V

10 .01 10
480V

5 .005 5
240V

3 .003 3

TIME IN SECONDS
2 .002 2
100,000

200,000
10,000

20,000

30,000

40,000
50,000
60,000
70,000
80,000
90,000

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

Maximum interrupting time


.02 .02

.01 .01

.005 .005

.003
Interrupting
.003
rating
determines
.002 end of curve .002
(see above)

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
1000

2000

3000

4000
5000
6000

8000
9000
500

700
200

300

400

600

800
900
100

CURRENT IN AMPERES

Figure 54. Type FDC 60A—Curve Number SC-5524-93A


Data subject to change without notice. UBW Technical Manual | 17
EATON www.eaton.com 57
Molded-Case Circuit Breakers

Time Current Curves


225 N., H. CURRENT IN AMPERES
70A

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000
Circuit breaker time/current curves

2 HOURS
2 HOURS

Series
5,000 Catalog types ED, EHD, FDB, FD and HFD circuit breakers, two-, three- 5,000
andCircuit
four-poles. breaker time/current curves

1 HOUR
1 HOUR

3,000
225 circuit breakers 3,000
Based on 40˚C ambient, cold start. Connected with four (4) feet of
rated wire (60˚C
Tested in
2,000 2,000
For application and coordination purposes only . Based on 40°C ambient, cold start .
Maximum Vac: 600 at 50/60 Hz
Connected
Maximum with four (4)
Vdc: 250 feet of rated wire (60°C up to 125A, 75°C above 125A) per
terminal . Tested in open air .
Breaker rating
1,000 Continuous amperes Instantaneous trip amperes 1,000
70A
Maximum Vac:600 at 50/60 Hz
See curve
Maximum Vdc: 250
Interrupting rating (UL/CSA listed)
Breaker Symmetrical Rms amperes (KA) Amps (KA)
500 type Breaker
@ 240 Vac rating
@ 480 Vac @ 600Vac 250 Vdc 125 Vdc 500
EHD 18 14 — 10 —
FDB
Continuous
18 14
amperes 14
Instantaneous
10 —
trip, amperes
300 FD 65 35 18 10 — 300
HFD 70A 100 65 25 See
22 curve —
ED 65 — — 10
200 1 Single-pole test data at 25˚C based on NEMA procedures 200
Interrupting
(AB Rating
4-2003) for verifying (UL/CSA
performance Listed)
of molded case
Maximum single-
pole trip times circuit breakers. Symmetrical RMS amperes (kA)
at 25°C 1 Breaker Type @240Vac @480Vac @600Vac 250Vac
100 100
N 65 35 18 10
H 100 65 25 50 22

1 MINUTE
1 MINUTE

50

30 Notes: 30

20 1 Single-pole test data at 25°C based on NEMA procedures


20 (AB 4-2003) for verifying
performance of molded case circuit breakers .
Minimum Maximum
10 10

5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

Maximum interrupting time


.02 .02

.01 .01

Interrupting
.005 rating .005
determines
end of curve
.003 (see above) .003

.002 .002

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
500

1000

2000

3000

4000
5000
6000

8000
9000
700
200

300

400

600

800
900
100

CURRENT IN AMPERES

18 | 1-800-ASK-4WEG | www/weg/met Data subject to change without notice.


Proof 1 — October 20, 2015 10:24 PM
Series C
Molded-Case Circuit Breakers
F-Frame

UBW Time Current Curves


CURRENT IN AMPERES
225L 70A

100,000
20,000

30,000

40,000
50,000
60,000
70,000
80,000
90,000
10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
50 60 70 80 90
10,000
Circuit breaker time/current curves

2 HOURS
2 HOURS

circuit breakers

5,000 Catalog type FDC circuit breaker, two-, three- and four-poles. 5,000
Circuit breaker time/current curves

1 HOUR
1 HOUR

For application and coordination purposes only.


225 L circuit breakers (4) feet of
3,000 125A, 3,000

2,000 For application


Maximum Vac:and600coordination
at 50/60 Hz purposes only . Based on 40°C2,000
ambient,
cold start .
Maximumwith
Connected 250 (4) feet of rated wire
Vdc: four (60°C up to 125A, 75°C above 125A) per
terminal .
BreakerTested
rating in open air .
Continuous amperes Instantaneous trip amperes
1,000 1,000
Maximum
70A Vac: 600 at 50/60 See
Hz curve
Maximum Vdc: 250
Interrupting rating (UL/CSA listed)
Breaker Symmetrical Rms amperes (KA) Amps (KA)
Breaker
type rating
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc
500 500
FDC 200 100 35 22
Continuous amperes Instantaneous trip, amperes
1 Single-pole test data at 25˚C based on NEMA procedures
300 70A See curveof molded case
(AB 4-2003) for verifying performance 300
circuit breakers.
Maximum single- Interrupting Rating (UL/CSA Listed)
200 200
pole trip times
at 25°C 1 Symmetrical RMS amperes (kA) Amps (KA)
Breaker Type @240Vac @480Vac @600Vac 250Vdc
100
L 200 100 35 100 22

Notes:

1 MINUTE
1 MINUTE

50 1 Single-pole test data at 25°C based on NEMA procedures (AB


50 4-2003) for verifying
performance of molded case circuit breakers .

30 30

20 20

10 10

5 5

3 3

TIME IN SECONDS
Minimum Maximum
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03
Maximum interrupting ti me
.02 .02

600V

.01 .01
480V

.005 .005
240V
.003 .003

.002 .002

.001 .001
50 60 70 8090
100,000

200,000
10000

20,000

30,000

40,000
50,000
60,000
70,000
80,000
90,000
7000
1000

2000

3000

4000
5000
6000

8000
9000
500

700
200

300

400

600

800
900
100

CURRENT IN AMPERES

Figure 55. Type FDC 70A—Curve Number SC-5525-93A

Data subject to change without notice. UBW Technical Manual | 19


58 EATON www.eaton.com
Molded-Case Circuit Breakers

Time Current Curves


225 N., H.
CURRENT IN AMPERES
80A

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000

2 HOURS
2 HOURS

Series circuit breakers


5,000 Catalog types ED, EHD, FDB, FD and HFD circuit breakers, two-, three- 5,000

1 HOUR
Circuit
four-poles.breaker time/current curves
1 HOUR

and

3,000
C F-frame circuit breakers 3,000
Based on 40˚C ambient, cold start. Connected with four (4) feet of
rated wire (60˚C
open air with current in all poles.
2,000 2,000
For application
Maximum Vac: 600 atand coordination
50/60 Hz purposes only . Based on 40°C ambient, cold start .
Connected
Maximum with four (4) feet of rated wire
Vdc: 250 (60°C up to 125A, 75°C above 125A) per
terminal . Tested in open air .
Breaker rating
1,000 Continuous amperes Instantaneous trip amperes 1,000
80AMaximum Vac: 600 atSee
50/60
curve Hz
Maximum Vdc: 250
Interrupting rating (UL/CSA listed)
Breaker Symmetrical Rms amperes (KA) Amps (KA)
500 typeBreaker rating
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc 500
EHD 18 14 — 10 —
FDB Continuous
18 amperes
14 14 Instantaneous
10 — trip, amperes
300 FD 65 35 18 10 — 300
HFD80A 100 65 25 See curve
22 —
ED 65 — — — 10
200 Maximum single- 1 Single-pole test data at 25˚C based on NEMA procedures 200
pole trip times Interrupting
(AB Rating
4-2003) for verifying (UL/CSA
performance Listed)
of molded case
at 25°C 1 circuit breakers.
Symmetrical RMS amperes (kA)
Breaker Type @240Vac @480Vac @600Vac 250Vac

1 MINUTE
100 100
N 65 35 18 10
50
H 100 65 25 22
1 MINUTE

50

30
Notes: 30

20 1 Single-pole test data at 25°C based on NEMA procedures


20 (AB 4-2003) for verifying
performance of molded case circuit breakers .

10 10

5 5

3 3
Minimum Maximum

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

Maximum interrupting time


.02 .02

.01 .01

Interrupting
.005 rating .005
determines
end of curve
.003 (see above) .003

.002 .002

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
500

1000

2000

3000

4000
5000
6000

8000
9000
700
200

300

400

600

800
900
100

CURRENT IN AMPERES

20 | 1-800-ASK-4WEG | www/weg/met Data subject to change without notice.


Proof 1 — October 20, 2015 10:24 PM
Series C
F-Frame Molded-Case Circuit
Effective Breakers
September 2015

UBW Time Current Curves CURRENT IN AMPERES


80A

100,000
225L

20,000

30,000

40,000
50,000
60,000
70,000
80,000
90,000
10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
50 60 70 80 90
10,000
Circuit breaker time/current curves

2 HOURS
2 HOURS
Series C F-frame circuit breaker

5,000 Catalog type FDC circuit breaker, two-, three- and four-poles. 5,000
Circuit breaker time/current curves

1 HOUR
1 HOUR

and coordination purposes only.


UBW 225L current curves cold start. Connected with four (4) feet of
3,000 rated wire (60˚C up to 125A, 75˚C above 125A) per terminal. 3,000
Tested in open air with current in all poles.

2,000 For application and coordination


Maximum Vac: 600 at 50/60 Hzpurposes only . Based on 40°C ambient,
2,000 cold start .
Connected
Maximumwith four250
Vdc: (4) feet of rated wire (60°C up to 125A, 75°C above 125A) per
terminal . Tested in open air .
Breaker rating
Continuous amperes Instantaneous trip amperes
1,000 80A Vac: 600 at 50/60 Hz
Maximum See curve 1,000
Maximum Vdc: 250
Interrupting rating (UL/CSA listed)
Breaker Symmetrical Rms amperes (KA) Amps (KA)
Breaker
type rating
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc
500 500
FDC 200 100 3522
Continuous amperes Instantaneous trip, amperes
1 Single-pole test data at 25˚C based on NEMA procedures
300
80A See curve of molded case
(AB 4-2003) for verifying performance 300
circuit breakers.
Interrupting Rating (UL/CSA Listed)
200 200
Maximum single- Symmetrical RMS amperes (kA) Amps (KA)
pole trip times
at 25°C 1 Breaker Type @240Vac @480Vac @600Vac 250Vdc
L 200 100 35 22
100 100
Notes:

1 MINUTE
1 MINUTE

1 Single-pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying
50 performance of molded case circuit breakers . 50

30 30

20 20

10 10

5 5

3 3

TIME IN SECONDS
2 2
Minimum Maximum

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03
Maximum interrupting time
.02 .02

600V

.01 .01
480V

.005 .005
240V
.003 .003

.002 .002

.001 .001
50 60 70 8090
100,000

200,000
10000

20,000

30,000

40,000
50,000
60,000
70,000
80,000
90,000
7000
1000

2000

3000

4000
5000
6000

8000
9000
500

700
200

300

400

600

800
900
100

CURRENT IN AMPERES

Figure 56. Type FDC 80A—Curve Number SC-5526-93A

Data subject to change without notice. UBW Technical Manual | 21


EATON www.eaton.com 59
Molded-Case Circuit Breakers

Time Current Curves


225 N., H. CURRENT IN AMPERES
90A

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000

2 HOURS
2 HOURS

5,000 5,000
Circuit breaker time/current curves

1 HOUR
1 HOUR

225 circuit breakers


3,000 3,000

2,000 2,000
For application and coordination purposes only . Based on 40°C ambient, cold start .
600 at 50/60 Hz
Connected with
250 four (4) feet of rated wire (60°C up to 125A, 75°C above 125A) per
terminal . Tested in open air .
1,000 1,000
Maximum Vac: 600 at 50/60 Hz
Maximum Vdc: 250
Symmetrical Rms amperes (KA) Amps (KA)
500 Breaker
@ 240 rating
Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc 500
18 14 — 10 —
Continuous
18
amperes
14 14
Instantaneous
10 —
trip, amperes
300 65 35 18 10 — 300
90A 100 65 25 See curve22 —

200 200
Maximum single- Interrupting Rating (UL/CSA Listed)
pole trip times ) for verifying performance of molded case
at 25°C 1 Symmetrical RMS amperes (kA)
Breaker Type @240Vac @480Vac @600Vac 250Vac
100 100

1 MINUTE
1 MINUTE

N 65 35 18 10
50 H 100 65 25 50 22

30 Notes: 30

20 1 Single-pole test data at 25°C based on NEMA procedures


20 (AB 4-2003) for verifying
performance of molded case circuit breakers .

10 10

Minimum Maximum
5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

Maximum interrupting time


.02 .02

.01 .01

Interrupting
.005 rating .005
determines
end of curve
.003 (see above) .003

.002 .002

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
500

1000

2000

3000

4000
5000
6000

8000
9000
700
200

300

400

600

800
900
100

CURRENT IN AMPERES

22 | 1-800-ASK-4WEG | www/weg/met Data subject to change without notice.


Proof 1 — October 20, 2015 10:24 PM
Series C
Molded-Case Circuit Breakers
F-Frame

Time Current Curves


225L 90A
CURRENT IN AMPERES

100,000
20,000

30,000

40,000
50,000
60,000
70,000
80,000
90,000
10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
50 60 70 80 90
10,000
Circuit breaker time/current curves

2 HOURS
2 HOURS

Series C F-frame circuit breakers

5,000 Catalog type FDC circuit breaker, two-, three- and four-poles. 5,000
Circuit breaker time/current curves

1 HOUR
1 HOUR

For application and coordination purposes only.


225L Circuit Breakers (4) feet of
3,000 rated wire (60˚C up to 125A, 75˚C above 125A) per terminal. 3,000

2,000 For application andVac:


Maximum coordination purposes
600 at 50/60 Hz only . Based on 40°C ambient,
2,000cold start .
Connected with four
Maximum (4) 250
Vdc: feet of rated wire (60°C up to 125A, 75°C above 125A) per
terminal . Tested in open air .
Breaker rating
Continuous amperes Instantaneous trip amperes
1,000 Maximum Vac: 600 at 50/60 Hz
100A See curve 1,000
Maximum Vdc: 250
Interrupting rating (UL/CSA listed)
Breaker Symmetrical Rms amperes (KA) Amps (KA)
Breakertype
rating @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc
500 500
FDC
Continuous 200
amperes 100 35 trip,
Instantaneous 22
amperes
1 Single-pole test data at 25˚C based on NEMA procedures
90A Seeperformance
(AB 4-2003) for verifying curve of molded case 300
300
circuit breakers.
Interrupting Rating (UL/CSA Listed)
200
Maximum single- Symmetrical RMS amperes (kA) Amps200(KA)
pole trip times
at 25°C 1 Breaker Type @240Vac @480Vac @600Vac 250Vdc
L 200 100 35 22
100 100
Notes:

1 MINUTE
1 MINUTE

1 Single-pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying
50 performance of molded case circuit breakers . 50

30 30

20 20

10 10

Minimum Maximum
5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

Maximum interrupting time


.02 .02

600V

.01 .01
480V

.005 .005
240V
.003 .003

.002 .002

.001 .001
50 60 70 8090
100,000

200,000
10000

20,000

30,000

40,000
50,000
60,000
70,000
80,000
90,000
7000
1000

2000

3000

4000
5000
6000

8000
9000
500

700
200

300

400

600

800
900
100

CURRENT IN AMPERES

Figure 57. Type FDC 90A—Curve Number SC-5527-93A


Data subject to change without notice. UBW Technical Manual | 23
60 EATON www.eaton.com
Molded-Case Circuit Breakers

Time Current Curves


225 N., H. 100A
CURRENT IN AMPERES

1000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000
2 HOURS

2 HOURS
Circuit® breaker time/current curves
Series C F-frame circuit breakers
225 circuit breakers
5,000
1 HOUR

1 HOUR
3,000 Based on
rated wire (60˚C up to 125A, 75˚C above 125A) per terminal.
For application
Tested in open air and coordination
with current purposes only . Based on 40°C ambient, cold start .
in all poles.
2,000 Connected
Maximum Vac: with four
600 (4) feet
at 50/60 Hz of rated wire (60°C up to 125A, 2,00075°C above 125A) per
Maximum Vdc: 250
terminal . Tested in open air .
Breaker rating
Continuous amperes Instantaneous trip amperes
Maximum
100A Vac: 600 at 50/60 Hz
See curve
1,000 Maximum Vdc: 250 1,000
Interrupting rating (UL/CSA listed)
Breaker Symmetrical Rms amperes (KA) Amps (KA)
Breaker
type rating
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc
ED 65 — — — 10
500 Continuous
EDB 22 amperes— —Instantaneous
— trip,
10 amperes
500
EDS 42 — — — 10
EDH 100 — — — 10
100A
EDC 200 — —See curve — 10
EHD 18 14 — 10 — 300
300 FDB 18 14 14 10 —
FD
Interrupting 65 Rating35 (UL/CSA 18 Listed)
10 —
HFD 100 65 25 22 —
200
Maximum single- Symmetrical RMS amperes
1 Single-pole test data at 25˚C based on NEMA procedures (kA) 200

pole trip times Breaker


(AB 4-2003Type @240Vac
) for verifying @480Vac
performance of molded case @600Vac 250Vac
at 25°C 1 circuit breakers.
N 30
65 35 18 10
100 H 100 65 25 22
20
Notes:
1 MINUTE

50 1 Single-pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying
performance of molded case circuit breakers . 10

30

20

10

Minimum Maximum
5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

Maximum interrupting time


.02 .02

.01 .01

Interrupting
.005 rating .005
determines
end of curve
.003 (see above) .003

.002 .002

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
500

1000

2000

3000

4000
5000
6000

8000
9000
700
200

300

400

600

800
900
100

CURRENT IN AMPERES

24 | 1-800-ASK-4WEG | www/weg/met Data subject to change without notice.


Proof 1 — October 20, 2015 10:24 PM
Series C
F-Frame
Molded-Case Circuit Breakers
Effective September 2015

UBW Time Current Curves


225L 100A
CURRENT IN AMPERES

100,000
20,000

30,000

40,000
50,000
60,000
70,000
80,000
90,000
10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
50 60 70 80 90
10,000
Circuit breaker time/current curves

2 HOURS
2 HOURS
®
Series C F-frame circuit breakers

5,000 Circuit breaker time/current


Catalog type curves
FDC circuit breaker, two-, three- and four-poles. 5,000

1 HOUR
1 HOUR

225L Circuit Breakers


Based on 40˚C ambient, cold start. Connected with four (4) feet of
3,000 3,000
Tested in open air with current in all poles.
For application and coordination purposes only . Based on 40°C ambient, cold start .
2,000 Connected Maximum
with fourVac: 600of
(4) feet at 50/60 2,000
ratedHzwire (60°C up to 125A, 75°C above 125A) per
Maximum Vdc: 250
terminal . Tested in open air .
Breaker rating
Maximum Vac: 600 atamperes
Continuous 50/60 Hz Instantaneous trip amperes
1,000 100A 250 1,000
Maximum Vdc: See curve

Interrupting rating (UL/CSA listed)


Breaker rating
Breaker Symmetrical Rms amperes (KA) Amps (KA)
type @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc
500 Continuous
FDC
amperes
200
Instantaneous
100
trip, amperes
35 22
500

100A 1 Single-pole test dataSee curvebased on NEMA procedures


at 25˚C
300 (AB 4-2003) for verifying performance of molded case 300
circuit breakers.
Interrupting Rating (UL/CSA Listed)
200 Symmetrical RMS amperes (kA) Amps 200
(KA)
Maximum single-
pole trip times Breaker Type @240Vac @480Vac @600Vac 250Vdc
at 25°C 1 L 200 100 35 22
100 100
Notes:

1 MINUTE
1 MINUTE

1 Single-pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying
performance of molded case circuit breakers .
50 50

30 30

20 20

10 10

Minimum Maximum
5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

Maximum interrupting time


.02 .02

600V

.01 .01
480V

.005 .005
240V
.003 .003

.002 .002

.001 .001
50 60 70 8090
100,000

200,000
10000

20,000

30,000

40,000
50,000
60,000
70,000
80,000
90,000
7000
1000

2000

3000

4000
5000
6000

8000
9000
500

700
200

300

400

600

800
900
100

CURRENT IN AMPERES

Figure 58. Type FDC 100A—Curve Number SC-5528-93A


Data subject to change without notice. UBW Technical Manual | 25
EATON www.eaton.com 61
Molded-Case Circuit Breakers

Time Current Curves


225 N., H.
CURRENT IN AMPERES
125A

10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000

2 HOURS
2 HOURS

Circuit
®
breaker time/current curves
F-frame circuit breakers
225 circuit breakers
5,000 5,000

1 HOUR
1 HOUR

3,000 3,000

For application and coordination purposes only . Based on 40°C ambient, cold start .
2,000 Connected600 with four Hz
at 50/60 (4) feet of rated wire (60°C up to2,000
125A, 75°C above 125A) per
250
terminal . Tested in open air .

Maximum Vac: 600 at 50/60 Hz


1,000 1,000
Maximum Vdc: 250
Symmetrical Rms amperes (KA) Amps (KA)
Breaker
@ 240 rating
Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc
65 — — — 10
500
Continuous
22 amperes
— — Instantaneous
— trip, 500
10 amperes
42 — — — 10
100 — — — 10
125A 200 — — See curve— 10
300 18 14 14 10 — 300
65 35 18 10 —
Interrupting
100 Rating
65 (UL/CSA
25 Listed)
22 —
200 200
Symmetrical RMS amperes (kA)
4-2003) for verifying performance of molded case
Maximum single- Breaker Type @240Vac @480Vac @600Vac 250Vac
pole trip times 30
at 25°C 1 N 65 35 18 10
100
H 100 65 25 20
22
1 MINUTE

Notes:
50
1 Single-pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying
performance of molded case circuit breakers . 10

30

20

10

Minimum Maximum
5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

Maximum interrupting t ime


.02 .02

.01 .01

.005 Interrupting .005


rating
determines
.003 end of curve .003
(see above)
.002 .002

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
500

1000

2000

3000

4000
5000
6000

8000
9000
700
200

300

400

600

800
900
100

CURRENT IN AMPERES

26 | 1-800-ASK-4WEG | www/weg/met Data subject to change without notice.


Proof 1 — October 20, 2015 10:24 PM
Series C
F-Frame Molded-Case Circuit
Effective Breakers
September 2015

UBW Time Current Curves


CURRENT IN AMPERES
225L 125A

100,000
20,000

30,000

40,000
50,000
60,000
70,000
80,000
90,000
10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
50 60 70 80 90
10,000
Circuit breaker time/current curves

2 HOURS
2 HOURS
Series C F-frame circuit breakers

5,000 Catalog type FDC circuit breaker, two-, three- and four-poles. 5,000
Circuit breaker time/current curves

1 HOUR
1 HOUR

For application and coordination purposes only.


UBW 225L Circuit Breakers cold start. Connected with four (4) feet of
3,000 rated wire (60˚C up to 125A, 75˚C above 125A) per terminal. 3,000
Tested in open air with current in all poles.

2,000 For application


Maximumand Vac:coordination purposes only . Based on 40°C ambient,
600 at 50/60 Hz 2,000 cold start .
Maximum
Connected with Vdc: 250feet of rated wire (60°C up to 125A, 75°C above 125A) per
four (4)
terminal . Tested
Breaker in open air .
rating
Continuous amperes Instantaneous trip amperes
1,000 125AVac: 600 at 50/60 Hz See curve
Maximum 1,000

Maximum Vdc: 250


Interrupting rating (UL/CSA listed)
Breaker Symmetrical Rms amperes (KA) Amps (KA)
Breaker
typerating@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc
500 500
FDC 200 100 35 22
Continuous amperes Instantaneous trip, amperes
1 Single-pole test data at 25˚C based on NEMA procedures
300 125A (AB 4-2003) for verifying See curve of molded case
performance 300
circuit breakers.

200 Interrupting Rating (UL/CSA Listed) 200


Symmetrical RMS amperes (kA) Amps (KA)
Maximum single- Breaker Type @240Vac @480Vac @600Vac 250Vdc
pole trip times
at 25°C 1 L 200 100 35 22
100
100

Notes:

1 MINUTE
1 MINUTE

50 1 Single-pole test data at 25°C based on NEMA procedures (AB 50


4-2003) for verifying
performance of molded case circuit breakers .

30 30

20 20

10 10

Minimum Maximum
5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

Maximum interrupting time


.02 .02

600V

.01 .01
480V

.005 .005

240V
.003 .003

.002 .002

.001 .001
100,000

200,000
10000

20,000

30,000

40,000
50,000
60,000
70,000
80,000
90,000
7000
1000

2000

3000

4000
5000
6000

8000
9000
500

700
200

300

400

600

800
900
100

50 60 70 8090

CURRENT IN AMPERES

Figure 60. Type FDC 125A—Curve Number SC-5530-93A

Data subject to change without notice. UBW Technical


EATON www.eaton.com Manual 63
| 27
Molded-Case Circuit Breakers

Time Current Curves


225 N., H. CURRENT IN AMPERES
150A

10000
1000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
10,000
2 HOURS

2 HOURS
Circuit
®
breaker time/current curves
F-frame circuit breakers
225 circuit breakers
5,000 5,000
1 HOUR

1 HOUR
Catalog Types: ED, EDB, EDS, EDH, EDC, EHD, FDB, FD and HFD circuit breakers,

3,000 two-, three- and four-pole . 3,000

For application and coordination purposes only . Based on 40°C ambient, cold start .
2,000 Connected with four
600 at (4)
50/60 Hzfeet of rated wire (60°C up to 125A,
2,000 75°C above 125A) per
250 in open air .
terminal . Tested

Maximum Vac: 600 at 50/60 Hz


1,000 1,000
Maximum Vdc: 250
Symmetrical Rms amperes (KA) Amps (KA)
Breaker rating
@ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc
65 — — — 10
500 Continuous
22 amperes
— —Instantaneous
— trip,
10 500
amperes
Maximum single- 42 — — — 10
pole trip times 100 — — — 10
at 25°C 1 150A 200 — —See curve — 10
300 18 14 14 10 — 300
65 35 18 10 —
Interrupting
100 Rating
65 (UL/CSA25 Listed)
22 —
200
Symmetrical RMS amperes (kA)200
(AB 4-2003) for verifying performance of molded case
Breaker Type
circuit breakers. @240Vac @480Vac @600Vac 250Vac
30
N 65 35 18 10
100 H 100 65 25 22
20
Notes:
1 MINUTE

50 1 Single-pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying
performance of molded case circuit breakers . 10

30

20

10

Minimum Maximum
5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

Maximum interrupting t ime


.02 .02

.01 .01

.005 Interrupting .005


rating
determines
.003 end of curve .003
(see above)

.002 .002

.001 .001
5 6 7 8 9 10 20 30 40 50 60 70 8090
10000
7000
500

1000

2000

3000

4000
5000
6000

8000
9000
700
200

300

400

600

800
900
100

CURRENT IN AMPERES

28 | 1-800-ASK-4WEG | www/weg/met Data subject to change without notice.


Proof 1 — October 20, 2015 10:24 PM
Series C
Molded-Case Circuit Breakers
F-Frame
UBW Time Current Curves
225L CURRENT IN AMPERES
150A

100,000
20,000

30,000

40,000
50,000
60,000
70,000
80,000
90,000
10000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
50 60 70 80 90
10,000
Circuit breaker time/current curves

2 HOURS
2 HOURS

®
Series C F-frame circuit breakers

5,000 Catalog type FDC circuit breaker, two-, three- and four-poles. 5,000
Circuit breaker time/current curves

1 HOUR
1 HOUR

For application and coordination purposes only.


225L Circuit Breakers
3,000 rated wire (60˚C up to 125A, 3,000

2,000 For application and coordination


Maximum purposes
Vac: 600 at 50/60 Hz only . Based on 40°C ambient, cold start .
2,000
Connected with fourVdc:
Maximum (4) feet
250of rated wire (60°C up to 125A, 75°C above 125A) per
terminal . Tested in open air .
Breaker rating
Continuous amperes Instantaneous trip amperes
1,000 150A 600 at 50/60 Hz
Maximum Vac: See curve 1,000
Maximum Vdc: 250
Interrupting rating (UL/CSA listed)
Breaker Symmetrical Rms amperes (KA) Amps (KA)
Breaker rating
type @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc
500 500
FDCamperes
Continuous 200 100
Instantaneous35
trip, 22
amperes
1 Single-pole test data at 25˚C based on NEMA procedures
300
150A See curve
(AB 4-2003) for verifying performance of molded case 300
circuit breakers.
Interrupting Rating (UL/CSA Listed)
200 200
Symmetrical RMS amperes (kA) Amps (KA)
Maximum single- Breaker Type @240Vac @480Vac @600Vac 250Vdc
pole trip times
at 25°C 1 L 200 100 35 22
100 100
Notes:

1 MINUTE
1 MINUTE

1 Single-pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying
50 performance of molded case circuit breakers . 50

30 30

20 20

10 10

Minimum Maximum
5 5

3 3

TIME IN SECONDS
2 2

1 1
TIME IN SECONDS

.5 .5

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

.02 Maximum interrupting time .02

600V

.01 .01
480V

.005 .005

240V
.003 .003

.002 .002

.001 .001
50 60 70 8090
100,000

200,000
10000

20,000

30,000

40,000
50,000
60,000
70,000
80,000
90,000
7000
1000

2000

3000

4000
5000
6000

8000
9000
500

700
200

300

400

600

800
900
100

CURRENT IN AMPERES

Figure 61. Type FDC 150A—Curve Number SC-5531-93A


Data subject to change without notice. UBW Technical Manual | 29
64 EATON www.eaton.com
Molded-Case Circuit Breakers

Time Current Curves 200–225A CURRENT IN MULTIPLES OF In

225 N., H.

1000
100

200

300

400
500
600
700
800
900
1 2 3 8 4 5 6 17 9 0 20 30 8 40 50 60 70 0 90
10,000

2 HOURS
2 HOURS
Catalog types FD/HFD circuit breakers, two-, three- and four-poles.
5,000 For application and coordination purposes only. 5,000
Circuit Based
breaker
on 40˚Ctime/current curveswith four (4) feet of rated

1 HOUR
1 HOUR

ambient, cold start. Connected


wire (75˚C) per terminal. Tested in open air with current in all poles.
225 circuit breakers
Maximum Vac: 600 at 50/60 Hz
3,000 3,000

Breakerand
For application rating
coordination purposes only . Based on 40°C ambient,
2,000 2,000 cold start .
In amperes Instantaneous pick-up, amperes Rms
Connected with four (4) feet of rated wire (75°C) per terminal . Tested in open air .
175 2400
200 2400
Maximum Vac: 600 at 50/60
225 2400 Hz
1,000 Maximum Vdc: 250 1,000
Interrupting ratings
BreakerBreaker
rating Symmetrical Rms amperes (kA), Icu
type 240 Vac 480 Vac 600 Vac 250 Vac
In amperes Instantaneous pick-up, amperes Rms
500 FD 65 35 18 10 500
HFD 100 65 25 22
Maximum single- 175 2400
pole trip times 200 Notes: 2400
300 1 Fixed inverse–time overcurrent release. 300
at 25°C 225 2 Single-pole test data at 25 2400
°C based on NEMA procedures (AB 4-2003)
for verifying performances of molded case circuit breakers.
200 3 Total operation time. 200
terrupting rating determines end of curve.
Interrupting
4 In thisRating
interruption region:
The curve is drawn for In = 200A. For In π 200A, the end points in this
Symmetrical RMS amperes (kA), I
region are displaced along the current-axis by a factor (200A/Incu
)

100 Breaker Type 240Vac 480Vac 600Vac 250Vac


100
N 65 35 18 10

1 MINUTE
1 MINUTE

H 100 65 25 22
50 50

Notes:
30 30
Maximum 1 Fixed inverse-time overcurrent release .
trip time
20 20
2 Single-pole test data at 25°C based on NEMA procedures (AB 4-2003) for verifying
performance of molded case circuit breakers .

3 Total operation time .


10 10
4 In this interruption region:
The curve is drawn for In = 200A . For In π 200A, the end points in this region are
displaced along the current-axis by a factor (200A/In)
5 5

3 3

TIME IN SECONDS
2 Minimum 2
trip time

1 1
TIME IN SECONDS

175 A
.5 .5

200 A
.3 .3

.2 225 A .2

.1 .1

.05 .05

.03 .03

.02 .02

.01 .01

.005 .005

.003 .003

.002 .002

.001 .001
1 2 3 8 4 5 6 17 9 0 20 30 8 40 50 60 70 0 90
1000
100

200

300

400
500
600
700
800
900

CURRENT IN MULTIPLES OF In

30 | 1-800-ASK-4WEG | www/weg/met Data subject to change without notice.


Molded-Case Circuit Breakers

Time Current Curves


200 L
10000.000

Circuit Breaker time/current curves

Series C F-Frame Circuit Breakers


Maximum Single Pole Trip
Times at 25°C

For application and coordination purposes only.


Based on cold start at rated ambient temperature.
1000.000 Connected with four (4) feet of rated wire (60/75°C) per terminal
with all poles wired in series. Tested in open air.
Instantaneous tripping is single pole.

Maximum Vac: 600V at 50/60Hz


Maximum Vdc: 250V

Breaker Rating
Continuous Amps Instantaneous trip amperes

200A See curve


May be 42% higher for dc voltages

Interruption Ratings (UL/CSA listed)


100.000
Breaker Symmetrical RMS amperes (kA)
Type 240 Vac 480Vac 600 Vac 250 Vdc
L 200 100 35 22

Maximum
Tolerance
Time in Seconds

Minimum
10.000
Tolerance

1.000

0.100
interruption rating and
application determines
end of curve

240V 480V 600V

0.010
10 100 1000 10000 100000 1000000
Current in Amperes

Data subject
Figure 45.toTypes
change without
ED, EDB, notice. UBW Technical Manual | 31
EDS, EDH, EDC, EHD, FDB, FD, HFD, FDC 200A 2, 3, & 4 pole—Curve Number TC012034EN
Eaton Corporation January 2012
Molded-Case Circuit Breakers

Time Current Curves


225L
10000.000

Circuit Breaker time/current curves

Series C F-Frame Circuit Breakers


Maximum Single Pole Trip
Times at 25°C

For application and coordination purposes only.


Based on cold start at rated ambient temperature.
1000.000 Connected with four (4) feet of rated wire (60/75°C) per terminal
with all poles wired in series. Tested in open air.
Instantaneous tripping is single pole.

Maximum Vac: 600V at 50/60Hz


Maximum Vdc: 250V

Breaker Rating
Continuous Amps Instantaneous trip amperes

225A See curve


May be 42% higher for dc voltages

Interruption Ratings (UL/CSA listed)


100.000
Breaker Symmetrical RMS amperes (kA)
Type 240 Vac 480Vac 600 Vac 250 Vdc
L 200 100 35 22

Maximum
Tolerance
Time in Seconds

Minimum
10.000
Tolerance

1.000

0.100
interruption rating and
application determines
end of curve

240V 480V 600V

0.010
10 100 1000 10000 100000 1000000
Current in Amperes

32 | 1-800-ASK-4WEG | www/weg/met Data subject to change without notice.


Figure 46. Types ED, EDB, EDS, EDH, EDC, EHD, FDB, FD, HFD, FDC 225A 2, 3, & 4 pole—Curve Number TC012035EN
Molded-Case Circuit Breakers

Data subject to change without notice. UBW Technical Manual | 33


Molded-Case Circuit Breakers

34 | 1-800-ASK-4WEG | www/weg/met Data subject to change without notice.


Molded-Case Circuit Breakers

UBW Time Current Curves


400N, H
Current in Percent of Breaker Trip Unit Rating (In)
10 100 1000
10,000.000 Thermal-Magnetic Circuit Breaker Time/Current Curves

For application and coordination purposes only . Based on cold start at rated ambient temperature .
Connected with four (4) feet of rated wire (60/75°C) per terminal with all poles wired in series .
Tested in open air .

Maximum
Minimum
1000.000

Breaker Rating
Rated Amperes (In) Instantaneous Trip Amperes
100-400 Settings are 500 to 1000% of trip unit rating. For DC, instantaneous
trip may be 42% higher.

100.000 UL/CSA rms Sym . kA, 50/60 Hz


Breaker Type 240V 480V 600V 250Vdc
N 65 35 25 10
H 100 65 35 22

10.000
Maximum Single-Pole Trip Times
Time in Seconds

at 25°C

7.5 7.5 7.5


C Thermal Push to Trip
Typical Magnetic
Trip Unit Trip Unit

1.000 Nameplate 10 5 10 5 10 5

Magnetic Amps Cat.


Multiples Of In (In) 40°C No.
+30% / –20%
+30% / –20%

Individual Pole
Adjustments

Adjustable Magnetic Trip, 5x - 10x


0.100

Minimum Maximum

Interruption Rating Determines


End of Curve

0.010

0.001
10 100 1000 10,000 100,000 1,000,000
Current in Percent of Breaker Trip Unit Rating (In)

Data subject to change without notice. UBW Technical Manual | 35


Molded-Case Circuit Breakers

UBW Time Current Curves Current in Percent of Breaker Trip Unit Rating (In )
400L
10 100 1000
10000 .000 Thermal-Magnetic Circuit Breaker Time/Current Curves

For application and coordination purposes only . Based on 40°C ambient, cold star
Connected with four (4) feet of rated wire (60°C up to 125 amps . 75°C above 125
amps) per terminal . Tested in open air with current in all poles . Instantaneous
calibration based on single-pole tests .
Maximum
Minimum Maximum Voltage: 600 Vac (60 Hz) – 250 Vdc

1000 .000 Breaker Rating


Rated Amperes (In) Instantaneous Trip Amperes
100-400 500 to 1000% of trip unit rating (See Figure Below)
(Dc values are approximately 40% higher)

UL/CSA rms Sym . kA, 50/60 Hz


Breaker Type 240V 480V 600V 250Vdc
L 200 100 65 22

Single-pole test data at 25°C based on NEMA Procedures (AB 4) for


100 .000 verifying performance of molded-case circuit breakers .

Note: For additional information on the trip unit, see IL 29C603 .

Maximum Single Pole Trip


Times at 25°C

10 .000
Time in Seconds

1 .000
+30%-20%

+30%-20%

Adjustable magnetic trip


0 .100
Minimum
Maximum
interruption rating determines
end of curve
600V AC

480V AC
0 .010

240V AC

0 .001
10 100 1000 10000 100000 1000000

Current in Percent of Breaker Trip Unit Rating (In )

36 | 1-800-ASK-4WEG | www/weg/met Data subject to change without notice.


Molded-Case Circuit Breakers

UBW Time Current Curves


600N/H
CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (I n)
Circuit Breaker Time/Current Curves

10,000
1000

2000

3000

4000

5000
6000
7000
8000
9000
For application and coordination purposes only . Thermal calibration based on 40°C ambient, cold

100

200

300

400

500
600
700
800
900
50
60
70
80
90
10,000
start . Connected with four (4) feet of rated wire (75°C) per terminal . Tested in open air with
2 HOURS

current in all poles . Instantaneous calibration based on single-pole tests .

5,000 Maximum Voltage: 600V, AC (50/60 Hz) 250V, DC


1 HOUR

3,000

2,000

Breaker Rating
Rated Instantaneous Trip Amperes
1,000
Amperes (In) (See Figure Below)
300-600 500 to 1000% of trip unit rating (DC values are approximately 40% higher)
500

Interrupting Rating
Maximum Single
300 Pole Trip Times UL/CSA rms Sym. kA, 50/60 Hz kA, DC
at 25°C 1
Breaker Type 240V 480V 600V 250V
200
N 65 35 25 10
H 100 65 35 20
Minimum Maximum
100

IEC 60947-2 rms Sym. kA, 50/60 Hz kA, DC


1 MINUTE

Breaker Type 240V, (Ue) 415V, (Ue) 690V (Ue) 250V, (Ue)
50
Icu Ics Icu Ics Icu Ics Icu Ics
N 65 17 40 10 40 10 10 3
30 H 100 25 65 17 65 17 20 5
Utilization Category A
20 UIMP = 8 kV

Notes: For additional information on the trip unit, see IL 29C606 .


10
10 Typical
Trip Unit
Nameplate 1 Single pole data at 25°C based on NEMA Procedures for verifying performance
of molded case circuit breakers . 5

3 3
7 .5 7 .5 7 .5
C Thermal Push to Trip
Magnetic
2 Trip Unit 2
10 5 10 5 10 5
TIME IN SECONDS

TIME IN SECONDS
Magnetic Amps Cat .
Multiples OfnI (In) 40°C No .
±20% ±10%
10X
5X

1 1

Individual Pole
Adjustments
.5 .5
Adjustable Magnetic Trip

.3 .3

.2 .2

.1 .1

.05 .05

.03
Maximum Interrupting Time .03

.02 .02

.01 .01

Interrupting Rating
Determines End of
.005 .005
Curve

.003 .003

.002 .002

.001 .001
100,000
20,000

30,000

40,000

50,000
60,000
70,000
80,000
90,000
10,000
60
50

70
80

500
90

700

7000
200

300

400

600

800
900
100

1000

2000

3000

4000

5000
6000

8000
9000

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (I n)

Data subject to change without notice. UBW Technical Manual | 37


Molded-Case Circuit Breakers

UBW Time Current Curves


600L CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (I n)

10,000
1000

2000

3000

4000

5000
6000
7000
8000
9000
100

200

300

400

500
600
700
800
900
Circuit Breaker Time/Current Curves
50
60
70
80
90
10,000 10,000

2 HOURS
2 HOURS

5,000

1 HOUR
1 HOUR

3,000
For application and coordination purposes only . Thermal calibration based on 40°C ambient, cold
3,000
start . Connected with four (4) feet of rated wire (75°C) per terminal . Tested in open air with
current in all poles . Instantaneous calibration based on single-pole tests .
2,000 2,000

Maximum Voltage: 600V, AC (50/60 Hz) 250V, DC

1,000 Breaker Rating 1,000

Rated Instantaneous Trip Amperes


Amperes (In) (See Figure Below)
500 500
300-600 500 to 1000% of trip unit rating (DC values are approximately 40% higher)
Maximum Single
300 Pole Trip Times 300
at 25°C 1 Interrupting Rating
200 UL/CSA rms Sym. kA, 50/60 Hz 200 kA, DC
Breaker Type 240V 480V 600V 250V
Minimum Maximum L 200 100 50 --
100 Utilization Category A 100

UIMP = 8 kV

1 MINUTE
1 MINUTE

50
Notes: For additional information on the trip unit, see IL 29C606 .
50

30
1 Single pole data at 25°C based on NEMA Procedures (AB 4) for verifying performance
30
of molded case circuit breakers .
20 20

7 .5 7 .5 7 .5
C Thermal Push to Trip
10 Typical Magnetic 10
Trip Unit Trip Unit

Nameplate 10 5 10 5 10 5

Magnetic Amps Cat .


Multiples OfnI (In) 40°C No .

5 5

Individual Pole
3 3
Adjustments

2 2
TIME IN SECONDS

TIME IN SECONDS
±20% ±10%
10X
5X

1 1

.5 .5
Adjustable Magnetic Trip

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03

.02 .02
Maximum Interrupting Time

600V A .C .

.01 .01
480V A .C .

240V A .C .
.005 .005

.003 .003

Interrupting Rating
.002 Determines End of .002
Curve

.001 .001
100,000
20,000

30,000

40,000

50,000
60,000
70,000
80,000
90,000
10,000
60
50

70
80

500
90

700

7000
200

300

400

600

800
900
100

1000

2000

3000

4000

5000
6000

8000
9000

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (I n)

38 | 1-800-ASK-4WEG | www/weg/met Data subject to change without notice.


Molded-Case Circuit Breakers

UBW Time Current Curves


800S, H
CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)

10,000
1000

2000

3000

4000

5000
6000
7000
8000
9000
100

200

300

400

500
600
700
800
900
50
60
70
80
90
10,000 10,000

2 HOURS
2 HOURS

Circuit Breaker Time/Current Curves


5,000
For application and coordination purposes only . Thermal calibration based on 40°C ambient, cold

1 HOUR
1 HOUR

2,000
start . Connected with four (4) feet of rated wire (75°C) per terminal . Tested in open air with
current in all poles . Instantaneous calibration based on single-pole tests .
3,000

Maximum Voltage: 600V, AC (50/60 Hz) 250V, DC 1,000


2,000

1,000

Breaker Rating
Rated Instantaneous Trip Amperes
500 500
Amperes (In) (See Figure Below)
Maximum Single 700 - 800 400 to 800% of trip unit rating (DC values are approximately 40% higher)
300 Pole Trip Times 300
at 25 o C 1
Interrupting Rating
200 200
UL/CSA rms Sym. kA, 50/60 Hz kA, DC
Breaker Type 240V 480V 600V 250V
Minimum Maximum
100 S 65 50 25 100 22
H 100 65 35 25

1 MINUTE
1 MINUTE

IEC 60947-2 rms Sym. kA, 50/60 Hz kA, DC


50 Breaker Type 240V 380V 415V
50 250V
Icu Ics Icu Ics Icu Ics
30 S 65 65 50 50 20 30 10 20 10
H 100 100 70 50 25 13 20 10
20 Utilization Category A 20
UIMP = 8 kV
Typical
Notes:
Trip Unit
10 Nameplate For additional information on the trip unit, see IL 29C607 . 10

1 Single pole data at 25°C based on NEMA Procedures (AB 4) for verifying performance of
molded case circuit breakers .
5 5

6 6 6
3 Thermal 3
Magnetic Push to Trip
Trip Unit
8 4 8 4 8 4
2 2
Magnetic Amps o
C Cat .
(I n)
TIME IN SECONDS

Multiples OfnI No .

TIME IN SECONDS
+ 20% + 10%
4X

8X

1 1
Individual Pole
Adjustments

.5 .5
Adjustable Magnetic Trip

.3 .3

.2 .2

.1 .1

.05 .05

.03 .03
Maximum Interrupting Time

.02 .02

.01 .01

Interrupting Rating
Determines End of
.005 .005
Curve

.003 .003

.002 .002

.001 .001
100,000
20,000

30,000

40,000

50,000
60,000
70,000
80,000
90,000
10,000
60
50

70
80

500
90

700

7000
200

300

400

600

800
900
100

1000

2000

3000

4000

5000
6000

8000
9000

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)

Data subject to change without notice. UBW Technical Manual | 39


Molded-Case Circuit Breakers

UBW Time Current Curves


1200S, H, L 0+ Circuit Break
Breaker
er T ime/Current
ime/Current Cur
Curvves
es (Phase Current)
Current Multiples of (Ir )

0.5 0.7 1 2 3 4 5 7 10 12 20 30
10000
9000
2 Hours

8000
7000
6000 Available Sensors
Available Rated Amperes
Rated
5000 (Irr)) // (I
(I (Inn)) 800A
800A 1200A
1200A
1.15
4000
1 Hour

AA 320A
320A 500A
500A
BB 400A
400A 600A
600A
3000
CC 450A
450A 630A
630A
DD 500A
500A 700A
700A
2000 EE 600A
600A 800A
800A
FF 630A
630A 900A
900A
GG 700A
700A 1000A
1000A
HH 800A
800A 1200A
1200A
1000
900
800 Long Delay Time Settings +0%/ -30% (seconds)
700 Maximum Total
600 800A 2 4 6 8 10 12 14 14
Clearing Time
500 1200A 2 4 7 10 12 15 20 24

400

300
Notes:
Notes:
200 1 . Curve accuracy applies from –20°C to +55°C ambient . For possible continuous ampere derating for
1. Curve
ambient accuracy applies
above 40°C, from
refer to–20°C
Eaton .to +55°C ambient.
Temperatures aboveFor+85°C
possiblecausecontinuous ampere derating
an over-temperature for
protection
Available Long Delay Time ambient
trip . above 40°C, refer to Eaton. Temperatures above +85°C cause an over-temperature protection
(For 1200A Only): trip.
2, 4, 7, 10, 12, 15, 20, 24 Sec. 2 . Application frequency is 50/60 Hz .
100 Shown at 6x
90 I 2. Application frequency is 50/60 Hz.
80 2, 4, 7, 15, 24 r 3 . There is a memory effect that can act to shorten the Long Delay . If the breaker trips on a Long Delay
Seconds +0/–30% 3. There is aand
memory effect thatthe
canmemoryact to shorten thewill
Long Delay.
have Ifcharge
the breaker trips on a Long Delay
1 Minute

70 overload is quickly reset, capacitor still and a subsequent overload


60 (See Chart) overload
will causeand theisbreaker
quickly to
reset, thea memory
trip in shorter time capacitor will stillThe
than normal . )amount
have chargeof and a subsequent
time delay reduction overload
is
50 will cause
inverse to the breaker
amount to of trip
timeinthata shorter time than
has elapsed normal.
since The amount
the previous of time
overload . delay reduction
Approximately five is
inverse
minutestoisthe amount
required of timeoverloads
between that has elapsed since the
to completely resetprevious
memory . overload. Approximately five
40 minutes is required between overloads to completely reset memory.
4 . The right portion of the curve is determined by the interrupting rating of the circuit breaker .

.
30 4. The right portion of the curve is determined by the interrupting rating of the circuit breaker.
5 . The left portion of the curve is shown as a multiple of the Long Delay Setting .
5. The
(Long leftDelay
portion of the
Pickup curve of
= 115% is shown
Ir ) . Rangeas aismultiple
110–120% .of the Long Delay Setting.
20 24 (Long Delay Pickup = 115% of Ir ). Range is 110–120%.
. 6 . Total clearing times shown include the response times of the trip unit, the breaker opening,
6. Total
and the clearing times shown
interruption include the response times of the trip unit, the breaker opening,
of the current .
15 and the interruption of the current.
Time in Seconds

Minimum Total
10 Clearing Time 7 . The Short Delay Pickup has nine settings/positions, 2–8; the last two switch positions are
7. The Short Delay
the same: 9X . Pickup has nine settings/positions, 2–8; the last two switch positions are
.
9
8 the same: 9X.
7 8 . Short Delay I2 T band has a tolerance of +15% .
6 7 8. Short Delay I2 T band has a tolerance of +15%.
9 . Breakpoint back to FLAT response occurs @ 8x Ir for upper line of the I2 T curve .
.
5
9. Breakpoint back to FLAT response occurs @ 8x Ir for upper line of the I2 T curve.
4 10 . For high fault current levels, an additional fixed instantaneous hardware override is provided to trip the
4 10. breaker
For highat fault current
14400A . levels, an additional
Instantaneous tolerancefixed instantaneous
is +/- 20% . For the hardware
1600A frame override is ifprovided
only, Ir is set to
to trip
the the
3 breaker
maximum at 14400A.
(position Instantaneous
H) and SDPU istolerance set to the is maximum
+/- 20%. For the 1600A
(position frame
9), then theonly,
SDPU if Isetting
r is set and
to the the
maximum (position H) andareSDPU
set toisthe setsame
to thevalue .
maximum (position 9), then the SDPU setting andover the
.
Instantaneous Override The Instantaneous Override has precedence
Instantaneous
SDPU . Therefore, Override are setwill
the breaker to trip
the onsame value. The Instantaneous
Instantaneous Override . Override has precedence over
2 3 SDPU. Therefore, the breaker will trip on Instantaneous Override.
2 11 . Maximum clearing time when using zone selective interlocking is 62ms .
2
4
1
0.9 LS
0.8 LS
5
6646 C05 H11

0.7
6646 C05 H11

STATUS
STATUS
0.6 TEST / ALARM t R (s)
TESTI / ALARM
R∑ t R (s)
I sd (xIR)
ISHORT
sd (xIR)
9
LONG
I ∑ LONG
D RE F 5 6 SHORT
7
0.5 CD
BC
E F
G
HG
4 5
34
6 7
8
98
BA H 32 9 9

0.4 7 A 2 9

0.3

0.2 0.2
8 Available Short Delay
6 Instantaneous
Pickup Settings
I 2T Short Delay
Time in Seconds

2–8, 9 x I r + 5% Override (See Note 10)


(See Note 8)
(See Notes 7 and 10)
0.1 0.1
0.09 0.09
0.08
0.07
0.06
. Application Determines
0.08
0.07
0.06
67 ms End of Curve
0.05 0.05
0.04 0.04

0.03 0.03
See Note 9
0.02 0.02
14400A

0.01 0.01
0.5 0.7 1 2 3 4 5 7 10 12 20 30 40 50 70 100 2 3 4 5 7 10 20 30 40 50 70 100

Current in Multiples of (Ir ) Current in 1000A Increments


2
I T Trip Style (LS and LSG)

40 | 1-800-ASK-4WEG | www/weg/met Data subject to change without notice.


Molded-Case Circuit Breakers

UBW Time Current Curves


1200S, H, L 10+
0+ Circuit Breaker
Breaker Time/Current Curv
Curves (Phase Current)

Current in Multiples of (Ir )

0.5 0.7 1 2 3 4 5 7 10 12 20 30
10000
2 Hours

9000
8000
7000
6000 Available Sensors Rated Amperes
5000 (Ir) / (In) 800A 1200A
1.15
1 Hour

4000
A 320A 500A
3000 B 400A 600A
C 450A 630A
D 500A 700A
2000
E 600A 800A
F 630A 900A
G 700A 1000A
H 800A 1200A
1000
900
800 Long Delay Time Settings +0%/ -30% (seconds)
700 Maximum Total
600 Clearing Time 800A 2 4 6 8 10 12 14 14
500 1200A 2 4 7 10 12 15 20 24
400

Notes:
300
Notes:
1. Curve accuracy applies from –20°C to +55°C ambient .
1 . ambient. For possible continuous ampere derating for
200 ambient above 40°C refer to WEG. Temperatures above +85°C cause an over-temperature protection
trip.
trip .
2. Application frequency is 50/60 Hz .
2 . Hz.
Available Long Delay Time
100 (For 1200A Only): 3. There is a memory effect that can act to shorten the Long Delay .
3 . Delay. If the breaker trips on a Long Delay
90 2, 4, 7, 10, 12, 15, 20, 24 Sec. overload and is quickly reset, the memory capacitor will still have charge and a subsequent overload
80 Shown at 6xIr normal. The amount of time delay reduction is
will cause the breaker to trip in a shorter time than normal .
1 Minute

70 2, 4, 7, 15, 24 overload. Approximately five


inverse to the amount of time that has elapsed since the previous overload .
60 Seconds +0/–30% memory.
minutes is required between overloads to completely reset memory .
50 (See Chart )
4. The right portion of the curve is determined by the interrupting rating of the circuit breaker .
4 . breaker.
40
5. The left portion of the curve is shown as a multiple of the Long Delay Setting .
5 . Setting.

.
30
). Range is 110–120% .
(Long Delay Pickup = 115% of Ir ) . 110–120%.

20 24 6. Total clearing times shown include the response times of the trip unit, the breaker opening,
6 .

.
current.
and the interruption of the current .

7 .. The Short Delay Pickup has nine settings/positions, 2–8; the last two switch positions are
Time in Seconds

15
Minimum Total 9X.
the same: 9X .
10 Clearing Time
9
.
8. For high fault current levels, an additional fixed instantaneous hardware override is provided to trip
8 .
8
14400A. Instantaneous tolerance is +/- 20% .
the breaker at 14400A . 20%. For the 1600A frame only, if Ir is set to
7
6
the maximum (position H) and SDPU is set to the maximum (position 9), then the SDPU setting and
7 value. The Instantaneous Override has precedence
the Instantaneous Override are set to the same value .
5 SDPU. Therefore, the breaker will trip on Instantaneous Override .
over SDPU . Override.
4 .
4 9 . Maximum
LSI
clearing time when using zone selective interlocking
LSIG is 62ms .
3
6646 C05

6646 C05
STATUS STATUS
TEST / ALARM t R (s) I sd (xIR) tsd (ms) t *
/

.
IR∑ LONG SHORT SHORT
LSID E F 5 6 7 120
C G 4 8
B H 3 9 Inst. 300
2
6646 C05

A 2
STATUS 9

TEST / ALARM t R (s) I sd (xIR) tsd (ms)


IR∑
2 C
D E F
G
LONG

4
SHORT
5 6 7
8
SHORT
120

Available Short Delay B


A
H 3
2 9
9 Inst. 300

Pickup Settings 2 4
ALSI (With Maintenance Mode)

2–8, 9 x Ir + 5%
1

6646 C05
6646 C05

STATUS STATUS

*
Remote MM Remote MM

0.9 (See Note 7) t R (s) I sd (xIR) tsd (ms) Push to Trip TEST / ALARM t R (s) I sd (xIR) I g (xIn) t sd / tg (ms)
*
6646 C06

Push to Trip TEST / ALARM t g (ms)


6646 C06

Settings
I R ∑Mode)
ALSI (With Maintenance LONG SHORT SHORT ALSIG (WithI (xIn)
Maintenance
I R ∑ Mode)
LONG SHORT GND SHORT / GND
50 120 300

3 6 I i (xIn) D E F 5 6 7 .6 .8 1.0 M N O
i

0.8
E D F 5 6 7 120 INST
INST 50 J K L
7 8 C G 4 8 7 8 C G 4 8 .4 L P t sd 120 M N O
6 6 B H 3 9 .3 K Q (ms)
B H 3 9 50 300
0.7
300 P Q R
9

6646 C05
4 A 2 9 .2 J R
6646 C05

4 A 2 9 STATUS
STATUS 2.5

*
2.5 Remote MM
Remote MM Maintenance Mode
Maintenance Mode
TEST / ALARM t R (s) I sd (xIR) I g (xIn) t sd / t g (ms)
*
Push to Trip

0.6 t R (s) I sd (xIR) tsd (ms)


6646 C06

Push to Trip TEST / ALARM t g (ms)


6646 C06

5
Settings
IR∑ LONG SHORT SHORT IR∑ LONG SHORT GND SHORT / GND
I i (xIn) I i (xIn) 50 120 300
D E F 5 6 7 120 INST D E F 5 6 7 .6 .8 1.0 M N O
INST 50 J K L
7 8 C G 4 8 7 8 C G 4 8 .4 L P t sd 120
0.5
M N O
0.5
6 6 B H 3 9 .3 K Q (ms)
B H 3 9 50 300 4 300 P Q R
4 A 2 9 .2 J R
A 2 9
Time in Seconds
2.5 2.5
Maintenance Mode Maintenance Mode

0.4 0.4

0.3 300 ms 0.3


(P, Q, R)
Instantaneous
0.2 Override (See Note 8) 0.2

7
Application Determines
120 ms End of Curve
0.1 (M, N, O) 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 8 0.06
0.05 Inst. 0.05
(J, K, L)
0.04 0.04

0.03 0.03

0.02 0.02

14400A

0.01 0.01
0.5 0.7 2 3 4 5 7 10 12 20 30 40 50 70 100 2 3 4 5 7 10 20 30 40 50 70 100

Current in Multiples of (I r ) Current in 1000A Increments

Adjustable Flat Trip Style (LSI, LSIG, ALSI, ALSIG)

Data subject to change without notice. UBW Technical Manual | 41


Molded-Case Circuit Breakers

UBW Time Current Curves Notes:

2500H/L 1 . The maintenance mode feature must be ENABLED for these curves to apply . The LED
indicator is blue when in maintenance mode .

2 . The end of the curve is determined by the interrupting rating of the circuit breaker .
Maintenance Mode/Instantaneous Setting
3 . Total clearing times shown include the response times of the trip unit, the breaker
opening, and the interruption of the current .
Trip Unit Type: 38 (ALSI), 39 (ALSIG)
4 . Available pickup settings ( x In) (tolerance is ±15%) 2 .5, 4, 6, 7, 8, 10 .
ALSI (With Maintenance Mode) 5 . The Maintenance Mode consists of the two lowest settings of the INST switch: 2 .5x and 4 .0x .

6 . The Remote Maintenance Mode is enabled by applying 24 VDC to the two wire cable that exists

6646 C05
STATUS
Remote MM the left side of the breaker . The wires are color coded as follows: Yellow = +24 V and Black =
Push to Trip TEST / ALARM t R (s) I sd (xIR) tsd (ms) common ground . A blue colored LED, on the left side of the breaker is the Maintenance Mode
6646 C06

IR∑ LONG SHORT SHORT section of the trip unit, will light . The lighted blue LED indicates that the lowest setting of the
I i (xIn)
INST D E F 5 6 7 120
Maintenance Mode is enabled . This setting corresponds to 2 .5x of In . Turning the adjustable
7 8 C G 4 8
6 B H 3 9 50 300 switch on the trip unit has no affect on either the Maintenance Mode or the INST Mode settings
4
2.5
A 2 9 while the blue LED is lit . In addition to the blue colored LED, a relay contact (C, NO) is available .
Maintenance Mode The wires for this contact exit the left hand side of the breaker and are color coded as follows:
Blue = C, and Red = NO .

NO
C

6646 C05
Left Side of Breaker

Black Yellow

24 Vdc

Blue
Relay Wiring
Red

Maintenance Mode Trip Instantaneous Mode Trip


10 10
9 9
8 8
7 7
6 Last 6
5 Instantaneous 5
4 Value 4
800A 18x
3 3
1200A/1250A 12x
2
1600A 9x 2

1 1
0 .9 0 .9
0 .8 0 .8
0 .7 0 .7
0 .6 2 .5 4 .0 6 .0 0 .6
8 .0
0 .5 0 .5
0 .4 0 .4
Time in Seconds

Time in Seconds
0 .3 0 .3

0 .2 7 .0 0 .2

10 .0

0 .1 0 .1
0 .09 0 .09
0 .08 0 .08
0 .07 0 .07
0 .06 Application 12 .0 Application 0 .06
0 .05 Determines Determines 0 .05
End of Curve End of Curve
0 .04 0 .04

0 .03 0 .03

0 .02 0 .02

0 .01 0 .01
0 .5 0 .7 0 .9 2 3 4 5 6 7 8 9 10 20 30 40 50 1 10 100
0 .6 0 .8 1
Current in Multiples of Ratings (In )

42 | 1-800-ASK-4WEG | www/weg/met Data subject to change without notice.


Molded-Case Circuit Breakers

UBW Time Current Curves


2500H, L Circuit Breaker Time/Current Curves (Phase Current)

Current in Multiples of (Ir)

0.5 0.7 2 3 4 7 12
Available Sensors Rated Amperes
1 5 10 20 30
10000 (Ir) / (In) 1600A 2000A 2500A
2 HOURS

9000
8000
7000
A 800A 1000A 1600A
6000 B 900A 1200A 1700A
5000 C 1000A 1400A 1800A
1.15 D 1100A 1600A 2000A
1 HOUR

4000
E 1200A 1700A 2100A
3000 F 1400A 1800A 2200A
G 1500A 1900A 2400A
H 1600A 2000A 2500A
2000

1000
900
800
700 Notes:
Maximum Total
600
Clearing Time 1 . Curve accuracy applies from –20°C to +55°C ambient . For possible continuous ampere derating for
500
ambient above 40°C, refer to WEG. Temperatures above +85°C cause an over-temperature protection
400 trip .

300 2 . Application frequency is 50/60 Hz .

3 . There is a memory effect that can act to shorten the long delay . If the breaker trips on a long delay
200 overload and is quickly reset, the memory capacitor will still have charge, and a subsequent overload
will cause the breaker to trip in a shorter time than normal . The amount of time delay reduction is
inverse to the amount of time that has elapsed since the previous overload . Approximately five
minutes is required between overloads to completely reset memory . .
Available Long Delay Time
100
2, 4, 7, 10 ,12, 15, 20, 24 sec 4 . The right portion of the curve is determined by the interrupting rating. of the circuit breaker .
90
80 Shown @ 6 x Ir +0/–30%
1 MINUTE

70 5 . The left portion of the curve is shown as a multiple of the Long Delay Setting .
60 (Long Delay Pickup = 115% of Ir ) . Range is 110–120% .
50
6 . Total clearing times shown include the response times of the trip unit, the breaker opening,
40 and the interruption of the current .

7 . The short delay pickup has nine settings/positions;


.
30
1600A/2000A - 2, 3, 4, 5, 6, 7, 8, 8, 9
2500A - 2, 2, 2, 3, 4, 5, 6, 6, 6
20 24

.
TIME IN SECONDS

8 . For high fault current levels, an additional fixed instantaneous hardware override is provided to trip the
breaker at 17,500A . Instantaneous tolerance is ± 20% .
15
Minimum Total 9 . Maximum clearing time when using zone selective interlocking is 62ms .
10
9
Clearing Time
8
7
6
.
7
LSI ALSI (With Maintenance Mode) ALSIG (With Maintenance Mode)

CAUSE OF TRIP CAUSE OF TRIP

L L

Ir Rating Ir Rating Ir Rating

.
5 Chart
S
RESET

Chart
S
RESET

Chart I I

4 G

4
3 B C B C
B C A D I TEST / ALARM A D I TEST / ALARM
A D I TEST / ALARM r r
r E ∑
E ∑ E ∑
F F
F H G H G
H G

.
4 7 4 7
4 7 2 10 t (s) 2 10 t (s)
2 10 t (s) r r
r STATUS 12 LONG STATUS
12 LONG STATUS 12 LONG Engaged Engaged
Engaged 15
15 15 24 20
24 20 24 20
3 4 3 4

2
3 4 2 5 I sd (xIr)
2 5 I sd (xIr) 2 5 I sd (xIr) Remove Remove
Remove 6 6 SHORT
6 SHORT SHORT
9 7 9 7
9 7 8
8 8
.4 .6
.2 .8 I (x 1000A)

2
g
1.0 GND
1.2

Available Short *
Inst. 50 K L
J M t / t (ms)
t sd (ms) t sd (ms) sd g
120 SHORT N SHORT / GND
120 SHORT
R O Remote MM

2
Remote MM

Delay Pickup
300 Q P
300

4 I i (xIn)
INST * Settings t g (ms)
Inst. 120 300
I i (xIn)
INST
J K L 7 8

Settings
7 8 50
t sd 120 M N O 6 Max

1
6 Max
(ms)
4 300 P Q R 4
2.5 2.5

0.9 Maintenance Mode Maintenance Mode

0.8 ISD x Ir ± 5% 3
6 NP 6635C07 H24 NP 6635C07 H21

(See Note 7)
NP 6635C07 H25

0.7
0.6
5 9
0.5 0.5
300 ms *1600A/2000A Faceplates shown, 2500A Faceplates may differ
8
TIME IN SECONDS

0.4 (P,Q,R) 0.4


Instantaneous
0.3 Override (See Note 8)
0.3

0.2 0.2

7
Override curve should start
120 ms from 21000A (17500 with
0.1 (M,N,O) +20 % tolerance applied)
0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05
Inst. 0.05
(J,K,L)
0.04 0.04
Application Determines
0.03 End of
0.03Curve

0.02 0.02

17500A

0.01 0.01
0.5 0.7 2 3 4 5 7 10 12 20 30 40 50 70 100 2 3 4 5 7 10 20 30 40 50 70 100

Current in Multiples of (Ir) Current in 1000A Increments

Adjustable Flat Trip Style (LSI, LSIG, ALSI, ALSIG)

Data subject to change without notice. UBW Technical Manual | 43


Molded-Case
Time Circuit
Current Curves Breakers
TD012030EN Series G
Effective September 2015 R-Frame

UBW Time Current Curves


2500H, L Circuit Breaker Time/Current Curves (Phase Current)

Current in Multiples of (Ir)


Available Sensors Rated Amperes
0.5 0.7 1 2 3 4 5 7 10 12 20 30
(Ir) / (In) 1600A 2000A 2500A
10000
1 HOUR 2 HOURS

9000 A 800A 1000A 1600A


8000
7000 B 900A 1200A 1700A
6000 C 1000A 1400A 1800A
5000 D 1100A 1600A 2000A
1.15 E 1200A 1700A 2100A
4000
F 1400A 1800A 2200A
3000 G 1500A 1900A 2400A
H 1600A 2000A 2500A
2000

1000 Notes:
900
800
700 1 . Curve accuracy applies from –20°C to +55°C ambient . For possible continuous ampere derating for
Maximum Total ambient above 40°C, referto WEG. Temperatures above +85°C cause an over-temperature protection
600
Clearing Time trip .
500

400 2 . Application frequency is 50/60 Hz .

300 3 . There is a memory effect that can act to shorten the long delay . If the breaker trips on a long delay
overload and is quickly reset, the memory capacitor will still have charge, and a subsequent overload
will cause the breaker to trip in a shorter time than normal . The amount of time delay reduction is
200
inverse to the amount of time that has elapsed since the previous overload . Approximately five
minutes is required between overloads to completely reset memory .
Available Long Delay Time
2, 4, 7, 10, 12, 15, 20, 24 sec 4 . The right portion of the curve is determined by the interrupting rating of the circuit breaker .
100 Shown at 6 x Ir +0 / –30% 5 . The left portion of the curve is shown as a multiple of the Long Delay Setting .
90
1 MINUTE

80 (Long Delay Pickup = 115% of Ir ) . Range is 110–120% .


70
60 6 . Total clearing times shown include the response times of the trip unit, the breaker opening,
50 and the interruption of the current .
40 7 . The short delay pickup has nine settings/positions; 1600A/2000A - 2, 3, 4, 5, 6, 7, 8, 8, 9
2500A - 2, 2, 2, 3, 4, 5, 6, 6, 6

.
30
8 . For high fault current levels, an additional fixed instantaneous hardware override is provided to trip the
breaker at 17,500A . Instantaneous tolerance is ± 20% .
20 24

.
TIME IN SECONDS

9 . Short delay I2T band has a tolerance of ±15% .

Minimum Total
15 10 . Breakpoint back to FLAT response occurs at 8 x Ir for upper line of the I2T curve .
10
Clearing Time 11 . Maximum clearing time when using zone selective interlocking is 62ms .
.
9
8
7
6 7 LS

.
5

4
Ir Rating
4 Chart
3

2
3 . A
B C

H G
D I

F
r
E ∑
TEST / ALARM

2 2
4 7
10 t (s)
r
12 LONG STATUS
Engaged
15
24 20
3 4
2 5 I sd (xIr)
2 6 SHORT
Remove

4 9
8
7

1
0.9
0.8
0.7 5
0.6
9 0.5
0.5
NP 6635C07 H26

0.4 7

0.3 *1600A/2000A Faceplates shown, 2500A Faceplates may differ 0.3


6

0.2 0.2
TIME IN SECONDS

Available Short Delay


2
I T Short Delay Pickup Settings Instantaneous
8
(See Note 9) 2–8, 9 x Ir ± 5% Override (See Note 8)
0.1
(See Notes 7 and 10)
0.1
0.09 0.09
0.08
0.07
0.06
. Application Determines
End of Curve
0.08
0.07
0.06
0.05
67 ms 0.05

0.04 0.04

0.03 0.03

See Note 9
0.02 0.02
17500A
Override curve
should start from
the 21000A (17500
0.01 with
0.01 +20%
0.5 0.7 1 2 3 4 5 7 10 12 20 30 40 50 70 100 2 3 4 5 7 10 20 30 40 50 70 100tolerance applied)

Current in Multiples of (Ir) Current in 1000A Increments

I2T Trip Style (LS, LSG)

Figure 3. Digitrip 310+ Long Delay Response and Short delay with I2T Response Curve (LS, LSG) - Curve Number TC01210021E,
44 | 1-800-ASK-4WEG
September 2017 | www/weg/met Data subject to change without notice.
6 EATON www.eaton.com
Time Current Curves TD012030EN Series G
Effective September 2015 R-Frame
Molded-Case Circuit Breakers

UBW Time Current Curves


Series 2500-Frame Trip Unit Nameplates
2500H, L

ALSI (With Maintenance Mode)

Notes:
CAUSE OF TRIP

1 . The Maintenance Mode feature must be ENABLED for these Ir Rating


L

RESET
S
curves to apply . The LED indicator is blue when in Maintenance Chart
Mode .
I

2 . The end of the curve is determined by the interrupting rating of the


circuit breaker . B C
A D I TEST / ALARM
r
E ∑

3 . Total clearing times shown include the response times of the trip H G
4 7
F

unit, the breaker opening, and the interruption of the current . 2 10 t (s)
r
12 LONG STATUS
Engaged
15
24 20
3 4
4 . Available pickup settings ( x In) (tolerance is ±15%) 2 5
6
I sd (xIr)
SHORT
Remove

1600A Frame: 2 .5, 4, 6, 7, 8, 8, 11 9


8
7

2000A Frame: 2 .5, 4, 6, 7, 8, 8, 9


50
5 . These curves are comprehensive for the complete family of t sd (ms)
120 SHORT

Series 2500
G R-F rame electronic breakers, including all frame sizes, 300 Remote MM

ratings, and constructions . The total clearing times shown are I i (xIn)
INST

conservative and consider the maximum response times of the trip 6


4
7 8
Max

unit, the circuit breaker opening, and the interruption of the current 2.5
Maintenance Mode

in worst case conditions such as: maximum rated voltages,


single-phase interruption, and minimum power factor . Faster NP 6635C07 H24

clearing times are possible depending on the specific system


conditions . *1600A/2000A Faceplates shown, 2500A Faceplates may differ

Maintenance Mode Trip Instantaneous Mode Trip


10 10
9 9
8 8
7 7
6 Maintenance Mode Instantaneous Mode Pickup 6
5
Pickup tolerance (+/- 15%) Tolerance (+/- 15%) 5

4 4

3 3

2 2

1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 2.5 4.0 6.0
Max. for 0.6
8.0
0.5 2000A 0.5

0.4
Frame 0.4
TIME IN SECONDS

TIME IN SECONDS

0.3 0.3
Max. for
1600A
0.2 7.0 9.0
Frame 0.2

11.0

0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 Application Application 0.06
0.05 Determines Determines 0.05
End of Curve End of Curve
0.04 0.04

0.03 0.03

0.02 0.02

0.01 0.01
0.9
0.6

1
0.5

0.7
0.8

10
5
6

50
20
2

30

40
10
3

100
7

Current in Multiples of Rating (In)

Figure 5. Maintenance Mode/Instantaneous Setting 1600A/2000A (ALSI, ALSIG) - Curve Number TC01210024E, September 2015

8 EATON www.eaton.com

Data subject to change without notice. UBW Technical Manual | 45


Molded-Case Circuit Breakers

Time Current Curves


225, 250, 400, 600

1000 kA

500 kA

400

250
600

225

Available Short Circuit Current, kA rms


100 kA

50 kA

10 kA

5 kA

1 kA
10,000,000

5,000,000

1,000,000

500,000

100,000

10,000
Peak Let-Through I2t, A2 sec

Peak Let-Through I2t Curve — 240 V

1000 kA

500 kA
225
400
600

350

Available Short Circuit Current, kA rms

100 kA

50 kA

10 kA

5 kA
symm. 1/2 cycle
avail. Ip for 1st

1 kA
100 kA

50 kA

10 kA

1 kA
5 kA

Peak Let-Through Current, kA

Peak Let-Through Current Curve — 240 V

46 | 1-800-ASK-4WEG | www/weg/met Data subject to change without notice.


Molded-Case Circuit Breakers

100 kA

400
600

50 kA

Available Short Circuit Current, kA rms


10 kA

250

5 kA

1 kA
10,000,000

5,000,000

1,000,000

500,000

100,000
Peak Let-Through I2t, A2 sec

Peak Let-Through I 2t — 600 V

100 kA
600

400

50 kA Available Short Circuit Current, kA rms

10 kA
250

5 kA
symm. 1/2 cycle
avail. Ip for 1st

1 kA
100 kA

50 kA

10 kA

1 kA
5 kA

Peak Let-Through Current, kA

Peak Let-Through Current — 600 V

Data subject to change without notice. UBW Technical Manual | 47


EATON www.eaton.com 21
Molded-Case Circuit Breakers

1000 kA

500 kA

400
600

225
250

Available Short Circuit Current, kA rms


100 kA

50 kA

10 kA

5 kA

1 kA
10,000,000

5,000,000

1,000,000

500,000

100,000
Peak Let-Through I2t, A2 sec

Peak Let-Through I2t Curve — 480 V

1000 kA

500 kA
400
600

Available Short Circuit Current, kA rms

100 kA

50 kA
250

10 kA
225

5 kA
symm. 1/2 cycle
avail. Ip for 1st

1 kA
100 kA

50 kA

10 kA

1 kA
5 kA

Peak Let-Through Current, kA

Peak Let-Through Current — 480 V

48 | 1-800-ASK-4WEG | www/weg/met Data subject to change without notice.


Molded-Case Circuit Breakers
UBW Dimensions
(Outside)
Frames 225, 250, 400, 600, 800, 1200, 2500

Overall Dimensions
Frame Size A B C
Inches/mm Inches/mm Inches/mm
225 6/152 4.1/104 3.5/89

250 10/254 4.1/104 4.3/110

400 10.12/257 5.49/139 4.3/110

600 10.75/273.05 8.25/209.6 4/101.57

800 16/406.4 8.22/208.74 4.06/103.18

1200 16/406.4 8.25/209.55 5.5/139.7

2500 16/406.4 15.5/393.7 9./228.6


Data subject to change without notice. UBW Technical Manual | 49
Molded-Case Circuit Breakers

Mounting Hardware and Mounting Holes Dimensions

Metric
Frame Qty Std Bolt Size Size
225 4 5/32-32 M4x0.70

250 4 1/4-20 M6-1.0

400 4 1/4-20 M6-1.0

600 4 1/4-20 M6-1.0

800 4 1/4-20 M6-1.0

1200* 4 5/16-18 M8-1.25

2500^ 4 3/8-16 M11-1.50


^ Supplied with Breaker

50 | 1-800-ASK-4WEG | www/weg/met Data subject to change without notice.


Molded-Case Circuit Breakers

Rotary Handle Mounting Hardware Provided


Mechanism Kit
UBW 225 (2)8-32 x 1.5 screw, (2)8-32 x 3.5 screw, (4) .164
lock washer, (2).164 flat washer
UBW250 (2)1/4-20 x 2.75 screw, (2)1/4-20 x 4.5 screw,
(2)10-32 x 3.375 screw, (4) .250 lock washer, (2)
.250 flat washer, (2) 190 lock washer, (2) #10 flat
washer
UBW400 (2)1/4-20 x 1.5 screw, (2)1/4-20 x 4.5 screw,
(2)10-32 x 3.375 screw, (4) .250 lock washer, (2)
.250 flat washer, (2) 190 lock washer, (2) #10 flat
washer
UBW600/800 ($) 8-32 x 2.125 screw, (4) 1/4-20 x 20 screw,
(2)8-32 x2.50 screw, (4) .250 lock washer, ($)
.250 flat washer, (4) .164 lock washer

Data subject to change without notice. UBW Technical Manual | 51