Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

Request for Information No. 000209.

Title: RFI #210: Water Feature Power Distribution Panel Requirements

Project: Eau Claire Plaza Redevelopment – Phase 2


Project No.: AB003836-2003308

Discipline: Electrical, Fountain


Date: 2024-May-13 18:31
Required By: 2024-May-17

Question

Date: 2024-May-13

Please see attached RFI #210: Water Feature Power Distribution Panel Requirements for your review and
comments.

Suggestion/Comments

Attachment(s)
RF 210-I-E1, Water Feature Power Distribution Panel Requirments

Sonia Bakhtiar
Per: Stuart Olson Construction Ltd. (CAL)

Electrical
Response

Date: 2024-May-13

DIALOG
300, 134 - 11 Avenue SE
Calgary, Alberta, T2G 0X5
Canada
Unless noted otherwise, you are instructed to proceed with the following on the assumption that no change in the
Contract Price or Schedule is involved. Should you disagree, prior to proceeding, notify us in writing.

Project No.: 1/3


Request for Information No. 000209.0

As indicated in Electrical BP Revisions package 2024-04-19 there is a 200A 120/208V 3Ø 4W point provided
by base building to the water feature.

All electrical past the single point connection is by the water feature designer.

Suggestion/Comments

Attachment(s)

Russell Murray
Per: DIALOG

Fountain
Response

Date: 2024-May-15

Crystal Fountains
60 Snow Blvd
Unit 3
Toronto, Ontario, L4K 4B3
Unless noted otherwise, you are instructed to proceed with the following on the assumption that no change in the
Contract Price or Schedule is involved. Should you disagree, prior to proceeding, notify us in writing.

No concerns from Crystal Fountains. Please provide the Distribution Panel and Design & Details as suggested.

Suggestion/Comments

Attachment(s)

Project No.: 2/3


Request for Information No. 000209.0

Peter Lacza
Per: Crystal Fountains

Attachment(s)

Project No.: 3/3


InCom Electric Corp.
5740 Burbank Cres. SE
Calgary, AB T2H 1Z6

REQUEST FOR INFORMATION (RFI)


RFI NUMBER: 1 STARTUP SYSTEM NO.: DATE: 5/8/2024
PROJECT NUMBER: 24-01-0022 PROJECT NAME: Eau Claire Plaza, Water Feature
PREPARED BY: Neal Dann DISCIPLINE: Electrical
SUBJECT: Water Feature Power Distribution Panel
CONTRACT NUMBER: PO#0000010223 CONTRACT NAME: Eau Claire Plaza, Water Feature
LOCATION: Lumber Co. Building, basement
TO: Lyle Horodecki OF: Ful-Flo Industries

REFERENCE DRAWING(S): PTA-2, 11252-IFT-WF-510 REV.: DCN/FCN:

SPECIFICATION(S): PTA-2 REV.: SCN/FCR:

There is a power distribution panel required as per PTA-2 drawing 11252-IFT-WF-510 but there are no
specs, single line or panel schedule provided for this. A cash allowance of $1600 has been carried for the
REASON FOR RFI:
supply and install of a 3ph, 4w, 120/208v, 400a,42cct branch power panel including the tub, interior and
cover.

RECOMMENDED Provide a design detailing the panel requirments including a panel schedule, voltage rating, phases,
SOLUTION: amperage rating, kA rating, circuit count requirment and breaker requirements for connected loads
REPLY REQUIRED BY: May 15, 2024

IMPACTS: Cost (additional equipment/requirments/breakers), schedule (lead time, shop drawings)

CONTRACTOR SIGNATURE: DATE:


REVIEWED BY
CONSTRUCTION DATE:
COORDINATOR:

REVIEWED BY FIELD
DATE:
SUBCONTRACT MANAGER:

INFORMATION TO REQUESTOR
TO: FROM:
TO: FROM:
RESPONSE:

RESPONSE BY: DATE:


REVIEWED BY: DATE:
No specification,
panel
schedule,detail,
breakers provided
cash allowance
carried based on this
information only

You might also like