Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

Transformer Bushings for GIS

.
Oil to SF6 Connections
GARIP RTKG 72.5 - 550 kV
SQS certified
ISO 9001 / ISO 14001

Bushings
RIP - Technology for SF6 / Oil - Bushings

In modern metal enclosed switchgear SF6 - gas is used


as an extinguishing and insulating medium, ensuring
highest security standard for operating staff and resi-
dents, especially in most confined and dense populated
areas.
As a result, today’s space saving design requires excel-
lent mechanical and electrical performance of all com-
ponents involved.
Micafil’s contribution to this world - wide development is
it’s new product range of GARIP bushings. These have
been designed for the direct single phase connection
between power transformers and gas insulated switch-
gear (GIS) for rated voltages of 72.5 kV up to 550 kV.

Since more than 40 years Micafil AG produces high vol-


tage bushings made with Vacuum Resin Impregnated
Paper Technology (RIP).
We are proud of our leading position in this field, making
available to our customers profound expertise in the
latest state of the art technology, which is based upon
more than 50000 RIP - bushings successful in operation.

The insulation body of the GARIP condenser bushing


series consists of a robust and solid core, made of
wound crepe paper and inserted aluminium foils for field
control, carefully vacuum dried and subsequently
impregnated with special epoxy resin.

The basic procedure for this new kind of manufacture


was originally developed by Micafil AG in Switzerland
already in 1958 and continuously improved in the course
of four decades.

Advanced standardisation, highly skilled craftsmanship


and computer - aided engineering guarantee today’s
most reliable and advanced insulation system for every
voltage level.

Main advantages of Micafil’s


RIP - technology
• Short delivery times
• Low dielectric losses (tan δ ~ 0.35 %)
• Partial discharge free up to double service voltage
• Fully dry, maintenance free
• Oil - free and environmental friendly
• Highest mechanical and thermal properties
• Robust design and vandalism resistant
• Option for any operating position
• Gas and oil tight
• Easy handling

2
Design and Accessories
.

Manufacturing of the main RIP - insulating body includes


the solid and non - removable conductor, resulting in a
perfect reliable structure, matching today’s stringent
electrical, thermal and mechanical requirements.

Main features of the SF6 interface


Dimensions and physical properties of GARIP type bu-
shings fully comply with all standard aspects according
to IEC publication 61639.
This enables complete compatibility of the interface for
both, producers of transformers and GIS manufacturers.
The specifically shaped head both acts as silver- coated
terminal with tapped holes as well as epoxy - coated high
voltage electrode. Therefore additional shields are not
necessary. Only adjacent conductor parts should be well
adapted to the bushing terminal.

Intended for the whole range of rated voltages from 72.5


to 550 kV, Micafil’s GARIP bushings are specified up to
750 kPa working pressure SF6 in the GIS.
Our new series of GARIP bushings require minimum
functional SF6 - gas pressures of 350 kPa (72.5 - 420 kV)
and 390 kPa (525 kV) respectively.

Flange design
All flanges are made of corrosion proof aluminium
alloys. Standard equipment encompasses a test tap, four
threads at the transformer side flange plate either for
grounding or as forcing threads and a de - aeration on
the transformer side.
A set of most advanced seals between the main insula-
ting RIP - body and the flange systems guarantees per-
manent gas and oil tightness during operation.

Test tap
All GARIP bushings include a self - grounded test tap
connecting the outer control layer of the RIP - body for
capacitance and tang measurement on site.

Main features of the transformer interface


The scope of new GARIP bushings offers CT spaces of
0, 300, and 600 mm as a standard equipment (note:
L6min = 100 mm for 170 kV types).
Special shields, which are dismountable for better
handling, are supplied for all bushings with rated voltage
greater than 72.5 kV.

Customised design for every Oil / SF6 application is avai-


lable on request.

3
Technical Data and Dimensions
Dimension Flange dimensions for: RTKG 72.5 -350 / 2000
drawing D13 RTKG 72.5 -350 / 2500
4 x M12 D14 Aluminium, RTKG 123 -550 / 2000
25 deep silver plated RTKG 123 -550 / 2500
RTKG 145 -650 / 2000

80
RTKG 170 -750 / 2000

22.5°
D10
45
L2

D9 °
Sealing area
A Ra = 1.6 (N7)
D8 View A:

D12
D11
SF6 side
s2

B
LF

Test tap
s1
L

L6 20

n11 x Øw
D1 Sealing area
Ra = 3.2 (N8) De-aeration of transformer
opposite to test tap 22.5°
L16

Grounded D2 45
length °
D5
20

D7 Shields removable View B:

D4
D3
Oil side
115

Ø18 Types 123kV - 245 kV


40
85
c6

n3 x Øv
20

Types 362kV - 525 kV


Copper, M12 (2 x 180°) M12 (2 x 180°)
d4
thickness 30 mm d5
d6

RTKG 362 -1300 / 2000


Flange RTKG 245 -1050 / 2000 RTKG 420 -1550 / 2000
dimensions for: RTKG 170 - 750 / 2500 RTKG 245 -1050 / 2500 RTKG 525 -1800 / 2000

22.5
22.5° 11.5° ° 11.5° 22.5
°
45
°

View A:
D11
D12

D11
D12

D11
D12

SF6 side

n11 x Øw n11 x Øw n11 x Øw


De-aeration of transformer
15° 15° 22.5
opposite to test tap 30
°
30
° 11.5° °
n3 x Øv n3 x Øv n3 x Øv

View B:
D4
D3
D4
D3

D4
D3

Oil side

M12 (2 x 180°) M12 (2 x 180°) M12 (2 x 180°) M12 (2 x 180°) M12 (2 x 180°) M12 (2 x 180°)

prospectus No. D 4352 E 4


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44

Dielectric data Dimensions of the bushing


Conductor Mechanical Adjacent
.
Type
loading design GIS Core, Oil side terminal Flange, Flange, Core, Terminal
IEC 60137 IEEE C57.19.01-2000 Flange
oil side and shield oil side SF6 side SF6 side SF6 side

Condenser bushing,
oil to SF6,

prospectus No. D 4352 E


for transformers
DGIS L L6 L16 D1 D7 c6 d4 d5 d6 LF s1 s2 D2 D3 D4 D5 n3 x Øv D9 D10 D11 D12 n11 x Øw L2 D8 D13 D14

current, 2s
pressure at 20°C

Rated thermal
Max. operating

Max. operating

Rated voltage Ur
Ur / √3
AC test voltage
BIL 1,2/50 µs
SIL 250/2500 µs
System voltage
to-ground voltage
AC test voltage
BIL 1,2/50 µs
SIL 250/2500 µs
current
short time
Weight
load, 1 Min.
bending moment
on the flange
operating
GARIP min.

Rated max. line-


SF6: Min.

Cantilever test
RTKG kPa
kV kV kV kV kV kV kV kV kV kV A kA kg kN kNm (abs) mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm n x mm mm mm mm mm n x mm mm mm mm mm

2400 37 770 0 175


RTKG 72.5-350/2000 72.5 42 140 325 - 69 44 160 350 - 2200 60 48 4 5 350 250 1070 300 475 130 90 - 52 - - 150 20 20 165 250 290 220 8 x Ø16 200 260 285 315 8 x Ø16 330 130 99 70
2000 58 1370 600 775
3000 45 770 0 175
RTKG 72.5-350/2500 72.5 42 140 325 - 69 44 160 350 - 2700 75 60 4 5 350 250 1070 300 475 130 110 - 52 - - 150 20 20 165 250 290 220 8 x Ø16 200 260 285 315 8 x Ø16 330 130 99 70
2450 75 1370 600 775
2200 49 1180 0 310
RTKG 123-550/2000 123 71 230 550 - 92 73 185 450 - 2040 55 59 4 10 350 300 1480 300 610 130 90 220 52 107 160 150 20 20 165 250 290 220 8 x Ø16 220 280 305 335 8 x Ø16 520 130 99 70
1900 69 1780 600 910
2850 65 1180 0 310
RTKG 123-550/2500 123 71 230 550 - 92 73 185 450 - 2650 71 80 4 10 350 300 1480 300 610 130 110 220 52 140 180 150 20 20 165 250 290 220 8 x Ø16 220 280 305 335 8 x Ø16 520 130 99 70
2500 95 1780 600 910
2100 51 1230 0 360
RTKG 145-650/2000 145 84 275 650 - 138 88 310 650 - 2000 53 61 4 10 350 300 1530 300 660 130 90 220 52 107 160 150 20 20 165 250 290 220 8 x Ø16 220 280 305 335 8 x Ø16 520 130 99 70
1900 71 1830 600 960
2100 55 1390 100 520 Var1:107/160
RTKG 170-750/2000 170 98 325 750 - 161 102 365 750 - 2000 53 62 4 10 350 300 1590 300 720 130 90 220 52 150 20 20 165 250 290 220 8 x Ø16 220 280 305 335 8 x Ø16 520 130 99 70
1900 72 1890 600 1020 Var2:140/180

2600 75 1390 100 520


RTKG 170-750/2500 170 98 325 750 - 161 102 365 750 - 2500 65 85 4 10 350 300 1590 300 720 152 110 220 52 140 180 150 20 20 190 290 335 260 12 x Ø16 220 280 305 335 8 x Ø16 520 152 99 70
2400 100 1890 600 1020
2000 95 1740 0 590 Var1:107/160
RTKG 245-1050/2000 245 141 460 1050 850 230 146 425 900 - 1900 50 110 4 20 350 450 2040 300 890 172 90 220 52 180 25 25 210 290 335 260 12 x Ø16 450 510 535 565 16 x Ø16 770 172 139 110
1750 123 2340 600 1190 Var2:140/180

2600 132 1740 0 590


RTKG 245-1050/2500 245 141 460 1050 850 230 146 425 900 - 2500 65 154 4 20 350 450 2040 300 890 200 110 220 52 140 180 180 25 25 240 400 450 370 12 x Ø16 450 510 535 565 16 x Ø16 770 200 139 110
2400 173 2340 600 1190
2100 230 2110 0 650
RTKG 362-1300/2000 362 209 570 1300 1050 345 220 520 1175 825 2000 53 260 4 40 350 540 2410 300 950 282 140 250 52 176 292 180 30 30 340 620 680 580 16 x Ø20 540 600 640 690 16 x Ø20 1050 282 139 110
1900 290 2710 600 1250
Technical Data and Dimensions

2100 240 2180 0 720


RTKG 420-1550/2000 420 242 680 1550 1175 - - - - - 2000 53 270 4 40 350 540 2480 300 1020 282 140 250 52 176 292 180 30 30 340 620 680 580 16 x Ø20 540 600 640 690 16 x Ø20 1050 282 139 110
1900 300 2780 600 1320
2000 300 2310 0 850
RTKG 525-1800/2000 525 303 790 1800 1300 500 318 750 1675 1175 1900 50 335 4 40 390 540 2610 300 1150 342 150 250 52 176 292 180 30 30 400 620 680 580 16 x Ø20 540 600 640 690 16 x Ø20 1050 342 139 110
1800 375 2910 600 1450

explanations of the columns:

5 Lightning impulse withstand voltage according to IEC 60137 12 Conductor loading according to IEC 60137 & IEEE C57.19.00 25 The copper terminal is flat with two holes Ø18 mm
(max. daily means: oil 95°C, SF6 - gas 75°C)
6 Switching impulse withstand voltage according to IEC 60137 26 Bushings Ur > 72.5 kV are equipped with an oil end shield. The shield is epoxy coated
13 Short time current after operation with rated current
10 Lightning impulse withstand voltage according to IEEE C57.19.01 27 For better handling the shield is dismountable.
20 CT spaces L6 as standard, other lengths on request.
Note: For the 170 kV / 2000 A and 245 kV / 2000 A types, two different shield sizes are
11 Switching impulse withstand voltage according to IEEE C57.19.01 Note: L6 min = 100 mm for 170 kV types
available depending on the transformer current

5
General Informations

Conductor loading Type designation


Rated current dependent on the bushing lower length The type designation is included in an overall system. An
(see "Technical Data" page 5 & 6, column 12). example of nomenclature used to designate our GARIP
Bushings selected with Ir not less than 120 % of the rated bushings:
current of the transformer are considered to be able to GARIP RTKG 245 -1050 / 2000
withstand the overload conditions according to IEC
Publication 60354 (Loading guide).
Nominal current (A)
Lightning impulse
Recommendations for bushing installation voltage (kV)
Transformer
Rated voltage (kV)
The field strength in the oil on the surface of the shield
insulation must be limited to values normal for insulated R = RIP Insulation
components. As a guideline minimum distances A to T = Transformer application
grounded transformer parts are given below: K = Short oil side part
G = SF6 - gas application
Bushing series
Type AC test A
RTKG voltage (kV) (mm) Testing of the bushing
123 185 130 Each bushing undergoes routine testing before leaving
230 145 the factory, either according to IEC 60137 or IEEE
C57.19.00.
145 275 170
310 200 The standard tests include:
• Tan δ, capacitance and partial discharge measure-
170 325 210 ment
365 230 • Power frequency test
245 460 300 • Lightning impulse test (if applicable)
• Leakage test
362 570 400
420 630 450 Ordering particulars
680 500
When ordering please state:
525 750 550 • Type and catalogue no. see the table below
790 600 • CT space L6, see "Technical Data" page 5 & 6, column
20
• For 170 kV / 2000 A respective 245 kV / 2000 A only:
choose the size of oil side shield depending on the
transformer current; see "Technical Data" page 5 & 6,
columns 26 & 27

Bushing type Catalogue no.


GARIP RTKG 72.5 - 350 / 2000 HLJM 154484
GARIP RTKG 72.5 - 350 / 2500 HLJM 154964
GARIP RTKG 123 - 550 / 2000 HLJM 154504
GARIP RTKG 123 - 550 / 2500 HLJM 154514
GARIP RTKG 145 - 650 / 2000 HLJM 154524
GIS A
Observe the minimum enclosure GARIP RTKG 170 -750 / 2000 HLJM 154534
diameter DGIS as well as the minimum GARIP RTKG 170 -750 / 2500 HLJM 154544
operating SF 6 - gas pressure (see
"Technical Data" page 5 & 6, columns GARIP RTKG 245 -1050 / 2000 HLJM 154554
17 & 18). Adjacent conductor parts should GARIP RTKG 245 -1050 / 2500 HLJM 154564
be well adapted to the bushing terminal.
GARIP RTKG 362 -1300 / 2000 HLJM 154574
General
Because the bushing is completely dry it can be GARIP RTKG 420 -1550 / 2000 HLJM 154584
operated vertically or horizontally or in any position. GARIP RTKG 525 -1800 / 2000 HLJM 154594

6
Continuity over the last 75 Years
.
Photography & layout by RGB Photo GmbH, Zurich
-
Alternations reserved
Printed in Switzerland
Prospectus no. D 4352 E

Micafil AG Phone +41 (0)58 586 03 33


GARIP2003en / SO

Badenerstrasse 780 Fax +41 (0)58 586 04 44


CH - 8048 Zurich E-mail info @ micafil.ch
Switzerland Web www.micafil.ch