RTKG Garip - General Info
RTKG Garip - General Info
.
Oil to SF6 Connections
GARIP RTKG 72.5 - 550 kV
SQS certified
ISO 9001 / ISO 14001
Bushings
RIP - Technology for SF6 / Oil - Bushings
2
Design and Accessories
.
Flange design
All flanges are made of corrosion proof aluminium
alloys. Standard equipment encompasses a test tap, four
threads at the transformer side flange plate either for
grounding or as forcing threads and a de - aeration on
the transformer side.
A set of most advanced seals between the main insula-
ting RIP - body and the flange systems guarantees per-
manent gas and oil tightness during operation.
Test tap
All GARIP bushings include a self - grounded test tap
connecting the outer control layer of the RIP - body for
capacitance and tang measurement on site.
3
Technical Data and Dimensions
Dimension Flange dimensions for: RTKG 72.5 -350 / 2000
drawing D13 RTKG 72.5 -350 / 2500
4 x M12 D14 Aluminium, RTKG 123 -550 / 2000
25 deep silver plated RTKG 123 -550 / 2500
RTKG 145 -650 / 2000
80
RTKG 170 -750 / 2000
22.5°
D10
45
L2
D9 °
Sealing area
A Ra = 1.6 (N7)
D8 View A:
D12
D11
SF6 side
s2
B
LF
Test tap
s1
L
L6 20
n11 x Øw
D1 Sealing area
Ra = 3.2 (N8) De-aeration of transformer
opposite to test tap 22.5°
L16
Grounded D2 45
length °
D5
20
D4
D3
Oil side
115
n3 x Øv
20
22.5
22.5° 11.5° ° 11.5° 22.5
°
45
°
View A:
D11
D12
D11
D12
D11
D12
SF6 side
View B:
D4
D3
D4
D3
D4
D3
Oil side
M12 (2 x 180°) M12 (2 x 180°) M12 (2 x 180°) M12 (2 x 180°) M12 (2 x 180°) M12 (2 x 180°)
Condenser bushing,
oil to SF6,
current, 2s
pressure at 20°C
Rated thermal
Max. operating
Max. operating
Rated voltage Ur
Ur / √3
AC test voltage
BIL 1,2/50 µs
SIL 250/2500 µs
System voltage
to-ground voltage
AC test voltage
BIL 1,2/50 µs
SIL 250/2500 µs
current
short time
Weight
load, 1 Min.
bending moment
on the flange
operating
GARIP min.
Cantilever test
RTKG kPa
kV kV kV kV kV kV kV kV kV kV A kA kg kN kNm (abs) mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm n x mm mm mm mm mm n x mm mm mm mm mm
5 Lightning impulse withstand voltage according to IEC 60137 12 Conductor loading according to IEC 60137 & IEEE C57.19.00 25 The copper terminal is flat with two holes Ø18 mm
(max. daily means: oil 95°C, SF6 - gas 75°C)
6 Switching impulse withstand voltage according to IEC 60137 26 Bushings Ur > 72.5 kV are equipped with an oil end shield. The shield is epoxy coated
13 Short time current after operation with rated current
10 Lightning impulse withstand voltage according to IEEE C57.19.01 27 For better handling the shield is dismountable.
20 CT spaces L6 as standard, other lengths on request.
Note: For the 170 kV / 2000 A and 245 kV / 2000 A types, two different shield sizes are
11 Switching impulse withstand voltage according to IEEE C57.19.01 Note: L6 min = 100 mm for 170 kV types
available depending on the transformer current
5