956-0120 Onan DFE (spec L) Diesel Genset Operators manual (05-1981)
956-0120 Onan DFE (spec L) Diesel Genset Operators manual (05-1981)
956-0120 Onan DFE (spec L) Diesel Genset Operators manual (05-1981)
The tollowlng symbols rn this manual signal potentially 0 Before starting work on the generating set, disconnect
dangerous conditions to the operator or equipment. Read batteries. This will prevent starting the set accidentally.
this manual carefully. Know when these conditions can
exrst. Then, take necessary steps to protect personnel as Fuel System
well as equrpment. 0 DO NOT fill fuel tanks while enaine is runnina. unless
Read your manual and become thoroughly acquainted w ~ t h tanks are outside engine comcartrnent. ~ u e r c o n t a c t
IP and your equrpment before you start your unit. These with hot engine or exhaust is a potential fire hazard.
recommendations and the follow~ngsafety precautions are
for your protection.
0 DO NOT SMOKE OR USE AN OPEN FLAME in the
v~cinityof the generator set or fuel tank. Internal
Fuels, electrical equipment, batteries, exhaust gases and combustion engine fuels are highly flammable.
movrng parts present potential hazards that could result in
serious, personal injury. Take care in following these Fuel l~nesmust be adequately secured and free from
recommended procedures. leaks. Plping at the engine should be approved flexible
line. Do not use copper piping on flexible lines as
This sy~raboli%used fhl~~dlgh- copper will work harden and become brittle.
out this manuad to warn of
Be sure all fuel supplies have a positive shutoff valve.
possibbe serious personal injury or death.
Guard Against Electric Shock
Thissymbo'refersfopossib'e w Remove electric power before removing protective
egujppnent cdamage. shields or touching electrical equipment. Use rubber
~nsulativemats placed on dry wood platforms over
floors that are metal or concrete when around electrical
General equipment. Do not weardamp clothing (particularly wet
shoes) or allow skin surfaces to bedamp when handling
Keep your electric generating set and the surrounding
electrical equipment.
area clean and free Prom obstruct~ons.Remove any
debr~sfrom set and keep the floor clean and dry. 0 Use extreme caution when working on electrical com-
* ponents. High voltages cause injury or death. DON'T
Provrde appropriate frre extingurshers and install them
In convenient locations. Consult your local fire depart- tamper wrth interlocks.
the 'Orrect type of extinguisher to use. Do not
Follow all state and local electrical codes. Have all
use foam on efectrlcal fires. Use extinguisher rated ABC
electrical installations performed by a qualified licens-
by NFPA.
ed electrician. Tag open switches.
o Make sure that all fasteners on the generating set are
secure. Tighten supports and clamps, keep guards in DO NOT SMOKE while servicing batteries. Lead acid
positlon over fans, driving belts, etc. batteries emit a highly explosive hydrogen gas that can
be Ignited by electrical arcing or by smoking.
e Do not wear loose clothlng in the v~cinityof moving
parts, OF jewelry while working on electr~cal
equipment.
Exhaust Gases Are Toxic
Loose clothing and jewelry can become caught in Provide an adequate exhaust system to properly expel
rnovlng parts Jewelry can short out electrical contacts; discharged gases. Inspect exhaust system dally for leaks
cause shock or burn~ng. per the maintenance schedule. Ensure that exhaust
manifolds are secure and not warped. Do not use
8 I f adj~stmentmust be made while the unit is running, exhaust gases to heat a compartment.
use extreme caution around hot manifolds, moving
parts, etc. w Be sure the u n ~ is
t well ventilated.
0 Do no: work on this equrpment when mentally or Keep the Unit and Surrounding Area Clean
physically fatigued.
Make sure that oily rags are not left on or near the
8 Coolants under pressure have a higher boiling point engine.
than water. DO NOT open a radiator or heat exchanger
pressure cap while the englne IS running. Bleed the 0 Remove all 011deposits. Remove all unnecessary grease
system pressure flrst. and 011from the unit. Accumulated grease and oil can
cause overheating and subsequent englne damage and
may present a potential fire hazard.
Keep y o u r hands away from moving parts.
LS- 3
Contents
TITLE PAGE
Safety Precautions.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Inside Cover
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Operation .................................................. 19
General Maintenance ....................................... 25
WARNING 1
TO AVOID POSSIBLE PERSONAL INJURY OR
EQUIPMENT DAMAGE, A QUALIFIED ELECTRI-
C I A N OR A N A U T H O R I Z E D SERVICE
REPRESENTATIVE MUST PERFORM IN-
STALLATION AND ALL SERVICE.
ntroduction
The manual should be used in conjunction with the 180.0 DFE 15R 1 1 L
Cummins engine manual, for specific engine infor-
mation.
TTT 1T
I 2 3 4 5
Left side and right side are considered when viewed from the
engine or front end of the generating set.
Dizziness Vomiting
Intense Headache Muscular Twitching
Weakness and Sleepiness Throbblng in Temples
If you experience any of the above symptoms, get out into fresh air
immediately.
ENGINE DETAILS
Engine Manufacturer.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cummins
Engine Series.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NT 855-G
Numbers of Cylinders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Displacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 855 in3 (14.0 litre)
BHP@ 1800r/min . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 355 (265 kW)
Compression Ratio.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14.1:l
Bore . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.50 inch (140 mm)
Stroke ................................................. 6.00 inch (132 mm)
Fuel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Diesel
Battery Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Battery Group (Two 12-Volt, 225 A.H. [a10 k c ] ) . . . . . . . . . . 8D
Starting Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Solenoid Shift
Governor Regulation ................................... lsochronous
Battery Charging Current 35-Amperes Max
GENERATOR DETAILS
Type ..................................................
Ratings
60 Hertz Continuous Standby.. ....................... 155 kW (193.75 kVA)
50 Hertz Continuous Standby.. ....................... 130 kW (162.5 kVA)
AC Voltage Regulation ................................. +2 O/o
GENERAL AC Panel
An Onan DFE series electric generating set IS a AC Voltmeter: Indicates AC generator output voltage.
complete unit consisting of an engine driven AC Dual range instrument: measurement range i n use
generator, w ~ t hstandard and optional controls and shown on indicator light.
accessories as ordered.
Voltage Regulator: Rheostat, provides approximately
plus or minus 5% adjustment of the rated output
ENGINE voltage.
The engine on the DFE is a Cummins NT855-G, as
described in the engine manual. Basic measurements Exciter Circuit Breaker: Provides generator exciter
and requirements w i l l be f o u n d under and regulator protection from overheating, in the
SPECIFICATIONS. For operation, maintenance and event of certain failure modes of the generator,
service information, consult the Cummins manual. exciter and voltage regulator.
Battery Charge Rate DC Ammeter: lndicates battery Lamp Test: Press to test warning lamp bulbs (when
charging current. engine is running only).
Warning Light: lnd~cates"Fault" in engine operation. Frequency Meter: lndicates the frequency of the
generator output in hertz. It can be used to check
engine speed. (Each hertz equals 30 rlmin.)
R U N N I N G TIME 'A T U R N FASTENERS- T U R N B O T H
METER-, T O OPEN H I N G E 0 C O N T R O L
PANEL DOORS
INDICATOR LAMPS
-- - - -
INDICATE UPPER AND LO
PANEL LIGHT AND SWITCH
O N VOLTMETER A N D AMMETER-
DUAL RANGE
AC V O L T M E T E @
I1I
'.
O I L PRESSURE
GAUGE
VOLTAGE
ADJUSTING
RHEOSTAT
P H A S E SELECTOR SWITCH
@, I WATER TEMPERATURE
GAUGE
U D C AMMETER
I \ k w I 1I
- 1 \ * ! RUN-STOP-REMOTE SWITCH
POTENTIOMETER
'/, T U R NFASTENERS- T U R N B O T H
D U A L R A N G E AC AMMETER- C R E W S T O OPEN HINGED C O N T R O L
PANEL DOORS
INDICATOR LAMPS
INDICATE UPPER AND LOWER SCALE
NEL LIGHT AND SWITCH
O N VOLTMETER A N D AMMETER
DUAL RANGE
AC VOLTMETER OIL PRESSURE
GAUGE
VOLTAGE
ADJUSTING
RHEOSTAT
WATER TEMPERATURE
GAUGE
D C AMMETER
UN-STOP-REMOTE SWITCH
LSO A RESET SWITCH FOR
ENGINE M O N I T O R )
FAULT LAMPS
ROTATING
DIODES
COOLANT F l L T E
SHUT-OFF VALV
GENERAL
Installations must be considered individually. Use Radiator set cooling air travels from the rearof theset
these instructions as a general guide. All installations and is removed by a pusher fan which blows out
must meet regulations of state and local building through the radiator. Locate the air inlet to the rear of
codes, fire ordinances, etc., which may affect installa- the set. Make the inlet opening at least 1'12' times
tion details. See Figure 6. larger than the radiator.
Requirements to be considered prior to installation: Locate the cooling air outlet directly in front of the
1. Level mounting surface. radiator and as close as possible. The opening size
2. Adequate cooling air. should be at least llh times as large as the radiator
area. Length and shape of the air outlet duct should
3. Adequate fresh induction air.
offer minimum restriction to air flow. Use a duct of
4. Discharge of circulated air. canvas or sheet metal between the radiator and the air
5. Discharge of exhaust gases. outlet opening. The duct prevents recirculation of
6. Electrical connections heated air.
7. Fuel installation.
8. Water supply (city water cooling). Provide a means of restricting the air flow in cold
weather to keep the room or compartment
9. Accessibility for operation and servicing temperature at a normal point. Keep in mind,
10. Vibration isolation. however, that the engine must get adequate cooling
11. Noise levels. air.
,SWEEPING ELBOW
EXHAUST L I N E
F L E X I B L E SECTION
9
COOLING SYSTEM This system reduces set enclosure airflow re-
quirements and noise levels. Proper operation is
Standard Radiator Cooling, uses a set mounted dependent on a constant supply of cooling water. The
radiator and engine driven pusher type fan to cool
system cannot be protected from freezing. See Figure
engine water jacket. Air travels from the generator
8.
end of the set, across the engine and out through the
radiator. An integral discharge duct adapter flange
surrounds the radiator grille.
pTRA -
Heat Exchanger Cooling (optional), uses a shell and
tube type heat exchanger instead of the standard ANTI-SI PHON
radiator and fan. Engine jacket coolant circulates
through the shell side of the heat exchanger, while
raw cooling water is pumped through the tubes.
Engine coolant and raw water do not mix. This type of N
FROM
ENGINE
FIGURE 8. TYPICAL STANDPIPE SYSTEM
-\ HEAT EXCHANGER
SOLENOID
VALVE
(OPENS WHEN
SET IS RUNNING)
ADJUSTABLE /
Remote Radiator Cooling (optional), substitutes a
VALVE STRAINER remote mounted radiator and an electrically driven
(RATE OF FLOW) fan, for the set mounted components. Removal of the
radiator and fan from the set reduces set enclosure
FIGURE 7. TYPICAL HEAT EXCHANGER SYSTEM airflow requirements and noise levels without forcing
dependence on a continuous cooling water supply.
The remote radiator system can be completely
protected against freezing.
WAR~ING]
-.--
Pipe POISONOUS exhaust gas outside
enclosure. Inhalation of exhaust gases can
result in serious injury or death.
DRIP C A P
MAXIMUM PIPE LENGTH 460 315
I N FEETIMM (140) (96)
HOLES IN END O
INNER SLEEVE
9 INCH MINIMUM
TYPE OF FITTING 6
Inches - - --
Inch - -
--
pp
.- -
STANDARD ELBOW 16
Feet (Metres) --- (4 88) - -
FUEL CONNECTIONS
Check local regulations governing the installation of
a fuel supply tank.
INJECTOR F U E L
ELECTRIC
FUEL SOLENOI
LINE II
tI
tI
tI
I) UNDERGROUND
II
II FUEL TANK
rI
11
II
Ib
*PI5 U
Re"
(W12 WIRE)
NNECT L O O S E W I R E
O M TERMINAL # 6 3
EITHER H 3 , H 4 . H 5 O R
DEPENDING O N
L T A G E SELECTED
GROUNDING
Typical requirements for bonding and grounding are
given in the National Electrical Code, 1981 Article
250.
For 3 phase loads, connect separate load wires to Circuit and System Grounding
each of the set terminals L1, L2 and L3. Single phase This refers to the intentional grounding of a circuit
output of the higher nameplate voltage is obtained conductor or conductors. The design and installation
between any two 3 phase terminals as shown in Fig- of grounding system encompasses many considera-
ure 22. tions, such as multiple transformers, standby genera-
tors, ground protection, physical locations of equip-
The terminal marked LO can be grounded. For 1 ment and conductors, just to mention a few.
phase loads, connect the neutral (white) load wire to
the LO terminal. Connect the black load wire to any Although the consulting engineer and installer are
one of the other three terminals-L1, L2 or L3. Three responsible forthe design and wiring of each particu-
separate 1 phase circuits are available. Total 1 phase lar grounding application, the basic grounding
current available is 2/3 rated 3 phase capacity of requirements must conform to national and local
generator. codes.
120/240 VOLT, 1 PHASE, 60 HERTZ 3 4 7 / 6 0 0 ~ 0 ~ ~PHASE,
,3 60 HERTZ
1 NAMEPLATE VOLTAGE CODE 3 1 INAMEPLATE VOLTAGE CODE 9 X 1
T1
T1
CONNECT LEAD FROM CONNECT LEAD FROM
TERMINAL 6 3 TO HS TERMINAL 6 3 TO H5
5
A
15 120/240 1 60 HS
W
115/230 1 50 H6
515 3
110/220 1 50 H6 2
L2 L3
15
C,D 240/480
515
120/240
115/230
110/220
3 60
3
3
60
50
SO
H5
~5
ti6
H6
?g*
,
a
g
l3
112
rp
15
b
I 11
F !
L3
hc#
T l 110 7677
F:
120/208 3 60 H3 LO L1 12 13
15 127/220 3 60 H4
CT25 -
#
134/140 3 60 HS 5 CT
(-
CT23
= -2
-
110/190 3 50 H3 710
a
115/200 3 50 l b 112 Lo
515
H4
2
124208 3 50 H4 2 13 19
127/220 3 50 H5 T2 1 8 T3 1 9
240/416 3 60 H3 L2 L3
15 254/440 3 60 H4
C 124
277/480 3 60 H5
; 110
111
LO
CT CT T2#
224380 3 50 H3 v,
Y
230/400 3 50 H4 19
515 V)
240/416 3 50 H4
7 220/380 3 60 H3 98C2193
GENERAL
Onan DFE Series electric generating sets are given a 1. Verify that h e electric solenoid valve used
complete running test under various load conditions with citv water cooled sets is ooen before
and are thoroughly checked before leaving the fac- initial starting of unit to allow coolant chambers to fill. Overheating
tory. Inspect your unit closely for loose or missing and damage to the engine could result from noncompliance.
partsand damage which may haveoccurred in transit.
If engine is equipped with a cooling system
Tighten loose parts, replace missing parts and repair
filter, do not use antifreeze with an anti-leak
any damage before putting set into operation. formula. The stop leak element can prevent or retard the coolant
flow through the filter, thereby eliminating the filtering process
PRESTART SERVICING completely.
Lubrication System: Engine oil was drained prior to Be careful when checking coolant under
shipment. Fill crankcase to capacities shown below. pressure. It is advisable to shut engine down
After engine has been run, check dipstick, add oil to and bleed off pressure before removing pressure cap. Severe burns
bring level to full mark. Record capacity for future oil could result from contact with hot coolant.
changes.
EXHAUST
CONNECTION ELECTRIC
O I L SUPPLY I N L E T LINE. ACTUATOR
DISCONNECT A T THIS
POINT T O PRIME
I
I
INJECTION
PUMP
EXERCISE PERIOD
Generator sets on continuous standby service are
STARTING required to be operative at essential loads from a cold
start in a short period of time in the event of a power
When the preceding service functions have been outage.
performed, recheck to verify unit is ready to start.
1. Crankcase filled. This imposes severe conditions on the engine. Fric-
2. Cooling system filled-input solenoid valve open. tion of dry piston rings upon dry cylinder walls
causes scuffing and rapid wearing. These can be
3. Batteries charged and connected. relieved b y exercising the set at least once a week for
4. Fuel solenoid valve open. a minimum time of 30 minutes per exercise period.
Preferably, run the set under at least 50 percent load
t o allow the engine to reach normal operating
To start, move the "run-stoplreset-remote" switch to temperature. This will keep engine parts lubricated,
the "run" position. The engine should start aftera few maintain fuel prime, prevent electrical relay contacts
seconds of cranking. Immediately after start, observe from oxidizing and insure easy emergency starts.
the oil pressure gauge. Normal oil pressure is Onan automatic transfer switches have as an option
between 50 and 70 psi (345.0-483 kPa). Check the
an exerciserwhich, by pre-selection, will start, deter-
following gauges:
mine run period and shut down a set on a weekly
1. DC Ammeter-10 to 30 amperes. frequency. For example, the switch can be set for
2. AC Voltmeter-AC generator output voltage. time of start, length of run, A.M. or P.M. and day of
3. Frequency Meter-AC generator output frequen- week.
cy.
After each exercise period, top off fuel tank, check
After running 10 minutes under load the water engine for leaks and unit for general condition.
temperature gauge should have stabilized at 165OF to Locate cause of leaks (if any) and correct.
195" F (74" C to 90.6"C). On citv water cooled unitsan
adjustable valve is connected i;l the watersupply line.
Adiust the hand wheel valve to ~ r o v i d ea water flow OUT-OF-SERVICE PROTECTION
that will keep the water temper'ature gauge reading For storage periods of all durations, referto Cummins
within the range of 165" F to 195" F (74OC to 90.6" C). manual.
TABLE 4.
TROUBLESHOOTING ENGINE SHUTDOWN SYSTEM
(Engines with only one fault lamp)
1. Engine stops cranking and fault 1. See engine service manual for
lamp lights, after cranking troubleshooting fuel system.
approximately 75 seconds.
After correcting problem, reset engine
monitor relay by placing Run-Stop/
Reset-Remote switch to Stop/Reset,
then back to the required running
position.
SYMPTOM
5. Overspeed shutdown.
II 5. Check governor and throttle linkages
for freedom of movement.
Check overspeed switch.
I
6. Overspeed light on, no shutdown. 6. Disconnect wire at TB11-29. Light on
after reset; replace engine monitor
board.
OIL PRESSURE SW
THERMO
INLET
OPERATIONAL HOURS
MAINTENANCE ITEMS 8 50 100 200-250
Inspect Set x7 --
NOTE: The above schedule is a minimum requirement. For the recommended service periods for your engine,
refer to engine manual.
ENGINE SPEED
Generator frequency is in direct ratio to engine speed,
which is controlled by the governor.
10. Shut engine. Restart engine is make sure t ~ g h t A llgh: c?at~rtgoi :;on-rrlnductrve cjreas* will
that ur-i~tdoes not overspeed retard corrosion ni terrn~nals Keep the electrolyt:, at
the proper I e v ~abgve
l the plates by addrng ctist~lied
11. Shut down engine. Replace governor conirol box
water Check s p e c ~ t grav~ty,
~c recharge ~f below 1 260
cover. Engine is now ready for service.
R INTAKE
FILTER
FILTERS
A planned program of filter cleaning or replacement
will pay dividends in engine life, operation and
reliability.
SUPPLY L I N E .
F I L T E R TO F U E L SUPPLY
INJECTION PUMP INLET
FUEL FILTERS
WATER HEATER
9 A T T E R Y CHARGING OUTLET '
ALTERNATOR
@ OIL PLUG WATER
I a
'a
BREATHER
COVER
-
BREATHER