Professional Documents
Culture Documents
140001 Human Factor Engineering - Human Machine Interface and Control Room Design
140001 Human Factor Engineering - Human Machine Interface and Control Room Design
140001 Human Factor Engineering - Human Machine Interface and Control Room Design
PTS 14.00.01
January 2017
FOREWORD
PETRONAS Technical Standards (PTS) has been developed based on the accumulated knowledge,
experience and best practices of the PETRONAS group supplementing National and International
standards where appropriate. The key objective of PTS is to ensure standard technical practice across
the PETRONAS group.
Compliance to PTS is compulsory for PETRONAS-operated facilities and Joint Ventures (JVs) where
PETRONAS has more than fifty percent (50%) shareholding and/or operational control, and includes
all phases of work activities.
Contractors/manufacturers/suppliers who use PTS are solely responsible in ensuring the quality of
work, goods and services meet the required design and engineering standards. In the case where
specific requirements are not covered in the PTS, it is the responsibility of the
Contractors/manufacturers/suppliers to propose other proven or internationally established
standards or practices of the same level of quality and integrity as reflected in the PTS.
In issuing and making the PTS available, PETRONAS is not making any warranty on the accuracy or
completeness of the information contained in PTS. The Contractors/manufacturers/suppliers shall
ensure accuracy and completeness of the PTS used for the intended design and engineering
requirement and shall inform the Owner for any conflicting requirement with other international
codes and technical standards before start of any work.
PETRONAS is the sole copyright holder of PTS. No part of this document may be reproduced, stored
in a retrieval system or transmitted in any form or by any means (electronic, mechanical, recording or
otherwise) or be disclosed by users to any company or person whomsoever, without the prior written
consent of PETRONAS.
The PTS shall be used exclusively for the authorised purpose. The users shall arrange for PTS to be
kept in safe custody and shall ensure its secrecy is maintained and provide satisfactory information to
PETRONAS that this requirement is met.
ANNOUNCEMENT
As part of the recent transformation exercise, the PTS numbering system has been revised to 6-digit
numbers and drawings, forms and requisition to 7-digit numbers. All newly revised PTS will adopt this
new numbering system, and where required make reference to other PTS in its revised numbering to
ensure consistency. Users are requested to refer to PTS 00.01.01 (PTS Index) for mapping between
old and revised PTS numbers for clarity. For further inquiries, contact PTS administrator at
ptshelpdesk@petronas.com.my
Table of Contents
1.0 INTRODUCTION ..................................................................................................... 6
1.1 SCOPE ............................................................................................................................ 6
1.2 GLOSSARY OF TERMS..................................................................................................... 6
1.3 SUMMARY OF CHANGES ............................................................................................... 7
2.0 HUMAN FACTORS ENGINEERING (HFE) .................................................................. 8
2.1 GENERAL ........................................................................................................................ 8
2.2 HFE IN DESIGN ............................................................................................................... 8
3.0 CONTROL BUILDING ............................................................................................ 10
3.1 LOCATION ....................................................................................................................10
3.2 ACCESSIBILITY ..............................................................................................................10
3.3 LAYOUT OF ROOMS WITHIN CONTROL BUILDING ......................................................13
4.0 CONTROL ROOM ................................................................................................. 15
4.1 LAYOUT ........................................................................................................................15
4.2 LAYOUT OF OTHER WORKPLACES ...............................................................................16
4.3 WINDOWS ...................................................................................................................16
5.0 WORKSTATION LAYOUT ...................................................................................... 17
5.1 DIMENSIONS AND SHAPE ............................................................................................17
5.2 PLACEMENT OF VDU WITHIN WORKSTATION (CONSOLE) ..........................................21
6.0 ENVIRONMENTAL FACTORS AND FURNISHING ..................................................... 24
6.1 AIR CONDITIONING ......................................................................................................24
6.2 LIGHT AND OUTSIDE VIEW ..........................................................................................24
6.3 NOISE ...........................................................................................................................25
6.4 MATERIALS AND COLOUR............................................................................................26
6.5 FURNITURE ..................................................................................................................27
6.6 HYGIENE .......................................................................................................................27
7.0 VDUS AND CONTROLS ......................................................................................... 28
7.1 VDU SCREENS ..............................................................................................................28
7.2 LARGE SCREEN/VIDEO WALL PROJECTOR ...................................................................29
7.3 CONTROLS ...................................................................................................................31
8.0 PRESENTATION OF INFORMATION ....................................................................... 35
8.1 TOUCH TARGETS ..........................................................................................................35
8.2 CURSORS ......................................................................................................................35
1.0 INTRODUCTION
This PTS provides the minimum technical requirements for the application of Human Factors
Engineering principles in the design of central control rooms and DCS consoles located there
for new projects or plant changes in existing facilities.
This PTS also incorporates PETRONAS lesson learnt and best practices.
1.1 SCOPE
1.1.1 This PTS gives a summary of state of the art and details out recommendations for Greenfield
and Brownfield projects involving control room design.
Refer to PTS 00.01.03 for PTS Requirements, General Definition Of Terms, Abbreviations &
Reading Guide.
No Terms Definition
2 Horizontal Illumination The light falling onto the surface (work station
desk or VDU screen) from a horizontal
direction.
No Terms Description
No Terms Description
5 PC Personal Computer
7 PI Practical Instructor
This PTS 14.00.01 (January 2017) replaces PTS 14.00.01 (September 2013).
2.1 GENERAL
2.1.1 Human Factors Engineering (HFE) is an ergonomic study of designing control room and its
equipment to improve panel operators’ functional capabilities.
2.1.2 HFE elements shall be incorporated during project design with active inputs from end-users
and ergonomic design experts. Sufficient design reviews will avoid unnecessary change
during construction and/or commissioning. Panel operators will benefits from a safer, more
efficient and more comfortable control without increasing life-cycle costs.
i. The Owner’s TA shall ensure that HFE is incorporated in the design process of the
project as outlined in PTS 18.53.09
ii. The Owner’s TA shall ensure the HFE scope definition for project has been done
by personnel who are familiar with HFE requirements.
iii. HFE shall be considered as part of the overall total design decisions due to its
implications to operational and maintenance personnel.
iv. Design decisions shall strive for optimum HFE solution, where the pros and cons
are weighed carefully, especially if limits are exceeded e.g. limits for physical or
mental load are reached. Where limits are exceeded, re-engineering shall be
executed.
v. Producing CAD 3D model, even in a simple form, and design reviews are valuable
methods for checking and adjusting the design in respect of HFE aspects
(accessibility, range, layout, etc.). This is where good human modelling software
will be of value.
vi. Inclusion of operations and maintenance personnel in the design process is critical
for successful HFE design.
TA shall be responsible to ensure relevant stake holders participate in the HFE design as per
PTS 18.53.09, including but not limited to the following aspects:
v. Means of communication.
vi. Location and layout of panels for Operator Override Switches (OOS) and
Maintenance Override Switches (MOS)
3.1 LOCATION
3.1.1 The following minimum list of non-HFE factors dictates location of control building:
i. safety of control room in event of a process fire and explosion in the vicinity
ii. the number of plants that are to be controlled from the control room
3.1.2 Preference with regards to location of Control Building is in a safe non-hazardous area
Closer contact with plant thus shorter Further contact from plant thus longer
walking/cycling/driving distances walking/cycling/driving distances
Potentially more exposure to noise and/or Less exposure to noise and/or odour
odour from plant
Generally, the control room should be located in a safe area, away from process area but
within facility perimeter.
3.2 ACCESSIBILITY
Accessibility legislation (i.e. governing access by wheelchair users and other disabled persons)
shall be reviewed and applied by the TA in all projects.
3.2.1 General
ii. If the building is required to be located within a major hazard area, these
additional requirements shall apply:
a) Building design shall (PSR) meet the hazardous area requirements
b) a positive air pressure shall (PSR) be maintained inside to keep external air-
borne contaminants out.
c) Access to the building shall be via an airlock with explosion-resistant and
gas-proof doors. The space between the airlock doors can be used for
storing safety equipment (emergency breathing masks, etc.), provided
this is allowed for in the design. Automatic doors shall be used for this
purpose, as these are easier to operate.
d) See PTS 11.14.03 and PTS 11.14.01 for building requirements.
i. Escape routes should lead right through the building. Routing them along a wall
and far apart is a good practical compromise in the control room. See Appendix 2
for an example of a control room building.
ii. Emergency exit and escape routes shall be free from any obstruction.
3.2.3 Signposting
i. Signs shall be installed at clearly visible points for the following purposes:
a) help visitors find persons or locations
b) indicate escape routes and emergency exits for fire-safety purposes.
ii. In large control buildings, a floor plan of the building should be provided at a
visible location near the main entrance.
iii. Various standards specify where signs and emergency lighting shall be installed
and the appropriate dimensions, etc.
i. Other personnel and visitors should enter the control building via a separate
entrance (main entrance) and the central corridor instead of via the plant
entrance
ii. There should be a waiting/shift room, complete with a desk to issue permits and
receiving visitors, upon passing through the main entrance. Due care shall be
given to possibility of draft arising from areas with and without positive pressure.
The desk shall comply with the legal requirements relating to workplace
ergonomics.
iii. Design should accommodate Visitors' car park, number of spaces and location (i.e.
proximity to the control room main entrance).
i. Preference with regards to location of Control Room within the Control Building
are:
a) The control room does not need to be situated at the most central point
of the building
b) Personnel not directly involved with the control room should be kept
away
i. Preference with regards to location of General shift supervisor's room within the
Control Building are:
a) near to the control room to allow necessary functional and work flow
process.
b) not be accessible solely via the control room to avoid associated human
traffic from disturbing operators' concentration.
There shall be a sign informing visitors where to report upon absence of shift supervisor.
i. The computer area should be situated in the direct vicinity of the control room.
ii. A raised computer floor should not be installed so that operators have visual
contact with every part of the control room.
iii. When dimensioning the computer area, account should be taken of the creation
of a workplace for engineering tasks. This workplace shall comply with the local
legislation provisions relating to workplace ergonomics.
i. Area for issuing work permits should be furnished for writing/PC tasks, an
overview of activities, issue and storage of safety equipment and storage of gas
test equipment.
ii. A separate filing room should be provided adjacent to the Work Permit Issuance
area to allow filing of permits, plant records and drawings
iii. Sufficient rooms shall be provided to accommodate all personnel that are
intended to be working within the building.
iv. Social area, including pantry, should be situated close to the control room,
although clearly separated from the latter. Social Area shall be sized large enough
to take role as an Assembly Area(refuge), if design dictates that Assembly area
shall be within inside of Control Building
v. Toilets, washing, changing rooms, lockers and disabled persons’ facilities should
be situated directly off the central corridor. They shall have good mechanical
ventilation. The areas should be large enough and have a clear demarcation
between male and female. A design with "clean" and "dirty" areas is worth
considering.
vi. Office areas should be designed for the tasks (writing, VDU work and meetings)
to be performed in them.
viii. Conference rooms for meetings, training etc., should be provided within the
Control Building, complete with conference peripherals (i.e. whiteboards,
projector and screen, etc.).
ix. Storage rooms; sufficient space should be provided in the control building for
storing equipment. The room for the breathable air equipment shall be situated
near the plant entrance. This shall be large enough to avoid congestion in
emergencies.
x. Smoking area, shall not be combined with the Social Area. Instead, a separate
location shall be provided.
xi. Bulletin board for essential mass communications shall be made available.
Suggested spots are along main passage ways and social area.
4.1 LAYOUT
Ergonomic studies, covering overall control room layout, lighting, placement of VDU consoles,
etc., shall be carried out to optimise control room layout for new and revamped control room.
Where there is a conflict between the ergonomic studies and this PTS, the ergonomic studies
shall take precedence.
v. Number of operators.
vii. Space for administration (only if building is used during plant shutdowns); for
example for charts, spading procedure, etc.).
iii. Space needed for VDU operation (sitting, standing and walking).
4.2.1 There shall be a number of workplaces in the control room for administrative work, checking
of drawings ("manual table"), meetings, etc.
4.2.2 Visual partitions are necessary between the various workplaces (sufficient separation, plant
boxes, partition wall), but the console shall be visible at all times.
4.2.3 When planning the area, it is preferable not to locate any workplace in the direct vicinity of
the ventilation grids.
4.2.4 In small control rooms (less than 36 m2), measures should be taken to avoid a shut-in feeling
(vertical glass strips in the walls, windows, wall decoration, etc.).
4.2.5 In large control rooms, measures shall be taken to reduce the noise level and enhance
audibility of speech (adjustable volume of auditory signals, "trunking" of communication
means and clustering workplaces).
4.2.6 In view of the noise and heat they produce, computers and peripherals should be installed in
a separate area, as far as possible.
4.2.7 The furnishing of these workplaces should take account of their functions.
4.3 WINDOWS
4.3.1 There shall (PSR) be no windows on outer walls of control room building.
5.1.1 The position the of work materials and the office equipment which are used regularly should
be in front of the Operators so that they do not have to constantly reach out and put them in
an awkward posture.
5.1.2 Sufficient desk space should be ensured to allow the Operators to put keyboard, mouse,
computer monitor, document holder, telephone and other accessories within a comfortable
reach.
i. The workstation layout should have a separate keyboard, which, when pushed
back, allows room for writing
5.1.3 Log books and other necessary documents should also be taken into account. The use of
electronic log books shall be considered
Figure 5.5: Example of Console with DCS separated through instrument and communications
panel
vi. If a hard wired display panel installed, this panel shall be placed above the VDU.
Figure 5.6: Example Console with hardwired display panel hanging above VDU
5.1.5 The workstation (monitor, CPU system unit, keyboard, mouse) should be placed on a stable
working surface with adequate room for proper arrangement. If this work surface is going to
be used for writing on paper, as well as computer, use a flat surface that is suggested
between 28"-30" above the floor (suitable for most adults).
i. Each Operator Console shall consist of DCS workstation(s), console for ESD push
buttons, annunciator lamps and switches, as well as Telecommunication Console
(which includes telephone, PAGA microphone, etc.)
iii. The configuration of the plant layout consoles (e.g. mimics) in the control room
shall conform with the process flow, from left to right. This is particularly
important for the alarm displays.
iv. The consoles should be grouped functionally for each part of the process.
vi. The console arrangements for different processes or parts of processes shall be
clearly separated. Clustering of consoles shall consider number of operators
manning the console section and the functional relationship between the various
parts of the process. Each of these arrangements has its specific pros and cons
vii. The maximum number of VDUs (video display units) that an operator can
physically operate in an upset situation is four next to one another (e.g. 1
overview screen, 1 detail screen, 1 trend screen and 1 alarm display). The
maximum number of control loops that a single operator can handle is 150 loops.
These facts, in conjunction with the number of operators needed in the control
room, is one of the factors determining the console configuration.
5.2.1 The VDU with the most important process information should be positioned straight in front
of the operator.
5.2.3 The maximum number of VDUs (video display units) that an operator can physically operate
in an upset situation is four next to one another (e.g. 1 overview screen, 1 detail screen, 1
trend screen and 1 alarm display).
5.2.4 The display face shall be perpendicular to the Operator's normal line of sight whenever
feasible, and shall be not less than 45° from the normal line of sight.
The adjustment range of the monitor surface should accomplish the required -15° to -20° view
angles below horizontal eye level for the 5th percentile seated female (21” monitor) to the
95th percentile standing male (17” monitor) Operator as illustrated in Figure 5.7.
The vertical height of a Video Display Terminal (VDT) screen represents a compromise
between minimizing visual discomfort and musculoskeletal discomfort of the neck and
shoulders. In general lowering a screen or increasing the viewing distance will reduce visual
discomfort. However, lowering the screen increases the loading on neck and shoulder
muscles. Display screen height above eye level has also been associated with musculoskeletal
discomfort.
i. The entire visual area of visual display terminal console desk systems should be
located between 0° and 60° below eye height when the Operators assume the
upright sitting, declined sitting or standing reference posture.
ii. The centre of the visual display screen should be located 15° to 20° below
horizontal eye level to achieve the optimum visualization.
iii. Display faces shall be perpendicular to the Operator's normal line of sight
whenever feasible, and shall be not less than 45° from the normal line of sight.
iv. Displays used most frequently should be grouped together and placed in the
optimum visual zone
i. Vertical angles
The optimum viewing angle is 15° above and below normal line of sight, and the
maximum will be 90° above normal line of sight.
5.2.8 In general, the ergonomic console desk system design can be tailored to an individual of nearly
any size. However, any design for multiple Operators, whose specific physical needs are
unknown or may change along with personnel changes, is typically accommodated by
ensuring the 5th percentile seated female to the 95th percentile standing male requirements
are met.
6.1.1 Control rooms contain a large number of VDUs relatively close together. VDUs, especially
those other than LED type, generate considerable amounts of heat, and their impact on air-
conditioning requirements shall be taken into account at an early stage in the design (ISO
11064-2).
6.1.2 For further information regarding air quality and indoor climate, see PTS 12.24.01.
6.2.1 The lighting plan, based on the control room layout (locations of consoles, workstations, etc.),
should be produced at the earliest possible stage of the design. For outside view see (4.3).
6.2.2 The illuminance at the work surface should be between 200 lx and 500 lx. Very high levels of
illumination can make a computer screen appear low in contrast and difficult to view. Very
low levels of illumination can make it difficult to read source documents or other printed
materials.
6.2.3 If colour VDUs are used (information luminance 20 cd/m2), the maximum horizontal
illuminance shall be 320 lx.
6.2.4 The computer monitor screen should not be backed to a bright window or facing a bright
window such that the screen looks washed out.
6.2.5 The reflection factors of the room surfaces should be about 0.2 to 0.4 on floors, 0.4 to 0.6 on
walls, and about 0.4 to 0.8 on the ceiling
6.2.6 Tratios between the viewed object, the immediate environment and the periphery shall be in
the ratio of approximately 10:3:1.
i. Deep reflector fittings with plastic or metal mirror grids, for example ‘Paracube’
as shown in Figure 6-1 shading under fluorescent strip lights, as these direct the
light vertically downwards and give a relatively dark surface when seen from the
side.
ii. Screening grids should limit lateral light emission to approximately 40° relative to
the horizontal. Outside this range the luminance should not exceed 200 cd/m2.
iii. The light fittings shall be positioned relative to the VDUs so that the fittings are
outside the operators' field of vision.
vi. The colour temperature should be between 3300 K and 4000 K. For limited
daylight entry: 3300 K. For daylight in combination with artificial light: 4000 K.
vii. The colour reproduction index (Ra) of fluorescent lamps should be at least 83.
6.3 NOISE
6.3.1 Requirements are laid down in respect of noise and audibility of speech in control rooms.
Depending on the nature of the work (degree of concentration) and the necessity for voice
communication, there are several different values for maximum noise levels in control
building areas.
Plant laboratory 50
Social rooms 50
Changing rooms 50
Computer rooms 60
Table 6.1: Maximum noise level according to area
6.3.2 If there are several control units in a central control room, account should be taken of the
following noise sources that could disturb voice communication:
i. Noise due to the (large) number of VDUs; especially cooling fan noise.
ii. Noise generated by acoustic alarms; these should be adjustable for each unit.
iii. Noise resulting from communication between plant operator and panel operator;
the panel operators of the various units shall not be disturbed by one another.
Use of headphones is a possible solution. The sound-absorbent properties of the
floor, walls and ceiling can also affect speech audibility in the control room.
6.3.3 Extra attention should be devoted to measures for controlling air-borne and contact sound
transmission, since a control building is located in the direct vicinity of the plant
ii. When choosing the colour in the room (walls, ceiling, furniture, etc.), account
should be taken of the luminance ratios (6.2.2).
iii. Fairly inconspicuous colour should be chosen, particularly for the large areas
(walls, ceiling, etc.).
iv. The ceilings should be light-coloured, the walls somewhat tinted, and the floor
dark coloured.
v. As regards diffuse reflections of the various surfaces, the following values are
recommended:
Ceiling > 60 %
Walls 40 % to 60 %
Floor 15 % to 30 %
Table 6.2: Reflection values for specific Control Room surfaces
vi. In order not to make an unnecessarily large transition between the screen and
the other surfaces of the console these surfaces should have a reflection
percentage of between 30 % and 50 %. Light colours should be used for the
worktop surface, with a luminance ratio 10:3:1, see 6.2.2).
vii. For colours and their influence on human behaviour, see Appendix 6.
6.4.2 Materials
ii. antistatic
vi. Surface of floor covering is smooth enough to allow easy cleaning and easy gliding
of wheeled chairs
6.5 FURNITURE
6.5.1 General
The furnishing of the control room and office cells in the control building shall be adapted to
the users and the office tasks to be performed (VDU, reading and writing tasks). Account shall
also be taken of the HFE requirements applicable to the use of furniture.
6.5.2 Chairs
The chair should be pneumatically adjustable so that the Operators can adjust the seat pan
height while they are sitting on the chair. Some chairs with a mechanical height adjustment
(spinning) mechanism are also acceptable.
Lumbar supports that can be adjusted up and down and forwards and backwards to best fit
operator’s shape should be considered as well. The alternative choice is that the Operator
need to be provided with armrests on a chair which can be helpful to aid getting into and
getting out of the chair. Also, the armrests can be useful for the occasional resting of the arms
when on the phone, etc. The chair should be equipped with synchronized tilt and multi-limited
tilting which enables the backrest and seat pan slope to independently conform to the natural
body movements.
6.6 HYGIENE
6.6.1 The following requirements are applicable to control rooms as well as rooms containing PCS
equipment:
ii. Shoes/boots shall not be worn inside; a proper storage or shelf for safety boots
should be provided in a control room building, e.g. within the airlock space. Only
clean dedicated “indoor” shoes should be allowed into rooms containing PCS
equipment for safety requirements.
VDU screens shall be flat panel LED or LCD screens, typically 20” to 24” diagonal size. LED
screens are more preferred due to their less power consumption, less heat dissipation and
that they succeed the technology of LCD screens.
7.1.1 Resolution
For displaying graphic symbols, screens should be used which can reproduce at least 1280
pixels x 1024 pixels.
The reflection factor of VDU screens should be approximately 0.5 % which can be achieved,
for example, with a 1/4 lambda coating.
For facilities that use LED or LCD screens (which generally do not create flicker), their refresh
frequency can be sufficiently set at 59 Hz or 60 Hz at native resolution.
For facilities that are still using CRT screens, screens with dark symbols against a light
background, an image refresh frequency of at least 70 Hz is needed to avoid irritating
flickering. This is especially important if multiple users use multiple VDUs. As the human eye
is more sensitive to flicker in the periphery, the refresh rate of the VDUs shall be kept at 70 Hz
or above, preferably at least 75 Hz.
Screens with dark symbols against a light background are preferred because they are less
susceptible to reflections and have better luminance ratios in the field of view.
7.2.1 Large screen/video wall projector can be considered for operator to collect, visualize, and
distribute data and information to give a complete overview on the ongoing situations and to
increase efficiency and productivity through sharing information and collaborative work.
Large screen also can be used for the purpose of management dashboard for the management
to quickly receive an overview on what is happening inside the control room and make swift
reaction planning and provide direction to the Operators.
7.2.2 The screen should be put in the front central of control room. The curvature of video wall
must cover all areas/fields of Operator’s viewing angles.
7.2.3 Viewing distances should consider physical restrictions, such as ceiling height or the height of
the consoles in the control room. Ideally the display size should be selected according to the
amount of information required, and the required or available viewing distances.
have shown that the minimum required character or object size must be greater
than a 16-arc minute, that is, 16/60°.This implies that the maximum viewing
distance is 215 times the height of the character. It is recommended to choose
215 times as the maximum limit instead of 300 to 400 times to get a clearer view
of objects/images on the screen.
.
Figure 7.2: Distance view
The ratio between viewing distance and image height is 5:1. A viewing distance of
4 times the height of the image is recommended as providing the optimum
information from an image
Figure 7.3: The ratio between viewing distance and image height
Image brightness should be at least at the level of the average luminance level in the field of
vision, provided that a sufficient contrast ratio can be obtained.
7.2.6 Resolution
For large screen/video wall projector, the resolution shall be at least Full HD 1920 pixels x
1080 pixels.
7.3 CONTROLS
The relationship between an operation of the controls and the resulting movement shall
correspond with familiar patterns and habits for local staff. For example, if a process is
regulated by turning a knob clockwise, the pointer on the corresponding display shall also
move clockwise. This is called compatibility. The movement stereotypes for a cursor,
keyboard, mouse, etc. are shown below. Panel operators should be included in the design
process to confirm the stereotypes.
Function Movement
Switch on Up
To right
Forwards
Turn clockwise
Pull a switch
Function Movement
Up Up
Forwards
Downs Down
Backwards
Increase Forwards
Up
To right
Turn clockwise
Reduce Backwards
Down
To left
Turn anticlockwise
Table 7.1: Control function stereotypes
7.3.2 Compatibility
For the display of information, all types of compatibility shall be considered, however only two
types are emphasized in this PTS. Any control display relationship that is consistent with a
prevailing mental stereotype is deemed compatible.
Location of the control relates to the position of the response within the display.
7.3.3 Keyboard
7.3.3.2 If auditory feed-back is used, for example by means of a bleep, it shall be possible to adjust
the sound level.
7.3.3.3 The keyboard should be connected to the VDU by means of a flexible cable.
7.3.3.5 Membrane keyboards are only suitable for an extremely low typing speed.
7.3.3.6 The keyboard should be placed at an angle of 5° to 15° from the horizontal.
7.3.3.8 If much numerical data has to be entered, the keyboard should be fitted with a numerical
keypad. The choice then has to be made between a calculator layout and a telephone-type
layout.
7.3.4 Cursor
7.3.4.1 There are two layouts for the cursor control keys:
i. The inverted T: 3 keys for left, down, and right, in a row, and the up key placed
above them in the middle.
ii. The "cross" layout: the direction of cursor movement should be indicated on the
keys.
7.3.4.2 The cursor should not disturb the legibility of the screen data.
7.3.5 Mouse
7.3.5.1 A mouse is eminently suitable for point and selects tasks. It is unsuitable for data entry.
7.3.6.1 Touch screens should be used for selecting subjects, browsing, data entry/retrieval and
applications in which it is undesirable or time consuming to divert attention from the screen.
This technique can only be used if high precision is not required. Direct feedback (e.g.
auditory) should be provided.
7.3.6.2 The sensitive zones should be large enough for finger touch (at least 4 cm2) and should take
account of screen parallax.
7.3.6.3 A drawback of the use of a touch screen is the static loading of the user’s arm and the constant
recalibration.
Eye-hand coordination + 0
Suitability for:
Pointing + +
Rapid pointing + 0
Drawing - 0
Tracing - -
8.2 CURSORS
Cursors shall not hinder the reading of other information and should flash only if immediate
action is required. Cursors shall be easy and quick to move; this agility shall be controllable by
the user (especially useful if the user has limited dexterity capabilities), see (7.2.5).
8.3.1 The coding methodology shall be consistent (always used in the same way). Redundant coding
(two or more coding forms in use at the same time) should be used for information points
which are crucial for the interpretation of the process.
i. Colour: colour coding should only be used redundantly, i.e. in addition to other
coding (for meanings of stereotypes, (7.2.2).
ii. Brightness: no more than two levels of brightness shall be used; these should still
be clearly differentiable at the screen's maximum brightness setting.
iii. Reverse video: in order to speed up a retrieval task, a word or code can be inserted
in a block with reversed contrast (foreground and background colour reversed).
iv. Size of a shape or character: no more than 3 different sizes shall be used.
8.4.2 One continuous signal shall be produced with adjustable volume, at least 15 dB(A) above
background noise level (and shall be at least 65 dB(A)).
8.4.3 One intermittent signal shall be produced for high-priority alarms, duration and volume
adjustable, at least 15 dB(A) above background noise level (see also ISO 7731).
ii. The visual display design procedure addresses the following key questions:
Step 1: How do the operators view the process? Which main and sub-
components do they distinguish and what relationships are there
between them?
Step 2: Which information from the process is really necessary for a good
overview? How accurate must this be and how must it be shown on
the screen?
Step 3: How must the results of steps 1 and 2 be integrated in a prototype?
Step 4: How do the operators rate the (re)designed graphic in comparison
with the old one. How do they perform a number of typical interface
activities using the old and new interface designs?
3 Integration of results • Guidelines form step 2 • Proposal for VDU graphic, and its
from steps 1 and 2 (e.g. spatial separation of configuration on the process control
dynamic and structural system
process Information)
9.0 BIBLIOGRAPHY
In this PTS, reference is made to the following other Standards /publications: Unless
specifically designated by date, the latest edition of each publication shall be used, together
with any amendments/supplements/revisions thereto.
PETRONAS STANDARDS
Index to PTS PTS 00.01.01
PTS Requirements, General Definition of Terms & Reading PTS 00.01.03
Guide
Design and Engineering of Buildings PTS 11.14.01
Blast Resistance Building Design PTS 11.14.03
Heating, Ventilation And Air Conditioning (HVAC) System PTS 12.24.01
For Onshore Application
Alarm Management : Design and Implementation PTS 14.12.08
Requirement
INTERNATIONAL STANDARDS
Process plant control desks utilizing human-computer EEMUA 201
interfaces – A guide to design, operational and human
interface issues
Ergonomics danger signals for public and work areas – ISO 7731
Auditory danger signals. 0
Lighting of work places– Part 1: Indoor ISO 8995-1
Ergonomic design of control centres – Part 2: Principles ISO 11064-2
for the arrangement of control suites
APPENDIX 1: HUMAN MACHINE INTERFACE (HMI) AND CONTROL ROOM DESIGN CHECKLISTS
These checklists identify any bottlenecks in existing control rooms, panel rooms and other relevant
human machine interfaces, and include a checklist for project management purposes. The relevant
checklist can also be used to determine the scope of a new building and/or HCI project.
1. CONTROL ROOM
SPATIAL CONFIGURATION
SPACE REQUIREMENT
- making separations
- number of operators
- peripherals
- administration
- discussion
- document storage
DAYLIGHT/WINDOWS
2. CONSOLE LAYOUT
- height of monitor
- writing by operators
- communication facilities
CONFIGURATION
7 Are monitors set at the right working height and the right
angle for operators, including any standalone PCs?
3. PHYSICAL FACTORS
LIGHT
NOTE: 3300 K with limited ingress of daylight or 4000 K with daylight plus artificial light.
CLIMATE
17 Does the indoor climate during the heating season satisfy the
following criteria:
NOISE
LIGHT
NOTE: 3300 K with limited ingress of daylight or 4000 K with daylight plus artificial light.
CLIMATE
17 Does the indoor climate during the heating season satisfy the
following criteria:
NOISE
CONTROLS
INFORMATION PRESENTATION
27 Has the use of upper case only been avoided with long texts?
Plan View
1. INTRODUCTION
The influence of colour on people in a production or office workplace has not been rigorously
examined. Most studies on the effects of environmental colour have been preference studies,
where aesthetics are the prime consideration.
2. GENERAL OBSERVATIONS
From these examinations the following observations about preferences can be made:
In Western culture the order of colour preference is blue, red, green, violet,
orange and yellow. These preferences are broad and transcend racial and sexual
differences. Children may prefer red-containing colours, but these preferences
shift toward the blue end of the spectrum at maturity.
Generally speaking blue, green and violet shades are considered cool colours,
while red, orange, yellow and brown are considered warm.
Blue and green are considered soothing colours; orange, yellow and brown are
considered stimulating; red and violet are described as "aggressive", "alarming",
"discouraging" and "disturbing".
Colour can influence a person's perception of size and distance within a closed
space. Walls covered with shorter-wavelength colours, such as blues and greens,
are said to recede, while walls covered with the longer-wavelength colours are
said to advance. Thus blues and greens cause a room to appear larger, while reds
achieve the opposite effect. Similarly, there is an interaction between brightness
and colour in the distance effect. Light colours tend to recede and dark colours to
advance.
The formation of a reaction to a colour takes time, and the reaction, once formed,
is subject to adaptation. Thus a person's initial reaction may be quite pronounced,
but it will tend to diminish in magnitude with the passage of time. The end result
after complete adaptation has occurred could be relative indifference.
3. GUIDELINES
From the above information about colour, the following guidelines for the use of specific
colours, brightness and saturation levels in the workplace have been developed:
For large areas, colours that give uniform reflectivity should be chosen. Good
visual contrasts can be obtained without significant brightness contrasts. For
example doors, protruding wall segments or other barriers may be painted in a
different hue of the same brightness as the overall wall space. Thus these features
Pastel colours are generally preferred for walls, large room units and tabletops or
work surfaces.
In areas where highly repetitive work is performed or where there is a large area
of wall or floor space, some stimulating colours can be used to highlight a door or
partition. In addition, some pieces of equipment in the area may be painted in a
brighter shade of the colour to which the room is keyed. Equipment such as
conveyors, cabinets, shelving and small pieces of production machinery are often
painted this way. Large surfaces should not have these bright colours.
The selection of colour schemes should be coordinated with the decisions about illumination
type. High-pressure sodium lighting has only fair colour-rendering characteristics; subtle
shadings of colour that would be appropriate under white light may be lost under this type
of illumination.