GENERAL NOTES
NOTE 5,9
V

1"
AMAO GENERAL NOTES:
2"x1" A) ALL INSTRUMENTS ARE PREFIXED BY 137.
4"x3"
B) FOR GENERAL NOTES, SYMBOLS AND DETAILS SEE DRAWINGS FROM PU-PP-152-01000-01÷15.
3"x2" 3"x1-1/2" 3"x1-1/2" 3"x1-1/2" 3"x1-1/2" 3"x1-1/2" 3"x1-1/2" 3"x1-1/2" 3"x1-1/2" 3"x1-1/2" 3"x1-1/2" 4"x1-1/2" 4"x1-1/2" 4"x1-1/2" 4"x1-1/2" 4"x1-1/2" 4"x1-1/2" 4"x1-1/2" 4"x1-1/2" 4"x1-1/2" 4"x1-1/2" 4"x1-1/2" 4"x1-1/2" 4"x1-1/2" C) SIZE OF HEADER FOR EACH SINGLE SPRINKLER HEAD SHALL BE 1".
SPRINKLER HEAD END CONNECTION IS NPT MALE THREADED.
1 1
D) HORIZONTAL FIRE WATER HEADER DOWNSTREAM OF SPRINKLER ALARM VALVE SHALL BE FITTED WITH
4300-SZ-DM-660260081

ADEQUATE DRAIN FACILITES. ALL DRAINS SHOWN ON THIS P&ID ARE FOR REFERENCE ONLY. FOR ACTUAL
LOCATION REFER TO ISOMETRIC DRAWINGS.
E) SPACING OF SPRINKLER NOZZLE (VERTICAL AND HORIZONTAL) SHALL BE IN THE RANGE OF 2500 TO 3000 MM.
66-PP-152-260081

F) MINIMUM AND MAXIMUM OPERATING PRESSURE OF ANY SPRINKLER SHALL BE 7 PSI (0.5 BAR) AND 175 PSI (12 BAR)
RESPECTIVELY.

V
CONTRACTOR :

1"X1/2"
BOROUGE :

C
1"

DETAIL - "A"
(APPLICABLE FOR ALL SPRINKLER HEADS)

2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2"
NOTES:
2 3"x2" 3"x2" 3"x2" 3"x2" 3"x2" 3"x2" 3"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 6"x2" 6"x2" 6"x2" 6"x4" 1. PIPE CONNECTION FROM DRAIN VALVE. 2
2. WATER ALARM GONG CONNECTED WITH DRAIN VALVE.
3"x2" 4"x3" 6"x4" 3. RETARD CHAMBER.
4. SPRINKLER ALARM VALVE SHALL BE LOCATED OUTSIDE OF BUILDING THEY PROTECT.
5. VENT VALVE SHALL BE LOCATED AT THE HIGHEST ELEVATION ON THE WATER SPRAY HEADER.
6. RISER ON TRANSITION FROM UNDER GROUND PIPING TO ABOVE GROUND PIPING SHALL BE EQUIPPED WITH
CATHODIC PROTECTION, ISOLATION KIT AND, WHERE NECESSARY, WITH PROTECTION AGAINST PHYSICAL
DAMAGE, SPECIAL ITEM TAG REFERS TO ISOLATION KIT.
7. INSPECTOR TEST VALVE 1" SHALL BE PROVIDED AT 1200 MM FROM FLOOR LEVEL VALVE SHALL BE DESIGNED
TO SEAL IN CLOSED DIRECTION.AN ALARM TEST CONNECTION NOT LESS THAN 1 IN. (25 MM) IN DIAMETER,
TERMINATING IN A SMOOTH BORE CORROSION RESISTANT ORIFICE, GIVING A FLOW EQUAL TO OR LESS
NOTE 5,9 THAN ONE SPRINKLER OF A TYPE HAVING THE SMALLEST K-FACTOR INSTALLED ON THE PARTICULAR
V SYSTEM, SHALL BE PROVIDED TO TEST EACH WATERFLOW ALARM DEVICE FOR EACH SYSTEM.
2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 8. FOR DETAILED FIRE AND GAS LOGICS, REFER TO "CAUSE AND EFFECT MATRIX FOR FIRE AND GAS SYSTEM"
1"
DOC. NO. 137-IE-163-00001.
9. VENT VALVE IS USED DURING THE COMMISSIONING PHASE AND DURING THE REFILLING OF THE
2"x1" 3"x2" 3"x2" 3"x2" 3"x2" 3"x2" 3"x2" 3"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 6"x2" 6"x2" 6"x2" SYSTEM DURING MAINTENANCE, IN ORDER TO REMOVE AIR FROM THE BRANCHES.

3"x2" 4"x3" 6"x4"

3
3"x2" 4"x3" 6"x4" REFERENCES : 3

3"x2" 3"x2" 3"x2" 3"x2" 3"x2" 3"x2" 3"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 6"x2" 6"x2" 6"x2" PUX-MR-572-00004 : FIRE FIGHTING WATER SPRAY DELUGE / SPRINKLER SYSTEMS DATA SHEETS.
THIS INFORMATION IS NOT TO BE USED, DISCLOSED, OR REPRODUCED IN WHOLE OR IN PART TO ANYONE OUTSIDE OF ABU DHABI POLYMERS COMPANY LIMITED (BOROUGE) AND ITS SUBSIDIARIES,

BGS-MU-200 : BOROUGE GENERAL SPECIFICATION FIRE PROTECTION DESIGN PHILOSOPHY


2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" BGS-MU-201 : BOROUGE GENERAL SPECIFICATION WATER SPRAY FIRE PROTECTION SYSTEMS
P4-PH-567-00002 : FIRE FIGHTING GENERAL SPECIFICATION PO & 1-HEXENE PLANT

6"-66-FW-26532-A2AU16-V
PUX-PH-581-00009 : DELUGE & SPRINKLER SYSTEM TECHNICAL SPECIFICATION
PU-PH-407-00001 : HYDRAULIC CALCULATION UNDERGROUND FIREWATER NETWORK PO, 1-HEXENE AND U&O

1002
KPAH
137-PH-407-00001 : FIREFIGHTING SYSTEMS HYDRAULIC CALCULATION WET SPRINKLER SYSTEM - PRODUCT HANDLING
THIS DOCUMENT CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF ABU DHABI POLYMERS COMPANY LIMITED (BOROUGE) OR ANY OF ITS LICENSORS.

1001

NOTE 8
KPAH
3"x2" 4"x3" 6"x4" FGD
133-0-65-01 Fire Water Underground for PE7 Substations

3"x2" 3"x2" 3"x2" 3"x2" 3"x2" 3"x2" 3"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 4"x2" 6"x2" 6"x2" 6"x2" 6"x4"
C 137-8-66-03 Fire Water Sprinkler Deluge System 66-SD-13701
KPG
C 1002
2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" 2"x1-1/2" V
4 128-0-77-01 Open Drains 4
NOTE 2 V
EXCEPT PURSUANT TO A WRITTEN AGREEMENT WITH ABU DHABI POLYMERS COMPANY LIMITED (BOROUGE).

KPSH
1/4" T
1001

KAV
1001
NOTE 4
NOTE 3 1/2" TR-TCMS-NSH-P00885
NC

NC

NOTE 1
V 1/4" T

2"x1-1/2" 2"x1-1/2" 3"x1-1/2" 3"x1-1/2" 3"x1-1/2" 3"x1-1/2" 3"x1-1/2" 3"x1-1/2" 3"x1-1/2" 3"x1-1/2" 3"x1-1/2" 3"x1-1/2" 3"x1-1/2" 3"x1-1/2" 3"x1-1/2" 3"x1-1/2" 4"x1-1/2" 4"x1-1/2" 4"x1-1/2" 4"x1-1/2" 4"x1-1/2" 4"x1-1/2" 4"x1-1/2"
C 2" FML LO
5 3"x2" 4"x3" KPG 5
2"x1" 1003

1" NC

V
NOTE 7

NOTE 6
UG AG
FIRE WATER
6"-65-FW-26165-A2AU16-B 6"-66-FW-26531-A2AU16-V P 23-Mar-2023 APPROVED FOR DESIGN A.Waykole C.Balsano/S.Naik/
R.Soldinger
26747 65-PP-152-260001-03 R.Santangelo/A.Pirani

1002 1002 L 19-Oct-2022 ISSUED FOR COMPANY REVIEW A.Waykole T.Rossi/S.Soni/


T.Rossi
UNIT 65 UNIT 66
R.Santangelo/A.Pirani

FROM FIRE WATER


UNDERGROUND Prepared Checked Approved
Rev. Date Description
By By By

ABU DHABI POLYMERS COMPANY LIMITED


(BOROUGE)

PETROCHEMICALS PROJECT
SURFACE AREA DESIGN DESIGN SPRINKLER K SPRINKLER HEAD NO. OF COMPANY PROJECT NO PROJECT TITLE:
SPRINKLER ALARM OCCUPANCY
6 AREA SPRINKLER VALVE SIZE. BUILDING DESCRIPTION ROOM PROTECTED
HAZARD
COVERED BY ALARM REMOTE DENSITY FACTOR TEMPERATURE SPRINKLER 4700000900 BOROUGE 4 PROJECT - EPC PACKAGE 3 - 6
VALVE (M2) AREA (M2) (LPM/M2) (METRIC) RATING (°C) (UPRIGHT) CONTRACTOR PROJECT NO
SYSTEM NO.
(AMAO) 4300 - PO
PO UNIT - RUWAIS, UAE
PRODUCT PE6-PE7 BLENDER SILOS BAGGING GROUND ORDINARY 4464.4 80 68°C 504 DRAWING TITLE: PIPING AND INSTRUMENTATION DIAGRAM
66-SD-13701 6" 139 8.1
HANDLING FLOOR HAZARD GROUP 2
UNIT 66 - SPRINKLER AND DELUGE, WET SPRINKLER
SYSTEM 66-SD-13701, PRODUCT HANDLING PE6 / PE7 BLENDING SILOS
BOROUGE DOCUMENT CLASS' N PROJECT DRAWING NO REV: P

CONTRACTOR: 4300-SZ-DM-660260081 SHEET UNIT: 66


1 BOROUGE: 66-PP-152-260081 OF AREA: 26
CADD SHEET
A B C D E F REF. 66-PP-152-260081-ISP SCALE: SIZE A1