GENERAL NOTES

GENERAL NOTES:
A) SIZE OF HEADER FOR EACH SINGLE SPRAY NOZZLE SHALL BE 1". SPRAY NOZZLE HEAD END
CONNECTION IS NPT MALE THREADED.
B) HORIZONTAL DRY PIPING. DOWNSTREAM OF THE BLOCK VALVE AND OF THE AUTOMATIC ON-OFF VALVE,
SHALL BE FITTED WITH ADEQUATE DRAIN FACILITIES; WEEP HOLES IN SPRAY HEADERS AND AUTOMATIC
1 DRAIN VALVES SHALL BE PROVIDED AT SELECTED LOCATIONS. ALL DRAINS SHOWN ON THIS P&ID ARE FOR 1
4300-SZ-DM-660260037

REFERENCE ONLY. FOR ACTUAL LOCATION REFER TO ISOMETRIC DRAWINGS.


66-PP-152-260037

C V

1"
CONTRACTOR :

1"x1/2"
BOROUGE :

DETAIL- "A"
(APPLICABLE FOR ALL SPRAY NOZZLES)
Q 131-VV-014 NOTE 1
1" 1" 3/4"
NC
1" 1-1/2" 1-1/2"

1" 1" 1-1/2" 1-1/2" 1-1/2" 1-1/2"

NOTES:
DETAIL-"A"
2 2
1-1/2"x1" 1-1/2"x1" 2"x1-1/2" 2"x1-1/2" 1) INSPECTOR TEST VALVE 3/4" SHALL BE PROVIDED AT 1200 MM FROM GRADE LEVEL.
VALVE SHALL BE DESIGNED TO SEAL IN CLOSED DIRECTION.
2"x1-1/2" 2"x1-1/2"

1-1/2" 2" 2"


BOTTOM RING MIDDLE RING TOP RING
Q

1" Q
2"

1-1/2"

1"
2" 2" 2"
2" 2" REFERENCES:
1-1/2" 2"x1-1/2" 2"x1-1/2" 1-1/2" 3"x2" 3"x2" 3"x2" 3"x2" FOR GENERAL NOTES AND REFERENCES SEE DWG N. FROM PU-PP-152-01000-01÷15;
PIPING AND INSTRUMENTATION DIAGRAM-SYMBOL, ABBREVIATIONS AND NOTES.
3 3
PUX-MR-572-00004 FIRE FIGHTING WATER SPRAY DELUGE / SPRINKLER SYSTEMS DATASHEETS
BGS-MU-200 GENERAL SPECIFICATION FIRE PROTECTION DESIGN PHILOSOPHY
THIS INFORMATION IS NOT TO BE USED, DISCLOSED, OR REPRODUCED IN WHOLE OR IN PART TO ANYONE OUTSIDE OF ABU DHABI POLYMERS COMPANY LIMITED (BOROUGE) AND ITS SUBSIDIARIES,

BGS-MU-201 GENERAL SPECIFICATION WATER SPRAY FIRE PROTECTION SYSTEMS


P4-PH-567-00002 FIRE FIGHTING GENERAL SPECIFICATION PO & 1-HEXENE PLANT
PUX-PH-581-00009 DELUGE AND SPRINKLER SYSTEM TECHNICAL SPECIFICATION
PU-PH-407-00001 HYDRAULIC CALCULATION UNDERGROUND FIREWATER NETWORK PO, 1-HEXENE AND U&O
131-PH-407-00001 FIREFIGHTING SYSTEMS HYDRAULIC CALCULATION WATER SPRAY
2" SYSTEM - PO PURIFICATION COMMON-1
Q
THIS DOCUMENT CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF ABU DHABI POLYMERS COMPANY LIMITED (BOROUGE) OR ANY OF ITS LICENSORS.

3"
2" 4"x2" 6"x3"
Q
6"x4"
Q 3"

Q
FIRE WATER
6"-66-FW-26390-A2RU16-V 131-2-66-13 Fire Water Spray Deluge System 66-SD-13121
66-PP-152-260035 26501
1003
FROM DELUGE VALVE
4 (SYSTEM 66-SD-13121) 4
EXCEPT PURSUANT TO A WRITTEN AGREEMENT WITH ABU DHABI POLYMERS COMPANY LIMITED (BOROUGE).

TR-TCMS-NSH-P01451

5 5

RATE OF REQUIRED
SR. NO. EQUIPMENT. NO. DESCRIPTION SURFACE DELUGE NO. OF CONE P4-PH-106-00001
DIA (M) HEIGHT (M) APPLICATION FLOW DEMAND K-FACTOR TYPE
AREA (M²) SYSTEM NOZZLES ANGLE (DEG) COMMODITY CODE / IDENT CODE
(LPM/SQ.M) (m³/h)

1 131-VV-014 HP FLARE KO DRUM 4.5 9.000 165.321 66-SD-13121 (6") 10.2 152.8 49 30.0 120 MEDIUM VELOCITY

C.Balsano/S.Naik/
Q 14-Aug-2023 APPROVED FOR CONSTRUCTION A.Waykole R.Santangelo/A.Pirani R.Soldinger
TOTAL 152.8
Q P 24-Mar-2023 APPROVED FOR DESIGN A.Waykole C.Balsano/S.Naik/
R.Santangelo/A.Pirani R.Soldinger

L 22-Sep-2022 ISSUED FOR COMPANY REVIEW A.Waykole T.Rossi/S.Soni/


R.Santangelo/A.Pirani T.Rossi

Prepared Checked Approved


Rev. Date Description
By By By

ABU DHABI POLYMERS COMPANY LIMITED


(BOROUGE)

PETROCHEMICALS PROJECT
COMPANY PROJECT NO PROJECT TITLE:
6 4700000900 BOROUGE 4 PROJECT - EPC PACKAGE 3 - 6
CONTRACTOR PROJECT NO
4300 - PO
PO UNIT - RUWAIS, UAE
DRAWING TITLE: PIPING AND INSTRUMENTATION DIAGRAM
SYSTEM-66, SPRINKLER AND DELUGE,
WATER SPRAY DELUGE SYSTEM 66-SD-13121, PO COMMON AREA
BOROUGE DOCUMENT CLASS' N PROJECT DRAWING NO REV: Q

CONTRACTOR: 4300-SZ-DM-660260037 SHEET UNIT: 66


1 BOROUGE: 66-PP-152-260037 OF AREA: 26
CADD SHEET
A B C D E F REF. 66-PP-152-260037-ISQ SCALE: SIZE A1

You might also like