GENERAL NOTES

GENERAL NOTES
A) SCOPE BREAK BETWEEN VENDOR AND BOROUGE 4 EPC CONTRACTOR IS INDICATED BY:

FIREWATER

FIREWATER

FIREWATER
SHEET 1 OF 2

SHEET 1 OF 2

SHEET 1 OF 2

SHEET 1 OF 2
FROM 1-HEXENE UNIT

FROM 1-HEXENE UNIT

FROM 1-HEXENE UNIT

FROM 1-HEXENE UNIT


C

FIRE WATER
V

65-PP-152-260009-01 19724

65-PP-152-260009-01 26838

65-PP-152-260009-01 26839

65-PP-152-260009-01 19402
B) DIAMETERS SHOWN FOR L0TU16 REFERS TO HDPE NOMINAL SIZE PIPE.
4300-SZ-DM-650260009-02

1 1
SIZE EQUIVALENCE TABLE
FIRE WATER PIPES AND FITTINGS
65-PP-152-260009-02

HDPE NOMINAL SIZE HDPE NOMINAL OD HDPE NOMINAL ID EQUIVALENT CARBON


(INCH) (MM) (MM) STEEL NOMINAL SIZE (INCH)

500 mm-65-FW-26413-L0TU16-N
180 mm-65-FW-26697-L0TU16-N

180 mm-65-FW-26698-L0TU16-N
2 63 49 2

500 mm-65-FW-26349-L0TU16-N
4 125 97 4
6 180 140 6
CONTRACTOR :

1001
1001

1001
1001
BOROUGE :

8 225 175 -
10 250 194 8
12 315 245 10
14 355 276 12
16 400 311 -
18 450 350 14

6"-65-FW-26693-A2AU16-B

6"-65-FW-26694-A2AU16-B
20 500 389 16
22 560 422 18

1002

1002
24 630 490 20
2 2
28 710 535 24
32 800 603 28

500 mmx400 mm
125-0-65-01 Fire Water Underground for 1-Hexene (Process Area)
16"-65-FW-26529-A2AU16-N NOTES
Q 16"
1002
HD HD 1) HYDRANTS WILL BE EQUIPPED WITH 2 X 2 ½" VALVE HOSE CONNECTIONS WITH INSTANTANEOUS
65-SV-2668 Q Q
COUPLINGS AND 2 X 4" VALVED PUMPER CONNECTIONS.
500 mmx400 mm 2) MONITORS SHALL BE INSTALLED AT LEAST 15M FROM THE AREA TO BE COVERED.
3) ALL UNDERGROUND GATE VALVES SHALL BE CAR SEALED IN OPEN POSITION. ALL UNDERGROUND GATE
VALVES AND ASSOCIATED TRANSITION PIECE JOINTS SHALL BE INSTALLED INSIDE PIT. ALL GATE VALVES
SHALL BE PROVIDED WITH EXTENDED SPINDLE AND POST INDICATOR.
125-SG-0013 125-SG-0012 4) THE A2AU16-B PIPES WILL BE COATED IN SITE WITH POLYURETHANE, ACCORDING TO
``COATING FOR UNDERGROUND STEEL PIPE BGS-MY-001''.
5) RISERS ON TRANSITION FROM UNDERGROUND PIPING TO ABOVE GROUND PIPING SHALL BE EQUIPPED
WITH PROTECTION AGAINST PHYSICAL DAMAGE
6) TYPICAL HYDRANT WITH MONITOR CONNECTION, BUTTERYFLY VALVE TO BE PROVIDED ON THE 6" STANDPIPE
IS IN VENDOR SCOPE

3 3

HD
THIS INFORMATION IS NOT TO BE USED, DISCLOSED, OR REPRODUCED IN WHOLE OR IN PART TO ANYONE OUTSIDE OF ABU DHABI POLYMERS COMPANY LIMITED (BOROUGE) AND ITS SUBSIDIARIES,

Q
TR-TCMS-NSH-P01451 V
6"
1-HEXENE CYCLO HEXENE
STORAGE TANK & (INSULATION KIT TYPICAL)

AG
C
IMPURE TANK
THIS DOCUMENT CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF ABU DHABI POLYMERS COMPANY LIMITED (BOROUGE) OR ANY OF ITS LICENSORS.

6"

UG
NOTE 9
A2AU16-B LOTU16

7) TYPICAL HYDRANT CONNECTIO, BUTTERYFLY VALVE TO BE PROVIDED ON THE 6" STANDPIPE.

HD

500 mm-65-FW-26413-L0TU16-N
Q

1001
4 V 4
6"
EXCEPT PURSUANT TO A WRITTEN AGREEMENT WITH ABU DHABI POLYMERS COMPANY LIMITED (BOROUGE).

(INSULATION KIT TYPICAL)

AG
C
125-SG-0008 125-SG-0010
Q 6"

UG
A2AU16-B LOTU16
6"-65-FW-26525-A2AU16-B 180 mm-65-FW-26523-L0TU16-N

HD
125-SG-0011
1002 1001 8) FLUSHING CONNECTION OUTLET TO BE ROUTED TO NEAR BY CLEAN WATER TRENCH.
Q Q
HD HD 9) SEMI FIXED FOAM SYSTEM SHALL BE PROVIDED FOR INTERNAL FLOATING ROOF TANK AND DIKE.

REFERENCE :
P4-PP-152-01000-01 TO 11: PIPING AND INSTRUMENTATION DIAGRAM-SYMBOLS, ABBREVIATIONS
6"-65-FW-26696-A2AU16-B

6"-65-FW-26531-A2AU16-B

AND NOTES.
B4-LP-201-00001 : OVERALL PLOT PLAN ALL UNITS OF BOROUGE 4
1002

1002

BGS-MU-200 : FIRE PROTECTION DESIGN PHILOSOPHY


B4-PH-587-00004 : FIRE FIGHTING GENERAL SPECIFICATION
65-PP-152-280009-04 : PIPING & INSTRUMENTATION DIAGRAM UNIT 65-
FIREWATER UNDERGROUND SYSTEM UTILITIES AREA SHEET 4 OF 4
5 5
65-PP-152-250009-01 : PIPING & INSTRUMENTATION DIAGRAM UNIT 65-
FIREWATER SYSTEM UNDERGROUND SYSTEM DERIVATIVE AREA SHEET 1 OF 2
180 mm-65-FW-26695-L0TU16-N

180 mm-65-FW-26530-L0TU16-N

65-PP-152-260005-01 : PIPING & INSTRUMENTATION DIAGRAM UNIT 65-


FIREWATER SYSTEM UNDERGROUND SYSTEM POLYOLEFINS PE UNIT SHEET 1 OF 3
125-PH-169-00001-01 : FIRE PROTECTION GENERAL LAYOUT 1-HEXENE UNIT SHEET 1 OF 2.
1001

1001

Q
FIREWATER 630 mmx500 mm Q 31-Aug-2023 APPROVED FOR CONSTRUCTION A.Waykole C.Balsano/S.Naik/
R.Santangelo/A.Pirani R.Soldinger
630 mm-65-FW-28007-L0TU16-N 500 mm-65-FW-26532-L0TU16-N 500 mm-65-FW-26528-L0TU16-N
20688 65-PP-152-280009-04 P 24-Mar-2023 APPROVED FOR DESIGN A.Waykole C.Balsano/S.Naik/
R.Santangelo/A.Pirani R.Soldinger
1001 1001 1001 L 17-Mar-2022 ISSUED FOR COMPANY REVIEW A.Waykole T.Rossi/S.Soni/
T.Rossi
FROM B4 UTILITIES R.Santangelo/A.Pirani

SHEET 4 OF 4 Prepared Checked Approved


Q Rev. Date Description
By By By
TEI IN POINT
IP-C-U4-P4-L-028 ABU DHABI POLYMERS COMPANY LIMITED
(BOROUGE)

PETROCHEMICALS PROJECT
COMPANY PROJECT NO PROJECT TITLE:
6 4700000900 BOROUGE 4 PROJECT - EPC PACKAGE 3 - 6
CONTRACTOR PROJECT NO
4300 - PO
PO UNIT - RUWAIS, UAE
DRAWING TITLE: PIPING AND INSTRUMENTATION DIAGRAM
UNIT 65
FIRE WATER NETWORK 1-HEXENE PLANT SHEET 2 OF 2
BOROUGE DOCUMENT CLASS' N PROJECT DRAWING NO REV: Q

CONTRACTOR: 4300-SZ-DM-650260009-02 SHEET UNIT: 65


1 BOROUGE: 65-PP-152-260009-02 OF AREA: 26
CADD SHEET
A B C D E F REF. 65-PP-152-260009-02-ISQ SCALE: SIZE A1