Ceiling Pendants - Operation and Maintenance Manual

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 45

CEILING PENDANTS

OPERATION AND MAINTENANCE MANUAL

Exemple of configuration

1
NOVAIR

GENERAL DESCRIPTION

As a leading specialist group in operating theatre departments and medical gas pipeline
systems, NOVAIR is uniquely qualified to understand both the user and construction
requirements.

NOVAIR supplies a comprehensive range of high quality ceiling suspension systems,


competitively priced, which can be purchased as a part of NOVAIR Piped medical gas
installation or as a stand‐alone product.

The range of pendants has been developed in response to the following criteria:

 Increased Safety
 Increased Hygiene and Sterility
 Ease of Use

2
NOVAIR

The many advantages in the field of safety and hygiene are;

 No more trailing leads or hoses to restrict movement within the department, all equipment
is attached via short connecting hoses or cables to integral hook up points.
 Fully encapsulated system, incorporating modular service boxes, makes maintenance and
general use easier.
 Single or two pieces arm assemblies, motorised or static, equipment can now be located at
point of use with the greatest of ease.
 Fully equipped as desired with, high and low voltage supplies, medical gas outlet points,
communication points, miscellaneous.
Generally, there are two types of Operating theatre Pendant;

1. Rotating Head Rigid Pendant


2. Multi‐Movement Pendants (Single & Twin Arms)
3. Horizontal Arm Pendants (Single & Twin Arms)
4. Double Arm ICU Pendant

ROTATING HEAD RIGID PENDANT (ACP‐90)

General Description
The unit is a vertically mounted Services Column that is rigidly mounted to the Ceiling
Structure of the Building Fabric. These units normally contain the Medical Gas, AGSS and
Electrical Services such as standard sockets together with UPS Sockets that are required at the
point of use. Configurations of these services will vary depending on the Customer
Specifications and requirements.
Care should be taken to ensure that the unit is securely fixed to ensure that there is a minimum
of deflection at the head/console.

The fixing method and supporting steelwork will vary according the building structure and the
depth of ceiling void.

Practical Considerations
The standard recommended height of the lower face of a rigid pendant with a horizontal shelf
is 1.4 meter, which will provide access to the equipment mounted on the Shelf.

3
NOVAIR

However, Pendants that have no shelf may be mounted at a higher level and which must take
into account the differing heights of theatre personnel who will have to make the connections
to the services, or conditions needed for particular operations.
The pendant should be located near the head of the operating table. However, note must be
taken of any moving equipment in the theatre, such as operating theatre lamps, to ensure
that the location of the pendant does not foul this equipment.
Finish
The pendant is normally supplied in white epoxy finish (RAL 9002), but other colours can be
provided. The unit can also be supplied with a special non‐reflective finish suitable for use with
laser equipment.
Electrical Requirements
The standard supply to the pendant is 220 volts, single phase, 50 Hz. Other voltages and
frequencies are available on request.
Drawing

340

Typical Drawing of the Rigid Pendant with Rotating Head

4
NOVAIR

Medical Gas Terminal Units


The Medical Gas and AGSS Terminal Units are designed to fully comply with the following
specifications:

 BS.5682‐1984 Medical Gases


 BS.6834‐1992 AGSS Systems
 NHS Estates Health Technical Memorandum – 2022
 NHS Estates Model Engineering Specification ‐ C11
Terminal Units are available for the following gases,
 Oxygen
 Nitrous Oxide
 Oxygen – Nitrous Oxide Mixture
 Medical Air 400 kPa
 Surgical Air 700 kPa
 Medical Vacuum
 AGSS
Terminal Units are available in the following configurations:

 Flush Wall Mounted


 Surface Wall Mounted
 Bed‐Head Trunking Mounted
 Rigid Pendant Mounted
 Flexible Pendant Mounted

The simple design of the Terminal Unit enables ease of installation to suit most applications.
If your particular application is not listed please contact us for specific details.

The Terminal Unit consists of a terminal block with integral shut off valve and stub of 12‐mm
copper pipe (150‐mm or 200‐mm) and a back‐plate or bed‐head back‐plate.

The different gases are clearly identified on the ring socket by the use of bold permanent
colours to BS 5682 – 1992. An anti rotational pin is fitted to all horizontally mounted units to
ensure the correct orientation of downstream equipment.

5
NOVAIR

Performance of Terminal Units

The terminal unit exceeds the criteria given in the table below:

TERMINAL UNIT PERFORMANCE BS 5682:1984

Gas Pipeline Design flow Pressure drop Pressure drop


pressure across T.U. inc. Hose *
O2 or N2O 400kPa 40 L/Min 3.4kPa 10kPa
O2/N2O 400kPa 275 L/Min 55kPa 150kPa
Medical Air 4 400kPa 50 L/Min 3.4kPa 11kPa
Surgical Air 7 700kPa 250 L/Min 34kPa 75kPa
Vacuum 53.3kPa** 40 L/Min 13.3kPa 20kPa (150mm
(400mm Hg) (100mm Hg) (150mm Hg) Hg)

* Maximum pressure drop across terminal unit with NIST connectors and 2M of flexible
hose.

** Below standard atmospheric pressure of 101.3 kPa


Terminal unit performance ISO 9170 – 400 kPa
 Connection Force Max 100N
 Disconnection Force Max 110N
Min 20N
 Leakage 0.333 ml/Min

Medical Gas Hoses


The Medical Gas Hoses within the Pendant have NIST connections at the Ceiling connection
and at the connections to the Terminal Units in the Console Head. These Hose Assemblies
comply with EN 739. Frequent checking and Maintenance of these hoses is important to
ensure that the flexible connectors have not become worn or leaks have occurred that will
not be noticeable due to them being enclosed inside the Pendant.
Generally, these hoses and connectors should be replaced regularly and the replacement
timescale depends on the frequency of use of the Pendant. It is suggested that all hoses are
replaced, with factory supplied and tested items, every 2 years.

6
NOVAIR

Electrical Sockets
The Electrical Sockets installed may conform to differing standards to suit the user. The
operation of the sockets and the electrical connections should be checked on a regular basis
to ensure fault free conditions apply. Full safety checks of these electrical sockets and any
other electrical sockets in the Operating Theatre should be checked by the Hospital staff
frequently.

Pressure Gauges
Pressure gauges/indicators are provided in the Console to give an approximate indication of
the pressure at the gases within the Pendant. These units are not to be used as a finite
pressure indication and they are to be used only as an aid to fault identification.

General Description
The Multi‐movement pendant is a modular unit, which can be supplied with or without height
adjustment. The pendant consists of a ceiling mount, upon which a wide selection of arms can
be mounted. Flexible connectors carry services. Gas services are physically separated from the
electrical services. The bottom panel of the pendant can be removed to provide access for
maintenance.
An optional motor can be provided and gives 300mm of height adjustment. Other travel
lengths are available, depending on the installation. Operation is by an electrically activated
remote control push‐button located at the pendant, or if required, at a theatre wall panel.
The pendant meets the requirements of the UK DHSS Health Technical memorandum No.
2022. The standard medical gas terminals installed in the pendant conform to HTM No. 2022
and to BS.5682. The pendant can be constructed to other standards, and other makes of
terminal can be fitted.
It is recommended that the terminal units fitted into the pendant be of a similar type to those
in other parts of the hospital.

7
NOVAIR

Services
Services are installed to suit the particular installation. Typical services are:
1. Medical Gas Services
2. Electrical Outlets
3. Waste Anaesthetic Gas Outlets
4. Vacuum (Suction) Outlet

Medical Gases
These services are to BS 5682, and include 02, N2O, O2/N2O mixture (50%/50%), vacuum, air
(4 bar) and air (7 bar). Maximum number of medical gases that can be accommodated: 8

Electrical outlets
These can be high or low voltage. Outlets can be splash proof. Maximum number of 13 amp
sockets that can be accommodated: single: 6 twin: 3

Waste Anaesthetic Gas Outlets


These can be in accordance with appropriate standards. However, only the outlet is installed
in the pendant. The waste gas extraction system is and additional system.

Vacuum (Suction) outlet


An outlet for medical suction can be installed in the pendant. The suction can be piped away
to an external regulator/collecting jar assembly, such as can be installed in a wall panel

Practical Consideration
The standard recommended height of the lower face of a pendant is 1.7 meter. However,
this does not take into account the differing heights of theatre personnel, or conditions
needed for particular operations.

8
NOVAIR

The pendant allows the unit to be lifted above working height when the unit is not required,
but also allows the height to be adjusted to suit particular circumstances. The pendant should
be located near the head of the operating table. However, note must be taken of any moving
equipment in the theatre, such as operating theatre lamps, to ensure that the location of the
pendant does not foul this equipment.
Finish
The pendant can be supplied in white epoxy finish (RAL 9002), or in stainless steel. The unit
can also be supplied with a special non‐reflective finish suitable for use with laser equipment.

Electrical Requirements
The standard supply to operate the pendant is 240 volts, single phase, 50 Hz. Other voltages
and frequencies are available on request.
Drawing

15
Z

X
Electrical Box NIST Connectors

Cover
630

m
0m
100

210 210 350


500

500

Y
530
1100

9
NOVAIR

Operation
Pressing a switch in the remote control unit operates the pendant. One switch controls the
rise and another controls the fall. Components fitted into the pendant should be operated in
accordance with the manufacturer instructions.

Maintenance
Maintenance is important for this pendant to ensure that the flexible connectors have not
become worn. Generally, these connectors should be replace regularly. ‘Competent’ persons
as defined by HTM 2022 should carry out maintenance.
Maintenance of components should be in accordance with the manufacturer instructions.
It is recommended that the maintenance requirements for the components be combined into
one program of maintenance for the pendant and incorporated into the planned maintenance
program for the hospital.

Safety
The pendant should be installed by Competent’ persons as defined by HTM 2022. Particular
care should be taken when installing pendants with several gases to ensure that the pipeline
to each gas terminal outlet is connected to the correct gas supply pipeline.
Checks should be made using gas flow and gas identity tests to ensure that the connections
are correct.
Care should be taken to ensure that electrical earth connections are not disturbed and to
ensure that the pendant itself is correctly electrically bonded to the gas and electricity supply
to avoid hazard to patients and theatre personnel.

HORIZONTAL ARM PENDANTS


General Consideration
Horizontal arm pendants can be classified as single and twin horizontal arm pendants. As its
name implies, single horizontal arm pendant has a single arm (generally 1000mm long) which
has a capability of 340o rotation around its vertical axis. Twin horizontal Arm Pendant has two
arms 600mm and 800mm long respectively and capable of reaching further distances of
equipment in the area installed.

10
NOVAIR

Lengths of Arms used in Pendants are standard and 1000mm for single horizontal arm pendant
and 600 and 800mm for twin horizontal arm pendant. Optionally, other sizes can be
manufactured upon customer request.

Finish
The pendant is normally supplied in white epoxy finish (RAL 9002), but other colours can be
provided. The unit can also be supplied with a special non‐reflective finish suitable for use with
laser equipment.

Safety
The pendant should be installed by Competent’ persons as defined by HTM 2022. Particular
care should be taken when installing pendants with several gases to ensure that the pipeline
to each gas terminal outlet is connected to the correct gas supply pipeline.
Checks should be made using gas flow and gas identity tests to ensure that the connections
are correct.
Care should be taken to ensure that electrical earth connections are not disturbed and to
ensure that the pendant itself is correctly electrically bonded to the gas and electricity supply
to avoid hazard to patients and theatre personnel.

11
NOVAIR

Drawing

NIST CONNECTORS

SELV Electrical Box LV Electrical Box

1000 mm

600 mm

DOUBLE ARM ICU/HDU PENDANT (DAP‐90)


General Consideration
The double arm ICU pendant is a modular unit which provides the ideal arrangement for all
necessary services and equipment connection facilities required in an ICU or CCU for all clinical
purposes. The pendant consists of a ceiling mount, upon which a wide selection of arms can
be mounted, wet side and dry side equipment consoles.
Wet side equipment console consists of double horizontal arms in 1000mm and 600mm
lengths and has drip hooks, infusion stands, equipment rail as well as gas and electric services.
Dry side equipment console consists of single horizontal arm in 1000mm length and has
shelves for equipment, drawer and gas and electric services. Gas services are carried to outlets
via flexible connectors and physically separated from the electrical services. Each pendant arm
has 340o rotatibility feature around its vertical axis. There are totally three pneumatic brakes,
two of them are mounted in supporting bracket systems of arms and the other one is mounted
to the joint between the arms of wet side equipment console. Brakes are controlled by buttons

12
NOVAIR

on the consoles and during movement of the consoles buttons should be pushed. The
specifications of services (medical gas services and electric services) on pendant are same as
the services defined in previous sections.

Finish
The pendant is normally supplied in white epoxy finish (RAL 9002), but other colours can be
provided. The unit can also be supplied with a special non‐reflective finish suitable for use with
laser equipment.
Drawing

SELV ELECTRIC BOX


LV ELECTRIC BOX 1
NIST CONNECTOR LV ELECTRIC BOX 2

1000 mm

1000 mm 1000 mm

600 mm 600 mm

FINISHED FLOOR LEVEL

13
NOVAIR

Electrical Requirements
The standard supply to the pendant is 220 volts, single phase, 50 Hz. Other voltages and
frequencies are available on request.

The services are run to a first‐fix unit in the ceiling. For medical gases, these services will
terminate in a Non‐interchangeable screw connection (NIST) to BS 5682. The first fix
installation should be completed, fully tested and blanked until the second‐fix installation is
needed. The pendant is supplied as a second‐fix item for installation during the finishing of
the theatre and is normally supplied with all components installed and tested in the factory.
Gas services are via flexible hose connectors, which are attached to the first‐fix NIST
connectors. Electrical services in the pendant normally terminate in a junction (electrical) box,
at the top of the pendant for connection to the hospital electrical wiring system. The pendant
should be fitted to the solid ceiling of the theatre and not supported by a false ceiling only.
The pendant can be supplied as one long unit, which is secured to the main ceiling and then
passes through the false ceiling. Alternatively, a framework can be attached to the main
ceiling, which extends downwards to just above the false ceiling. The pendant can then be
attached to the framework. The pendant is supplied with a beveled fascia plate to provide a
neat junction at the ceiling. All securing bolts must be adequate for the load of the pendant.
Any framework must also be designed for rigidity. Even small loads, such as those imposed by
inserting gas probes can cause large deflections on a long pendant. Any framework should be
designed for maximum rigidity to avoid these deflections.

Installation of First Fix


As shown in Figure 1 the ceiling flange of NOVAIR pendants can be fixed by using male type
steel anchors placed to the holes drilled to the ceiling.
 Drill 8 holes to the ceiling according to the fixing plan of the ceiling flange (1).
 Mount M12 steel anchors (2) to the holes drilled and fix them.
 Locate the ceiling flange (1) to the anchors (2) and fix it by means of hexagonal
nuts, M12 (3) and washers (4).

14
NOVAIR

Figure 1 Installation of Ceiling Flange

 Tighten the hexagonal nuts M12 (3) and be sure that the ceiling plate is fitted firmly to the
raw ceiling and leveled correctly.
After completing the installation of ceiling flange, interface flange should be installed.
Installation of interface flange should be as described below and shown in Figure 2;
 The interface flange should be fixed to the ceiling flange by means of 4 pieces of 50 mm
diameter steel pipes, M20 threaded rods, washers and nuts which are manufactured for the
required length.
 Screw the hexagonal nut M20 (10) approximately 25 mm on the threaded rod M20 (8) and
apply a lock washer (9) then fix on the nut (11) which is welded on the ceiling flange (1).
 Screw the threaded rod M20 (8) to the ceiling flange (1) until it stops. And tighten the
hexagonal nut (10) securely.

Figure 2 Installation of Interface Flange

15
NOVAIR

 If the threaded rods (8) have not been screwed securely, the supporting system may fall
down. Hence, screwing of the threaded rods should be securely to the ceiling flange (1).
 Supporting pipes (7) may cause heavy injuries. Since the interface flange (6) does not provide
safe fixing of the supporting pipes (7) on the threaded rod (8), nobody must be allowed under
the installation area during installation.
 After installation of the supporting pipes (7) on the threaded rods (8) place the interface
flange and fix it to the ceiling plate (1) by tightening the hexagonal nuts M 20 (12) and
washers (9). Be sure that the interface flange (6) is fitted firmly to the ceiling plate (1) and is
leveled correctly.
 After fixing the interface flange (6) locate the supporting bracket system (13) to the opening
of the interface flange (6) as shown in Figure 3.
 Fix the supporting bracket system (13) to the interface flange (6) with 6 pieces of M 18 x
60 mm hexagonal bolts (14), washers (15) and M 18 nuts (16).

Figure 3 Installation of Supporting Bracket System

16
NOVAIR

 The supporting bracket must be mantled in a horizontally aligned position to ensure light
mobility and safe positioning of the supporting bracket system (13)
 After tightening nuts (16) check the horizontal alignment by means of a spirit level (17) and
if required adjust the horizontal alignment by using shims between the interface flange (6)
and the supporting bracket system (13)
 The vertical arm (21) is mounted to the supporting bracket system (13) by means of twelve
M6x10mm screws (22).
 Fix the M6x10mm screws (22) and after checking the vertical alignment of the vertical arm
(21) tighten them.
 After mounting the vertical arm slip on the cap (23) over the vertical arm (21) towards the
horizontal arm side to hide the screws and fix it by using the 102x3,5 O‐ring (24).

32
13
Electric (Junction) Box
6

NIST Connection

22

21

23

24

Figure 4 Installation of Vertical Arm

Installation of Pendant

17
NOVAIR

21
26

25

Figure 5 Installation of Horizontal Arm

 The electrical horizontal arm (25) should be mounted to the vertical arm (21) by means of
eight M6x10mm screws (26).
 Fix the screws (26) and after checking the horizontal alignment of the electrical horizontal
arm (25) tighten them.

Figure 6 Assembly of Console

18
NOVAIR

After installation of horizontal arm, pendant console should be assembled to the horizontal
arm. During the assembly of console, please take care in handling the hoses and electric cables
which are connected to the console. Steps that should be followed are described below and
shown in Figure 6.
 Before assembly of the console (26) to the electric horizontal arm (25) slide the hoses and
cables of the console carefully through the arms installed before and fix them to the interface
flange (6) temporarily.
 The console (26) is mantled to the electrical horizontal arm (25) by means of eight M6x10mm
screws (27).
 Fix the screws (27) and after checking the horizontal alignment of the console (26) tighten
them.

Console Side

21

25

Electric Motor
Side

Figure 7 Assembly of Electrical Arm’s Covers


 Mount the plastic covers (28) to both ends of the electrical arm and fix them with screws
(See Figure 7)
 Mount the metal covers (29) to both ends of the electrical arm and fix them with screws.
 Locate the greater plastic covers (31) to the motor side of the electrical arm and fix them
with screws.
 Locate the small plastic covers (30) to the console side of the electrical arm and fix them with
screws.

19
NOVAIR

34

32
33
Electric Box
6

NIST
CONNECTIONS

Figure 8 Connections of the Gases and Electrical Cables


 At the interface flange (6) there are NIST connectors (33) as seen in Figure 8 and an electric
(junction) box (32) to connect gas hoses and the electric cables.
 After connecting the copper pipes available at the ends of the NIST connectors (33) which
are on the interface flange to the appropriate gas system, connect the hoses (34) to the
appropriate NIST connector.
 Connect the air hose of the pneumatic brake to a min. 5 bar air outlet.
 Connect the cables coming from the console to the electric box (32) and then to the mains.

INSTALLATION OF DAP‐90 PENDANTS


Installation of First Fix
As shown in Figure 9 the ceiling flange of NOVAIR pendants can be fixed by using male type
steel anchors placed to the holes drilled to the ceiling.
 Drill 8 holes to the ceiling according to the fixing plan of the ceiling flange (1).
 Mount M12 steel anchors (2) to the holes drilled and fix them.
 Locate the ceiling flange (1) to the anchors (2) and fix it by means of hexagonal nuts, M12 (3)
and washers (4).
 Tighten the hexagonal nuts M12 (3) and be sure that the ceiling plate is fitted firmly to the
raw ceiling and leveled correctly.

20
NOVAIR

Figure 9 Installation of Ceiling Flange


After completing the installation of ceiling flange, interface flange should be installed.
Installation of interface flange should be as described below and shown in Figure 10;
 The interface flange should be fixed to the ceiling flange by means of 6 pieces of 50 mm
diameter steel pipes, M20 threaded rods, washers and nuts which are manufactured for the
required length.
 Screw the hexagonal nut M20 (9) approximately 25 mm on the threaded rod M20 (7) and
apply a lock washer (8) then fix on the nut (10) which is welded on the ceiling flange (1).
 Screw the threaded rod M20 (7) to the ceiling flange (1) until it stops. And tighten the
hexagonal nut (9) securely.
 If the threaded rods (7) have not been screwed securely, the supporting system may fall
down. Hence, screwing of the threaded rods should be securely to the ceiling flange (1).
 Supporting pipes (6) may cause heavy injuries. Since the interface flange (5) does not provide
safe fixing of the supporting pipes (6) on the threaded rod (7), nobody should be allowed
under the installation area during installation.

21
NOVAIR

Figure 10 Installation of Interface Flange

 After installation of the supporting pipes (6) on the threaded rods (7) mount the interface
flange (5) and fix it to the ceiling plate (1) by tightening the hexagonal nuts M 20 (11) and
washers (8). Be sure that the interface flange (5) is fitted firmly to the ceiling plate (1) and is
leveled correctly.

Figure 11 Installation of Supporting Bracket System

22
NOVAIR

After fixing the interface flange (5) locate the supporting bracket systems (12 & 13) to the
openings of the interface flange (5) as shown in Figure 11.
 Fix the supporting bracket systems (12 & 13) to the interface flange (5) by 6 pieces of
M18x60 mm hexagonal bolts (14), washers (15) and M18 nuts (16).
 The supporting brackets should be mantled in a horizontally aligned position to ensure light
mobility and safe positioning of the supporting bracket systems (12 & 13)
 After tightening nuts (16) check the horizontal alignment by means of leveling device (17)
and if required adjust the horizontal alignment by using shims between the interface flange
(5) and the supporting bracket systems (12 & 13).

13
5

12

20
21
18 20
21

23

22

19

25

23

24
Figure 12 Installation of Horizontal and Vertical Arms of Dry and Wet Side Consoles

23
NOVAIR

After completing the assembly of supporting bracket systems (12&13), system is ready for the
assembly of horizontal and vertical arms of wet and dry side equipment consoles. Assembly
of arms are described below.
 Initially the horizontal arms should be mounted. Installation of horizontal arms (18 &19) can
be mounted by means of sixteen M8x16 allen screws (20) and washers (21) to the supporting
bracket systems (12&13).
 Covers (25) should be fitted to the vertical arms (22&24) as shown in Figure 7.4.
 Then, vertical arms (22&24) can be mounted to horizontal arms (18&19) by means of
M6x12mm screws (23). For each arm twelve screws will be used.
Nous ne pouv ons pas afficher l’image.

22

27

26

24
25

27
28
DRY SIDE

WET SIDE
Figure 13 Assembly of Dry and Wet Side Equipment Consoles

24
NOVAIR

After installation of horizontal and vertical arms, wet and dry side equipment consoles should
be assembled to the vertical arms (22&24). During the assembly of consoles, please take care
in handling the hoses and electric cables which are connected to the consoles. Steps that
should be followed are described below and shown in Figure 13.
 Before assembly of the consoles (26&28) to the vertical arms (22&24) slide the hoses and
cables of the console carefully through the arms installed before and fix them to the interface
flange (5) temporarily.
 The consoles (26&28) are mantled to the vertical arms (22&24) by means of twelve
M6x10mm screws (27).
 Fix the screws (27) and after checking the horizontal alignment of the consoles (26&28)
tighten them.

INSTALLATION OF MTP‐90 PENDANTS

Installation of First Fix


Nous ne pouv ons pas afficher l’image.

Figure 14 Installation of Ceiling Flange

As shown in Figure 14 the ceiling flange of the pendants can be fixed by using male type steel
anchors placed to the holes drilled to the ceiling.
 Drill 8 holes to the ceiling according to the fixing plan of the ceiling flange (1).
 Mount M12 steel anchors (2) to the holes drilled and fix them.

25
NOVAIR

 Locate the ceiling flange (1) to the anchors (2) and fix it by means of hexagonal nuts, M12 (3)
and washers (4).
 Tighten the hexagonal nuts M12 (3) and be sure that the ceiling plate is fitted firmly to the
raw ceiling and leveled correctly.

10
10 1 8
7
8 X 9
6 9

8 5 DETAIL X

11
Figure 15 Installation of Interface Flange

After completing the installation of ceiling flange, interface flange should be installed.
Installation of interface flange should be as described below and shown in Figure 15;
 The interface flange should be fixed to the ceiling flange by means of 4 pieces of 50 mm
diameter steel pipes, M20 threaded rods, washers and nuts which are manufactured for the
required length.
 Screw the hexagonal nut M20 (9) approximately 25 mm on the threaded rod M20 (7) and
apply a lock washer (8) then fix on the nut (10) which is welded on the ceiling flange (1).
 Screw the threaded rod M20 (7) to the ceiling flange (1) until it stops. And tighten the
hexagonal nut (9) securely.
 If the threaded rods (7) have not been screwed securely, the supporting system may fall
down. Hence, screwing of the threaded rods should be securely to the ceiling flange (1).
 Supporting pipes (6) may cause heavy injuries. Since the interface flange (5) does not provide
safe fixing of the supporting pipes (6) on the threaded rod (7), nobody should be allowed
under the installation area during installation.
 After installation of the supporting pipes (6) on the threaded rods (7) place the interface
flange and fix it to the ceiling plate (1) by tightening the hexagonal nuts M 20 (11) and washers

26
NOVAIR

(8). Be sure that the interface flange (5) is fitted firmly to the ceiling plate (1) and is leveled
correctly.
After fixing the interface flange (5) locate the supporting bracket system (12) to the opening
of the interface flange (5) as shown in Figure 8.3.
 Fix the supporting bracket system (12) to the interface flange (5) with 6 pieces of M 18 x
60 mm hexagonal bolts (13), washers (14) and M18 nuts (15).
 The supporting bracket must be mantled in a horizontally aligned position to ensure light
mobility and safe positioning of the supporting bracket system (12).
 After tightening nuts (15) check the horizontal alignment by means of leveling device (16)
and if required adjust the horizontal alignment by using shims between the interface flange
(5) and the supporting bracket system (12)

13

12

5
14
15
16

Figure 16 Installation of Supporting Bracket System

27
NOVAIR

Figure 17 Installation of Horizontal and Vertical Arms

After completing the assembly of supporting bracket systems (12), assembly of horizontal and
vertical arms should be carried out. Assembly of arms is described below.
 Initially the horizontal arm (17) should be mounted. Installation of horizontal arm (17) can
be done by means of sixteen M8x16 allen screws (18) and washers (19) to the supporting
bracket systems (12).
 Then, vertical arm (22) can be mounted to horizontal arm (17) by means of M6x12mm screws
(21).
 Cover (20) should be fitted to the vertical arm (22) as shown in Figure 8.4.

28
NOVAIR

Figure 17 Installation of Horizontal Arm

 The electrical horizontal arm (24) should be mounted to the vertical arm (22) by means of
eight M6x10mm screws (23) as shown in Figure 17.
 Fix the screws (23) and after checking the horizontal alignment of the electrical horizontal
arm (24) tighten them.
After installation of electrical horizontal arm, console should be assembled to the electrical
horizontal arm (24). During the assembly of console, please take care in handling the hoses
and electric cables which are connected to the console. Steps that should be followed are
described below and shown in Figure 18.
 Before assembly of the console (26) to the electrical horizontal arm (24) slide the hoses and
cables of the console carefully through the arm installed before and fix them to the interface
flange (5) temporarily.
 The console (26) is mantled to the horizontal electrical arm (24) by means of twelve
M6x10mm screws (25).
 Fix the screws (25) and after checking the horizontal alignment of the console (26) tighten
them.

29
NOVAIR

22

Figure 18 Assembly of Dry and Wet Side Equipment Consoles

Finally, the covers of electrical horizontal arm should be mounted. Assembly of covers should
be as follows and shown in Figure 19;
 Mount the plastic covers (27) to both ends of the electrical arm and fix them with screws.
 Mount the metal covers (28) to both ends of the electrical arm and fix them with screws.
 Locate the greater plastic covers (30) to the motor side of the electrical arm and fix them
with screws.
 Locate the small plastic covers (29) to the console side of the electrical arm and fix them with
screws.

30
NOVAIR

Console Side

22

24

Electric Motor
Side

Figure 19 Assembly of Electrical Arm’s Covers

INSTALLATION OF HTP‐90 PENDANTS

Installation of First Fix Nous ne pouv ons pas afficher l’image.

Figure 20 Installation of Ceiling Flange

31
NOVAIR

As shown in Figure 20 the ceiling flange of the pendants can be fixed by using male type steel
anchors placed to the holes drilled to the ceiling.
 Drill 8 holes to the ceiling according to the fixing plan of the ceiling flange (1).
 Mount M12 steel anchors (2) to the holes drilled and fix them.
 Locate the ceiling flange (1) to the anchors (2) and fix it by means of hexagonal nuts, M12 (3)
and washers (4).
 Tighten the hexagonal nuts M12 (3) and be sure that the ceiling plate is fitted firmly to the
raw ceiling and leveled correctly.

10
10 1 8
7
8 X 9
6 9

8 5 DETAIL X

11
Figure 21 Installation of Interface Flange

After completing the installation of ceiling flange, interface flange should be installed.
Installation of interface flange should be as described below and shown in Figure 21;
 The interface flange should be fixed to the ceiling flange by means of 4 pieces of 50 mm
diameter steel pipes, M20 threaded rods, washers and nuts which are manufactured for the
required length.
 Screw the hexagonal nut M20 (9) approximately 25 mm on the threaded rod M20 (7) and
apply a lock washer (8) then fix on the nut (10) which is welded on the ceiling flange (1).
 Screw the threaded rod M20 (7) to the ceiling flange (1) until it stops. And tighten the
hexagonal nut (9) securely.
 If the threaded rods (7) have not been screwed securely, the supporting system may fall
down. Hence, screwing of the threaded rods should be securely to the ceiling flange (1).

32
NOVAIR

 Supporting pipes (6) may cause heavy injuries. Since the interface flange (5) does not provide
safe fixing of the supporting pipes (6) on the threaded rod (7), nobody should be allowed
under the installation area during installation.
 After installation of the supporting pipes (6) on the threaded rods (7) place the interface
flange and fix it to the ceiling plate (1) by tightening the hexagonal nuts M 20 (11) and washers
(8). Be sure that the interface flange (5) is fitted firmly to the ceiling plate (1) and is leveled
correctly.

14

12

13

5
15
16
17

Figure 22 Installation of Supporting Bracket System

After fixing the interface flange (5) locate the supporting bracket system (12) to the opening
of the interface flange (5) as shown in Figure 22.
 Fix the supporting bracket system (12) to the interface flange (5) with 6 pieces of M 18 x 60
mm hexagonal bolts (14), washers (15) and M18 nuts (16).
 The supporting bracket must be mantled in a horizontally aligned position to ensure light
mobility and safe positioning of the supporting bracket system (12).

33
NOVAIR

 After tightening nuts (16) check the horizontal alignment by means of leveling device (17)
and adjust the horizontal alignment by using shims (13) between the interface flange (5) and
the supporting bracket system (12).

Figure 23 Installation of Horizontal and Vertical Arms

34
NOVAIR

After completing the assembly of supporting bracket system (12), horizontal and vertical arms
of the console should be done. Assembly of arm is described below.
 Initially the horizontal arms (18) should be mounted. Installation of horizontal arms (18) can
be done by means of sixteen M8x16 allen screws (19) and washers (20) to the supporting
bracket system (12).
 Covers (21) should be fitted to the vertical arm (23) as shown in Figure 9.4.
 Then, vertical arm (23) can be mounted to horizontal arms (18) by means of twelve
M6x12mm screws (22).

24
25

Figure 24 Assembly of Equipment Console

35
NOVAIR

After installation of horizontal and vertical arms, equipment console is going to be assembled
to the vertical arm (23). During the assembly of console, please take care in handling the
hoses and electric cables which are connected to the consoles. Steps that should be followed
are described below and shown in Figure 24.
 Before assembly of the console (25) to the vertical arm (23) slide the hoses and cables of the
console carefully through the arm installed before and fix them to the interface flange (5)
temporarily.
 The console (25) is mantled to the vertical arm (23) by means of twelve M6x10mm screws
(24).
 Fix the screws (24) and after checking the horizontal alignment of the console (25) tighten
them.
LABELS USED ON THE PENDANTS

Earthing Label: It is the label attached to the frame.

Danger Sign: Attached on to the terminal block inside the panel

Phase Status Label: Indicates the connection of Electrical phase 1 L1

Phase Status Label: Indicates the connection of Electrical phase 2 L2

Line Label: Indicates the connection of Electrical neutral line N

Motor Coil Tip Label: Indicates the motor coil tip. U

Motor Coil Tip Label: Indicates the motor coil tip. V

36
NOVAIR

W
Motor Coil Tip Label: Indicates the motor coil tip.

Test Label: Tested.

Gauge Label: Indicates the gauge which measures the pressure


of oxygen gas.

Gauge Label: Indicates the gauge which measures the


pressure of nitrous oxide gas.

Gauge Label: Indicates the gauge which measures the pressure of Air 4
bar gas.

Gauge Label: Indicates the gauge which measures the pressure of Air 7
bar gas.

Gauge Label: Indicates the gauge which measures the level of Vacuum

PACKAGING

When opening the Pendant package, follow the caution marks on the package.
Otherwise, you can cause the unit to damage.

Take care to the direction of arrow while opening the package.

37
NOVAIR

APPENDIX 1 Electrical Wiring Diagram of Anaesthesia Pendant

CAT 6 CABLE

CAT 6 CABLE
CAT 6 CABLE

MICRO SWITCH

II
I

DOUBLE POLE
CAPASITY

SWITCH
M
1

38
NOVAIR

APPENDIX 2 Electrical Wiring Diagram of Surgical Pendants for Rooms N4 144 & N4 260

CAT 6 CABLE

CAT 6 CABLE
CAT 6 CABLE

CAT 6 CABLE
CAT 6 CABLE

MICRO SWITCH
5
3
1

6
5

II
I
4
2

DOUBLE POLE
CAPASITY

SWITCH
4
3
2
1

M
1
1

39
NOVAIR

APPENDIX 3 Electrical Wiring Diagram of Surgical Pendants for Rooms N4 144 & N4 260

CAT 6 CABLE

CAT 6 CABLE
CAT 6 CABLE

CAT 6 CABLE
CAT 6 CABLE

MICRO SWITCH
5
3
1

6
5

II
I
4
2

DOUBLE POLE
CAPASITY

SWITCH
4
3
2
1

M
1
1

40
NOVAIR

APPENDIX 4 Electrical Wiring Diagram of Wet Side of ICU/HDU Double Arm Pendants

CAT 6 CABLE
CAT 6 CABLE

CAT 6 CABLE
CAT 6 CABLE

CAT 6 CABLE
CAT 6 CABLE

41
42
CAT 6 CABLE
CAT 6 CABLE
CAT 6 CABLE
CAT 6 CABLE
CAT 6 CABLE
CAT 6 CABLE
CAT 6 CABLE
TELEPHONE CABLE
APPENDIX 5 Electrical Wiring Diagram of Dry Side of ICU/HDU Double Arm Pendants
NOVAIR
NOVAIR

APPENDIX 6 Rotational and Vertical Movements of Anaesthesia Pendants

Vertical and Rotational movement of pendants can be controlled by the buttons available on
front of the console as shown below. There are two pneumatic brakes which are located in
supporting bracket system and joints between two horizontal arms on anaesthesia pendants.
Brake button (1) operates the pneumatic brake in supporting bracket system and brake button
(2) operates the brake at the joints between two horizontal arms. Vertical (up & down)
movement of console can be adjusted by the button (3).

1 2 3

APPENDIX 7 Rotational and Vertical Movements of Surgical Pendants

Same as anaesthesia pendants for surgical pendants vertical and rotational movements of
pendants can be controlled by the buttons available on front of the console as shown below.
There is single pneumatic brake on surgical pendant located in the supporting bracket system.
The button (1) operates the pneumatic brake and vertical (up & down) movement of console
can be adjusted by the button (2).

1 2

43
NOVAIR

APPENDIX 8 Rotational Movement of ICU/HDU Pendants (Dry Side)

Rotational movement of dry side can be controlled by the button available on front of the
console as shown below. There is single pneumatic brake which is located in supporting
bracket system and controlled by button (1). Button (2) is used to switch on/off night light on
the console.

APPENDIX 9 Rotational Movement of ICU/HDU Pendants (Wet Side)

Rotational movement of wet side can be controlled by the buttons available on front of the
console as shown below. There are two pneumatic brakes which are located in supporting
bracket system and joints between two horizontal arms. Brake button (1) operates the
pneumatic brake in supporting bracket system and brake button (2) operates the brake at the
joints between two horizontal arms.

44
139, rue de la Belle Etoile, 95942 Roissy CDG, France

Tel. +33 (0) 1 56 46 02 03

Fax +33 (0) 1 49 89 29 13

contact@novair.fr