Professional Documents
Culture Documents
Ch06
Ch06
6.1 INTRODUCTION
Heat transfer of a phase change coolant is much more complex than the previous
modes of heat transfer that we have studied. By phase change we denote the following
processes:
pressure is equal to the surrounding atmospheric pressure, the liquid will form vapor
bubbles throughout and boil.
Latent heat—As an object absorbs energy, the object will display a temperature
increase, defined by the specific heat of the object. We call this temperature increase
sensible heat. Another form of heat is latent heat, by which an object will absorb
energy but will not increase in temperature. The latent heat of vaporization is higher
than the latent heat of fusion because the molecules are spaced farther apart in a
gas than in a liquid.
c p ( T s T sat )
Ja -------------------------------
-
h fg
This dimensionless group characterizes the heat transfer during a phase change.
The Jakob number is usually quite small. For example, we can let Ts equal the
temperature of the liquid surface of an ice block Ti equal the internal temperature
of the ice block. If we say the temperature difference between an ice block and a
liquid surface is 10°C, then Ja 0.058. The Bond number is the ratio of the
gravitational buoyancy force to the surface tension.
qs h ( T w T sat ) h T e
where qs is the rate of heat generation per unit of surface (W/m2) and Te is the excess
temperature. As we know from experience, bubbles within the liquid characterize
the boiling process. The dynamics of the bubbles reaching the surface affect the
fluid motion and, therefore, the convection.
The boiling heat transfer process consists of two basic types: pool boiling, which
occurs in an initially stagnant liquid, and flow boiling, which occurs in the presence
of liquid velocity. Boiling may occur in both process when no bubbles are visible.
We call this subcooled boiling. In this process, the temperature of the liquid is below
the saturation temperature. In subcooled boiling, bubbles form in the superheated
liquid at the wall but are condensed when they grow large enough to extend into the
subcooled bulk liquid. When the vapor extends into the subcooled liquid, it loses its
heat and collapses. Figure 6.2 shows the phases in subcooled boiling. Saturated boiling
FIGURE 6.2 Fluid flow pattern induced by a bubble in a subcooled liquid in different stages
of development collapse.
is the type of boiling with which we are most familiar: the temperature of the liquid
exceeds the saturation temperature, bubbles form, and they rise to the liquid surface.
2
p p l -------
Rb
where Rb is the radius of the vapor bubble. If we assume that the bubble and the
liquid are at identical temperatures, the p between the vapor and the liquid can be
translated into a temperature by the Clausius-Clapeyron relation. Therefore, from
Hetsroni1 we see that
2 fg
T Tl Ts 1 ------- ------ -----------------
R b h fg l
While this equation is for an isothermal condition, Bergles and Rohsenow2 found
the theoretical temperature difference between the wall surface and the liquid satu-
ration temperature that will form the first bubble, or the incipience of boiling
8qT
T b T w T sat -----------------
v h fg k f
This equation assumes that temperature decreases linearly with increasing distance
from the heated wall. Since this is not strictly true in actual occurrences of wall
superheat, the equation underpredicts the wall superheat, Tb.
The familiar boiling process is actually called nucleate boiling. When a bubble
becomes large enough to detach from a heated surface, the bubble is said to have
nucleated. In nucleate boiling the characteristic length is the size of the bubble when
it separates from the surface, Lb. To find this dimension, we balance the bubble surface
tension to the bubble buoyancy force, as shown in Figure 6.3; therefore,
FIGURE 6.3 Force balance on vapor bubbles in a fluid: (a) unattached forces, (b) attached
vapor bubble forces.
3 gc 0.5
R b ------------------------
-
( l )g
gc 0.5
L b ------------------------
-
( l )g
4 1.25 2
E 0 [ 1.5 10 ( Ja ) ]
4 2
10 ( Ja ) ]
1.25
E 0 [ 4.65
where:
g ( l )D b
2
Now that we have correlated the bubble departure diameter, we can find the
frequency of departure. Although current experimental data are irregular, Hetsroni1
found that bubbles that grow very slowly depart at a frequency of about
0.5625 Ja
2
f -------------------------------
2
-
Db
Cole4 roughly correlated the frequency of departure for rapidly growing bubbles as
0.5
g ( l )
4
---
f ---------------------------
3
C D l Db
q
Q ------------
h fg
where is the dimensionless fraction of the heat flux that will result in a net generation
of bubbles. Unfortunately, is not a constant. Graham and Hendricks5 found that
varies in a complex manner from about 0.01 to 0.02 at low heat fluxes, to 0.5 at
about 20% of the critical heat flux, and approaches 1.0 at the critical heat flux.
If the vapor flux can be determined, then we can find the amount of agitation
caused by nucleate boiling, which is described as the bubble Reynolds number
Db Q
Re b -------------
l
gc 0.5
L b ------------------------
-
( l )g
( l )gg c 0.25
V max ~ ---------------------------------
-
2
The maximum bubble velocity can also be described using what is known as
the Helmholtz* theory of instability. That is, the bubble vapor column is disrupted
by a wavelength disturbance of Lb, the characteristic length, and becomes unstable
at VH, or
2 g 0.5
V H ~ ----------------c
Lb
gc gc
- D b 5.45 ------------------------
3.14 ------------------------ -
g ( l ) g ( l )
then we may use a quick estimate of the velocity of an undisturbed bubble given
by Zuber et al.7
1
V b --- 4gr
3
˙
4 2 1 -----------
2 Rb 2
-------
H -t --- R˙ -
---- Ja ------- - 3
2
R b, i 3 ---------
b R b, i
R b, i
where Rb is the bubble radius and Rb,i is the initial bubble radius.
If we define the bubble collapse period as the time when the bubble volume is
1% of the departure bubble volume, then the ratio Rb/Rb,i 0.2. We now define the
collapse period, c, as
1 -----------
2 Rb 2
-------
c --- R˙ - - 3
R b, i Rb
2.32
3 ---------
b
---------- 0.2
R b, i
R b, i
* Hermann von Helmholtz (1821–1894) described the theory of instability and also provided a physical
proof of Fourier’s Theorem by producing complex musical tones using individual tuning forks.
2 2
2.32 R b, i R b, i
c ---------- ------------
- 0.580 ------------
-
4 Ja 2
Ja
2
We can now determine the relationship among the rise velocity, Vb, the rate of
collapse, c, and the departure diameter, Db , to the collapse length, Lc, as
c
Lc 0 V b dt
Substituting the equations for the collapse rate, H, and the undisturbed bubble
velocity, Vb, and letting the ratio of the bubble radius, Rb /Rb,i, equal the ratio of the
bubble diameter, Db /Db,i, we have an equation for the collapse length, Lc, as
2.5 2.5
D b 2g D b 2g
L c 1.4 -------------------
- ------ 0.0292 -----------------------
-
Ja Ja
2 48 2
FIGURE 6.4 Temperature distribution of the heated solid surface, Ts, and the boiling liquid,
Tsat , during saturated pool boiling.
FIGURE 6.5 The boiling curve generated by Nukiyama10 for saturated water. Adapted from
Incropera, F. P., and DeWitt, D. P., Fundamentals of Heat and Mass Transfer, 3rd ed., John
Wiley & Sons, New York, 1995, 722, using the data of Nukiyama, S., “The Maximum and
Minimum Values of Heat Transmitted from Metal to Boiling Water Under Atmospheric
Pressure,” J. Japan Soc. Mech. Eng., 37, 367, 1934. (Translation: Int. J. Heat Mass Transfer,
1419, 1966).
Boiling
regimes
Free convection Nucleate transition Film
{
{
{
{
Isolated Jets and
bubbles columns
107
qmax
max
qmax
106 C Critical heat flux, q"
P
q"s (W / m2 )
B
105
qmin
D min
Leindenfrost point, qq"min
A
10 4
ONB
∆Te,A ∆Te,B ∆Te,C ∆Te,D
10 3
1 5 10 30 120 1000
∆Te = Ts Tsat( C)
_ o
FIGURE 6.6 Characteristics of the boiling curve for a heated horizontal surface in water.
temperature range of Te,A Te Te,C where Te,C is about 30°C. This is the
range of operation for most heat transfer work. High levels of power can be dissipated
without a large increase in temperature. Point P indicates the point of the maximum
heat transfer coefficient. Ideally, equipment should operate at this point. In water, the
convection coefficient in this region can exceed 104 W/m2 K.
The region when Te,C Te Te,D, where Te,D is about 120°C, is called
the transition boiling, partial film boiling, or unstable film boiling range. In the
previous range, as each bubble left the surface, liquid covered the surface until a
new bubble formed. In the transition boiling range, new bubbles are formed before
the liquid can reach the surface. A continuous vapor film forms on the surface. The
entire heated surface oscillates between a liquid and vapor blanket. As the temper-
ature differential Te increases, the entire surface is more often covered by a vapor
layer than the liquid layer. Also, as Te increases, hc and therefore qs decrease,
because the thermal conductivity of the vapor layer is much lower than when the
adjacent layer was a liquid.
The region when Te Te,D is called film boiling. Point D of the boiling curve
is called the Leidenfrost point. In 1756, Leidenfrost noticed that when water droplets
are placed on a hot surface, the droplets dart about the surface, supported by a vapor
layer. We know that during the transition phase, as Te increases, a higher percentage
of the surface is covered by vapor at any point in time. The Leidenfrost point occurs
when the entire surface is covered by a vapor layer, and the heat flux reaches a minimum,
qs,D qmin. In the film boiling range, heat transfer can only occur by conduction through
the vapor layer. After the Leidenfrost point, radiation heat transfer through the vapor
layer becomes more important, and the heat flux increases with increasing Te.
Researchers have experimented with the region after point C, but in actual
engineering applications this region is difficult to control. Any increase in the heat
flux after point C creates a marked increase in temperature. The size of this increase
may cause destruction of the heat flux surface. For this reason, point C is often
called the burnout point or, more commonly, the Critical Heat Flux (CHF).
qs C T e n
a b
where:
b 1/3
g ( l ) 0.5
c p, l T e 3
----------------------
qs l h fg ------------------------
-
gc C h Pr n
sf fg l
where:
Figure 6.7 shows pool boiling data points for water that were correlated by the
Rohsenow method. Collier14 recommends the following correlation as being simpler
FIGURE 6.7 Pool boiling data for water correlated by the Rohsenow method. (Adapted from
References 13 and 36.)
where:
where the exponent m is 2.0 for water and 4.1 for other liquids.
Danielson et al.15 report a number of values for Csf . The value of Csf can be
assumed to equal ~0.013 when the experimental value is unknown. Hetsroni1 reports
that this value correlates a wide spectrum of experimental data to within 20%.
The most important variables that affect Csf are the surface roughness of the heated
TABLE 6.1
Values of the Surface/Liquid Coefficients
Liquid/Surface Combination Csf
Benzene–Chromium 0.010
Carbon Tetrachloride–Copper 0.013
Carbon Tetrachloride–Polished Copper 0.007
Ethyl Alcohol–Chromium 0.0027
Isopropyl Alcohol–Copper 0.0023
n-Pentane–Chromium 0.015
n-Pentane–Polished Copper 0.0154
n-Pentane–Lapped Copper 0.0049
Water–Brass 0.006
Water–Copper 0.013
Water–Scored Copper 0.0068
Water–Polished Copper 0.013
Water–Nickel 0.006
Water–Chemically Etched Stainless Steel 0.0133
Water–Mechanically Polished Stainless Steel 0.0132
Water–Ground and Polished Stainless Steel 0.008
surface and the angle of contact between the vapor bubble and the heated surface.
The surface roughness affects the number of nucleation sites, and the angle of contact
is a measure of the wettability of the surface. Smaller contact angles represent greater
wettability. A totally wetted surface has the least amount of vapor and represents
the greatest heat transfer coefficient. Values of the coefficients of liquid/surface
combinations are shown in Table 6.1.
Table 6.2 presents important boiling point thermophysical data for coolants
commonly used in electronic cooling.
The critical heat flux, point C in Figure 6.6, is determined by the maximum rate
that vapor bubbles can leave the heated surface. This can also be described as the
maximum speed that the liquid can re-wet the heated surface after a bubble leaves
the wall. We can now relate the bubble velocity to the critical heat flux by
qmax V max h fg
or
qmax
- C max
----------------------
V max h fg
TABLE 6.2
Fluid Properties at Respective Boiling Points (1.0 atm)
Coolant
Property FC-72 FC-77 FC-84 FC-87 L-1402 R-12 R-113 Water
Boiling Point, °C 52.0 100.0 83.0 30.0 51.0 30.0 48.0 100.0
Density, Liquid, l, kg/m3 1592 1590 1575 1633 1635 1487 1511 958.0
Density, Vapor, , kg/m3 12.68 14.31 13.28 11.58 11.25 6.34 7.40 0.59
Absolute Viscosity, , N s/m2 0.00045 0.00045 0.00042 0.00042 0.00052 0.00036 0.00050 0.00027
Specific Heat, cp, J/kg K 1088 1172 1130 1088 1059 – 979 4184
Heat Vaporization, hfg, J/kg 87927 83740 79553 87927 104675 165065 146824 2257044
Thermal Conductivity, k, W/m K 0.0545 0.0570 0.0535 0.0551 0.0596 0.0900 0.0702 0.683
Surface Tension, , N/m 0.0085 0.0080 0.0077 0.0089 0.0109 0.0118 0.0147 0.0589
Coefficient of Expansion, , 1/K 0.0016 0.0014 0.0015 0.0016 0.0016 – 0.0017 0.0002
0082-06.fm Page 322 Wednesday, August 23, 2000 3:54 PM
where:
Kutateladze17 defined the equation for the critical heat flux in 1948 by dimen-
sional analysis. Later, in 1959, Zuber18 found the equation for critical heat flux by
a hydrodynamic stability analysis. The critical heat flux can be found by
0.25
qmax C max h fg [ v ( l v )gg c ]
2
where Cmax is /24, also called the Zuber constant. Table 6.3 presents the exper-
imental data of Lienhard and Dhir19 for the value of Cmax using a dimensionless
parameter called L*. This parameter is the ratio of the characteristic length of the
heated surface, Ls, to the characteristic bubble dimension, Lb.
Pressure affects the maximum heat flux because of the influence on vapor density
and the boiling point of the liquid. As the boiling point changes, so does the heat
of vaporization and the surface tension. Therefore, each fluid has a specific pressure
that will yield a maximum heat flux. Cichelli and Bonilla20 have experimentally
demonstrated that the critical heat flux increases with pressure up to 1/3 of the critical
pressure. After this peak, the critical heat flux falls to zero at the critical pressure, as
shown in Figure 6.8.
TABLE 6.3
Values of Cmax (Zuber Constant) for Critical Heat Flux
Surface Geometry Cmax Characteristic Length Range of Applicability
FIGURE 6.8 Critical heat flux in nucleate boiling as a function of pressure. (From Cichelli,
M. T. and Bonilla, C. F., Trans. AIChE, 41, 755, 1945. With permission.)
When the liquid is subcooled, Zuber et al.7 have found that the critical heat flux
is correlated to a reasonable estimation by
2k l ( T sat T l ) 24
2
0.25
qmax qmax sat 1 ---------------------------------
- ---------------- ----------------------------------
l h fg v g g c ( l )
where:
gc
0.5 2 0.25
---- 2 ------------------------
- ----------------------------------
3 g ( l ) gg c ( l v )
The effect of subcooling on the critical heat flux was studied by Ellion.21 All of
the previous correlations are for clean horizontal surfaces. Bernath22 has shown that
a vertical surface may have a critical heat flux as much as 25% less than a horizontal
surface.
There are no adequate theories that describe the transition regime between critical heat
flux and vapor film boiling. This region corresponds to qs , D of Figure 6.6 and is called
the minimum heat flux, or the Leidenfrost point. Fortunately, this area of the boiling
curve has little practical value in electronic cooling. At lower temperatures within this
region, fluid motion is characterized by periodic, unstable liquid and heater contact. At
the higher-temperature region, a stable vapor film forms and the heat flux reaches a
minimum. If the heat flux drops below the minimum required to initiate a stable vapor
film, the liquid will again contact the heater surface and nucleate boiling will be rees-
tablished. Zuber23 used stability theory to derive an equation for minimum heat flux, qmin
gc g ( l ) 0.25
qmin C h fg ----------------------------------
( l v )
2
Kovalev24 notes that this correlation is accurate to only about 50% at moderate
pressures and has even less accuracy at high pressures. Nevertheless, Berenson,25
for a large flat horizontal heated surface, and Lienhard and Wong,26 for a horizontal
heated cylinder, found that C ~0.09.
The region of vapor film boiling, like minimum heat flux boiling, is not of great
concern in applications involving electronic cooling. Above the Leidenfrost point
the heat flux increases, but at a dramatic increase in surface temperature. In this
range the heated body is enveloped in a continuous blanket of vapor; therefore, heat
transfer is by conduction through the vapor. At temperature ranges much higher than
those seen in electronics, radiation heat transfer across the vapor film becomes
important. Because the vapor film is thin, the Rayleigh number is low, which indicates
heat transfer by conduction only. Because of this, analysis of the heat flux for vapor
film boiling is relatively simple. The minimum wall superheat that sustains the vapor
film was found by Berenson25 to be
, f h fg g ( l ) 23
gc 0.5
,f 13
T min 0.127 ---------------
- ------------------------- ----------------- ------------------------------
-
k ,f l g ( l ) gc ( l )
where the subscript f is that property at the film temperature. For film boiling, the
following correlation for the average heat transfer coefficient is commonly used:
g ( l ) k ( h fg 0.35c p, T e )
3 0.25
h c C fb -------------------------------------------------------------------------------------
-
D T e
where the constant Cfb is 0.62 for a horizontal cylinder (Bromley27), 0.67 for a sphere
(Frederking and Daniels28), and replacing D with L is 0.71 for a plane vertical surface
(Mills29). When the vapor flow rate is high, that is, when
L ( l )g ( h fg 0.50c p, v T e )
3
--------------------------------------------------------------------------------
- 5 10
7
k T e
Frederking and Clark30 recommend the following equation for the average film
boiling heat transfer coefficient
13
h 0.15 --------------------------------------------------------------------------------------
( l )g ( h fg 0.50c p, T e )k v
2
-
T e
ṁ
-------------------
ṁ ṁ l
-
where:
Another term often used in two-phase internal flow is the mass velocity, G,
which is the mass flow per cross-sectional area. The mass velocity is further divided
into vapor mass flow, Gv , and liquid mass flow, Gl. The quantities can be shown as
G G Gl
where:
ṁ
G v -----
Ac
-
ṁ l
G l -----
Ac
In electronic cooling external flow is usually a relative statement. The flow may be
external over hot components, but it is still within a conduit. The pressure drop in
this type of flow is not at all well understood. Some correlations are available, but
the range of applicability is so narrow as to be nearly useless for engineering design.
In cases of conduit flow which passes over exposed components, the engineer should
always build a scale model to determine pressure drop.
At temperatures before boiling incipience, standard correlations for forced con-
vection may be used, with attention to temperature-induced property variations within
the single phase. The maximum heat flux can be increased substantially by using
forced convection in the boiling regime. Researchers have recorded heat flux values
of 35 MW/m2. Lienhard and Eichhorn31 developed a correlation for the maximum
heat flux using the Weber number, which is similar to the Reynolds number. Their
correlation is usually accurate to about 20%. The Weber number, We, is the ratio of
inertia to surface tension and can be described as
V D
2
We ---------------
-
For a heated cylinder in a low-velocity liquid cross flow, the critical heat flux
is estimated by
1
qmax h fg V ---- 1 4 13
----------
-
We D
qmax
---------------- 0.275 0.5
------------- -----l 1
h fg V
For a heated cylinder in a high-velocity liquid cross flow, the critical heat flux
is estimated by
l
----
0.75 l
----
0.5
- -
q m ax h fg V -------------- -----------------------------
-
169 13
19.2 We D
qmax
---------------- 0.275 l 0.5
h fg V ------------- ----- 1
FIGURE 6.9 The fluid flow regime progression from liquid to vapor for two-phase vertical
internal flow.
( 1 ) l
FIGURE 6.10 The fluid flow regime progression from liquid to vapor for two-phase hori-
zontal internal flow.
Researchers have proposed many different and quite complex heat transfer
correlations to describe the regimes of internal forced boiling flow. Klimenko32
proposed a methodology which has sufficient accuracy, is not overly complex, and
applies to heat transfer stages before mist flow. To use the Klimenko method, we
must first determine if the heat transfer is dominated by film evaporation or by
nucleate boiling, by evaluating the dimensionless parameter Φ.
l
-
13
Gh
----------fg- 1 ----
-
1 ----
q l
p pL
p* --------------------------------------
-
0.5
---------b
[ g ( l ) ]
If the heat transfer mode is film evaporation , Φ 1.6 104, the Nusselt number
is found by
----- k----w-
0.2 0.09
0.6 1 6
Nu 0.087Re Pr l
l k l
where:
V Lb
Re ------------
l
-
G l
V ---- 1 ----- 1
pl
Finally, knowing the Nusselt number for the heat transfer mode, we can calculate
a single-phase heat transfer coefficient, which is based on the Reynolds number of
the liquid portion of the flow. Usually the single-phase heat transfer coefficient, hFC,
is so much smaller than the two-phase coefficient, hTP , that it can be ignored.
However, if it is significant, the overall heat transfer coefficient can be found by
3 3 13
h c ( h TP h FC )
6.4 EVAPORATION
Liquid may exist on a surface if the surface is below the saturation temperature, Tsat.
Evaporation, like boiling, is considered a convection heat transfer process. Evapora-
tion occurs when the molecules in a liquid gain enough energy to escape the liquid
binding energy and enter the vapor state. Since the molecules leaving the liquid
contain excess energy, the net effect is a loss of energy of the liquid. Since temperature
is a measure of energy, the temperature of the liquid decreases when evaporation
occurs. The convection of vapor from a surface is related to the mass transfer coef-
ficient, hm. The magnitude of evaporative cooling can be expressed as the equation
h
T T s h fg -----m [ A, sat ( T s ) A, ]
hc
FIGURE 6.11 Klimenko data for the effect of wall conductivity on the Nusselt number for internal forced convection boiling flow. (From Klimenko, V. V.,
Int. J. Heat Mass Transfer, 31, 541, 1988. With permission.)
0082-06.fm Page 331 Wednesday, August 23, 2000 3:54 PM
© 2001 by CRC PRESS LLC
FIGURE 6.12 Klimenko data showing the transition from nucleate boiling to film evaporation for internal forced convection flow. (From Klimenko,
V. V., Int. J. Heat Mass Transfer, 31, 541, 1988. With permission.)
0082-06.fm Page 332 Wednesday, August 23, 2000 3:54 PM
where:
The ratio of the heat transfer coefficient to the mass transfer coefficient, hc/hm,
can also be expressed in terms of a dimensionless Lewis number, Le,
h k
-----c ------------------n c Le l n
hm D AB Le p
where:
Using this relationship we see that the cooling effect can also be described as
A h fg p A, sat ( T s ) p A,
T T s --------------------------
23
- ----------
- ----------------------
c p Le Ts T
where:
Gilliland and Sherwood33 correlated the mass transfer coefficient from liquids
to air in a wetted-wall column as
where:
Rohsenow and Choi34 indicate that by using the Chilton-Colburn factor, j, the
mass transfer coefficient of evaporation from a flat, wetted surface in laminar flow
can be found by
V
h m 0.664 -------------------------
0.67
-
Re L Sc
V
h m 0.037 -----------------------
0.2 0.67
-
Re L Sc
where V is the velocity in m/s, and the Reynolds number is based on the length of
the surface.
A Reynolds number based on the thickness of a falling evaporative film has also
been proposed. In this case, the falling film Reynolds number, Re, is defined in
terms of the hydraulic diameter, DH, and the mean velocity, um, of the film as
l ------
- 4
l um DH l 4
Re -----------------
- ---------------------
- -------
l l l
where:
4 Ac 4
D H --------
-
P P
------
u m ------
l
-
0 l u dy ----------------------------------
3 l
-
In evaporation from falling films of water, Chun and Seban35 determined the
following correlations for the Nusselt number
1 3
Nu --- Re
3
0 Re 30
4
0.22
Nu 0.822Re 30 Re Re tr
3 0.4 0.65
Nu 3.8 10 Re Pr l Re tr Re
6.5 CONDENSATION
Condensation will form on a surface if the vapor contacting the surface is saturated,
and the surface temperature is lower than the temperature of the saturated vapor.
When this occurs, the latent heat within the vapor is transferred to the cooler surface.
Normally, condensation occurs as drops on a surface. If the conditions that caused
the condensation are steady state, and the surface is clean, the droplets will coalesce
and form a condensate film on the surface. In a gravity field, the laminar fluid film
will flow. If the surface is long enough, the laminar flow of condensate may become
wavy and then turbulent.
Contrary to other forms of heat transfer, as T increases the heat transfer coef-
ficient decreases. This is because as the temperature difference increases, more vapor
becomes condensate, which causes a thicker layer of film. Because condensation heat
transfer is a conduction process, the thicker film impedes the transfer of heat.
Because of the heat transfer impedance caused by the thick fluid film, applica-
tions using condensation often have short flow paths or use small horizontal cylin-
ders. The short flow paths do not allow the film to become very thick. Because of
the action of film condensation, droplet condensation provides a higher heat transfer
coefficient. Heat transfer rates of droplet condensation can be more than a magnitude
higher than film condensation. Therefore, most applications use some type of coating
on the condensation surfaces which promotes droplet formation.
The condensation film begins at point x 0 and continues down a surface. The
thickness of the film increases as x increases, as shown in Figure 6.13. Because the
FIGURE 6.13 The geometry and nomenclature used to describe film condensation on a
vertical surface.
flow moves at a constant velocity, and because the film is thicker at larger values
of x, the mass flow rate also increases with x.
The following correlations for condensation heat transfer are most accurate when
evaluated at the film temperature recommended by Addoms36:
T eval T w 0.33 ( T sv T w )
Nusselt37 obtained the first relationships for the condensation variables in 1916.
Nusselt used simplifying assumptions to arrive at the basic relationship of the
thickness of the film, ,
0.25
4 l k l x ( T sat T w )
-------------------------------------------
-
g l ( l )hf g
For a vertical surface of unit width and a height of L, the average heat transfer
coefficient can be written as
0.25
g l ( l )hf g k l sin
3
h c 0.943 --------------------------------------------------------
-
l L ( T sat T w )
0.25
p, l ( T sat T w )
1 0.68 c---------------------------- c p, l ( T sat T w ) k l ( T sat T w )
- 0.02 ---------------------------- - --------------------------
h fg h fg l h fg
hc hc -----------------------------------------------------------------------------------------------------------------------------
k l ( T sat T w ) c p, l ( T sat T w ) k l ( T sat T w )
-
1 0.85 -------------------------- 0.15 ----------------------------- --------------------------
l h fg h fg l h fg
where:
c p, l ( T sat T w )
------------------------------------ 2.0
h fg
k l ( T sat T w )
-------------------------------- 20
l h fg
1 Pr l 10.05
Chun and Seban35 found that the following correlations for the local and the
average Nusselt number are applicable for water condensation flowing down a flat
surface. When the Reynolds number, based on the film thickness, Reδ , represents
laminar film condensation, and 0 Reδ 30,
1 3
Nu --- Re
3
4
When the Reynolds number indicates wavy laminar film condensation, and 30
Reδ Retr,
0.22
Nu 0.822Re
When the Reynolds number indicates turbulent film condensation, and Retr Reδ,
3 0.4 0.65
Nu 3.8 10 Re Pr l
1.06
where Retr is the turbulent Reynolds number, which is equal to 5800 Pr l .
To find the average Nusselt number, we use an equation based on the distance
the condensate has traveled down the surface. Using the Reynolds number based on
that length, we have the equation for laminar film condensation, when ReL 30,
written as
0.25
2 13
4 -------l
Nu --- Pr l g
3 --------- ---------------
4Ja l L
When the Reynolds number indicates wavy laminar condensation flow, that is,
when 30 ReL Retr
0.18
2 13
l
Pr l ------
Nu -------- g
-
- ---------------
4Ja l L
FIGURE 6.14 Local Nusselt number as a function of the Reynolds number for laminar and
turbulent film condensation of water. Adapted from References 29 and 35.
When the Reynolds number indicates turbulent film condensation, that is, when
ReL Retr, then the average Nusselt number is described as
2 13
10 6
3
-------l 9.12 10 Ja l ( L x tr )
Pr g ----------------------------------------------------------
- 0.6
Nu --------l- --------------- 13 Re tr
4Ja l L ˙2l 0.35
------- Pr l
g
Figure 6.14 shows the local Nusselt number as a function of the Reynolds number
for laminar and turbulent film condensation data gathered by Chun and Seban.35
The average heat transfer coefficient of a pure saturated vapor condensing on a
horizontal tube can be found by
0.25
g l ( l )hf g k l
3
h c 0.725 --------------------------------------------
-
D l ( T sat T w )
Some applications have vertical rows of horizontal tubes; that is, the tubes are
arranged so that the film is falling from an upper horizontal tube to a lower horizontal
tube. If the condensation flow is continuous, the tube diameter, D, in the previous
equation can be replaced by DN, where N is the number of tubes. This method gives
conservative results because the condensation flow is rarely continuous.
Chen40 suggested that since the condensation flow is subcooled, additional con-
densation occurs when the condensate is between the horizontal tubes. Assuming
that all of the subcooling is used for additional condensation, Chen obtained the
0.25
g l ( l )hf g k l
3
c p ( T sv T w )
h c 0.728 1 0.2 ------------------------------- ( N 1 ) ---------------------------------------------
h fg DN l ( T sat T w )
( N 1 )c p ( T sv T w ) 2.0
---------------------------------------------------
-
h fg
q m am hm c p, s ( T m T i ) c p, l ( T 2 T m )
where:
FIGURE 6.15 Temperature distribution for ice forming on water, with ambient air as a heat
sink.
When a phase change material freezes, the problem can be considered to be one
of boundary condition values, as shown in Figure 6.15. We can see that the solution
to this problem is quite complex. Researchers have obtained only solutions for simple
cases. We can instead use an approximate solution that was obtained by assuming
that the heat capacity of the subcooled solid phase is negligible relative to the latent
heat of solidification. Another simplifying assumption is that the physical properties
are uniform and that the conductance and the heat sink temperature are constant
throughout the process. To find the time to form a solid phase of a specific thickness
we have:
-----
L
2
L
2k- --- U
-
t T T -
---------------------
-------------------
s o
-
h fs
REFERENCES
1. Hetsroni, G., Ed., Handbook of Multiphase Systems, Hemisphere, Washington, D.C.,
1982.
2. Bergles, A. E. and Rohsenow, W. M., The Determination of Forced Convection
Surface Boiling Heat Transfer, J. Heat Transfer, 86, 365, 1964.
3. Cole, R. and Rohsenow, W. M., Correlation of Bubble Diameters of Saturated Liquids,
Chem. Eng. Prog. Symp. Ser., 65(92), 211, 1969.
4. Cole, R., Photographic Study of Boiling in Region of Critical Heat Flux, AIChE J.,
6, 533, 1960.
28. Frederking, T. H. K. and Daniels, D. J., The Relation Between Bubble Diameter and
Frequency of Removal From a Sphere During Film Boiling, J. Heat Transfer, 88, 87,
1966.
29. Mills, A. F., Heat and Mass Transfer, Irwin, Chicago, 1995, 640.
30. Frederking, T. H. K. and Clark, J. A., Natural Convection Film Boiling on a Sphere,
Adv. Cryog. Eng., 8, 501, 1962.
31. Lienhard, J. H. and Eichhorn, R., Peak Boiling Heat Flux on Cylinders in a Cross
Flow, Int. J. Heat Mass Transfer, 19, 1135, 1976.
32. Klimenko, V. V., A Generalized Correlation For Two-Phase Forced Flow Heat Trans-
fer, Int. J. Heat Mass Transfer, 31, 541, 1988.
33. Gilliland, E. R. and Sherwood, T. K., Diffusion of Vapors into Air Streams, Ind. Eng.
Chem., 26, 516, 1934.
34. Rohsenow, W. M. and Choi, H., Heat, Mass, and Momentum Transfer, Prentice-Hall,
Englewood Cliffs, NJ, 1961.
35. Chun, K. R. and Seban, R. A., Heat Transfer to Evaporating Liquid Films, J. Heat
Transfer, 93, 391, 1971.
36. Addoms, J. N., Heat Transfer at High Rates to Water Boiling Outside Cylinders,
D. Sc. thesis, Massachusetts Institute of Technology, Cambridge, MA, 1948.
37. Nusselt, W., Die Oberflachenkondensation des Wasserdampfes, Z. Vergle. D-Ing., 60,
541, 1916.
38. Rohsenow, W. M., Heat Transfer and Temperature Distribution in Laminar Film
Condensation, Trans. ASME, 78, 1645, 1956.
39. Sadasivan, P. and Lienhard, J. H., Sensible Heat Correction in Laminar Film Boiling
and Condensation, J. Heat Transfer, 109, 545, 1987.
40. Chen, M. M., An Analytical Study of Laminar Film Condensation. I. Flat Plates.
II. Single and Multiple Horizontal Tubes, Trans. ASME, Ser. C., 83, 48, 1961.