COMMENTS RESOLUTION SHEET(CRS)

BU HASA SWAG CO2 EOR PILOT PROJECT

Contract No: 4700017117 Project No. P12512 Comment Code – 2


Transmittal No.
Document Number Document Title
☐ 1. Approved
☒ 2. Approved with comments - Resubmit
P12512-11-28-48-1605 Rev.No.: TR-P12512-4700017117-IC-1841 F&G JB Schedule - ☐ 3. Revise and Resubmit.
BAB SIMGAP Pilot ☐ 4. Rejected
A Facilities (Update)
Sl.
Reference/ Page. ADNOC ADNOC Onshore Comments ADNOC VENDOR / CONTRACTOR ADNOC Onshore
No. No. Onshore Onshore Response Remarks
Reviewer Disciplin
Name e

Natarajasund
Contractor shall refer comments marked. Contractor shall Engg.
1. Transmittal Manager
Noted
ara. D resubmit this document incorporating comments.
Contractor shall ensure below points:
1) There shall be 30% spare terminals and 20% branch
cable entries for future use. 1. Noted and Confirmed
Comments On 11- Natarajasund 2) Multi pair / multicore cables shall have overall minimum Engg.
2. Manager
28-48-1604 Rev A ara. D 20% spare pairs / cores for future. 2. Noted and Confirmed

1) Ensure all the JB tag numbering are followed as per


Company approval 1. Noted and Confirmed
2. Noted and Included
2) Include all the packages Junction box which are being
connected to plant ICSS/PLC. 3. Noted and Included
Comments On 11- Natarajasund Engg. 4. Noted and Updated
3. 3) Ensure all the signals from P&ID and mechanical Manager
28-48-1604 Rev A ara. D
packages are included 5. Noted and Confirmed
4) Update this document based on revised IO count and 6. Noted. Rev B JB
P&ID. schedule document is
generated from SPI

Page 1 of 2
COMMENTS RESOLUTION SHEET(CRS)

BU HASA SWAG CO2 EOR PILOT PROJECT

Contract No: 4700017117 Project No. P12512 Comment Code – 2


Transmittal No.
Document Number Document Title
☐ 1. Approved
☒ 2. Approved with comments - Resubmit
P12512-11-28-48-1605 Rev.No.: TR-P12512-4700017117-IC-1841 F&G JB Schedule - ☐ 3. Revise and Resubmit.
BAB SIMGAP Pilot ☐ 4. Rejected
A Facilities (Update)
Sl.
Reference/ Page. ADNOC ADNOC Onshore Comments ADNOC VENDOR / CONTRACTOR ADNOC Onshore
No. No. Onshore Onshore Response Remarks
Reviewer Disciplin
Name e

5) Junction Box segregation shall me maintained as per


project philosophy and P12512-30-99-39-1607.

6) This document is not generated from SPI, next revision of


this document shall be prepared and generated from SPI
database.

Originator Reviewed by Approved by:

Name: Shobha Bhat Mohammed Nasir Manoj Munishwar

Signature:

Date: 24.11.2023 24.11.2023 24.11.2023

Page 2 of 2
TECHNICAL CENTERS & PROJECTS (TC&P)

PROJECT & CONSTRUCTION (BUH)

EPC FOR BU HASA SWAG CO2 EOR PILOT PROJECT

ADNOC Onshore Contract No.: 4700017117


ADNOC Onshore Project No.: P12512

F&G JUNCTION BOX SCHEDULE - SIMGAP

SHOBHA.B M. NASIR MANOJ.M MOHAMED WALID


B 24-11-23 Issued for Approval
I&C Engineer Lead I&C Engineer Eng. Manager Project Manager

SHOBHA.B M. NASIR MANOJ.M MOHAMED WALID


A 16-10-23 Issued for Review
I&C Engineer Lead I&C Engineer Eng. Manager Project Manager

ORIGINATOR REVIEWED APPROVED APPROVED


REV. DATE DESCRIPTION
(BILFINGER) (BILFINGER) (BILFINGER) (PETROJET)

THIS DOCUMENT IS INTENDED FOR USE BY ADNOC AND ITS NOMINATED CONSULTANTS, CONTRACTORS, MANUFACTURERS AND SUPPLIERS.

EPC CONTRACTOR: PETROLEUM PROJECTS & TECHNICAL CONSULTATION. CO. PETROJET – ABU DHABI

ENGINEERING SUBCONTRACTOR: Bilfinger Tebodin Middle East

ADNOC Onshore Document No. : 11-28-48-1605 Doc. Class 2


ORGINATOR No.: 4347007 Revision : B
ADNOC Onshore Project No.: P12512 Date: 24-11-23
Page: 1 of 5
Security Code: 5 – Public
PROJECT NO. P12512
PROJECT EPC FOR BU HASA SWAG CO2 EOR PILOT PROJECT
DOCUMENT NO. 11-28-48-1605

AREA BAB FACILITY PAGE NO. 2 OF 5

DOCUMENT F&G JUNCTION BOX SCHEDULE - SIMGAP REV. B

INDEX
The table below is a brief summary of the most recent revisions to this document. Details of all revisions are held on
document by the issuing department.
Sr. No. Rev. No. Issue No. Date of Issue Description of Revision

1 A 1 16-10-23 Issued for Review (IFR)


1 B 2 24-11-23 Issued for Approval (IFA)

HOLD LIST

Sr. NO SHEET NO DESCRIPTION REVISION

Security Code: 5 – Public


PROJECT NO. P12512
PROJECT EPC FOR BU HASA SWAG CO2 EOR PILOT PROJECT
DOCUMENT NO. 11-28-48-1605

AREA BAB FACILITY PAGE NO. 3 OF 5

DOCUMENT F&G JUNCTION BOX SCHEDULE - SIMGAP REV. B

NOTES:
1. JUNCTION BOXES SHALL BE OF HIGH IMPACT RESISTANT, SUN AND UV RESISTANT SUITABLE FOR THE ENVIRONMENTAL CONDITIONS. MATERIAL OF CONSTRUCTION
OF JUNCTION BOXES SHALL BE 316L STAINLESS STEEL.

2. ALL OUTDOOR JUNCTION BOXES SHALL BE WEATHER PROOF,IP 65 MINIMUM.

3. JUNCTION BOXES SHALL BE SUPPLIED COMPLETE WITH TERMINALS AND ACCESSORIES SUCH AS MOUNTING RAILS,END PLATES, EARTH BOLTS, DRAIN PLUG,GLAND
PLATES, ETC. AND SHALL HAVE EARTH STRIP TO CONNECT SHIELD WIRES OF BRANCH CABLES AND MULTICORE CABLE, THE EARTH STRIP SHALL BE MOUNTED ON
INSULATED STUDS AND BOLTS.

4. SPARE TERMINALS IN JUNCTION BOXES SHALL BE AT LEAST 30% OF THIOSE ACTUALLY REQUIRED TO BE UTILIZED

5. THERE SHALL BE 20% BRANCH AND MAIN CABLE ENTRIES FOR FUTURE USE.

6. ALL SIGNAL TERMINALS SHALL BE SUITABLE FOR CONDUCTOR SIZES UP TO 2.5mm2.

7. THE TERMINAL SHALL BE CERTIFIED Ex'e' TYPE FOR THE JUNCTION BOXES TO BE INSTALLED IN SAFE AREA.TERMINALS IN INTRINSICALLY SAFE CIRCUITS SHALL BE OF
LIGHT BLUE COLOUR,TERMINALS IN NON-INTRINSICALLY SAFE CIRCUITS SHALL BE OF THE Ex'e' TYPE AND SHALL BE GREY COLOUR.

8. CABLE ENTRY SIZES SHALL BE FINALIZED BASED ON CABLE O.D PROVIDED BY SELECTED CABLE VENDOR.

9. DOORS SHALL BE HINGED AND BOLTED. DOOR LID FIXING SCREWS SHALL BE STAINLESS STEEL WITH NYLON RETAINED WASHERS. HINGES AND LOCKING DEVICES
SHALL BE OF SS 316L.
10. ARRANGEMENT INSIDE THE JUNCTION BOX SHALL BE SUCH THAT SUFFICIENT SPACE IS GIVEN TO WORK / MANOEUVRE ON THE TERMINAL AND OTHER
COMPONENTS.

11. W - WEATHER PROOF, Exi - INTRINSICALLY SAFE, Exd - EXPLOSION PROOF , Exe - INCREASED SAFE.

REFERENCE:

TITLE DWG. NO.

F&G CABLE SCHEDULE - SIMGAP AREA P12512-11-28-48-1608


INSTRUMENT AND F&G CABLE BLOCK DIAGRAM - SIMGAP
P12512-11-28-49-1602
AREA
INSTRUMENT LOCATION, CABLE AND TUBE ROUTING
P12512-11-28-49-1601
LAYOUT FOR SIMGAP AREA
FIRE & GAS DETECTION LAYOUT SIMGAP AREA P12512-11-28-45-1601

SPECIFICATION FOR INSTRUMENT BULK MATERIAL P12512-30-99-39-1607

SHELL STD,DRAWING-JUNCTION BOX CONSTRUCTION S 37.603

LEGEND:

FG : FIRE AND GAS


ID : INSTRUMENT DIGITAL
IA : INSTRUMENT ANALOG
I.S : INTRINSICALLY SAFE

Security Code: 5 – Public


PROJECT NO. P12512
PROJECT EPC FOR BU HASA SWAG CO2 EOR PILOT PROJECT
DOCUMENT NO. 11-28-48-1605

AREA BAB FACILITY PAGE NO. 4 OF 5

DOCUMENT F&G JUNCTION BOX SCHEDULE - SIMGAP REV. B

DOCUMENT INDEX

SHT. NO DESCRIPTION REVISION REMARKS

1 COVER SHEET A B

2 REVISION A B

3 NOTES A B

4 INDEX SHEET A B

5 F&G JUNCTION BOX SCHEDULE - SIMGAP A B

Security Code: 5 – Public


PROJECT: EPC FOR BU HASA SWAG CO2 PILOT PROJECT PRPD SHOBHA.B

PROJECT No: P12512


F&G JUNCTION BOX SCHEDULE - SIMGAP
CHKD M. NASIR

DOC. No: 11-28-48-1605

REV. No: B APPD MANOJ.M

GEO- GRAPHICAL
TAG NUMBER
LOCATION
Plant Area
Area

CODE CABLE SERVICE SERIAL No. TYPE (NOTE-1) CABLE LAYOUT DRAWING INTERCONN. / WIRING DIAGRAM TAG REV. DATE REMARKS

NIS, PLC-JB

Material:SS 316L, Total Terminal:50 Nos

Branch Cable Entry:10xM20


Branch Cable Entry Used:8 Nos
11 28 JB FG 1214 Exe P12512-11-28-49-1601 P12512-11-28-49-1601 B 24-11-2023
Branch Cable Entry Spare/Plugs:2 Nos

Main Cable Entry: 2xM40

Main Cable Entry Used:1 Nos

Main Cable Entry Spare/Plugs:1 Nos

NIS, PLC-JB

Material:SS 316L, Total Terminal:50 Nos

Branch Cable Entry:10xM20


Branch Cable Entry Used:8 Nos
11 28 JB FG 1215 Exe P12512-11-28-49-1601 P12512-11-28-49-1601 B 24-11-2023
Branch Cable Entry Spare/Plugs:2 Nos

Main Cable Entry: 2xM40

Main Cable Entry Used:1 Nos

Main Cable Entry Spare/Plugs:1 Nos

NIS, PLC-JB

Material:SS 316L, Total Terminal:20 Nos

Branch Cable Entry:5xM20


Branch Cable Entry Used:2 Nos
11 28 JB FG 1216 Exe P12512-11-28-49-1601 P12512-11-28-47-1601 B 24-11-2023
Branch Cable Entry Spare/Plugs:3 Nos

Main Cable Entry: 2xM32

Main Cable Entry Used:1 Nos

Main Cable Entry Spare/Plugs:1 Nos

NIS, PLC-JB

Material:SS 316L, Total Terminal:20 Nos

Branch Cable Entry:5xM20


Branch Cable Entry Used:2 Nos
11 28 JB FG 1217 Exe P12512-11-28-49-1601 P12512-11-28-47-1601 B 24-11-2023
Branch Cable Entry Spare/Plugs:3 Nos

Main Cable Entry: 2xM25

Main Cable Entry Used:1 Nos

Main Cable Entry Spare/Plugs:1 Nos