Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

SPECIFICATION OF TEMPERATURE TRANSMITTER

Project Ms. TRIVIKRAM CONSTRUCTION AND DEVELOPERS,

Boiler. 1 X 20 TPH TRAVELLING GRATE BOILER

S. No. Description Specification


1 Type Duplex (CR/AL)
2 Input From K type Thermocouple
3 Output 4 - 20 mA
4 Power supply 24V, DC (2 wire transmission)
5 Enclosure IP 65
6 Accuracy ± 0.1%
7 Calibration range for transmitters To suit the T/C
8 Load resistance Ohms 600 maximum
9 Quantity 1 No.
10 Electrical connection 1/2" NPT(F)
11 Process connection 1/2" NPT(F)
12 Mounting brackets Required (2" pipe mounting)
13 Span range Supplier to specify
14 Ambient temp. 50°C
15 Model No. Supplier to specify
16 Cable gland Required (Double compression)
Low copper cast - aluminium alloy with polyurethene
Housing materials
17 paint
18 Other wetted parts SS316
19 Turn down ratio 40:1
20 Make YOKOGAWA EJX / EMERSON3051 SMART / ABB
21 Tag No TT-201
Note:
Temperature transmitter should be provided with an engraved chrome plated tag plate with
1.
engraving filled with enamel.
Name plate should be 'SS' material and it should contain minimum and essential details of
2.
the component.
3. Transmitter should be provided with output meter/output gauge at the transmitter end.
Enclosures in field shall be dust proof, weather proof to NEMA 4 and secured against
4.
ingress of fumes, dampers, inseets & vermin.
5. All externals shall be provided with anti-corrosive protection.
6. Packing of instruments should be adequate to prevent from all damages.
APPLICATIONS:
Max. W.
Span
S. No. Description Input T/C Type & Range Temp. Qty.
Range
Deg. C
Supplier to
01. Steam line CR/AL (0-1200°C) 525 1 No.
specify
DETAILS REQUIRED FROM SUPPLIER
ALONG WITH OFFER AFTER ORDERING
01. 1 set of catalogue 01. Calibration certificate
Material construction for all
02. 02. Test certificate
components
03. 6 copies of O&M manual
04. Guarantee certificate
05. Mounting instruction
06. Data sheet

Page 1